1. General characteristics
General
PowerCube modules allow medium voltage air-insulated
switchgear to be constructed with the same rated currents as
those of the enclosure.
PowerCube modules are pre-assembled and tested in the
factory and comply with IEC 62271-100, CEI 17-1, IEC 60298
and CEI 17-6 Standards.
Degrees of protection
The degrees of protection of PowerCube modules comply
with IEC 60529 Standards.
The following standard degrees of protection are guaranteed
on the front:
external housing IP4X
Interlocks
The PowerCube module is fitted with interlocks to prevent
incorrect operations which might endanger the personnel in
charge of running the installation, as well as the efficiency and
reliability of the apparatus. Environmental conditions
In particular, locking devices to prevent the following The switchgear ratings are guaranteed under the following
operations are provided: ambient conditions:
– circuit-breaker closing in the intermediate position Minimum ambient temperature – 5 °C
– racking-out of closed circuit-breaker Maximum ambient temperature + 40 °C
– racking-in of closed circuit-breaker Maximum relative humidity 95%
– circuit-breaker compartment door opening in the connected Maximum altitude 1000 m a.s.l.
or intermediate position
– circuit-breaker racking-in with compartment door open. In an unpolluted and not corrosive atmosphere.
And, if the unit is fitted with an earthing switch:
– earthing switch closing with the circuit-breaker in the
connected or intermediate position
– racking-in the circuit-breaker with the earthing switch
closed
– feeder compartment door opening with the earthing switch
open
– earthing switch opening with the feeder compartment door
open.
4
1
3
2 4
6
5
7
2
A Circuit-breaker compartment
1 Voltage signalling device (on request)
2 Circuit-breaker/truck/VT truck
3 Metal shutters
4 Lower and upper monoblocs
5 Earthing switch (on request)
6 Door
7 Fans (only for 2500 A)
8 Lower door
5
1. General characteristics
6
2. Main components
7
2. Main components
Figure A
8
VT Compartment
PowerCube PR6 module can be configured as VT
compartment with withdrawable voltage transformers.
The voltage transformers are the dedicated type and are
protected by fuses. The fuses can be replaced with the
switchgear in service as the fuse compartment is segregated
metallically from the other compartments.
Consult the table on page 11 for the list of accessories.
Figure B Figure C
9
3. Types available and apparatus
Notes for using PowerCube modules Example of PR6 PowerCube modules (front view).
– Use of PowerCube PB6 modules is recommended
for constructing incoming, outgoing and bus-tie type
switchgear units (see table on following pages.
– Use of PowerCube PR6 modules is recommended for
constructing bus-riser, measurement and direct busbar
incoming switchgear units.
1. Monoblocs
2. Branches/terminals.
3. Fans. Pre-installed in 2500 A PB6 modules.
10
VD4 withdrawable circuit-breakers for PowerCube modules
W=1000 W=1000
P=275 P=275
u/l=380 u/l=380 Circuit-breaker
[kV] Isc [kA] Icw [kA]
type designation
H=ø =35 H= ø =79
Rated uninterrupted current of the
PowerCube module [A] (40 °C)
25 25
1250 VD4/W 36.12.32 p275 (1)
31.5 31.5 (1s)
25 25
1600 VD4/W 36.16.32 p275 (1)
31.5 31.5 (1s)
36
25 25
2000 VD4/W 36.20.32 p275 (1)
31.5 31.5 (1s)
20 20
2500 (3) VD4/W 36.25.32 p275 (1)
31.5 31.5 (1s)
11
3. Types available and apparatus
Accessories
The table below indicates the accessories available and the relative combination with the PowerCube modules.
12
4. Overall dimensions and weights
13
4. Overall dimensions and weights
14
PB6 PowerCube module - 1600 - 2500 A - with branches
15
4. Overall dimensions and weights
16
PR6 PowerCube module - with branches
17
4. Overall dimensions and weights
18
5. Completion of the switchgear
To complete the switchgear, ABB can also offer the components indicated below.
Voltage transformers
The voltage transformers are the type insulated in resin and
are used to supply measuring and protection devices.
The are available for fixed assembly or for installation on
withdrawable trucks.
They comply with the IEC 60044-2 Standards.
Their dimensions usually conform to the DIN 42600 Standard.
The transformers installed on withdrawable trucks are, on the
other hand, of the dedicated type.
These transformers can have one or two poles, with
performance and precision classes suited to the functional
requirements of the instruments connected to them.
When they are installed on withdrawable trucks, they are
fitted with medium voltage protection fuses. The fuses can be
replaced with the switchgear in service.
Current transformers
The current transformers are the type insulated in resin and
are used to supply measuring and protection devices. These
transformers can either have a wound core or a through bar
with one or more cores, with performance and precision
classes suited to the installation requirements.
They comply with IEC 60044-1 Standards.
Their dimensions usually conform to the DIN 42600 standard.
The current transformers can also be fitted with a capacitive
socket for connection to the voltage signalling lamps.
19
5. Completion of the switchgear
20
Configuration of the primary part is structured as shown in the Technical reference documentation
single-line diagram below. The pre-configured REF542plus unit described in this
The circuit-breaker can be fixed or withdrawable. The earthing catalogue is based on release 1.1 (V4C01 software version).
switch is manual. Configurations with a contactor in place
of the circuit-breaker are also provided foroutgoing motor For further information about the REF542plus unit, please ask
feeders. for the following documentation:
• REF542plus Technical Catalogue, 1VTA100001en-H PTMV,
The ATEX certified version, in accordance with directive 11.2003
94/9/EC for explosive environments, is also available. • REF542plus Manual Part 1: Operation and Maintenance,
Please contact ABB. 1VTA100002en-04 PTMV, 10.02.02.
• REF542plus Manual Part 2: Engineering & Technical
Note References, 1VTA100003en-04 PTMV, 10.02.02.
Specific and customised solutions and protection diagrams • REF542plus Manual Part 3: Installation and Commissioning,
are possible. Please contact ABB. 1VTA100004en-04 PTMV, 10.02.02.
• REF542plus Manual Part 4: Communication to station
control system, 1VTA100005en-01 PTMV, 10.02.02.
• REF542plus Technical References Modbus RTU,
1VTA100065-2 PTMV, 10.02.02.
• REF542plus Release 1.1 Type Test Certificate 1VTA100022
Fixed or withdrawable circuit-breaker
PTMV, 31.01.02.
• REF542plus Connection Diagram 401734, Rev. M3565
7/6/01 ABB.
• REF542plus EC Conformity, 1VTA100159 PTMV, 28.08.02.
• EC-Type-Examination Certificate (PTB 02 ATEX 3000) PTB
Manual earthing switch
September 2002.
21
Notes