Generator Set Data Sheet: 312.5 kVA Standby
Generator Set Data Sheet: 312.5 kVA Standby
Generator Set Data Sheet: 312.5 kVA Standby
Frequency: 60
Fuel Type: Diesel
Standby Prime
Fuel consumption Kw (kVA) Kw (kVA)
Ratings 250 (312.5) 225 (281.3)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 5.1 8.6 12.2 16.3 3.7 6.8 10.1 13.7
L/hr 23 39 56 74 17 31 46 63
Fuel flow
Maximum fuel flow, L/hr 165
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature (°C) 70
Air
Combustion air, m3/min 24.7 23.3
Maximum air cleaner restriction, kPa 6.2
©2007 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation
and Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy working for you.” are trademarks of Cummins
Power Generation. Other company, product, or service names may be trademarks or service marks of others.
Exhaust Standby rating Prime rating
Exhaust gas flow at set rated load, m3/min 65.2 56.1
Exhaust gas temperature, °C 580 500
Maximum exhaust back pressure, kPa 10.2
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
©2007 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation
and Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy working for you.” are trademarks of Cummins
Power Generation. Other company, product, or service names may be trademarks or service marks of others.
Alternator data
Feature code Connection1 Temp rise degrees C Duty2 Alternator Voltage
B252 Wye, 3 Phase 125/105 S/P HC4D 416-480V
B683 Wye, 3 Phase 150/125C S/P UCD274K 440-480
Ratings definitions
Emergency Standby Power (ESP) Limited-Time running Power Prime Power (PRP): Base Load (Continuous) Power
Applicable for supplying power to Applicable for supplying power to a Applicable for supplying power to Applicable for supplying power
varying electrical load for the constant electrical load for limited varying electrical load for unlimited continuously to a constant electrical
duration of power interruption of a hours. Limited Time Running hours. Prime Power (PRP) is in load for unlimited hours.
reliable utility source. Emergency Power (LTP) is in accordance with accordance with ISO 8528. Ten Continuous Power (COP) in
Standby Power (ESP) is in ISO 8528. percent overload capability is accordance with ISO 8528, ISO
accordance with ISO 8528. Fuel available in accordance with ISO 3046, AS 2789, DIN 6271 and BS
Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.
3046, AS 2789, DIN 6271 and BS 5514.
5514.