Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

ETAP Workshop Notes ANSI Short Circuit Example: Description

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6
At a glance
Powered by AI
This example demonstrates how to perform short circuit analysis in ETAP including entering device data, creating configurations and study cases, running fault calculations, and sizing protective devices.

The purpose of this example is to understand the impedance and ratings data required to run short-circuit analysis and covers 3-phase device duty calculations, unbalanced faults, and sizing of protective device equipment ratings.

Study case FaultAll-B results in the worst short circuit current because it considers motor contribution based on motor status and loading category (design) and calculates fault on all buses.

ETAP Workshop Notes

ANSI Short Circuit Example


Description
This is an example to run short-circuit studies for a system with different configurations and operating
conditions. The system contains the elements with most contributions towards short-circuit.

Purpose
The purpose of this example is to understand the impedance and ratings data required to run short-circuit
analysis. This example covers 3-phase device duty and unbalanced short-circuit calculations plus it
requires analysis of the results by inspection of the one-line results and reports. The final section of the
exercise deals with the sizing and selection of protective device equipment ratings.

Setup
Load the project file named “SC-ANSI-Example-1” located under the directory Examples/SCExample1
in Short-Circuit chapter of the workshop notes. Use the default ETAP library.

Procedure

1. Enter the following data to the components for SC calculations


Element Parameters Location
U1 3-phase: MVAsc = 2000, X/R = 55; 1-Phase: MVAsc = 1750, X/R = 48 OLV1 (Fig1)
Gen1 & Subtransient Model, Round-Rotor, Use Typical Data; Xd” Tolerance = 5% OLV1 (Fig1)
Gen3 (this option is in “Imp/Model” page)
Syn1 Xd” = X2 = X0 = 15.38%, all X/R = 30.8 Network2 (Fig2)
All Ind Mtr Use “Std MF” Option for ANSI SC Z (this option is in “Imp” page) Network2 (Fig2)
Cmtr1 (Fig3)
Lump Loads LRC = 650%, “High”; X/R = 15; Use “Std MF” option OLV1 (Fig1)
XFMR T1: Tol% = 10; T2: Tol% = 7.5 OLV1 (Fig1)
Cable* For all branch/equipment cables: Tmin = 25 °C, Tmax = 90 °C Network2 (Fig2)
(these value are in “Impedance” page) Cmtr1 (Fig3)
*Note: It may be easier to accomplish this from the SC study case.

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 1 of 6
ETAP Workshop Notes

ANSI Short Circuit Example

Figure 1: OLV1

4x500 HP Figure2: Network2

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 2 of 6
ETAP Workshop Notes

ANSI Short Circuit Example

Figure 3: Cmtr1

2. Create two configurations

Configuration Setup
Normal Open tie-CB CB1 and close all other CBs.
T3 Down Close CB1 and open CBs on both sides of T3
T4 Down Close CB1 and open CBs on both sides of T4

3. Create and set up the following study cases: (If steps 1 and 2 have not been completed, please open
project “SC-ANSI-Example-2”, otherwise, continue using project “SC-Example-1” for step 3).
Study Case: FaultBus4
Page Parameter Setting
Info Adjust Base kV for XFMR Tap
Do not consider cable/OL heater for motor
Motor contribution based on motor status
Fault only bus 4 – Report Contribution Level =3
Standard Prefault voltage = 100% of bus nominal kV
Use variable machine X/R
HV CB interrupting rating adjusted based on nominal kV
Device duty based on total bus fault current
Calculation according to C37.010-1999
LV MCCB & ICCB – Use “Higher MF” option
Adjustment Individual XFMR Z tolerance, global cable R temperature at 25 °C
Alert Marginal limit = 95%

Study Case: FaultAll-A


Page Parameter Setting
Info Adjust Base kV for XFMR Tap
Do not consider cable/OL heater for motor
Motor contribution based on motor status
Fault all buses – Report Contribution Level = 3
Standard Prefault voltage = 102% of bus nominal kV

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 3 of 6
ETAP Workshop Notes

ANSI Short Circuit Example


Use fixed machine X/R
HV CB interrupting rating adjusted based on nominal kV & Vf
Device duty based on total bus fault current
Calculation according to C37.010-1999
LV MCCB & ICCB – Use “Higher MF” option
Adjustment Individual XFMR Z tolerance, global cable R temperature at 25 °C
Alert Marginal limit = 95%

Study Case: FaultAll-B


Page Parameter Setting
Info Adjust Base kV for XFMR Tap
Do not consider Cable/OL heater for Motor
Motor contribution based on motor status and loading category
(Design)
Fault all buses – Report Contribution Level =3
Standard Prefault voltage = Vmag * nominal kV
Use fixed machine X/R
HV CB interrupting rating adjusted based on nominal kV & Vf
Device duty based on total bus fault current
Calculation according to C37.010-1999
LV MCCB & ICCB – Use “Higher MF” option
Adjustment Individual XFMR Z tolerance, global cable R temperature at 25 °C
Alert Marginal limit = 95%

4. Run Device Duty calculation


• Study Case – FaultBus4
• Configuration – Normal, T3 Down, T4 Down
• Run Device Duty Calculation
• Check OLV display (Where and how can you set OLV display?)
• Check report

5. Run Device Duty calculation


• Study Case – FaultAll-A
• Configuration – Normal, T3 Down, T4 Down
• Run Device Duty Calculation
• Check OLV display – Compare OLV display against the one in 2.
• Check report

6. Run Device Duty calculation


• Study Case – FaultAll-B
• Configuration – Normal, T3 Down, T4 Down
• Run Device Duty Calculation
• Check OLV display

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 4 of 6
ETAP Workshop Notes

ANSI Short Circuit Example


• Check report

Questions:
• Which study case results in the worst SC current?
• Which configuration results in the worst SC current?

Verify and Size Equipment Rating


1. Factors to be considered
• System configuration – PD status and load configurations
• Revision data
• Study case – Vf, X/R, rating adjustment, etc

2. Verify devices with existing settings


• Bus – Bus1 and Bus7
• PD – CB5, CB8, CB10, CB11, and CB23
• Are there any problems with the existing settings? - If yes, fix them
• Run SC with the configuration and study case that give the worst case

3. Select rating/size for some devices


• Bus –Bus5 and Bus6
• PD – CBs connected to Bus5 and Bus6 (CB1, CB12, CB13, CB14, CB15, CB16)
• Run SC with the configuration and study case that give the worst case

Suggested Ratings for Some Components


Element Parameters
Bus5 & Bus6 Switchgear: 800? 58 kA, 97.88 kA

CB1,12,13,14, 15, 16, 19 GE, VB-4.16-250, 4.76 kV, 1200 Amp,?, 29 kA

4. Select rating/size for some devices


• Bus –Bus3, and Bus8
• PD – CBs connected to Bus1, and Bus7 Steps for device sizing:
• Identify the worst SC case – combination of revision, configuration & study case
• Run SC calculation for the case and determine fault current
• Select a device size based on the fault currents
• Run SC calculation again to verify device rating

Suggested Ratings for Some Components


Element Parameters
Bus 3 Switchgear: 600 Amp? 37 kA, 62.44 kA
Bus 8 MCC: 600 Amp? 39 kA, 65.81 kA

CB3, 4, 7 ABB, 121PM20, 121 kV, 1200 Amp, 20 KA


CB20 Power-CB, ABB, K-800M, 0.48 kV, 800 Amp, 42 kA
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 5 of 6
ETAP Workshop Notes

ANSI Short Circuit Example


CB21 Molded Case, GE, TEML, 0.48kV, 150 Amp, 65 kA
CB22 Power-CB, ABB, K-800M, 0.48 kV, 800 Amp, 42 kA
Fuse Gould Shawmut, A4BQ, 0.6 kV, 700 A, 200 kA

Running Unbalanced SC Calculation

1. Set up grounding connection


• Set up layered protection – XFMR delta on HV side and Y grounded on LV side
• 13.8 kV – 100 amp resistance grounding
• 4.16 kV – 10 amp resistance grounding
• 0.48 kV – delta/Y solid-grounded
• Utility – solid grounded
• All loads – ungrounded

2. Run unbalanced calculations using existing configuration and study cases


• What are the differences between Max, 4, and Min SC calculations?

3. Check Result
• Check result on OLV – change display option to show different fault calculation results
• Check result on crystal report
• Check effect of grounding connection type and value on zero sequence current

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 6 of 6

You might also like