Siemens 7SJ4x Feeder PTT User Manual ENU
Siemens 7SJ4x Feeder PTT User Manual ENU
Siemens 7SJ4x Feeder PTT User Manual ENU
OMICRON PTL
User Manual
V1.000
Content
1. General ...................................................................................................................................................3
2. Software and Hardware Requirements ...............................................................................................3
3. Hardware ................................................................................................................................................3
4. Functional Range...................................................................................................................................4
5. XRIO Converter ......................................................................................................................................4
6. Specific Protection Tests ......................................................................................................................4
6.1 Pick-upTest Phase (7SJ45) ..................................................................................................................4
6.2 Pick-up Test Earth (7SJ45) ..................................................................................................................4
6.3 Trip Time Test Earth (7SJ45) ...............................................................................................................4
1. General
This user manual describes details of testing Siemens 7SJ45/7SJ46 relays with the OMICRON
Protection Test Template. General information on the usage of OMICRON Protection Testing Library
items can be found in the OMICRON PTL user manual.
Any CMC test set can be used with this Protection Test Template.
3. Hardware
There are multiple possibilities of wiring a Siemens 7SJ45 or 7SJ46 relay to a CMC test set. The advised
connections are shown in Figure 1. These connections are the default settings in the
Hardware Configuration of the PTT.
IC
IA
IB
Start *
CB aux. (52a)
Trip
4. Functional Range
Supported functions:
• Phase-Overcurrent (DMT/IDMT) (three-phase supply)
• Earth Overcurrent (DMT/IDMT) (three-phase supply)
5. XRIO Converter
The Test Object already contains the Siemens 7SJ45/7SJ46 XRIO Converter, which includes setting
parameters of the modelled protection relay. The setting parameters are built as an image of the front
plate with its DIP-switches.
The trip times as well as the reset times are calculated depending on the settings of the test current and
the active characteristic and are evaluated with the appropriate tolerance.
Figure 2 shows the test points of the three fault states. The test earth-current for the single testing point is
calculated as shown below:
+ . !
= ∗ (1 − )
100
+ . !
$ = ∗ (1 + )
100
% = ∗ 2.
Figure 2: schematic illustration of the trip time test in case of an earth fault