1 Preamble:
The HYDERABAD METROPOLITAN WATER SUPPLY AND SEWERAGE BOARD Water Supply
Distribution Network Project for the Peripheral Circles of GHMC -Construction of RCC Service
Reserviors and Providing Inlet, Outlet & Distribution network in Balanagar,package- 3
The present document covers the Design Basis applicable to 7750 KL Ground Level Service
Reservoir at BALANAGAR.
The general arrangements of the GLSR is prepared based on the Scheme requirements.
This Design is based on the IS Codes & Standards and Construction materials.
The design is carried out with different load combinations. The minimum cover is provided as per
IS 3370-2009.
(i) Exterior wall : The wall is designed as a cantilever with varying thickness keeping internal face
vertical and external face in steps. The thickness of the lower part of the wall is 1.3 m middle
portion is 0.8 m and the thickness of the upper part of the wall is 0.3 m. The wall is designed for
the water pressure inside and no earth pressure out side and checked for earth pressure out side
no water inside. The wall is designed as an uncracked section.
(d) Internal columns :
Internal columns are proposed in the GLSR to support the roof slab. The columns are provided
as a grid of 3.8 x 3.6 m in the center part of the reservoir.
(e) Foundation :
i) The foundation under external wall The footing is designed for the combined loads from the
external wall as well as adjacent column. Footing is designed for no tension condition, and
checked for maximum base pressure and base shear. It is designed as an uncracked section,
accordingly reinforcement is provided.
ii) The column footing is designed as isolated footing.
(f) Access to GLSR :
a dog legged stair case is provided to have an access to the roof with landings and flights as
applicable and access is also provided into the Reservoir by providing a dog legged stair case .
CONTENTS :
Deductions:
Volume of Columns =75 x0.35 x 0.35 x 6.15 = 56.5 m³
Dead storage =(60.6*21.6*0.15)-1.378125 = 195 m³
Pipe support portion (Assumption) - for 1 pipe = 5 m³
Staircase (Assumption) - for 1 pipe = 5 m³
Total deductions = 261.5 m³
Net Capacity of tank =8050.1 - 261.5 = 7788 m³
0.30
0.5
7.15
6.00
0.15
Design Constants
Grade of concrete M 30
Grade of steel Fe 500
m = 280/(3*σcbc) k = (m*σcbc)/[(m*σcbc)+σst]
j= 1-k/3 Q= 0.5*k*j*σcbc
σcbc 10 N/mm² m 9.3333 j 0.8607
σst 130 N/mm² k 0.4179 Q 1.7984
Load details
Self weight of slab 3.75 3.75 3.75 kN/m²
Live Load on the slab 1.5 1.5 1.5 kN/m²
Total load, W 5.25 5.25 5.25 kN/m²
Factored load, Wu ( Factor= 1 )
5.25 5.25 5.25 kN/m²
Span details
Clear span, x-axis 3.300 3.30 3.30 m
Clear span, y-axis 3.500 3.50 3.50 m
Width of beam 0.3 0.3 0.3 m
Top width of wall -- 0.3 0.3 m
Effective thk. of slab 0.12 0.12 0.12 m
Eff. Shorter Span, Lx 3.42 3.42 3.42 m
Eff. Longer Span, Ly 3.62 3.62 3.62 m
Longer span/Shorter spa Ly/Lx Ly/Lx Ly/Lx m
1.06 1.06 1.06
Two-way Two-way Two-way
Edge condition considered Cond'n 1 Cond'n 3 Cond'n 4
All Four Edges continuous One Long Edge Two Adjacent Edges
(Interior Panels) Discontinuous Discontinuous
Shorter span
At support, Mx (+) 1.474 1.719 2.149 kN-m
At mid span, Mx (-) 1.965 2.272 2.886 kN-m
Longer span
At support, My (+) 1.474 1.719 2.149 kN-m
At mid span, My (-) 1.965 2.272 2.886 kN-m
DATA
Unit weight of concrete 25 kN/m³
Unit weight of water 10 kN/m³
Size of the columns in connection with roof beam
0.35 X 0.35 m
Width of beam 0.3 m
Depth of beam 0.5 m
Cover to the reinforcement 45 mm
+[WdL²/12 +
+[WdL²/16 +
+[WdL²/16 +
+[WdL²/12 +
-[WdL²/10 +
-[WdL²/12 +
-[WdL²/10 +
Coefficients
WsL²/10]
WsL²/12]
WsL²/10]
WsL²/12]
Moment
WsL²/9]
WsL²/9]
WsL²/9]
0
0
(Outer Face)
(Outer Face)
Coefficients
+[0.4WdL +
+[0.4WdL +
+[0.6WdL +
+[0.5WdL +
+[0.6WdL +
0.45WsL]
0.45WsL]
0.6WsL]
0.6WsL]
0.6WsL]
Shear
0
1 2 3 4
+[0.55WdL +
+[0.55WdL +
(Inner Face)
(Inner Face)
Coefficients
0.6WsL]
0.6WsL]
Shear
3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
(1) (2) (3) (4) (5) (6) (7) (11) (12) (13)
Load Calculation
Wt. of slab on span (1)& span (13) 8.55 kN/m
Wt. of slab on span (2) & span (12) 8.55 kN/m
Wt. of slab on span (3)- (11) 7.65 kN/m
Wt. of slab on span (7) 3.825 kN/m
Wt. of slab on span (7) 11.73 kN/m
SW of beam 3.75 kN/m
Live Load upon slab at span (1) & span (13) 2.85 kN/m
Live Load upon slab at span (2) & span (12) 2.85 kN/m
Live Load upon slab at span (3) -(6) & (8) -(11) 2.85 kN/m
Live Load upon slab at span (7) 1.425 kN/m
Moment Eff. Depth Eff. Depth Ast Ast min Bar dia No. of No. of Ast Pt.
Sl.No. required provided required bars bars provided provided
required provided
(kN-m) (mm) (mm) (mm²) (mm²) (mm) (mm²) (%)
1 0 -- -- -- -- -- -- -- -- --
2 22.334 192.9 437 456.8 222.9 16 2.27 3 603.2 0.46
3 25.517 206.2 437 521.9 222.9 16 2.6 3 603.2 0.46
4 19.138 178.6 437 391.4 222.9 16 1.95 3 603.2 0.46
5 22.334 192.9 437 456.8 222.9 16 2.27 3 603.2 0.46
W₁ h3=2.30
H = 7.15
W₂
0.8 h2=2.30
1.3 0
h1=2.55
0 W₃
3.55
GL +576.100
Heel Toe 0.8
W₄
A
2.60 0.3 1 1.4
5.30 (b)
For the 1300 mm thick wall:
Case 1. Moment due to water pressure alone = 0.5 * γw* H * H * H/3
= 0.5 x 10 x 6.65^3 / 3
M = 490.1 kN-m
Effective depth of section available = 1242.5 mm
Thickness of wall provided = 1300 mm
Over all thickness of wall required √(6M/fb) = 1212.6 mm Okay
Main reinforcement:
Minimum percentage of steel required = 0.35 %
Minimum area of steel required = 875 mm²
The spacing of bars required at the bottom face = 139.3 mm C/C
Provided spacing of bars = 100 mm C/C
Area of steel provided at the bottom = 4909.00 mm²
Distribution Reinforcement:
Minimum percentage of steel required = 0.35 %
Minimum area of steel required = 875 mm²
Dia of bars proposed to be used = 12 mm
Area of each bar = 113.1 mm²
The spacing of bars required at the bottom face = 129.3 mm C/C
Provided spacing of bars = 120 mm C/C
Area of steel provided at the bottom = 942.50 mm²
Main reinforcement:
Minimum percentage of steel required = 0.35 %
Minimum area of steel required = 875 mm²
The spacing of bars required at the bottom face = 129.3 mm C/C
Provided spacing of bars = 120 mm C/C
Area of steel provided at the bottom = 942.5 mm²
Distribution Reinforcement:
Dia of bars proposed to be used = 12 mm
Area of each bar = 113.1 mm²
Minimum percentage of steel required = 0.35 %
Minimum area of steel required = 875 mm²
The spacing of bars required at the bottom face = 129.3 mm C/C
Provided spacing of bars = 120 mm C/C
Area of steel provided at the bottom = 942.5 mm²
Main reinforcement:
Minimum percentage of steel required = 0.35 %
Minimum area of steel required = 875 mm²
The spacing of bars required at the bottom face = 213.1 mm C/C
Provided spacing of bars = 200 mm C/C
Area of steel provided at the bottom = 2454.50 mm²
Distribution Reinforcement:
Minimum percentage of steel required = 0.35 %
Minimum area of steel required = 875 mm²
Dia of bars proposed to be used = 12 mm
Area of each bar = 113.1 mm²
The spacing of bars required at the bottom face = 129.3 mm C/C
Provided spacing of bars = 120 mm C/C
Area of steel provided at the bottom = 942.50 mm²
Main reinforcement:
Minimum percentage of steel required = 0.35 %
Minimum area of steel required = 875 mm²
The spacing of bars required at the bottom face = 129.3 mm C/C
Provided spacing of bars = 120 mm C/C
Area of steel provided at the bottom = 942.5 mm²
Distribution Reinforcement:
Dia of bars proposed to be used = 12 mm
Area of each bar = 113.1 mm²
Minimum percentage of steel required = 0.35 %
Minimum area of steel required = 875 mm²
The spacing of bars required at the bottom face = 129.3 mm C/C
Provided spacing of bars = 120 mm C/C
Area of steel provided at the bottom = 942.5 mm²
Main reinforcement:
Minimum percentage of steel required = 0.35 %
Area of steel required = 525 mm²
The spacing of bars required at the bottom face = 215.4 mm C/C
Provided spacing of bars = 200 mm C/C
Area of steel provided at the bottom = 565.5 mm²
Distribution Reinforcement:
Dia of bars proposed to be used = 12 mm
Area of each bar = 113.1 mm²
Minimum percentage of steel required = 0.35 %
Minimum area of steel required = 525 mm²
The spacing of bars required at the bottom face = 215.4 mm C/C
Provided spacing of bars = 120 mm C/C
Area of steel provided at the bottom = 942.5 mm²
Main reinforcement:
Area of steel required M/(σst j d) = 0 mm²
Minimum percentage of steel required = 0.35 %
Minimum area of steel required = 525 mm²
The spacing of bars required at the bottom face = 215.4 mm C/C
Provided spacing of bars = 120 mm C/C
Area of steel provided at the bottom = 942.5 mm²
Distribution Reinforcement:
Dia of bars proposed to be used = 12 mm
Area of each bar = 113.1 mm²
Minimum percentage of steel required = 0.35 %
Minimum area of steel required = 525 mm²
The spacing of bars required at the bottom face = 215.4 mm C/C
Provided spacing of bars = 120 mm C/C
Area of steel provided at the bottom = 942.5 mm²
Inner face 25mm dia bars @ 100mm c/c spacing up to height h1 and 25mm dia bars @ 200mm c/c
spacing up to height h2, 12mm dia bars @ 200mm c/c spacing up to height h3.
Outer face 12mm dia bars @ 120mm c/c spacing up to height h1, 12mm dia bars @ 120mm c/c
spacing up to height h2 and 12mm dia bars @ 120mm c/c spacing up to height h3.
Distribution RF 12mm dia bars @ 120mm c/c spacing up to height h1 (inner & outer), 12mm dia bars @
120mm c/c spacing up to height h2 (inner & outer) and 12mm dia bars @ 120mm c/c
spacing up to height h3 (inner & outer).
Z =
862.15 / 448.6
= 1.92 m
Eccentricity e =
b/2 -Z
= 0.728 m
b/6 =
5.3 / 6
= 0.883 m
HENCE OK
Maximum and Minimum Pressure at the base are given
W 6*e
Pmax = * 1
b b
= 154.397 kN/m² < 300 kN/m²
HENCE OK
Pmin = W 6*e
* 1
b b
= 14.884 kN/m² < 300 kN/m²
HENCE OK
Distribution R/F
Area of steel required near bottom face = 875 mm²
Dia. of bars adopted for top face = 16 mm
Area of bar = 201.1 mm²
Spacing of bars required = 229.83 mm C/C
Spacing Provided = 120 mm C/C
Main reinforcement of 20mm dia bars @ 120mm c/c spacing in the top face and
Required Steel distribution reinforcement of 16mm dia bars @ 120mm c/c spacing in the top face
---
of heel slab portion.
Distribution R/F
Area of steel required near top face = 875 mm²
Dia. of bars adopted for top face = 16 mm
Area of bar = 201.062 mm²
Spacing of bars required = 229.785 mm C/C
Spacing Provided = 120 mm C/C
Main reinforcement of 20mm dia bars @ 120mm c/c spacing in the bottom face
Required Steel
and distribution reinforcement of 16mm dia bars @ 120mm c/c spacing in the
---
bottom face of toe slab portion.
CASE (2) : For wall with one side earth fill, with no water
Load in Moment about A
Sl. NO Description Lever arm
(kN) (kN-m)
1 P1= 23.57 23.57 2.55 60.104
2 W1= 0.3 * 2.3 * 25 17.25 2.55 43.988
3 W2= 0.8 * 2.3 * 25 46 2.3 105.8
4 W3= 1.3 * 2.55 * 25 82.875 2.05 169.894
5 W4= 0.8 * 5.3 * 25 106 2.65 280.9
6 W5= 0 * 1.4 * 18 0 0.7 0
7 Moment due to soil= 1/6 * 0^3 * 0.333*18 0
8 Point load due to column 0 6.25 0
Total Load (W) 275.695 660.69
Z = 660.69 / 275.7
= 2.40 m
Eccentricity e = b/2 -Z
= 0.254 m
b/6 = 5.3 / 6
= 0.883 m
HENCE OK
Maximum and Minimum Pressure at the base are given
Pmax = W 6*e
* 1
b b
= 66.976 kN/m² < 300 kN/m²
HENCE OK
Pmin
= W 6*e
* 1
b b
= 37.06 kN/m² < 300 kN/m²
HENCE OK
Main R/F
Area of steel required = 1718.0 mm²
Minimum area of steel required = 875 mm²
The spacing of bars required at the top face = 182.9 mm C/C
Provided spacing of bars = 120 mm C/C
Area of steel provided at the bottom = 2617.99 mm²
Distribution R/F
Area of steel required near bottom face = 875 mm²
Dia. of bars adopted for top face = 16 mm
Area of bar = 201.062 mm²
Spacing of bars required = 229.79 mm C/C
Spacing Provided = 120 mm C/C
Main reinforcement of 20mm dia bars @ 120mm c/c spacing in the top face and
Required Steel --- distribution reinforcement of 16mm dia bars @ 120mm c/c spacing in the top face
of heel slab portion.
Distribution R/F
Area of steel required near top face = 875 mm²
Dia. of bars adopted for top face = 16 mm
Area of bar = 201.062 mm²
Spacing of bars required = 229.785 mm C/C
Spacing Provided = 120 mm C/C
Main reinforcement of 20mm dia bars @ 120mm c/c spacing in the bottom face
Required Steel and distribution reinforcement of 16mm dia bars @ 120mm c/c spacing in the
---
bottom face of toe slab portion.
Design constants
Grade of concrete M 30
Grade of steel Fe 500
Compressive stress in columns subjected to direct load
σsc = 140 N/mm²
Reduction Coefficient
Cr = 1.25 - lef/(48b)
Cr = 0.863
Lateral Ties
Dia of the bar 10 mm
Pitch of the ties 250 mm
Provide lateral ties of 10mm dia bars at 200mm c/c spacing.
(vi) DESIGN OF FOUNDATION(F₂) FOR COLUMN (C₁)
Design of footing
Moment obtained = 15.087 kN-m
Minimum thickness required = 212.7 mm
√(6M/fB) OK
Effective depth provided = 342 mm
Reinforcement details
Area of steel required, Ast = 394.3 mm²
Min, percentage of steel required = 0.35 %
Min. area of steel required = 700 mm²
Dia of main reinforcement = 16 mm
Area of single bar = 201.1 mm²
Spacing required = 287.3 mm
Spacing provided = 120 mm
Percentage of reinforcement = 0.49 %
Provide 16mm dia bars at 120 C/C spacing as main reinforcement.
The floor slab excluding footing portion is a non-structural member directly resting on the
ground.
Hence, provide minimum thickness 200 mm
Thickness provided 400 mm
As per IS-3370, Part IV, Cl. 8.1.1 and Fig. 2
~ The minimum Reinforcement is 0.35 % of surface zone area.
For ground slabs less than 300mm thick, the calculated minimum reinforcement, i.e. [0.35%
(400*1000)/2], should be placed in one face as near as possible to the upper surface
consistent with the nominal cover. Hence provide the reinforcement at the top only.
~ The bar spacing should not be greater than 300mm or thickness of the slab, whichever is
less.
Design constants
Grade of concrete M 30
Grade of steel Fe 500
Compressive stress in columns subjected to direct load
σsc = 140 N/mm²
Reduction Coefficient
Cr = 1.25 - lef/(48b)
Cr = 0.863
Lateral Ties
Dia of the bar 10 mm
Pitch of the ties 250 mm
Provide lateral ties of 10mm dia bars at 200mm c/c spacing.
(ix) DESIGN OF FOUNDATION (F₃) FOR STAIR CASE COLUMN (C₂)
Design of footing
Moment obtained = 16.687 kN-m
Minimum thickness required = 223.7 mm
√(6M/fB) OK
Effective depth provided = 342 mm
Reinforcement details
Area of steel required, Ast = 436.1 mm²
Min, percentage of steel required = 0.35 %
Min. area of steel required = 700 mm²
Dia of main reinforcement = 16 mm
Area of single bar = 201.1 mm²
Spacing required = 287.3 mm
Spacing provided = 120 mm
Percentage of reinforcement = 0.49 %
Provide 16mm dia bars at 120 C/C spacing as main reinforcement.
Sample Calculations for a depth of 2.055m below the top of water 0.91 kN
= 0.03*10*6.85*√(3)*(2.055/6.85-1/2*(2.055/6.85)^2)*TANH(√(3)*(60.6/6.85))
The maximum increase in the Hoop Tension considering the hydrodynamic pressure along
with the static pressure is, 14.41 %, which is less than the permicible.
As per the Clause No. B-2.3 of IS 456-2000, the permissible stresses be increased by 33.33
%, when stress due to live/dead/impact loads are combined with the earthquake loads.
In present case the increase in the forces due to EQ load is very small in comparison to the
static load, as it's not critical ,it's not considered in the final calculations.
(xi) CHECK FOR EARTH QUAKE FORCES DUE TO EXTERNAL SOIL PRESSURE
ZONE :- II
M30 - Grade of concrete 0.30 TOP R.L - 583.250
STT 0.30 m
SBT 1.300 m
DF 3.0 m
HT 0.80 m
TT 0.80 m 7.15
TP 1.40 m
HP 2.60 m
H 7.15 m BOT .R.L - 576.100
WH 0.00 m 0.80
EH 0.00 m 573.100
DE 1.80 t/m³ 2.60 1.300 1.40
DC 2.50 t/m³ 5.300
SBC 30 t/m²
B 5.300 m
2
Ca = (1+αv) Cos² φ-λ-α) x 1
Cosλ Cos²α Cos(δ+α+λ) 1 + Sin (φ+α) Sin (φ-I-λ) 1 /2
1.000 x 0.859 1
Ca =
0.981 x 0.990 1 + 0.500 x 0.5 ½
0.99 x 0.99
= 0.885 x 2
1
1 + 0.505
= 0.885 x 0.442
= 0.392
CASE :2 - EARTHQUAKE LOAD
EARTH PRESSURE DUE TO EARTHQUAKE ON THE RETAINING WALL AS PER ZONE II,
IS 1893 - 1984
Tan α = 1.000
h GL 7.15
= 0.140
δ
α = 7.97
Pa
Active Pressure
Pa = 1/2 wh² Ca
Pa = Active earth pressure in kg/m length of wall
w = Unit wt. of soil = 1.80 t/m³
2
1.015 ### 1
Ca = ½
0.980 ### 1 + 0.5000 x 0.4742
0.99 x 0.99
2
= 0.923 x 1
1 + 0.49
= 0.923 ### = 0.414
2
0.985 ### 1
Ca = ½
0.980 ### 1 + 0.5000 x 0.4734
0.99 x 0.99
= 0.897 x 1 ²
1 + 0.49
As per the Clause No. B-2.3 of IS 456-2000, the permissible stresses may be increased by 33.33
% when stress due to live/dead/impact loads are combined with the earthquake loads.
In present case the increase in the forces due to EQ load is very small in comparison to the
static load, so it's not critical.
(II) DESIGN OF TOP HEAD ROOM
(i) DESIGN OF ROOF SLAB, (S₂)
Unit weight of concrete = 25 kN/m³
Unit weight of water = 10 kN/m³
DATA
Clear cover of the slab = 25 mm
Thickness of the slab = 150 mm
Providing dia of main R/F bar = 10 mm
Load details
Self weight of the slab = 3.75 kN/m²
Live Load on the slab = 0.75 kN/m²
Total load, W = 4.5 kN/m²
Factored load, Wu ( Factor = 1)
= 4.5 kN/m²
Span details
Clear span, x-axis 3.000 m Width of beam 0.3 m
Clear span, y-axis 3.900 m Effective thk. of slab 0.12 m
Eff. Shorter Span, Lx 2.300 m
Eff. Longer Span, Ly 4.02 m
Longer span / Shorter span, r Ly/Lx 1.75 Two-way
Four Edges Discountinuous but Corners
Edge condition considered Cond'n 10 held down by providing Torsional
Reinforcement
Lateral Ties
Dia of the bar = 10 mm
Pitch of the ties = 250 mm
Provide lateral ties of 10mm dia bars at 200mm c/c spacing.
(III) DESIGN OF STAIR CASE
(i) DESIGN OF DOG-LEGGED STAIR CASE INSIDE THE RESERVOIR
Total height of the stair case 7.30 m
No. of flights 5
No. of landings 5
Height of top three flights individually 1.5 m
Height of bottom flight 1.3 m 950
Thickness of landing slab 200 mm
Length of landing 1100 mm
Width of landing 950 mm 3.8
Thickness of the waist slab 200 mm
Main R/F
Area of steel required, Ast = M/(σst j d) = 1485.4 mm²
Min. area of steel = 350 mm²
Dia of main reinforcement = 16 mm
Area of single bar, Ab = 201.1 mm²
Spacing of the bars required = 135.4 mm
Say 100 mm
Percentage of steel, Pt = 1.368 %
Distribution R/F
Dia of distribution reinforcement = 10 mm
Area of single bar, Ab = 78.5 mm²
Spacing of the bars required = 200 mm
Say 200 mm
Reinforcement details
Area of steel required, Ast = M/(σst j d) = 451.5 mm²
Min. area of steel = 875 mm²
Dia of main reinforcement = 20 mm
Area of single bar, Ab = 314.2 mm²
No. of bars required = 2.78
Say 3
Percentage of steel, Pt = 0.628 %
Provide main steel of 20mm dia bars of 3 no.s.
3.8
Thickness of the waist slab 200 mm
950
Riser, R 150 mm Tread, T 250 mm
Cover to the reinforcement 45 mm
Main R/F
Area of steel required, Ast = M/(σst j d) = 788.8 mm²
Min. area of steel = 700 mm²
Dia of main reinforcement = 12 mm
Area of single bar, Ab = 113.1 mm²
Spacing of the bars required = 143.4 mm
Say 120 mm
Percentage of steel, Pt = 0.633 %
Distribution R/F
Dia of main reinforcement = 10 mm
Area of single bar, Ab = 78.5 mm²
Spacing of the bars required = 112.1 mm
Say 100 mm
Reinforcement details
Area of steel required, Ast = M/(σst j d) = 242.8 mm²
Min. area of steel = 315 mm²
Dia of main reinforcement = 12 mm
Area of single bar, Ab = 113.1 mm²
No. of bars required = 2.79
Say 3
Percentage of steel, Pt = 0.377 %
Provide main steel of 12mm dia bars of 3 no.s.
Design constants
Grade of concrete M 30
Grade of steel Fe 500
Compressive stress in columns subjected to direct load σsc = 190 N/mm²
Lateral Ties
Dia of the bar 10 mm
Pitch of the ties 250 mm
Provide lateral ties of 10mm dia bars at 200mm c/c spacing.
DESIGN OF FOUNDATION SLAB(F₄), FOR COLUMN C₄
Reinforcement details
Area of steel required, Ast = 30.9 mm²
Min. area of steel required = 525 mm²
Dia of main reinforcement = 10 mm
Area of single bar = 78.5 mm²
Spacing required = 149.5 mm
Spacing provided = 140 mm
Percentage of reinforcement = 0.224 %
Provide 10mm dia bars of 140 mm c/c span as main reinforcement.
2 Wall
4 Middle Raft
6 Roof Beam
From the above calcualtions, Temperature reinforcments are governing the design
Hence drawings are prepared using the above reinforcments