Design of Box Culvert

The document provides details of the design of a beam and footing for a proposed cover canal project in Butuan City, Philippines. It includes beam load and moment calculations considering dead and live loads. It then describes the beam design process and specifications, including reinforcement sizes and spacing. Finally, it provides inputs and design of the column footing, specifying dimensions, reinforcement sizes and layout, and checking the ultimate axial capacity.
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
225 views

Design of Box Culvert

The document provides details of the design of a beam and footing for a proposed cover canal project in Butuan City, Philippines. It includes beam load and moment calculations considering dead and live loads. It then describes the beam design process and specifications, including reinforcement sizes and spacing. Finally, it provides inputs and design of the column footing, specifying dimensions, reinforcement sizes and layout, and checking the ultimate axial capacity.
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 24

Project Proposed Cover Canal

Location Gov. J.A. Rosales Ave., Butuan City


Owner Victor S. Uy

Beam Load Computation


γ(concrete) = 24 KN/m^3
h(slab) = 150 mm
h(beam) = 350 mm
w(beam) = 250 mm
tw = 0.25 m
s(beam) = 3.63 m
Length = 3m
A. DEAD LOAD
W(beam) = 2.1 KN/m
W(slab) = 0.900 KN/m
DL(total) = 3.000
DL = (1/8)(wL^2)
Mu(DL) = 3.375 KN-m
Vumax(DL) = 4.5 KN
B. LIVE LOAD
Sidewalk(normal) = 12 Kpa
LL = 12 KN/m
Mu(DL) = 13.5 KN-m
Vumax(DL) = 18 KN
Mu(total): Mu = 1.2MDL+1.6MLL
Where:
Mu = 25.650 KN-m
Vu = 34.200 KN
Beam Load Computation
tw = 0.25 m
A. DEAD LOAD
W(beam) = 2.1 KN/m
W(slab) = 0.900 KN/m
DL(total) = 3.000 KN/m
Mu(DL) = (1/8)(wL^2)
Mu(DL) = 3.375 KN-m

B. MOVING LOAD
Length of truck = 2.4
P1 = 40 kN
P2 = 60 kN
Centerline of the spa =
Length of the culvert = 3
For Loads P2
Resultant'( R) = 100 kN
Rx = 96
x, the location of R = 0.96 m
For maximum moment under 60 kN
Since P1 is outside the span, therefore consider 60KN
RA = 30 = RB
1.5 Mmax of P2 = 45 KN
Mmax of P2 = 45.9 KN-m
For maximum shear under 60 kN
3RA = 204
RA = 68
Vmax of P2 = 22.667 KN
IMPACT FACTOR
L+38 = 41
I 15.24/L+38 = 0.372
Mmax of all loads =
Mu(LL) for beam = Mmax of all load/2
Mu(LL) = 45.9 KN-m
Total Mu(LL) = Mu(LL)+Impact Factor(Mu(LL))
Total Mu = 1.2MDL+1.6MLL
Total Mu = 116.940
Vumax(LL) = 80.100
Vumax(DL) = 4.5
Vumax = 84.600

Beam Design
Mu =
f'c = 27.5
fy = 415
Ab 16mmΦ = 201 mm2
12mmΦ = 113 mm2
dv 10mmΦ 78 mm2

Compute the maximum and minimum ρ


ρ, the ration between area of the steel to the width of the beam and distence from the centeroid of the stee

ρbal = (0.85 β1fc'/fy) (600/600+fy) = 0.0283


As
ρ = = 0.00229714 < ρbal
bd
1.4
ρmin = = 0.00337349
fy
∴ fy = fs
As = ρbwd = 281.4 mm2
As
NsØ16 = Ab = 10.0

π*(Ø)2
As = n = 2010.6192983 mm2
4
C = T 0.85f'c aB =
Asfy
a = 0.85 f'c b = 142.786226
w
Mn1 Asfy { d-a/2}
= = 211.611364 KN-m

a
c = β1 = 167.983795416108
600{ d-c}
fs = = 221.507811
c
fs = 221.507810668071 MPa > 1000
∴ Tension Controlled Ø = 0.9
ØMn = 190.450227553045 KN-m
= ØMn = 190.450228 KN-m >

DESIGN FOR SHEAR


Vu = 84.60 kN
Reduction Factor (Shear) Ø = 0.75 Mpa
Yield Strenght of Shear Reinforcement, fyv = 275 (Normal Weight Concrete)
Modification Factor for Concrete Materiaƛ = 1
Vu ≤ ΦVn
Vn = Vc + Vs
Vu ≤ Vc + Vs
where
Vc = 0.17ƛ√fc bwd Vc
ØVc = 0.75 Vc ØVc
0.5ØVc = 0.75 Vc/2 0.5ØVc
Since = ØVc <
Shear Strength Required, Vs =

where
Area of Shear Reinf't. (2Xπdv2/4) ; Av
Spacing of Shear Reinforcement
Maximum Spacing of Shear Reinforcement
Vsmax = 0.67√fc bwd Vsmax
Vsmax = 348.73 KN
∴ Cross -Sectional Area is Adequate
Vs requirement = 0.33√fc bwd
Vs requirement = 0.5 KN
Therefore
Maximum Spacing of Shear Reinforcement
Smax < d/2 =
< 600 mm
Avx(fyt)x(d)
<
(4)x(Vs)x (1000)

Minimum Spacing of Shear Reinforcement


0.5ØVc < Vu > ØVc ; 9.70

= 0.062√fc bwSmax/fyv = 0.196 mm


= 0.35bw/fy = 0.2108 mm

Avmin
= 0.2108 Avmin = 282.6 mm2
s
∴ Use
10 - 16 mm
10 mm Φ

350
250

Mid-Support Support
d Computation
m the centeroid of the steel to the cpmpression fiber
Asfy

MPa

Mu = 116.940 KN-m

(Mild steel, R type)


Normal Weight Concrete)
KN

= 25.871 KN < 84.60 KN


= 19.40 KN
= 9.70
Vu ; Provide Adequate Shear Reinforcement (Need for Stirrups)
(Vu/Ø)-Vc ; Vs = 86.93 KN

= 157.08 mm2
= 348.73 KN
> Vs = 86.93 KN

= 0.5 KN
> Vs = 0.00 KN

160.00 mm
= 600 mm
= 59.5799 mm

< 84.60 > 19.40

Φ
@ 150 mm (2 legs)

350
250

Support
Design of Footing

I. Design Inputs :

L = 2.68 m
PDL = 75 KN
PLL = 35 KN

Axial Demand Pu = 1.4DL = 105


= 1.2DL + 1.6LL = 146

II. Material Properties

Compressive Concrete Strength fc' = 27.50


Steel Yeild Strenght Main Bar fy = 414
Steel Yeild Strenght Tie Bar fst = 414
Modulus Elasticity of steel Es = 200000

III. Design Assumption

Column Width b = 250 mm


Column Depth h = 250 mm
Concrete cover cc = 40 mm
Main Bar diameter Ø = 16 mm Vertical bars
Tie Bar diameter Øst = 10 mm Lateral ties
Stee ratio ρact = 0.02
vertical bars: N = 8 - 16 mm dia.

Design and Analysis:


>> Solve for gross area of concrete column and vertical reinforcements:
Ag = 62,500 mm2 (actual)
NAst = 1,608.50 mm2

>> Check ultimate axial capacity:


PU = (0.8 Po)
PU = 0.7 (0.8) [0.85 f 'c (Ag - Ast) + fy Ast]
PU = 1,191.04 kN > \ column section is adequate, safe!
Factor of Safety =
>> Spacing of lateral ties
S = 16 bar Ø = 256 mm
S = 48 tie Ø = 480 mm
S = least column dim = 250 mm

3.4 DESIGN OF COLUMNS

C-1 (RECTANGULAR COLUMN)

Materials Data:
f 'c = 20.70 Mpa
fy = 227.00 Mpa

Geometric and Load Data:


L = 2,800 mm (unsupported ht.) Sa = 250
Sb = 250
cbc = 20
Total Factored Load
PU = 1.4 PDL + 1.7 PLL = 164.50 kN
Design and Analysis:
>> Solve for gross area of concrete column and vertical reinforcements:
Ag = 62,500.00 mm2 (actual)
Ast = 1,608.50 mm2

>> Check ultimate axial capacity:


PU = f (0.8 Po)
PU = 0.7 (0.8) [0.85 f 'c (Ag - Ast) + fy Ast]
PU = 804.45 kN > \ column section is adequate,
Factor of Safety =
>> Spacing of lateral ties
S = 16 bar f = 256 mm
S = 48 tie f = 480 mm \
S = least column dim = 250 mm

C-2 (RECTANGULAR COLUMN )

Materials Data:
f 'c = 20.70 Mpa
fy = 227.00 Mpa

Geometric and Load Data:


L = 2,800 mm (unsupported ht.) Sa = 250
Sb = 250
cbc = 20
Total Factored Load
PU = 1.4 PDL + 1.7 PLL = 164.50 kN
Design and Analysis:
>> Solve for gross area of concrete column and vertical reinforcements:
Ag = 62,500.00 mm2 (actual)
Ast = 1,608.50 mm 2

>> Check ultimate axial capacity:


PU = f (0.8 Po)
PU = 0.7 (0.8) [0.85 f 'c (Ag - Ast) + fy Ast]
PU = 804.45 kN > \ column section is adequate, safe!
Factor of Safety =
>> Spacing of lateral ties
S = 16 bar f = 256 mm
S = 48 tie f = 480 mm \
S = least column dim = 250 mm
ting

KN
KN

Mpa
Mpa
Mpa
200000 Mpa

Vertical bars
Lateral ties

section is adequate, safe!


8.16

\ use S = 250 mm
mm vertical bars: 8 - 16 mm dia.
mm lateral ties: 10 mm dia.
mm

olumn section is adequate, safe!


4.89026208

use S = 250 mm

mm vertical bars: 8 - 16 mm dia.


mm lateral ties: 10 mm dia.
mm
n is adequate, safe!
4.89026208

use S = 250 mm
Design of Footing

I. Design Inputs :

PDL = 150 kN
PLL = 100 kN
T = 350 mm
dt = 1250 mm
D = 900 mm
C1 = 250 mm
C2 = 250 mm

II. Material Properties

Compressive Concrete Strength fc' = 27.50 Mpa


Steel Yeild Strenght Main Bar fy = 414 Mpa
Steel Yeild Strenght Tie Bar fst = 414 Mpa
Modulus Elasticity of steel Es = 200000
Density of Concrete γ = 24 KN/m^3
qallowable = 350 kPA
Factor of Safety FS = 3

III. Design Assumption

Width b = 1 m
Thickness d = 250 mm
Concrete cover cc = 75 mm
Main Bar diameter db = 16
As,dbmm 16mmΦ Ø = 201 mm2
Tie Bar diameter Øst = 10
10mmΦ Øst = 78 mm2
Steel ratio ρact = 0.02
Length L = 3 m
λ = 1
as = 40 Interior Column
= 30 Edge Column
= 20 Corner Column
φ = 0.9
β1 = 0.85 since f'c < 28 Mpa
Φ = 0.75

IV. Design and Analysis:

Design Computations:
A. Dependable ultimate soil bearing:

Soil Bearing Pressure

qULT
qna = = 116.67 kPA
FS

qn = qna - Σwieght pressure


qn = 87.74666667 kPA
P
qn >
A
150 + 75
87.7467 >
B 2

B > 1.601 m
B = 64.052
B = 1.6 m

Pu = 1.4 PDL = 210 kPA


= 1.2 DL + 1.6 LL = 340 kPA

P
qnu > = 132.8125 kPA
A

Check for Two-Way Shear (Punching Shear)


d = T - cc - db
d = 259 mm
=
bo = 2(C1+d) + 2(C2+d)
= 1.518 m
VuTWS = qnu ( B2-(C1+d)-(C2+d))
= 340 KN

L
β = = 1
S
VuCTWS = Φ 0.33 λ √ f'c bo d = 510.285333
2
= Φ 0.17 {  1 + } λ √ f'c bo d = 788.622788
β
ad
= Φ 0.083 {  1 + s b } λ √ f'c bo d = 1132.61056
o

VuCTWS = 510.2853332 KN > VuTWS = 340 KN O.K

Check for Flexure

X
Mu = qnu B X = 48.4101563 KN-m
2

Where B-c
X =
2

Mu < φ Mu
a
Mu < φ {  0.85f'c } Ac {  d - }
2
a > 8.6335 mm a = β1c a
c = c =
β1
600
fs = {  d - c } = 14699.7046389 Mpa > fy
c
d = dt
0.003
εt = {  dt - c } = 0.07349852 > 0.005
c

C = T
0.85 f'c a B = Asfy
As = 779.9345411 mm 2

for fy < 420 mm


Asmin = 0.002 B T = 1120 mm2
Asmin > As
∴ Use Asmin

Number of Re-Bars
Asmin
= π = 5.57040998 say 5- 16 mm ø 
(db)2
4

For Spacing
B = ndb + 2cc + (n-1)s
s = 342.50 mm < 3T = 1050
< 450
∴ ok

∴ Use 5- 16 mm ø  Bottom Barsbothways


510.285333 KN
788.622788 KN

1132.61056 KN

10.157

= fs

Φ = 0.9

main bars
Slab Design for Roadway

I. Design Inputs :

II. Material Properties

Compressive Concrete Strength fc' = 27.50 Mpa


Steel Yeild Strenght Main Bar fy = 414 Mpa
Steel Yeild Strenght Tie Bar fst = 414 Mpa
Modulus Elasticity of steel Es = 200000
Density of Concrete γ = 24 KN/m^3

III. Design Assumption

Width b = 1m
Thickness tw = 150 mm
Concrete cover cc = 40 mm
Main Bar diameter Ø = 16
As,dbmm 16mmΦ Ø = 201 mm2
Tie Bar diameter Øst = 10
10mmΦ Øst = 78 mm2
Steel ratio ρact = 0.02
Length L = 3 m

Design and Analysis:

A. DEAD LOAD
W(slab) = 3.6 KN/m
DL(total) = 3.60
DL = (1/8)(wL^2)
Mu(DL) = 4.050 KN-m
B. LIVE LOAD
Sidewalk = 40 Kpa
LL = 12 KN/m
Mu(DL) = 45 KN-m
Mu(total): Mu = 1.2MDL+1.6MLL
Where:
Mu = 76.860 KN-m

Assume that Mu = ØMn


Mn = T (d-a/2)
ØMn = ØT (d-a/2)
Assume that (d-a/2) = 0.95d
ØMn = ØT (d-a/2)
Assume that (d-a/2) = 0.95d
d = hf-min. cover-1/2 db
= 102 mm
Ø = 0.9
Mu = T(0.95d)/Ø
T = 0.71387
T = Asfy
As = 1724.3236 mm2
As,dbmm = 201 mm2
Number of bars = 8.5787244
n = 9 pcs.

spacing
b
s =
As/db
= 116.57 say 0.15 m on center