ZIV ZLV V3.70 Line PTT User Manual ENU
ZIV ZLV V3.70 Line PTT User Manual ENU
ZIV ZLV V3.70 Line PTT User Manual ENU
OMICRON PTL
User Manual
V1.100
Content
1. General .............................................................................................................................................3
2. Software and Hardware Requirements............................................................................................3
3. Hardware ..........................................................................................................................................4
4. Functional Range .............................................................................................................................4
5. XRIO Converter ................................................................................................................................5
6. Specific Protection Tests .................................................................................................................5
6.1 Close-Onto-a-Fault ..........................................................................................................................5
6.1.1 Manual Close/External Manual Close.........................................................................................5
1. General
This user manual describes details of testing ZIV ZLV relay with the OMICRON Protection Test Template.
General information on the usage of OMICRON Protection Testing Library items can be found in the
OMICRON PTL user manual.
Any CMC test set can be used with this Protection Test Template.
3. Hardware
There are multiple possibilities of wiring ZIV ZLV relay to a CMC test set. The advised connections are
shown in Figure 1. These connections are the default settings in the Hardware Configuration of the PTT.
VC
VN
VA
VB
IN
IC
IA
IB
CB aux (52a)
CB aux (52b)
Trip
Manual close
Start
4. Functional Range
Supported functions:
• Distance Protection (21/21N) (MHO/Quad/MHO or Quad zones 1-5 for Standard Protection
Scheme “Step Distance”)
• Load Encroachment (ph-ph)
• Load Encroachment (ph-gnd only with the same k0 Factor for all zones) (21)
• Close-Onto-Fault Detector (50SOF)
• Back-up Overcurrent Protection (50F/51F), (50N/51N)
The Relay Parameter Section of the XRIO Converter includes only protection parameters of supported
functions.
5. XRIO Converter
The Test Object contains ZIV ZLV XRIO Converter, which includes setting parameters of the modelled
protection relay. The setting parameters are built as an image of the ZivercomPlus V1.67 software.
6.1 Close-Onto-a-Fault
For testing Close-Onto-a-Fault (COF), the State Sequencer test module is used.