Operating Manual Pid Temperature Controller UTC-1202, 2202
Operating Manual Pid Temperature Controller UTC-1202, 2202
Operating Manual Pid Temperature Controller UTC-1202, 2202
OPERATING MANUAL
PID
PID TEMPERATURE
TEMPERATURECONTROLLER
CONTROLLER
UTC-1202, 2202
UTC-121P,221P & 421P
UTC 1202
ºC
23 4 UTC 2202
ºC
R1
R2 235
PV
R1
234 PV
235
SV
R2 SV
TUNE TUNE
Technical Specification
Model UTC 1202 UTC 2202
UPPER:- 4 Digit 7 seg 0.70”,red LED Display
Display
LOWER:- 4 Digit 7 seg 0.50”,green LED Display
Size(HXWXD) 96 X 96 X 50 mm 72 X 72 X 85 mm
Panel Cutout 92 X 92 mm 68 X 68 mm
Input J, K, PT-100 (selectable)
Temperature J: 0 to 600°C / K: 0 to 1200°C /
Range PT-100: -99 to 400ºC /PT.1: -99.0 to 400.0°C
Control Action PID /TP/ ON-OFF (selectable)
Output 2 relay, 1 C/O contact, 230V AC, 5A ; 1 SSR,12V DC, 30mA DC
Power Supply 100 to 250V AC, 50 / 60 Hz, Approx 4VA
Protection Level IP-65(Front side) AS per IS/IEC 60529:2001
(As per request)
Operating Relative Up to 95% RH Non Condensing
Temperature 0°C To 55°C Humidity
Note:
1) If Sensor Connection is reversed, Display will show “SRE” message.
2) If Sensor is not connected, Display will show Open message.
3) Every time the instrument is turned ON, Following pattern will be displayed
POWER ON
1 L 100 ~ 8
250V AC TC
50/60 Hz
20 19 18 17 16 15 14 13 12 11 2 N 4VA
- 9
- O/P + !
- TC
+
RTD
S.S.R RTD 3 NO 10
4 C 11
RELAY-1
100 ~
250V AC NC
50/60 Hz ! 5 NC 12
4VA
RELAY-1 RELAY-2
NC C NO NC C NO 6 -O/P RELAY-2 C 13
L N
S.S.R
1 2 3 4 5 6 7 8 9 10 NO
+
7 14
key
3) Press ENT key to save change in setting
4) Press key for 6 sec to start/stop PID AUTO TUNING set1 Set Point-1
ENT
5) Press + key for 3 sec to go to factory setting mode. 234
Press
6) Orange color LED glows during auto tuning mode.
set2 Set Point-2
255
Basic Configuration Press SET key for 3 sec to
enter Password
TO ENTER BASIC pass Password Message
CONFIGURATION 50
SETTING, ENTER “73”
OFST OFF-SET
t2md SOKT,SKRG,SKPS,ALMT,ONDL,OFF
0 almt
IF T2MD=OFF
SLL Set Point Low Limit
t2ut SEC/MIN/HOUR
0 E-AL
SHL Set Point High Limit
s2md INDIVIDUAL/RELATIVE
600 indu IF RELATIVE (-50°C To +50°C)
1 2 34 PV
1 2 3 4
F C S T
Press
for 3 sec
+ key
1234 SV
Y E S n O
PID
Parameters PID ON-OFF
Parameters ONOF TP
Parameters
TP
PARA PARA PARA
SET
IF R1MD = OFF SET SET
Proportional
Band Pb Hysteresis
HYS1 PB2
20.0 3 5
IF T1MD = OFF
key
Integral
Time It TIM1 CT2
SET
300 3 8
Press
key
IF R2MD = OFF
Derivative DT or E-AL
HYS2 MR
SET
Time
75 3 0
Press
IF T1MD = SOAK
IF T2MD = OFF or SKPS or SKRG
Cycle Time CT TIM2 TIM1
15 3 6
key
IF R2MD = OFF
or E-AL
Manual Reset
MR Press ENT key to HYS2
SET
IF T2MD = OFF
IF T1MD = SOAK
or SKPS or SKRG
TIM1 TIM2
6 6
IF R2MD = OFF hys2 Press ENT key to
Save & Exit
or E-AL 3
IF T2MD = OFF TIM2 Sr.
1
2
Parameter
PB
Range for J, K, PT100
000 to 999.9
Range for PT.1 sensor
000 to 999.9
6 3
IT
DT
000 to 9999
000 to 9999
000 to 9999
000 to 9999
4 CT 4 sec to 99 sec 4 sec to 99 sec
Press ENT key 5 MR -9 to +9 -9.0 to +9.0
6 PB 2 2 to 20 2.0 to 20.0
to Save & Exit 7 Time 1 1 to 999 Sec/MIN/HR 1 to 999 Sec/MIN/HR
8 Hysteresis 1°C to 50°C 0.1°C to 50.0°C
9 Off-set correction -20°C to +20°C -20.0°C to +20.0°C
10 CT 2 4 Sec to 99 Sec. 4-99 Sec
11 Time 2 1 to 999 Sec/MIN/HR 1 to 999 Sec/MIN/HR
Installation Guidelines
1) This equipment, being built-in-type, normally becomes a part of main control panel and such in case the
terminals do not remain accessible to the end user after installation and internal wiring.
2) Do not allow pieces of metal, wire clippings, or fine metallic fillings from installation to enter the product
or else it may lead to a safety hazard that may in turn endanger life or cause electrical shock to the operator.
3) Circuit breaker or mains switch must be installed between power source and supply terminal to
facilitate power ‘ON’ or ‘OFF’ function. However this mains switch or circuit breaker must be
installed at convenient place normally accessible to the operator.
4) Use and store the instrument within the specified ambient temperature and humidity ranges as
mentioned in this manual.
Mechanical Installation
B 136mm - 5.35 inches
UTC 1202 D E
F
120mm - 4.72 inches
ºC
R1
234 PV
MODEL A B C D E F
A R2 235 SV
C
TUNE
DIMENSIONS 96mm 96mm 92mm 92mm 3mm 50mm
SET ENT
UTC 2202
ºC
85mm - 3.34 inches
23 4 PV
MODEL A B C D E F
R1
C
A R2
TUNE
235 SV
DIMENSIONS 72mm 72mm 68mm 68mm 3mm 85mm
SET ENT
Maintenance
1) The equipment should be cleaned regularly to avoid blockage of ventilating parts.
2) Clean the equipment with a clean soft cloth. Do not use isopropyl alcohol or any other cleaning agent.
3) Fusible resistor must not be replaced by operator.
Product improvement and upgrade is a constant procedure. So for more updated operating information and support,
Please contact our helpline : +91-9978991474/82 or Email at marketing@multispanindia.com Ver: 01-2017
UTC-1202, 2202 Page - 4 www.multispanindia.com