Sitarama Lift Irrigation Project Lift-2: Design of Air Washer Water Tank Resting On Ground

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 8

SITARAMA LIFT IRRIGATION PROJECT LIFT-2

Design Of Air washer Water tank resting on ground :-

Grade of concrete M 30
Grade o fsteel Fe 500

Design For Internal Water Pressure :-

L B D
Size of water tank = 4.3 X 1.5 X 1.1 1.1m

Design of Side walls ( Long wall) 4.3m

b /a 3.909

Considering the wall is fixed at 3 sides and force at the top.

Design of wall at the bottom:

Vertical Reinforcement :
BM coeff. For Max -ve BM (As per table-3 3370 part-IV) '= 0.090
BM coeff. For Max +ve BM = 0.015
Max -ve BM =0.09x10x1.13 1.1979 Kn-m
Max +ve BM =0.015x10x1.13 0.1997 Kn-m

Assume d1/d = 0.75


Where
d1 = effective thickness of wall
d = Total thickness of wall
Max B.M in long walls in vertical direction. = Mx* wa3 = 1.20 Kn-m
M/b*d2 = 3.444
Pt = 0.334 %
Hence d= /M/(3.059*b)
5.90 cm
However provide thickness of long wall at bottom = 15 cm
vertical reinforcement.

Hence provide % of reinforcement ) = 0.334 %

Area of reinforcement required=Ast.= 501.00 Sq.mm


Provide T-12 = 200 mm c/c
Area of reinforcement provides=Ast.= 565.00 Sq.mm
o.k
Horizontal reinforcement. o.k
BM coeff. For Max +ve & -v =
Max -ve BM =0.063x10x1.83 0.063 0.8385 Kn-m
Max +ve BM =0.027x10x1.83 0.027 0.3594 Kn-m
Assume d1/d = 0.75
Where
d1 = effective thickness of wall
d = Total thickness of wall
Max B.M in long walls in vertical
M/b*d direction.
2= = Mx* wa3 = 0.84 Kn-m
3.059
Pt = 0.240 %(min)
Hence d= /M/(3.059*b)
5.24 cm

However provide thickness of side walls = 15 cm

Horizontal Reinforcement(at the bottom ):


M/b*d2 = 0.37

As the side wall is designed as vertical cantilever


provide min % of reinforcement in Horizontal direction ( Based on the m 0.240 %

Area of reinforcement required=Ast.= 360.00 Sq.mm


Reint. In each face = 180.00
Provide T-12
T-16 for
forhorizontal.
top half ht.Reint Of=wall =
Of wall 250
500 mm c/c
Area of reinforcement provides=Ast.= 452.00 Sq.mm
o.k
SITARAMA LIFT IRRIGATION PROJECT LIFT-2

Design Of Air washer Water tank resting on ground :-

Grade of concrete M 30
Grade o fsteel Fe 500

Design For Internal Water Pressure :-

L B D
Size of water tank = 4.3 X 1.5 X 1.1 2.8m
1.1m
4.3m
6m
Design of Side walls ( short wall)

b /a 1.364

Considering the wall is fixed at 3 sides and force at the top.

Design of wall at the bottom:

Vertical Reinforcement :
BM coeff. For Max -ve BM (As per table-3 3370 part-IV) '= 0.060
BM coeff. For Max +ve BM = 0.016
Max -ve BM =0.06x10x1.83 0.7986 Kn-m
Max +ve BM =0.016x10x1.83 0.213 Kn-m

Assume d1/d = 0.75


Where
d1 = effective thickness of wall
d = Total thickness of wall
Max B.M in long walls in vertical direction. = Mx* wa3 = 0.80 Kn-m
M/b*d2 = 3.444
Pt = 0.334 %
Hence d= /M/(3.059*b)
4.82 cm
However provide thickness of long wall at bottom = 15 cm
vertical reinforcement.

Hence provide % of reinforcement ) = 0.334 %

Area of reinforcement required=Ast.= 501.00 Sq.mm


Provide T-12 = 200 mm c/c
Area of reinforcement provides=Ast.= 565.00 Sq.mm
o.k
Horizontal reinforcement. o.k
BM coeff. For Max +ve & - =
Max -ve BM =0.063x10x1.83 0.044 0.5856 Kn-m
Max +ve BM =0.027x10x1.83 0.016 0.213 Kn-m
Assume d1/d = 0.75
Where
d1 = effective thickness of wall
d = Total thickness of wall
Max B.M in long walls in vertical
M/b*d direction.
2= = Mx* wa3 = 0.59 Kn-m
3.059
Pt = 0.240 %(min)
Hence d= /M/(3.059*b)
4.38 cm

However provide thickness of side walls = 15 cm

Horizontal Reinforcement(at the bottom ):


M/b*d2 = 0.26

As the side wall is designed as vertical cantilever


provide min % of reinforcement in Horizontal direction ( Based on the m 0.240 %

Area of reinforcement required=Ast.= 360.00 Sq.mm


Reint. In each face = 180.00
Provide T-12
T-16 for
forhorizontal.
top half ht.Reint Of=wall =
Of wall 250
500 mm c/c
Area of reinforcement provides=Ast.= 452.00 Sq.mm
o.k
Design of Bottom slab of Tank

As the bottom slab is directly resting on the ground the water load
is directly transferred to ground. Hence it is not subjected to any B.M & S.F
Hence it is proposed to provide 300mmthick R.c.c. M30
base slab Wih 100mm thick Pcc M10 at bottom of base
slab = 150 mm

As IS-3370(PART-II) -2009

Min % of steel required For top zone (D/2=250 MM thick) 0.35 %


262.50 sq.mm
Hence provide T-12 @ spacing in both directions = 250 mm c/c
Area of reinforcement provided=Ast.= 452.00 sq.mm

Min % of steel required For bottom zone ( 100mm thick) 0.35 %


350.00 sq.mm
Hence provide T-12 @ spacing in both directions = 250 mm c/c
Area of reinforcement provided=Ast.= 452.00 sq.mm
CHECK FOR UPLIFT
Load due to blower with motor on graded slab :-

Static Weight with motor = 2.75 tons

Dynamic Weight = 4.95 tons

(Load date considered as per approved mechanical drawing by TS GENCO )


0.479m
Unit Weight of RCC Concrete = 2.5 t/m3
Thickness of Pedestal = 0.25 m

3.104m
2.294m
Equivalent Static Weight = 6.188 tons

Selft Weight of Pedestal = 6.064 tons


2.66m
Total Weight = 12.251 tons

Stress on graded slab = 1.826 t/m2