OPERATING MANUAL

OPERATING MANUAL
PID
PID TEMPERATURE
TEMPERATURECONTROLLER
CONTROLLER
UTC-1202, 2202
UTC-121P,221P & 421P
UTC 1202

ºC

23 4 UTC 2202
ºC

R1

R2 235
PV

R1
234 PV

235
SV

R2 SV

TUNE TUNE

SET ENT SET ENT

Technical Specification
Model UTC 1202 UTC 2202
UPPER:- 4 Digit 7 seg 0.70”,red LED Display
Display
LOWER:- 4 Digit 7 seg 0.50”,green LED Display
Size(HXWXD) 96 X 96 X 50 mm 72 X 72 X 85 mm
Panel Cutout 92 X 92 mm 68 X 68 mm
Input J, K, PT-100 (selectable)
Temperature J: 0 to 600°C / K: 0 to 1200°C /
Range PT-100: -99 to 400ºC /PT.1: -99.0 to 400.0°C
Control Action PID /TP/ ON-OFF (selectable)
Output 2 relay, 1 C/O contact, 230V AC, 5A ; 1 SSR,12V DC, 30mA DC
Power Supply 100 to 250V AC, 50 / 60 Hz, Approx 4VA
Protection Level IP-65(Front side) AS per IS/IEC 60529:2001
(As per request)
Operating Relative Up to 95% RH Non Condensing
Temperature 0°C To 55°C Humidity
Note:
1) If Sensor Connection is reversed, Display will show “SRE” message.
2) If Sensor is not connected, Display will show Open message.
3) Every time the instrument is turned ON, Following pattern will be displayed
POWER ON

8 8 88 All digit segment will be turned ON for 3 sec


8888
j Previous or default sensor input will be displayed for 2 sec
INpt
34 Process Value
Set Value
234
Connection Diagram
+

1 L 100 ~ 8
250V AC TC
50/60 Hz
20 19 18 17 16 15 14 13 12 11 2 N 4VA
- 9
- O/P + !
- TC
+
RTD
S.S.R RTD 3 NO 10

4 C 11
RELAY-1

100 ~
250V AC NC
50/60 Hz ! 5 NC 12
4VA
RELAY-1 RELAY-2
NC C NO NC C NO 6 -O/P RELAY-2 C 13
L N
S.S.R
1 2 3 4 5 6 7 8 9 10 NO
+

7 14

UTC-1202,2202 Page - 1 www.multispanindia.com


Set Point Setting
Key Operation
1) Press SET key to go parameter setting. 34 Process Value
2) Press or key to change value or to select option. 234 Set Value

key
3) Press ENT key to save change in setting
4) Press key for 6 sec to start/stop PID AUTO TUNING set1 Set Point-1

ENT
5) Press + key for 3 sec to go to factory setting mode. 234

Press
6) Orange color LED glows during auto tuning mode.
set2 Set Point-2
255
Basic Configuration Press SET key for 3 sec to
enter Password
TO ENTER BASIC pass Password Message
CONFIGURATION 50
SETTING, ENTER “73”

pass Password Message


73
SET

INPT Input ( J / K / Pt.1 / Pt100 ) Press SET key


j K P T. 1 P T

OFST OFF-SET
t2md SOKT,SKRG,SKPS,ALMT,ONDL,OFF
0 almt
IF T2MD=OFF
SLL Set Point Low Limit
t2ut SEC/MIN/HOUR
0 E-AL
SHL Set Point High Limit
s2md INDIVIDUAL/RELATIVE
600 indu IF RELATIVE (-50°C To +50°C)

CTRL Control Action (PID/ON-OFF/TP) end IF R1/R2 MD=OFF


PID O N O F T P
NO Save / No
HEAT, COOL, H-AL,
R1MD L-AL, I-AL, O-AL, OFF Press ENT key to
Press SET key
HEAT
IF R1MD=OFF Save & Exit
tIMD SOKT,SKRG,SKPS,ALMT,ONDL,OFF
SOHT
IF T1MD=OFF
tIUT SEC/MIN/HOUR
HOUR

r2md HEAT, COOL, H-AL,


L-AL, I-AL, O-AL, E-AL, OFF
E-AL
IF R2MD=OFF

UTC-1202,2202 Page - 2 www.multispanindia.com


1 2 3 4

1 2 34 PV
1 2 3 4

F C S T
Press
for 3 sec
+ key

1234 SV
Y E S n O

yes : press ENT key to apply factory set


values as shown in table.

nO : press ENT key to escape


from factory setting.
PID AUTO-TUNING
Press key for 6 sec to start/stop Factory Setting
PID auto-tuning FACTORY SETTING
SR. PARAMETER VALUES
1 PB 20.0
2 IT 300
Control Parameter 3 DT 75
4 CT ( For PID) 15 SEC.
5 PB 2 5°C
TO ENTER CONTROL 6 CT 2 08
PARAMETER 7 MR 0°C
8 OFFSET 0°C
SETTING, ENTER “37”
pass Password Message 9
10
HYSTERESIS-1
HYSTERESIS-2
3°C
3°C
37 11
12
TIME-1
TIME-2
6 SEC
6 SEC
SET
IF PID SELECTED IF ON-OFF SELECTED IF TP SELECTED

PID
Parameters PID ON-OFF
Parameters ONOF TP
Parameters
TP
PARA PARA PARA
SET
IF R1MD = OFF SET SET

Proportional
Band Pb Hysteresis
HYS1 PB2
20.0 3 5
IF T1MD = OFF
key
Integral
Time It TIM1 CT2
SET

300 3 8
Press

key
IF R2MD = OFF
Derivative DT or E-AL
HYS2 MR

SET
Time
75 3 0

Press
IF T1MD = SOAK
IF T2MD = OFF or SKPS or SKRG
Cycle Time CT TIM2 TIM1
15 3 6
key

IF R2MD = OFF
or E-AL
Manual Reset
MR Press ENT key to HYS2
SET

0 Save & Exit 3


Press

IF T2MD = OFF
IF T1MD = SOAK
or SKPS or SKRG
TIM1 TIM2
6 6
IF R2MD = OFF hys2 Press ENT key to
Save & Exit
or E-AL 3
IF T2MD = OFF TIM2 Sr.
1
2
Parameter
PB
Range for J, K, PT100
000 to 999.9
Range for PT.1 sensor
000 to 999.9
6 3
IT
DT
000 to 9999
000 to 9999
000 to 9999
000 to 9999
4 CT 4 sec to 99 sec 4 sec to 99 sec
Press ENT key 5 MR -9 to +9 -9.0 to +9.0
6 PB 2 2 to 20 2.0 to 20.0
to Save & Exit 7 Time 1 1 to 999 Sec/MIN/HR 1 to 999 Sec/MIN/HR
8 Hysteresis 1°C to 50°C 0.1°C to 50.0°C
9 Off-set correction -20°C to +20°C -20.0°C to +20.0°C
10 CT 2 4 Sec to 99 Sec. 4-99 Sec
11 Time 2 1 to 999 Sec/MIN/HR 1 to 999 Sec/MIN/HR

UTC-1202,2202 Page - 3 www.multispanindia.com


Safety Precautions
All safety related codifications, symbols and instructions that appear in this operating manual
or on the equipment must be strictly followed to ensure the safety of the operating personnel as
well as the instrument.
If all the equipment is not handled in a manner specified by the manufacturer, it might impair the
protection provided by the equipment .
=> Read complete instructions prior to installation and operation of the unit.
WARNING : Risk of electric shock.
Warning Guidelines
1) To prevent the risk of electric shock power supply to the equipment must be kept OFF while doing the wiring
arrangement. Do not touch the terminals while power is being supplied.
2) To reduce electro magnetic interference, use wire with adequate rating and twists of the same of equal size shall
be made with shortest connection.
2
3) Cable used for connection to power source, must have a cross section of 1mm or greater. These wires
should have insulations capacity made of at least 1.5kV.
4) When extending the thermocouple lead wires, always use thermocouple compensation wires for wiring for the RTD
type, use a wiring material with a small lead resistance (5Ω max per line)and no resistance differentials among
three wires should be present.
5) A better anti-noise effect can be expected by using standard power supply cable for the instrument.

Installation Guidelines
1) This equipment, being built-in-type, normally becomes a part of main control panel and such in case the
terminals do not remain accessible to the end user after installation and internal wiring.
2) Do not allow pieces of metal, wire clippings, or fine metallic fillings from installation to enter the product
or else it may lead to a safety hazard that may in turn endanger life or cause electrical shock to the operator.
3) Circuit breaker or mains switch must be installed between power source and supply terminal to
facilitate power ‘ON’ or ‘OFF’ function. However this mains switch or circuit breaker must be
installed at convenient place normally accessible to the operator.
4) Use and store the instrument within the specified ambient temperature and humidity ranges as
mentioned in this manual.
Mechanical Installation
B 136mm - 5.35 inches
UTC 1202 D E
F
120mm - 4.72 inches

ºC

R1
234 PV
MODEL A B C D E F
A R2 235 SV
C
TUNE
DIMENSIONS 96mm 96mm 92mm 92mm 3mm 50mm
SET ENT

B D E F 95mm - 3.75 inches

UTC 2202
ºC
85mm - 3.34 inches

23 4 PV
MODEL A B C D E F
R1
C
A R2

TUNE
235 SV
DIMENSIONS 72mm 72mm 68mm 68mm 3mm 85mm
SET ENT

1) Prepare the panel cutout with proper dimensions as show above.


2) Fit the unit into the panel with the help of clamp given.
3) The equipment in its installed state must not come in close proximity to any heating source,
caustic vapors, oils steam, or other unwanted process by products.
4) Use the specified size of crimp terminal (M3.5 screws) to wire the terminal block. Tightening the
screws on the terminal block using the tightening torque of the range of 1.2 N.m.
5) Do not connect anything to unused terminals.

Maintenance
1) The equipment should be cleaned regularly to avoid blockage of ventilating parts.
2) Clean the equipment with a clean soft cloth. Do not use isopropyl alcohol or any other cleaning agent.
3) Fusible resistor must not be replaced by operator.

Product improvement and upgrade is a constant procedure. So for more updated operating information and support,
Please contact our helpline : +91-9978991474/82 or Email at marketing@multispanindia.com Ver: 01-2017
UTC-1202, 2202 Page - 4 www.multispanindia.com