Pressure Sensors and Accessories Code No.

LIT-1900405

P499 Series Electronic Pressure Transducers

Description
The P499 Series Electronic Pressure Transducers are compact,
economical, rugged, direct-mount pressure transducers designed for
use in commercial refrigeration and air conditioning applications.
These transducers produce an analog signal based on the sensed
pressure.
The P499 Series transducers feature environmentally protected
electronics with stainless steel construction. The digitally
compensated P499 transducers are highly accurate over a broad
temperature range, resisting the effects of wide ambient temperature
swings, high humidity, condensation, and icing.
The pressure port is machined from a solid piece of 17-4PH stainless
steel. No O-rings, organic materials, or welds are exposed to the
pressure media, allowing for a leak-proof, all-metal, sealed pressure
system.
The P499 Series transducers operate with any corrosive or P499 Electronic Pressure Transducers; Style 47 Fitting
non-corrosive pressure medium that is compatible with 17-4PH Shown on the Left and Style 49 Fitting Shown on the Right
stainless steel, including water, condensate, carbon dioxide, glycol,
most refrigerants (including ammonia), and many other compatible
fluids and gases. Refer to the P449 Series Electronic Pressure Transducer
The P499 Series provides transducers in a variety of pressure ranges, Product/Technical Bulletin (LIT-12011190) for important product
covering most common refrigeration and air conditioning applications. application information.

Features Repair Information


• single-piece machined 17-4PH stainless steel pressure port If the P499 Series Electronic Pressure Transducer fails to operate
provides a durable assembly that eliminates refrigerant loss due to within its specifications, replace the unit. For a replacement
O-ring or weld failures; resists damage due to physical shock, transducer, contact the nearest Johnson Controls® representative.
vibration, and pressure pulsations; enables use with non-corrosive
or corrosive pressure media that is compatible with 17-4PH Accessories
stainless steel. P499 transducers require wire harnesses for all models that do not
• environmentally protected electronics withstand the effects of have an integral cable.
adverse conditions associated with typical HVAC/R applications, Wire Harnesses with Packard Electrical Connectors
Product Code Number1 Length
including freeze/thaw applications on suction lines.
• reliable, repeatable performance and long operating life minimizes
WHA-PKD3-200C 6-1/2 ft (2.0 m)
service and replacement costs.
WHA-PKD3-400C 13 ft (4.0 m)
• many available pressure ranges provide a single line of
transducers for all refrigeration and air conditioning application WHA-PKD3-600C 19-5/8 ft (6.0 m)
needs. 1. Wire harnesses for P399 transducers and P499 transducers are
• 1% total error band provides high-accuracy performance. interchangeable.
• slender body design facilitates use of deep-socket wrenches for
ease of installation; requires zero turning radius.
• CE and UL agency listings allow for global applications.

Selection Chart
0.5 to 4.5 VDC Ratiometric P499 Transducer Models with Packard Electrical Connections, psis
Product Code Number Pressure Connection Pressure Range1 Individual or Kit2
Minimum Pressure Maximum Pressure
(Pmin) (Pmax)
P499RAPS100C 1/8 in. 27 NPT External Thread (Style 49) -10 psis (-0.7 bar) 100 psis (6.9 bar) Individual
P499RAPS100K [20 in. Hg] Kit
P499RAPS102C 0 psis (0 bar) 200 psis (13.8 bar) Individual
P499RAPS102K Kit
P499RCPS100C 1/4 in. SAE 45 Flare Internal Thread -10 psis (-0.7 bar) 100 psis (6.9 bar) Individual
P499RCPS100K (7/16-20 UNF) with Depressor (Style 47) [20 in. Hg] Kit
P499RAPS102C 0 psis (0 bar) 200 psis (13.8 bar) Individual
P499RAPS102K Kit
1. Transducer sealed and rated for IP67 harsh environments.
2. The Individual pack comes with a transducer only - you must order the wire harness separately. The Kit is packaged with a transducer, 6-1/2 ft (2 m) wire
harness, and technical documentation.

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult th
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.

R-119
Pressure Sensors and Accessories

P499 Series Electronic Pressure Transducers (Continued)

0.5 to 4.5 VDC Ratiometric P499 Transducer Models with Integral 2 m (6-1/2 ft) Shielded Cable, psis
Product Code Number Pressure Connection Pressure Range1
Minimum Pressure Maximum Pressure
(Pmin) (Pmax)
P499RCSS101C 1/4 in. SAE 45 Flare Internal Thread 0 psis (0 bar) 100 psis (6.9 bar)
(7/16-20 UNF) with Depressor (Style 47)
1. Transducer sealed and rated for IP67 harsh environments.

0.5 to 4.5 VDC Ratiometric P499 Transducer Models with Packard Electrical Connections, psi
Product Code Number Pressure Connection Pressure Range Individual or Kit1
Minimum Pressure Maximum Pressure
(Pmin) (Pmax)
P499RAP-101C 1/8 in. 27 NPT External Thread (Style 49) 0 psi (0 bar) 100 psi (6.9 bar) Individual
P499RAP-101K Kit
P499RAP-102C 0 psi (0 bar) 200 psi (13.8 bar) Individual
P499RAP-105C 0 psi (0 bar) 500 psi (34.5 bar) Individual
P499RAP-105K Kit
P499RAP-107C 0 psi (0 bar) 750 psi (51.7 bar) Individual
P499RAP-107K Kit
P499RCP-101C 1/4 in. SAE 45 Flare Internal Thread 0 psi (0 bar) 100 psi (6.9 bar) Individual
P499RCP-101K (7/16-20 UNF) with Depressor (Style 47) Kit
P499RCP-105C 0 psi (0 bar) 500 psi (34.5 bar) Individual
P499RCP-105K Kit
P499RCP-107C 0 psi (0 bar) 750 psi (51.7 bar) Individual
P499RCP-107K Kit
1. The Individual pack comes with a transducer only - you must order the wire harness separately. The Kit is packaged with a transducer, 6-1/2 ft (2 m) wire
harness, and technical documentation.

0 to 10 VDC P499 Transducer Models with Packard Electrical Connections, psi


Product Code Pressure Connection Pressure Range Individual or Kit1
Number Minimum Pressure Maximum Pressure
(Pmin) (Pmax)
P499VAP-101C 1/8 in. 27 NPT External Thread (Style 49) 0 psi (0 bar) 100 psi (6.9 bar) Individual
P499VAP-101K Kit
P499VAP-105C 0 psi (0 bar) 500 psi (34.5 bar) Individual
P499VAP-105K Kit
P499VAP-107C 0 psi (0 bar) 750 psi (51.7 bar) Individual
P499VAP-107K Kit
P499VCP-101C 1/4 in. SAE 45 Flare Internal Thread 0 psi (0 bar) 100 psi (6.9 bar) Individual
P499VCP-101K (7/16-20 UNF) with Depressor (Style 47) Kit
P499VCP-105C 0 psi (0 bar) 500 psi (34.5 bar) Individual
P499VCP-105K Kit
P499VCP-107C 0 psi (0 bar) 750 psi (51.7 bar) Individual
P499VCP-107K Kit
1. The Individual pack comes with a transducer only, you must order the wire harness separately. The Kit is packaged with a transducer, 6-1/2 ft (2 m) wire
harness, and technical documentation.

4 to 20 mA P499 Transducer Models with Packard Electrical Connections, psi (Part 1 of 2)


Product Code Pressure Connection Pressure Range Individual or Kit1
Number Minimum Pressure Maximum Pressure
(Pmin) (Pmax)
P499AAP-101C 1/8 in. 27 NPT External Thread (Style 49) 0 psi 100 psi Individual
P499AAP-101K (0 bar) (6.9 bar) Kit
P499AAP-105C 0 psi 500 psi Individual
P499AAP-105K (0 bar) (34.5 bar) Kit
P499AAP-107C 0 psi 750 psi Individual
P499AAP-107K (0 bar) (51.7 bar) Kit

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult th
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.

R-120
Pressure Sensors and Accessories

P499 Series Electronic Pressure Transducers (Continued)

4 to 20 mA P499 Transducer Models with Packard Electrical Connections, psi (Part 2 of 2)


Product Code Pressure Connection Pressure Range Individual or Kit1
Number Minimum Pressure Maximum Pressure
(Pmin) (Pmax)
P499ACP-101C 1/4 in. SAE 45 Flare Internal Thread 0 psi 100 psi Individual
P499ACP-101K (7/16-20 UNF) with Depressor (Style 47) (0 bar) (6.9 bar) Kit
P499ACP-105C 0 psi 500 psi Individual
P499ACP-105K (0 bar) (34.5 bar) Kit
P499ACP-107C 0 psi 750 psi Individual
P499ACP-107K (0 bar) (51.7 bar) Kit
1. The Individual pack comes with a transducer only, you must order the wire harness separately. The Kit is packaged with a transducer, 6-1/2 ft (2 m) wire
harness, and technical documentation.

Technical Specifications
P499 Series Electronic Pressure Transducers
Pressure Ranges -10 to 100 psis, 0 to 100 psi, 0 to 200 psi, 0 to 500 psi, 0 to 750 psi
Maximum Working Pressure 2x Pressure Range; short duration; infrequent, abnormal condition
Burst Pressure 5x Pressure Range
Vacuum 30 microns (0.03 mm Hg); short term
Media Compatibility All media compatible with 17-4PH stainless steel, including ammonia
Output Signal 0.5 to 4.5 VDC, 0 to 10 VDC, or 4 to 20 mA
Supply Voltage 0.5 to 4.5 VDC Ratiometric 5.0 ±0.25 VDC, Safety Extra-Low Voltage (SELV) or Class 2
Output
4 to 20 mA Output 9 to 30 VDC, SELV or Class 2
0 to 10 VDC Output 12 to 30 VDC, SELV or Class 2
Direct-Mount Pressure Connections 1/8 in. 27 NPT External Thread (Style 49),
1/4 in. SAE 45 Flare Internal Thread (7/16-20 UNF) with Depressor (Style 47)
Temperature and Storage -40 to 257F (-40 to 125C)
Humidity Operating -40 to 185F (-40 to 85C)
Compensated Range -4 to 185F (-20 to 85C)
Humidity 0 to 100% RH
Linearity ±0.25% Full Span best fit straight line
Accuracy ±1% Full Span (maximum) over compensated temperature range
Materials Pressure Port 17-4PH stainless steel construction
Packard Connector 40% glass-filled Polyetherimide (PEI)
Vibration 20G, 20 to 200 Hz
Shock 200G/11 ms
Compliance United States UL Listed, File E29374, CCN NKPZ
UL Recognized for Use in Class I, Division 2 Hazardous Locations, File E322274
Canada UL Listed, File E29374, CCN NKPZ7
UL Recognized for Use in Class I, Division 2 Hazardous Locations, File E322274
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential
requirements and other relevant provisions of the EMC Directive 2004/108/EC.
Australia/ C-Tick Mark, Emissions Compliant
New Zealand

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult th
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.