Elmeasure Manual Transfer Switch Catalog
Elmeasure Manual Transfer Switch Catalog
Elmeasure Manual Transfer Switch Catalog
MTS 250
Manual Transfer
Switch
User-friendly Installation | Safe Changeover
Benefits:
Elmeasure Manual Transfer Switch (MTS) is designed to provide smooth
and safe transmission of load from one power source to another and back The safest changeover during the failure of a primary source
again. MTS is reliable, safe and is is operated with a single handle
High short-circuit withstand capacity
manually to ensure supply continuity
facilitate easy installation and simplified wiring connections
MTS has a 3 position switch I-O-II High electrical and mechanical life
A Enlarged
J2
R
J1
P
OX
elmeasure.com 29
Specifica ons Dimensions Details
63A-630A
4 POLE MTS A B C D E J J1 J2 K L P R S T U OX Y Y1
DIMENSIONS
MTS-63A 265 116 185 140 125 125 82 200 86 6.5 30 13 23 2.5 103 8 42 92
MTS-100A 265 116 185 140 125 125 82 200 86 6.5 30 13 23 2.5 103 8 42 92
MTS-FR1-125A 265 116 185 140 125 125 82 200 86 6.5 30 13 23 2.5 103 8 42 92
MTS-FR2-125A 327 139 235 185 165 173 97 257 102 6.5 35 22 26 3.5 115 8 57 127
MTS- 160A 315 135 220 185 165 173 95 255 102 6.5 38 25 25 3.5 115 8 56 126
MTS-200A 370 185 225 215 200 228 95 305 110 6.5 55 25 40 3.5 148 10.8 72 153
MTS-250A 370 185 225 215 200 228 95 305 110 6.5 55 30 40 3.5 148 10.8 72 153
MTS-315A 370 185 255 215 200 228 95 305 108 6.5 55 30 40 3.5 148 12 72 152
MTS-400A 500 241 320 265 245 290 110 385 180 9.5 72 40 40 5 205 12 83 195
MTS-630A 500 260 320 265 245 290 117 385 180 9.5 65 42 55 6 225 12 83 195
Technical Specification:
MTS MTS MTS -FR1 MTS MTS MTS MTS MTS MTS
63A-4P 100A-4P 125A-4P 160A-4P 200A-4P 250A-4P 315A-4P 400A-4P 630A-4P
GENERAL CHARACTERISTICS
Thermal current Ith (40°C) 63 A 100 A 125 A 160 A 200 A 250 A 315 A 400 A 630 A
Max. Normal rating of fuses 63 100 125 160 200 250 315 400 630
Insulation voltage Ui (V) 750 750 750 750 1000 1000 1000 1000 1000
Dielectric strength (V) 50 Hz 1 mn. 4000 4000 5000 5000 5000 5000 5000 8000 8000
Impulse voltage (kV) 6 6 6 6 8 8 8 12 12
Rated operational currents Ie (A)
415 VAC-AC 23A 63 100 125 160 200 250 320 400 630
500 VAC-AC 23A 55 55 100 130 160 200 250 315 315
440 VDC-DC 21A 63 100 125 160 200 250 320 400 500
440 VDC-DC 22A 63 100 125 130 160 200 250 400 500
440 VDC-DC 23A 63 63 125 130 160 200 250 400 500
Protection
Short-circuit current
with fuses (kA rms) 80 80 80 80 80 80 80 80 80
Fuse rating 63 100 125 160 200 250 315 400 630
Peak short-circuit
making capacity (kA rms) 15 15 20 20 20 30 45 45 45
Admissible short
time current 1 sec (kA rms) 5 5 7 7 7 9 13 13 13
Making & Breaking Characteristics
Breaking Capacity (Arms)
415 VAC pf-0.35 504 504 1000 1280 1600 2000 2520 3200 5040
Making Capacity (Arms)
415 VAC pf-0.35 630 630 1250 1600 2000 2500 3150 4000 6300
Endurance
Mechanical No. of Operations 10000 10000 8000 8000 8000 8000 5000 5000 5000
Electrical No. of Operations 2500 1500 1000 1000 1000 1000 1000 1000 1000
Operating Force (Nm) 3.5 3.5 9.5 9.5 9.5 11 11 17 17
Connection
Min. Cu Cable / Bus bar size (mm2) 16 35 50 70 95 120 185 240 40 x 8
Min. Al Cable / Bus bar size (mm2) 25 2 x 25 70 95 150 185 240 300 40 x 8 x 2
30 elmeasure.com