Loop Cheking Procedure
Loop Cheking Procedure
Instrumentation
312SHARES
ShareTweet
Loop checking is the final process before the commissioning of the processing system. Loop
checking is the process that confirms the components wired correctly and also helps to ensure
that the system is functioning as designed.
The loop checking checks the connection between each component in the control loop. A control
loop consists of transmitter/sensor, process controller, final control element.
Before start, the loop check include, first list the number of loops, test actions, the procedure for
documenting the check and plan should specify the type and characterization of signal. For
example, differential flow meter generates a signal that has a square root relationship between
flow rate and differential pressure.
For loop checking the test to be carried out while there is no electric connection otherwise, the
circuit to be tested should be isolated from the electric supply.
Earth resistance tests are required to confirm that the installed earthing system will cause the
circuit protection devices to operate and maintain the integrity of the cable if there is a fault
between the active parts and the exposed conductive parts.
The resistance from any point of the electric installation should be earthed. The resistance from
the earthing electrode to the point where the main earthing conductor is connected to the neutral
conductor of the supply system shall not exceed 5 ohms.
Connect the short lead to the earth electrode and measure the earth resistance of the main
earthing conductor
The resistance shall not exceed 5 ohms for the main earthing conductor
Using the long lead and zeroed meter, measure for each circuit, the earth conductor
resistance from the circuit extremity to the switchboard.
To confirm the measured values are less than those values as provided by table
This test is applicable to all circuits, including socket outlets circuit, lighting circuits and
fixed equipment circuits.
The insulation resistance tests to ensure there is no current flow between conductor and ground
or insulation surface. If there is no current flow the wire could prevent electric shock hazards,
fire hazards and equipment damage.
Test procedure:
Polarity test:
Polarity tests are carried out to ensure that the correct connection of the active, neutral and
ground conductors to the electrical equipment ensures that the switches are not installed in
neutral conductors.
Test procedure:
Isolate the active conductors by turning the main switch OFF and tagging
Confirm the consumer and sub main cables by simply testing from the point of
distribution board to the main switch board using an ohm meter and long test loads. Test result=
0 ohms
Confirm the switching of the active conductors using an ohm meter with the long cable
connected to the active conductor on the board and the short wire connected to the terminals of
the switch as follows
Switch ON = 0Ώ for both terminals, Switch OFF = 0Ώ for one terminal and infinite for
the other terminal.
With the MEN link in place, confirm the polarity of the sockets using a 10Ώ resistor and
an ohm meter. Connect the 10Ώ resistor between the active circuit conductor and the neutral bus,
then connect the multimeter cable to the ground terminal and the second cable to the active
terminal. Test the resistance value for.
This test is performed to confirm that the impedance value of the fault loop of each circuit will
be low enough to guarantee the operation of the protection device during a fault.
Test procedure
https://automationforum.co/basic-control-system-interview-questions/