Short Circuit Analysis
Short Circuit Analysis
Short Circuit Analysis
The magnitude of short circuit current that the system is capable of producing is
determined using a short circuit analysis, which is then compared to the interrupting rating of
the over current safety devices (OCPD). Because the interrupting ratings are based on
standards, the methods utilized to conduct a short circuit study must follow the protocols
guidelines, which specify calculating methods, are published by the American National
that introduce huge amounts of destructive energy into a power system in the form of heat
and magnetic force. A fault is another term for a short circuit. It's a particular type of current
that injects a lot of energy into a power system. It can take the form of either heat or magnetic
force. In essence, it is a low-resistance energy route that bypasses part of a circuit and
causes the bypassed circuit to stop working. The accuracy and extensive understanding of
satisfactorily interrupt these currents, are critical to the dependability and safety of electric
power distribution systems. Engineers involved for the planning, design, operation, and
system analysis.
Short circuit currents offer the greatest general hazard to power distribution system
components, and they are the primary concern for designing and implementing protective
systems. Short circuit currents, on the other hand, are relatively simple to compute. The
underlying nature of short circuit currents can be determined by applying three or four
A device that interrupts short circuit current is a device that is linked to an electric
circuit to protect it from severe damage in the event of a short circuit. It provides this
protection by stopping huge current flows automatically, hence the device should be rated to
interrupt and cease fault current flow without causing harm to the over current protection
device.
Body:
Definition:
currents flowing during an electrical fault. The first step in verifying that the power system is
currents have the potential to harm or deteriorate equipment. Short-circuit currents that aren't
properly shielded can harm or kill maintenance workers. New initiatives have recently been
implemented to require facilities to correctly identify these problematic locations within the
A huge amount of current can flow across a short circuit. When extremely high
currents exceed the protection capabilities of protective devices (fuses, circuit breakers, etc. ),
huge, rapid releases of energy in the form of heat, extreme magnetic fields, and even
explosions known as arc blasts can occur. Wiring insulation and electrical components might
be damaged or destroyed by the heat. An arc blast creates a shock wave that can carry
vaporized or molten metal and can kill humans who are unprotected nearby.
power and lighting system circuit breakers and fuses, fault current calculations are required.
Fault current calculations are frequently used to calculate the required short-circuit ratings of
power distribution system components such as bus transfer switches, variable speed drives,
switchboards, load centers, and panel boards. In order to calculate the maximum fault
current, you must first figure out the total contribution from all paralleled generators, as well as
The steady state solution of a linear network with balanced three phase excitation is
what short circuit analysis is all about. Currents and voltages in a power system during a
faulty state are provided by such an analysis. This data is necessary for determining the
circuit breakers required interrupting capacity and designing a good relaying system. To
obtain sufficient data, several sorts of faults are simulated at various sites and the study is
repeated. Normally, in a short circuit analysis, all shunt parameters such as loads and lime
charging admittances are ignored*, leaving only the linear network to be solved.
Transmission network
Fault. By properly combining the representations of these components we can solve the
A bolted fault occurs when two conductors of differing voltages are “bolted” together,
manufacturing or assembly error. There is no arc formed since the connectors are solidly
fastened together, and the high current quickly tripped a protection device, reducing the
harm.
An arc fault occurs when a short circuit produces an arc. A flow of electricity between two
conductors that are not in touch is known as an arc. The extreme heat that results can
cause a fire, major equipment damage, and even an arc flash or arc blast, which can
ground fault. When that path passes through the human body, the ensuing heat can
inflict catastrophic burns, and the electrical shock can cause the human heart to stop
working (fibrillation).
fault current affects all phases in the same way. The fault current is asymmetrical if just
some of the phases are impacted, or if the phases are impacted unequally.
Symmetrical faults are simple to analyze, although they only account for a small
Protective devices are meant to identify a fault state and turn off the power before it
causes serious damage. Protective devices come in a variety of shapes and sizes, but the
Fuses and circuit breakers turn off the power supply to safeguard an electrical circuit
from an over-current scenario, which is usually caused by a short circuit. Fuses are only good
for one use. Circuit breakers can be reset and utilized again and again.
When the current flow in the electrified conductor does not equal the return current in
the neutral conductor, this gadget detects it. The GFI protects humans by switching off the
current flow rapidly, preventing shock damage. Ground Fault Interrupters are commonly used
in homes for electrical sockets in the bathroom, kitchen, and outdoors. In most cases, the GFI
will be incorporated into the electrical socket. The GFI will typically be built into the electrical
socket.
Over-current protection is not provided by a GFI, and the circuit that includes a GFI
Electrical protection devices, in addition to fuses, circuit breakers, and GFIs, include:
but this should not be the only time. Any facility expansion or the addition of new electrical
investigations. Short circuit studies must be performed on a regular schedule of at least every
To correctly apply equipment in line with NEC and ANSI regulations, short-circuit
calculations are required. The level of detail necessary to complete these computations varies
substantially depending on the size and utility connection. The short-circuit study performed
by Carelabs will contain calculations that follow the most recent ANSI guidelines.
Neplan
Short circuit analysis is performed so that existing and new equipment ratings were
sufficient to with stand the available short circuit current. This short circuit analysis can be
done either through hand calculations or through known software like NEPLAN.
Using NEPLAN we can perform short circuit studies on electrical systems in a quick
Determines the level and type of protective devices that are needed
Provides the information needed for NEC and NFPA required labels
Reduces the risk a facility could face and help avoid catastrophic losses
Increases the safety and reliability of the power system and related equipment
kVA x 1000
3Ø Transformer I F .L . A =
E L . L x 1.732
kVA x 1000
1 Ø Transformer I F .L . A =
E L. L
Step 1. Determine the transformer full load amps (F.L.A.) from either the nameplate, the
100
Multiplier=
¿ % Z transformer
* Note 1. Get %Z from nameplate or Table 1. Transformer impedance (Z) helps to determine
what the short circuit current will be at the transformer secondary. Transformer impedance is
the primary until full load current flows in the secondary. This applied voltage divided by the
Example: For a 480 Volt rated primary, if 9.6 volts causes secondary full load current
* Note 2. In addition, UL 1561 listed transformers 25kVA and larger have a ± 10% impedance
tolerance. Short circuit amps can be affected by this tolerance. Therefore, for high end worst
case, multiply %Z by .9. For low end of worst case, multiply %Z by 1.1. Transformers
current.
Note 3. Utility voltages may vary ±10% for power and ±5.8% for 120 Volt lighting services.
Therefore, for highest short circuit conditions, multiply values as calculated in step 3 by 1.1 or
1.058 respectively. To find the lower end worst case, multiply results in step 3 by .9 or .942
respectively.
Note 4. Motor short circuit contribution, if significant, may be added at all fault locations
throughout the system. A practical estimate of motor short circuit contribution is to multiply the
1.732 x L x I 3 Ø
3Ø Faults f¿
C x n x EL.L
2 x L x I L− L
1Ø Line-to-Line (L-L) Faults f¿
C x n x E L .L
See Note 5 & Table 3
2 x L x I L−N
1Ø Line-to-Neutral (L-N) Faults f¿
C x n x E L .N
See Note 5 & Table 3
Where:
C = constant from Table 4 of “C” values for conductors and Table 5 of “C” values for busway.
E = Voltage of circuit
Note 5. The L-N fault current is higher than the L-L fault current at the secondary terminals of
a single-phase center-tapped transformer. The short-circuit current available (I) for this case
in Step 4 should be adjusted at the transformer terminals as follows: At L-N center tapped
transformer terminals, IL-N = 1.5 x IL-L at Transformer Terminals. At some distance from the
terminals, depending upon wire size, the L-N fault current is lower than the L-L fault current.
The 1.5 multiplier is an approximation and will theoretically vary from 1.33 to 1.67. These
figures are based on change in turns ratio between primary and secondary, infinite source
available, zero feet from terminals of transformer, and 1.2 x %X and 1.5 x %R for L-N vs. L-L
resistance and reactance values. Begin L-N calculations at transformer secondary terminals,
1
M=
1+f
Step 6. Calculate the available short circuit symmetrical RMS current at the point of
Step 6A. Motor short circuit contribution, if significant, may be added at all fault
commonly accepted.
Known:
Use the following procedure to calculate the level of fault current at the secondary of
a second, downstream transformer in a system when the level of fault current at the
1Ø Transformer (I S.C. primary and IS.C. secondary are 1Ø fault values: IS.C. secondary is L-L)
1
Step B. Calculate "M" (multiplier). M=
1+f
Step C. Calculate the short-circuit current at the secondary of the transformer. (See
V primary
I SC secondary = x M x I SCprimary
V Secondary
Example Problem:
Single-Phase Short Circuits
1. It is necessary that the proper impedance be used to represent the primary system. For 3Ø
fault calculations, a single primary conductor impedance is used from the source to the
transformer connection. This is compensated for in the 3Ø short circuit formula by multiplying
the single conductor or single-phase impedance by 1.73. However, for single-phase faults, a
primary conductor impedance is considered from the source to the transformer and back to
the source. This is compensated in the calculations by multiplying the 3Ø primary source
impedance by two.
2. The impedance of the center-tapped transformer must be adjusted for the half-winding
(generally line-to-neutral) fault condition. The diagram at the right illustrates that during line-
to-neutral faults, the full primary winding is involved but, only the half-winding on the
secondary is involved. Therefore, the actual transformer reactance and resistance of the half-
winding condition is different than the actual transformer reactance and resistance of the full
winding condition. Thus, adjustment to the %X and %R must be made when considering line-
to-neutral faults. The adjustment multipliers generally used for this condition are as follows:
Note: %R and %X multipliers given in “Impedance Data for Single Phase Transformers”
Table may be used, however, calculations must be adjusted to indicate transformer kVA/2.
3. The impedance of the cable and two-pole switches on the system must be considered
“both-ways” since the current flows to the fault and then returns to the source. For instance, if
a line-to-line fault occurs 50 feet from a transformer, then 100 feet of cable impedance must
be included in the calculation. The calculations on the following pages illustrate 1Ø fault
are considered.
a. The multiplier of 2 for some electrical components to account for the single-phase
situation, and
Example problem: