MCC Panel
MCC Panel
MCC Panel
CV
DOCUMENT STATUS:
(Duplicate copy)
Observed Error(%) @ 60 Hz-P 0.081 -0.124 0.338 0.083 0.008 0.123 0.108 0.215 0.075
Notes:
1. The certificate shall not be reproduced except in full, without prior written approval of the issuing authority.
2. Vavg = 3-phase average voltage (line to neutral) in volt, Iavg = 3-phase average current in ampere
7.W Integrated over a period of time is equal to Wh. W accuracy is tested over a period of time(upto 30 samples)
This is to certify:
That the Motor Starter
Issued to
Schneider Electric Industries SAS
GRENOBLE, France
Application :
Motor- protected circuit breaker including overload release, thermal-magnetic or magnetic
release. Accessories: Under voltage trip, shunt trip, voltage trip, analogue modules, auxiliary
contacts
Product(s) approved by this certificate is/are accepted for installation on all vessels classed
by DNV GL.
This Certificate is subject to terms and conditions overleaf. Any significant change in design or construction may render this Certificate invalid.
The validity date relates to the Type Approval Certificate and not to the approval of equipment/systems installed.
© DNV GL 2014. DNV GL and the Horizon Graphic are trademarks of DNV GL AS.
Job Id: 262.1-003417-10
Certificate No: TAE0000202
Product description
Motor starters (circuit breaker/ contactor combination) type:
GV2-ME01, GV2-ME02, GV2-ME03, GV2-ME04, GV2-ME05, GV2-ME06, GV2-ME07,
GV2-ME08, GV2-ME10, GV2-ME14, GV2-ME16, GV2-ME20, GV2-ME21, GV2-ME22 and GV2-ME32.
GV2-P01, GV2-P02, GV2-P03, GV2-P04, GV2-P05, GV2-P06, GV2-P07, GV2-P08, GV2-P10, GV2-P14,
GV2-P16, GV2-P20, GV2-P21, GV2-P22 and GVP32.
GV2-L03, GV2-L04, GV2-L05, GV2-L06, GV2-L07, GV2-L08, GV2-L10, GV2-L14, GV2-L16, GV2-L20,
GV2-L22 and GV2-L32.
Application/Limitation
Motor- protected circuit breaker including overload release, thermal magnetic release.
Applicable for use in an IT net with a voltage up to 690 V.
Technical info:
“TeSys protection components”, parts of manufacturer’s catalogue.
Application For 3C Compulsory Certification Product Description
Catalogue 99422 dated March 1994 and catalogue ART. 27501 dated October 2001
Test reports;
STIE test reports nos. 00901-CB2013CQC-055141-1 ans 2 issued 2015-02-06.
CQC Test Certificate Appendix no. 2007010307236560.
For GV2-P:
ASEFA reports K11-94-06F, K11-94-06G, K11-94-22B, K11-94-25B, K11-94-19B,
K11-94-05C.
ASEFA certification of conformity no. 05-04BT and 06-04BT (GV2-P32).
For GV2-L:
ASEFA reports K11-94-35F, K11-94-35G, K11-94-47B, K11-94-51B, K11-94-43B,
K11-94-05C.
ASEFA certification of conformity no. 085-04BT and 086-04BT (GV2-L32).
Type tests according to IEC 60947-1, IEC 60947-2 (4th ed. + A1 & A2) including Annex H, IEC60 947-4-
1 (3rd ed. + A2), sequence 1, 2 & 3, and environmental tests.
Marking of product
Telemecanique - Schneider Electric - Type designation.
Periodical assessment
The scope of the periodical assessment is to verify that the conditions stipulated for the Type approval is
complied with and that no alterations are made to the product design or choice of materials.
END OF CERTIFICATE
This is to certify:
That the Contactor
Issued to
Schneider Electric Industries S.A.S.
Eybens, Isere, France
Application :
Contactors and reversing / pole-changing contactors with ac control circuit for installation in
enclosures onboard ship and mobile offshore units.
Products approved by this certificate are accepted for installation on all vessels classed by
DNV GL.
This Certificate is subject to terms and conditions overleaf. Any significant change in design or construction may render this Certificate invalid.
The validity date relates to the Type Approval Certificate and not to the approval of equipment/systems installed.
© DNV GL 2014. DNV GL and the Horizon Graphic are trademarks of DNV GL AS.
Job Id: 262.1-007395-6
Certificate No: TAE000033S
Product description
Electric contactors with ac or dc control circuit with electromechanical or electronic coils of type LC1-D _
_ and LC2-D _ _ reversing / pole-changing contactors with 3 poles and 4 poles and auxiliary contact
blocks. Contactor equipped with 1 NO and one NC contact.
Accessories:
Auxiliary contactor CAD-32… and CAD-50…
Aux contacts blocks and Accessories LAD-N, LAD-C, LAD-8N
LAD-T, LAD-S, LAD-R
LAD-6K10, LAD-4, LAD-9
May be followed by: Suffix 3 = Spring terminals
Suffix 6 = Lug connections
Suffix 9 = Faston connections
Application/limitation
With Uimp = 6 kV the max. rated voltage is 600 V when used in a IT (ship) net. It can be used in
applications with directly earthed systems with rated voltage of 400/690 V.
Test reports:
Electrical type tests test after IEC 60947-4-1 & IEC60947-5-1: VDE test reports TFR 242646-1 and 2
dated 2017-12-20, VDE test reports no. 234353 issued 2017-10-10, VDE test report no. 246224 issued
2018-03-20.
Environmental tests: F- Lab test report no. TFR_201703851_002, TFR_201703851_003 and
RI_201703851_004 dated 2017-09-01, Volta test report no. TFR_201604 dated 2017-02-23, Schneider
test reports nos. 545-00 dated April 2001, 546-00 and 548-00 dated June 2001, 547-00 dated October
2001, G0010077A, G0010078A and G0010080A dated October 2000, and GV 10058B dated 2001-05-31.
Marking of product
Telemecanique / Schneider Electric – Type designation
Periodical assessment
The scope of the periodical assessment is to verify that the conditions stipulated for the Type approval is
complied with and that no alterations are made to the product design or choice of materials.
To whomsoever it may
The below refered products are tested as per the relevant IS/IEC standards and the process meets the schneider electric - chennai ISO 9001:2008
procedure. We confirm the terms and conditions are as per the order acceptance/catalogue.
Disclaimer: Terms and conditions shall be changed without prior notice
Certificate of
Customer Name : Electro Care (India) Private Limited
Or der No : 0300379127 & 300379129
1 Rating,Type Passed
2 High Voltage Test Passed
3 Test of Instantaneous Tripping Passed
4 Conventional Non Trip Current Test Passed
5 Conventional Trip Current Test Passed
6 Visual Inspection Passed
Subject to correct installation, maintenance and use conforming to its intended purpose, to the applicable regulations and
standards, to the supplier's instructions and to accepted rules of the art.
This declaration becomes invalid in the case of any modification to the products not authorized by us.
Alain BERNERD
Vice President
Customer Satisfaction and Quality
Industrial Automation
Annex - Table of product references: RXZE sockets and RXM02/RXM04 protection modules
RXZE1M2C RXM021BN
RXZE1M4C RXM021FP
RXZE2M114 RXM021RB
RXZE2M114M RXM040W
RXZE2M2N RXM041BN7
RXZE2M4N RXM041FU7
RXZE2S108M
RXZE2S111M
RXZE2S114M
RXZE2S114S
RXZE14P
Subject to correct installation, maintenance and use conforming to its intended purpose, to the applicable regulations and
standards, to the supplier's instructions and to accepted rules of the art.
This declaration becomes invalid in the case of any modification to the products not authorized by us.
Alain BERNERD
Vice President
Customer Satisfaction and Quality
Industrial Automation
Annex - Table of product references: RXZE sockets and RXM02/RXM04 protection modules
RXZE1M2C RXM021BN
RXZE1M4C RXM021FP
RXZE2M114 RXM021RB
RXZE2M114M RXM040W
RXZE2M2N RXM041BN7
RXZE2M4N RXM041FU7
RXZE2S108M
RXZE2S111M
RXZE2S114M
RXZE2S114S
RXZE14P
CV
DOCUMENT STATUS:
Beständigkeit gegen – Ozon gut, Öl/Benzin gut, Lösungsmittel gut, Säuren/Laugen gut,
resistance to: Alterung sehr gut
Ozone good 200ppm/30°C48h without cracking, Oil/Petrol good,
Solvents good, Acids/bases good, Weathering good
Besondere Eigenschaften – bei Kupfer- und Silberkontakt: ätzend Lackdifferenz: keine Fleckenbildung
specifice properties: corrosive effect on copper and silver: corrosive paint staining: non staining
Diese Angaben wurden sorgfältig ermittelt und dienen der Beratung, ohne Rechtsverbindlichkeit.
This information on synthetic rubber foam is presented to our best knowledge. All test data are average values and should be
considered as guidline, not as a specification.
Die Daten beziehen sich auf ungespannte, unbelastete Teile. Diese Angaben gestalten nur eine Vorauswahl, bei wichtigen oder
extremen Anwendungsfällen müssen unbedingt praktische Versuche erfolgen.
The data refer to parts neither strained nor stressed. The indications above only allow a pre-selection. In important or extreme
application practical tests have to be performed absolutely.
Technische
Lieferspezifikationen
Technical specifications for
delivery
Artikelbezeichnung: Klebeband
Article designation: Adhesivetape
Anwendung - Klebt auf fast allen Materialien, geeignet auch für schwierige
Application: Oberflächen wie Schäumen und PE-Folien
suitable for nonpolar PE-foils and cellular materials
Diese Angaben wurden sorgfälltig ermittelt und dienen der Beratung, ohne Rechtsverbindlichkeit.
This information on synthetic rubber foam is presented to our best knowledge. All test data are average values and should be
considered as guidline, not as a specification.
Die Daten beziehen sich auf ungespannte, unbelastete Teile. Diese Angaben gestalten nur eine Vorauswahl, bei wichtigen oder
extremen Anwendungsfällen müssen unbedingt praktische Versuche erfolgen.
The data refer to parts neither strained nor stressed. The indications above only allow a pre-selection. In important or extreme
application practical tests have to be performed absolutely.
Sicherheitsdatenblatt
gemäß 91/155 EWG - Stand.19.06.2007
Safety Data Sheet
according to 91/155 EEC- Status: 19.06.2007
3. Mögliche Gefahren
Hinweis auf besondere Gefahren: keine
Besondere Gefahrenhinweise für Mensch und Umwelt: nicht relevant
3. Hazards identification
Special risks: none
Special environmental and health risks: not applicable
15. Vorschriften
Kennzeichnung: ist nach Gefahrstoff – Verordnung vom 01.10.1986 nicht kennzeichnungspflichtig.
15. Regulatory information
Labeling: Not subject to mandatory labeling, according to German Hazardous Substances Ordinance of
01.10.1986
CV
DOCUMENT STATUS:
DOCUMENT STATUS:
SHEET 06 OF 06
U
PHOTOGRAPH NO.: 1 6 1 7 - 0 1 8 0 1 3 / 0 0 1 7 9 6 7 3 / C
LT PANEL
CUSTOMER : PURITA WATER SOLUTIONS PVT. LTD.
END USER : BHARTIYA RAIL BIJLEE COMPANY LTD.
DOCUMENT STATUS:
DOCUMENT STATUS:
CV
DOCUMENT STATUS:
Hongshang
Hongshang Heat Shrinkable Materials Co., Ltd Issue 2011
No.9 Qilin Rd, Nankeng Cun, Bantian, Longgang, Shenzhen Date 2011-9-13
TECHNICAL REPORT ON
1 SCOPE
This specification covers the requirements for one type of flexible electrical
insulating, extruded tubing whose diameter will reduce to a predetermined size
upon the application of heat in excess of 70°C .This tubing meets the
requirements of UL 224 with a continuous operating temperature range of -55°C
to 125°C. H-2(Z) is free of any substances including polybrominated biphenyls
(PBB) and polybrominated biphenyl oxides (PBBO) and meet the requirement of
Latest RoHS ..
2 Applicable Documents
This specification takes precedence over documents referenced herein. Unless
otherwise specified, the latest issue of referenced documents applies. The
following documents form a part of this specification to the extent specified herein.
UL 224 Extruded Insulating Tubing
CSA CANADIAN STANDARDS ASSOCIATION
C22.2 No.198.1 Extruded Insulating Tubing
ASTM D 2671 Standard Test Method for Heat Shrinkable Tubing for
Electrical Use
IEC 60093-1980 Methods of Test for Volume Resistance and Surface
Resistance of Solid Electrical Insulating Materials
3 REQUIREMENTS
3.1 Materials
H-2(Z) flexible heat shrinkable tubing is made from radiation crosslinked
polyolefin. Specifically designed formulation makes the tubing to have outstanding
physical, chemical and electrical properties, and also meet the requirement of
RoHS and other environment concerned standards.
3.2 Color
The Standard colors for the tubing shall be black, red, blue, yellow, green and
white
3.3 Properties
The tubing shall meet all requirements of Table 1
LC = ( L1 – L0)/L0 x 100
LC = longitudinal change
L0 = length before shrinkage
L1 = length after shrinkage
3.4.2 Eccentricity
Perform the test in accordance with UL 224.
Eccentricity % = ( 1 – W1/W2) x 100
Table 1 Requirements
Applications
Widely used for electrical insulation and protects in-line components, disconnect
terminals, and splices with its high strength and excellent resilience. Bundles wires
for very flexible light-duty harnesses. Identifies or color-codes, wires, cables,
terminals, and components.
Features/Benefits
• Free from Environment harmful substance such as PBBS, PBBES, PBBOS and
toxic heavy metal compounds in its components.
• Low shrunk temperature reduces installation time and the risk of damage to
temperature- sensitive components.
• Very flexible, does not easily wrinkle when bent.
• Higher temperature rating, better thermal stability and higher resistance to
physical abuse than non-cross linked materials.
Standard Color: Black, white, blue, yellow, green, red, and grey.
Other colors available on request
Technical Specifications
RTIL/PRODUCTSPECS/2005 1
RIGIL TECHNO INDIA PVT.LTD
RTIL/PRODUCTSPECS/2005 2
RIGIL TECHNO INDIA PVT.LTD
Size selection
Always order the largest that will shrink snugly over the component to be covered.
Special order sizes are available on request.
Standard Packaging
On Spools
Marking
Marked with UL/CSA/-F-legends
Ordering Description
Specify Product name, Size, Color.
RTIL/PRODUCTSPECS/2005 3