P499 Series Electronic Pressure Transducers: Description
P499 Series Electronic Pressure Transducers: Description
P499 Series Electronic Pressure Transducers: Description
LIT-1900405
Description
The P499 Series Electronic Pressure Transducers are compact,
economical, rugged, direct-mount pressure transducers designed for
use in commercial refrigeration and air conditioning applications.
These transducers produce an analog signal based on the sensed
pressure.
The P499 Series transducers feature environmentally protected
electronics with stainless steel construction. The digitally
compensated P499 transducers are highly accurate over a broad
temperature range, resisting the effects of wide ambient temperature
swings, high humidity, condensation, and icing.
The pressure port is machined from a solid piece of 17-4PH stainless
steel. No O-rings, organic materials, or welds are exposed to the
pressure media, allowing for a leak-proof, all-metal, sealed pressure
system.
The P499 Series transducers operate with any corrosive or P499 Electronic Pressure Transducers; Style 47 Fitting
non-corrosive pressure medium that is compatible with 17-4PH Shown on the Left and Style 49 Fitting Shown on the Right
stainless steel, including water, condensate, carbon dioxide, glycol,
most refrigerants (including ammonia), and many other compatible
fluids and gases. Refer to the P449 Series Electronic Pressure Transducer
The P499 Series provides transducers in a variety of pressure ranges, Product/Technical Bulletin (LIT-12011190) for important product
covering most common refrigeration and air conditioning applications. application information.
Selection Chart
0.5 to 4.5 VDC Ratiometric P499 Transducer Models with Packard Electrical Connections, psis
Product Code Number Pressure Connection Pressure Range1 Individual or Kit2
Minimum Pressure Maximum Pressure
(Pmin) (Pmax)
P499RAPS100C 1/8 in. 27 NPT External Thread (Style 49) -10 psis (-0.7 bar) 100 psis (6.9 bar) Individual
P499RAPS100K [20 in. Hg] Kit
P499RAPS102C 0 psis (0 bar) 200 psis (13.8 bar) Individual
P499RAPS102K Kit
P499RCPS100C 1/4 in. SAE 45 Flare Internal Thread -10 psis (-0.7 bar) 100 psis (6.9 bar) Individual
P499RCPS100K (7/16-20 UNF) with Depressor (Style 47) [20 in. Hg] Kit
P499RAPS102C 0 psis (0 bar) 200 psis (13.8 bar) Individual
P499RAPS102K Kit
1. Transducer sealed and rated for IP67 harsh environments.
2. The Individual pack comes with a transducer only - you must order the wire harness separately. The Kit is packaged with a transducer, 6-1/2 ft (2 m) wire
harness, and technical documentation.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult th
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.
R-119
Pressure Sensors and Accessories
0.5 to 4.5 VDC Ratiometric P499 Transducer Models with Integral 2 m (6-1/2 ft) Shielded Cable, psis
Product Code Number Pressure Connection Pressure Range1
Minimum Pressure Maximum Pressure
(Pmin) (Pmax)
P499RCSS101C 1/4 in. SAE 45 Flare Internal Thread 0 psis (0 bar) 100 psis (6.9 bar)
(7/16-20 UNF) with Depressor (Style 47)
1. Transducer sealed and rated for IP67 harsh environments.
0.5 to 4.5 VDC Ratiometric P499 Transducer Models with Packard Electrical Connections, psi
Product Code Number Pressure Connection Pressure Range Individual or Kit1
Minimum Pressure Maximum Pressure
(Pmin) (Pmax)
P499RAP-101C 1/8 in. 27 NPT External Thread (Style 49) 0 psi (0 bar) 100 psi (6.9 bar) Individual
P499RAP-101K Kit
P499RAP-102C 0 psi (0 bar) 200 psi (13.8 bar) Individual
P499RAP-105C 0 psi (0 bar) 500 psi (34.5 bar) Individual
P499RAP-105K Kit
P499RAP-107C 0 psi (0 bar) 750 psi (51.7 bar) Individual
P499RAP-107K Kit
P499RCP-101C 1/4 in. SAE 45 Flare Internal Thread 0 psi (0 bar) 100 psi (6.9 bar) Individual
P499RCP-101K (7/16-20 UNF) with Depressor (Style 47) Kit
P499RCP-105C 0 psi (0 bar) 500 psi (34.5 bar) Individual
P499RCP-105K Kit
P499RCP-107C 0 psi (0 bar) 750 psi (51.7 bar) Individual
P499RCP-107K Kit
1. The Individual pack comes with a transducer only - you must order the wire harness separately. The Kit is packaged with a transducer, 6-1/2 ft (2 m) wire
harness, and technical documentation.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult th
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.
R-120
Pressure Sensors and Accessories
Technical Specifications
P499 Series Electronic Pressure Transducers
Pressure Ranges -10 to 100 psis, 0 to 100 psi, 0 to 200 psi, 0 to 500 psi, 0 to 750 psi
Maximum Working Pressure 2x Pressure Range; short duration; infrequent, abnormal condition
Burst Pressure 5x Pressure Range
Vacuum 30 microns (0.03 mm Hg); short term
Media Compatibility All media compatible with 17-4PH stainless steel, including ammonia
Output Signal 0.5 to 4.5 VDC, 0 to 10 VDC, or 4 to 20 mA
Supply Voltage 0.5 to 4.5 VDC Ratiometric 5.0 ±0.25 VDC, Safety Extra-Low Voltage (SELV) or Class 2
Output
4 to 20 mA Output 9 to 30 VDC, SELV or Class 2
0 to 10 VDC Output 12 to 30 VDC, SELV or Class 2
Direct-Mount Pressure Connections 1/8 in. 27 NPT External Thread (Style 49),
1/4 in. SAE 45 Flare Internal Thread (7/16-20 UNF) with Depressor (Style 47)
Temperature and Storage -40 to 257F (-40 to 125C)
Humidity Operating -40 to 185F (-40 to 85C)
Compensated Range -4 to 185F (-20 to 85C)
Humidity 0 to 100% RH
Linearity ±0.25% Full Span best fit straight line
Accuracy ±1% Full Span (maximum) over compensated temperature range
Materials Pressure Port 17-4PH stainless steel construction
Packard Connector 40% glass-filled Polyetherimide (PEI)
Vibration 20G, 20 to 200 Hz
Shock 200G/11 ms
Compliance United States UL Listed, File E29374, CCN NKPZ
UL Recognized for Use in Class I, Division 2 Hazardous Locations, File E322274
Canada UL Listed, File E29374, CCN NKPZ7
UL Recognized for Use in Class I, Division 2 Hazardous Locations, File E322274
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential
requirements and other relevant provisions of the EMC Directive 2004/108/EC.
Australia/ C-Tick Mark, Emissions Compliant
New Zealand
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult th
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.
R-121