Generator Set Data Sheet: Fuel Consumption

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Model: C28D5 (X-Series)

Frequency: 50
Fuel Type: Diesel

» Generator set data sheet

Our energy working for you.™

Spec sheet: SS26-CPGK


Noise data sheet (Open/enclosed): ND50-OS550 / ND50-CS550
Airflow data sheet: AF50-550
Derate data sheet (Open/enclosed): DD50-OS550 / DD50-CS550
Transient data sheet: TD50-550

Standby Prime
Fuel consumption kVA (kW) kVA (kW)
Ratings 27.5 (22) 24.8 (19.8)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
gph 0.4 0.7 1.1 1.4 0.3 0.7 1.0 1.3
L/hr 1.63 3.25 4.88 6.50 1.50 3.00 4.50 6.00

Engine Standby rating Prime rating


Engine manufacturer Cummins
Engine model X2.5G2
Configuration 4 Cycle; In-line; 3 Cylinder Diesel
Aspiration Naturally Aspirated
Gross engine power output, kWm 27 24.37
BMEP at set rated load, kPa 851 768.1
Bore, mm 91.7
Stroke, mm 127
Rated speed, rpm 1500
Piston speed, m/s 7.62
Compression ratio 18.5:1
Lube oil capacity, L 6.5
Overspeed limit, rpm 1650
Regenerative power, kW 2
Governor type Mechanical - Std
Starting voltage 12 Volts DC

Fuel flow
Maximum fuel flow, L/hr 40
Maximum fuel inlet restriction, mm Hg 28.0249
Maximum fuel inlet temperature (°C) 60

Air
Combustion air, m3/min 2.30 2.30
Maximum air cleaner restriction, kPa 4

©2010 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and
Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy working for you.” are trademarks of Cummins Power
Generation. Other company, product, or service names may be trademarks or service marks of others.
Exhaust Standby rating Prime rating
Exhaust gas flow at set rated load, m3/min N/A N/A
Exhaust gas temperature, °C 660 660
Maximum exhaust back pressure, kPa 3.38

Standard set-mounted radiator cooling


Ambient design, °C 50
Fan load, KW m 0.6
Coolant capacity (with radiator), L 7
Cooling system air flow, m3/sec @ 12.7mmH2O 0.78
Total heat rejection, BTU/min 2561 N/A
Maximum cooling air flow static restriction mmH2O N/A

Open set derating factors kVA (kW)


Note: Standard open genset options running at 400V, 150m above sea level. For enclosed product derates, please refer to datasheet - DD50-
CS550.

27°C 40°C 45°C 50°C 55°C


Standby 27.5 (22) 26.1 (20.9) 25.7 (20.58) 25.2 (20.17) 24.7 (19.76)
Prime 24.8 (20) 23.5 (18.81) 23.2 (18.52) 22.7 (18.16) 22.2 (17.78)

Weights* Open Enclosed


Unit dry weight kgs 441.5 766.5
Unit wet weight kgs 605 930
* Weights represent a set with standard features. See outline drawing for weights of other configurations

Dimensions Length Width Height


Standard open set dimensions 1667 930 1247
Enclosed set standard dimensions 2082 930 1448

Genset outline
Open set

Fuel tank capacity: 150 l; option 500 l

Enclosed set

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

©2010 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and
Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy working for you.” are trademarks of Cummins Power
Generation. Other company, product, or service names may be trademarks or service marks of others.
Alternator data
Feature code Connection1 Temp rise degrees C Duty2 Alternator Voltage
- 3 Phase 163/125C S/P PI144E 380-415V
3 Phase 150/125C S/P PI144F 380-440V

Ratings definitions
Emergency Standby Limited-Time running Prime Power (PRP) Base Load (Continuous)
Power (ESP) Power (LTP): Power (COP)
Applicable for supplying power to Applicable for supplying power to a Applicable for supplying power to Applicable for supplying power
varying electrical load for the constant electrical load for limited varying electrical load for continuously to a constant electrical
duration of power interruption of a hours. Limited Time Running unlimited hours. Prime Power load for unlimited hours.
reliable utility source. Emergency Power (LTP) is in accordance with (PRP) is in accordance with ISO Continuous Power (COP) in
Standby Power (ESP) is in ISO 8528. 8528. Ten percent overload accordance with ISO 8528, ISO
accordance with ISO 8528. Fuel capability is available in 3046, AS 2789, DIN 6271 and BS
Stop power in accordance with ISO accordance with ISO 3046, AS 5514.
3046, AS 2789, DIN 6271 and BS 2789, DIN 6271 and BS 5514.
5514.

Formulas for calculating full load currents:

Three phase output Single phase output

kWx1000 kWxSingleP haseFactor x1000


Voltagex1. 73x0.8 Voltage

See your distributor for more information.

Cummins Power Generation


Manston Park, Columbus Avenue
Manston, Ramsgate
Kent CT12 5BF, UK
Telephone: +44 (0) 1843 255000
Fax: +44 (0) 1843 255902
E-Mail: cpg.uk@cummins.com
Web: www.cumminspower.com

©2010 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and
Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy working for you.” are trademarks of Cummins Power
Generation. Other company, product, or service names may be trademarks or service marks of others.