Design of Box Culvert
Design of Box Culvert
Design of Box Culvert
γ(concrete) = 24 KN/m^3
h(slab) = 150 mm
h(beam) = 350 mm
w(beam) = 250 mm
tw = 0.25 m
s(beam) = 3.63 m
Length = 3m
A. DEAD LOAD
W(beam) = 2.1 KN/m
W(slab) = 0.900 KN/m
DL(total) = 3.000
DL = (1/8)(wL^2)
Mu(DL) = 3.375 KN-m
Vumax(DL) = 4.5 KN
B. LIVE LOAD
Sidewalk(normal) = 12 Kpa
LL = 12 KN/m
Mu(DL) = 13.5 KN-m
Vumax(DL) = 18 KN
Mu(total): Mu = 1.2MDL+1.6MLL
Where:
Mu = 25.650 KN-m
Vu = 34.200 KN
Beam Load Computation
tw = 0.25 m
A. DEAD LOAD
W(beam) = 2.1 KN/m
W(slab) = 0.900 KN/m
DL(total) = 3.000 KN/m
Mu(DL) = (1/8)(wL^2)
Mu(DL) = 3.375 KN-m
B. MOVING LOAD
Length of truck = 2.4
P1 = 40 kN
P2 = 60 kN
Centerline of the spa =
Length of the culvert = 3
For Loads P2
Resultant'( R) = 100 kN
Rx = 96
x, the location of R = 0.96 m
For maximum moment under 60 kN
Since P1 is outside the span, therefore consider 60KN
RA = 30 = RB
1.5 Mmax of P2 = 45 KN
Mmax of P2 = 45.9 KN-m
For maximum shear under 60 kN
3RA = 204
RA = 68
Vmax of P2 = 22.667 KN
IMPACT FACTOR
L+38 = 41
I 15.24/L+38 = 0.372
Mmax of all loads =
Mu(LL) for beam = Mmax of all load/2
Mu(LL) = 45.9 KN-m
Total Mu(LL) = Mu(LL)+Impact Factor(Mu(LL))
Total Mu = 1.2MDL+1.6MLL
Total Mu = 116.940
Vumax(LL) = 80.100
Vumax(DL) = 4.5
Vumax = 84.600
Beam Design
Mu =
f'c = 27.5
fy = 415
Ab 16mmΦ = 201 mm2
12mmΦ = 113 mm2
dv 10mmΦ 78 mm2
Compute the maximum and minimum ρ
ρ, the ration between area of the steel to the width of the beam and distence from the centeroid of the stee
π*(Ø)2
As = n = 2010.6192983 mm2
4
C = T 0.85f'c aB =
Asfy
a = = 142.786226
0.85 f'c bw
Mn1 Asfy { d-a/2}
= = 211.611364 KN-m
a
c = = 167.983795416108
β1
600{ d-c}
fs = = 221.507811
c
fs = 221.507810668071 MPa > 1000
∴ Tension Controlled Ø = 0.9
ØMn = 190.450227553045 KN-m
= ØMn = 190.450228 KN-m >
where
Area of Shear Reinf't. (2Xπdv2/4) ; Av
Spacing of Shear Reinforcement
Avmin
= 0.2108 Avmin = 282.6 mm2
s
∴ Use
10 - 16 mm
10 mm Φ
350
250
Mid-Support Support
d Computation
m the centeroid of the steel to the cpmpression fiber
Asfy
MPa
Mu = 116.940 KN-m
= 157.08 mm2
= 348.73 KN
> Vs = 86.93 KN
= 0.5 KN
> Vs = 0.00 KN
160.00 mm
= 600 mm
= 59.5799 mm
Φ
@ 150 mm (2 legs)
350
250
Support
I. Design Inputs :
L = 2.68 m
PDL = 75 KN
PLL = 35 KN
Axial Demand Pu =
=
Column Width
Column Depth
Concrete cover
Main Bar diameter
Tie Bar diameter
Stee ratio
vertical bars:
Materials Data:
f 'c = 20.70 Mpa
fy = 227.00 Mpa
Materials Data:
f 'c = 20.70 Mpa
fy = 227.00 Mpa
Geometric and Load Data:
L = 2,800 mm (unsupported ht.)
fc' = 27.50
fy = 414
fst = 414
Es = 200000
b = 250 mm
h = 300 mm
cc = 40 mm
Ø = 16 mm Vertical bars
Øst = 10 mm Lateral ties
ρact = 0.02
N = 6 - 16 mm dia.
mm2 (actual)
mm2
Sa = 188
Sb = 300
cbc = 20
kN #VALUE! \ #VALUE!
Factor of Safety =
= 256 mm
= 480 mm \
= 188 mm
Sa = 300
Sb = 300
cbc = 20
mm2 (actual)
mm 2
kN #VALUE! \ #VALUE!
Factor of Safety =
= 256 mm
= 480 mm \
= 300 mm
KN
KN
Mpa
Mpa
Mpa
200000 Mpa
ertical bars
, safe!
8.64
\ use S = 250 mm
mm vertical bars: 4 -
mm lateral ties: 10 mm dia.
mm
kN
#VALUE!
use S = 188 mm
mm vertical bars: 4 -
mm lateral ties: 10 mm dia.
mm
kN
#VALUE!
use S = 256 mm
16 mm dia.
16 mm dia.
II. Material Properties
FS = 3
T = 300 mm
dt = 1250 mm
D = 950 mm
C1 = 200 mm
C2 = 300 mm
qallowable = 350 kPA
Unit weight of concrete = 23.544
fy = 415 Mpa
f'c = 24.1 Mpa
PDL = 150 kN
PLL = 100 kN
db = 12
Φ = 0.75
λ = 1
as = 40 Interior Column
= 30 Edge Column
= 20 Corner Column
φ = 0.9
β1 = 0.85 since
qULT
qna = = 116.666666666667
FS
Pu = 1.4 PDL
= 1.2 DL +
P
qnu > = 132.8125
A
= 339.95 KN
L
β = = 1.5
S
VuCTWS = Φ 0.33 λ
= Φ 0.17 {
= Φ 0.083 {
VuCTWS = 369.04799782075 KN
X
Mu = qnu B X
Mu = qnu B X
2
Where
X =
Mu < φ Mu
Mu < φ { 0.85f'c
a > 8.6335 mm
600
fs = { d
c
0.003
εt = { dt
c
As = 681.85926746988 mm2
for fy < 420
Asmin = 0.002 B
Asmin >
∴ Use Asmin
Number of Re-Bars
Asmin
= π =
(db)2
4
For Spacing
B = ndb +
s = 167.75
∴ Use 9-
Footing
116.666666666667 kPA
75
= 210 kPA
1.6 LL = 340 kPA
kPA
db
√ f'c bo d
2
1 + } λ √ f'c
β
asd
1 + } λ √
bo
= 52.0625 KN-m
= 52.0625 KN-m
B-c
2
a
0.85f'c } Ac { d -
2
a = β1c
c
- c } = 11982.3825794869
d = dt
- c } = 0.059911912897435
C =
0.85 f'c a B =
420 mm
T = 960 mm2
As
8.48824378236143 say 9-
2cc + (n-1)s
mm < 3T = 900
< 450
∴ ok
12 mm ø Bottom Barsbothways
= 369.04799782075
bo d = 443.603148895649
f'c bo d = 740.225993435883
339.95 KN O.K
}
a
= c = 10.1570588235294
β1
> 0.005 Φ =
T
Asfy
12 mm ø main bars
900
KN
KN
KN
0.9
Slab Design for Roadway
I. Design Inputs :
Width b = 1m
Thickness tw = 150 mm
Concrete cover cc = 40 mm
Main Bar diameter Ø = 16
As,dbmm16mmΦ Ø = 201 mm2
Tie Bar diameter Øst = 10
10mmΦ Øst = 78 mm2
Stee ratio ρact = 0.02
Length L = 3 m
A. DEAD LOAD
W(slab) = 3.6 KN/m
DL(total) = 3.60
DL = (1/8)(wL^2)
Mu(DL) = 4.050 KN-m
B. LIVE LOAD
Sidewalk = 40 Kpa
LL = 12 KN/m
Mu(DL) = 45 KN-m
Mu(total): Mu = 1.2MDL+1.6MLL
Where:
Mu = 76.860 KN-m
spacing s = b-2min.cover-ndb/n-1
s =
Smax db = 16mm
Smax = 16mm
1000
20
16
62.933333