Rectangular Tank Design-Bluetax ETP-1
Rectangular Tank Design-Bluetax ETP-1
Rectangular Tank Design-Bluetax ETP-1
Grade of Concrete M 30
Grade of steel Fe 500
b/a 0.5
x/a for support 1
x/a for center 0.5
Page 1
Sheet1
pt = 50 fck/fy[1-sqrt{1-4.6xMy/fckxbxd^2}]
= 0.02 %
Min. Pt should be 0.24 %
Ast pt x b x d/100
240 mm^2
providing 8 mm dia reinforcement at 200 mm c/c
Ast provided 251.33 mm^2
https://www.youtube.com/watch?v=QZa9F8J5VKY
Page 2
Sheet1
0.54 kN.m
1.62 kN.m
-0.41 kN.m
-0.81 kN.m
-0.54 kN.m
-2.43 kN.m
0 kN.m
0 kN.m
Page 3
Sheet2
L/B 1< 2
Therefor, Design H-h as continuous frame and h as cantilever
h = H/4
h 1.16 >1 m
provide h = 1.16 m
Permissible Stress in
(1) Design Constants Grade of compression in Concrete
concrete
σcbc σcc
For M 30,σcbc 10 N/mm2 M25 8.5 6
σst 130 N/mm2 M30 10 8
σcc 8 N/mm2 M35 11.5 9
m = 280
3 σcbc
= 9.33
k = m σcbc
m σcbc + σst
= 0.42
j = 1-k/3
= 0.86
Q = 1/2 x σcbc x k x j
= 1.8
Page 4
Sheet2
P= 57.33 kN/m2
Mf AB = -PL^2/12
-19.11 kN.m
Bm Plan
Mf AD = +PL^2/12
19.11 kN.m
D
Distribution factor (D.F.)
D A B
0 0.5 0.5 0 D.F.
- 19.11 -19.11 - FEM
- 00 - Balance
19.11 -19.11 Final Moments
B.M. At center of AB
= PL^2/8 – Ma
= 9.56 kN.m
B.M. At center of AD
= PL^2/8 – Ma
= 9.56 kN.m
Page 5
Sheet2
Ast required = M
σst x j x d
= 854.03 mm^2
Provide 12 mm dia bars @ 125 c/c spacing ( Verticle steel on remote face)
Total D = 250 mm
effective D = 125 mm
Distribution steel:
Min. Ast = 300 mm^2 for one zone (on each face)
Provide 10 mm dia bars @ 200 c/c spacing ( Horizontal steel on both face)
(ii) At center
M= 9.56 kN.m
C= 57.33 kN
Modified moment M-Cx
5.26 kN.m
Ast required = M
σst x j x d
= 234.86 mm^2
Page 6
Sheet2
Provide 10 mm dia bars @ 200 c/c spacing ( Verticle steel on liquid face)
M = Q x b x d^2
Q= 1.8
d= 103.04 mm
Adopt d = 200 mm
Total D = 250 mm
Ast required = M
σst x j x d
= 854.03 mm^2
Provide 12 mm dia bars @ 125 c/c spacing ( Verticle steel on liquid face)
Total D = 250 mm
effective D = 125 mm
Distribution steel:
Min. Ast = 300 mm^2 for one zone (on each face)
Provide 10 mm dia bars @ 200 c/c spacing ( Horizontal steel on both face)
(ii) At center
M= 9.56 kN.m
C= 57.33 kN
Ast required = M
σst x j x d
= 427.01 mm^2
Provide 10 mm dia bars @ 175 c/c spacing ( Verticle steel on remote face)
Page 7
Sheet2
Cantilever Moment
Pressure at base = ka Ɣ' H + Ɣw
= 62.8 kN/m^2
M= 14.14 kN.m
Ast required = 632.04 mm^2
Total D = 250 mm
effective D = 125 mm
Provide 10 mm dia bars @ 100 c/c spacing (Both direction both face upto 1 m)
Mf AB = -PL^2/12
-7.66 kN.m
Bm
Mf AD = +PL^2/12
7.66 kN.m
D
Distribution factor (D.F.)
D A B
0 0.5 0.5 0 D.F.
- 7.66 -7.66 - FEM
- 00 - Balance
7.66 -7.66 Final Moments
Page 8
Sheet2
B.M. At center of AB
= PL^2/8 – Ma
= 3.83 kN.m
B.M. At center of AD
= PL^2/8 – Ma
= 3.83 kN.m
M = Q x b x d^2
Q= 1.8
d= 65.22 mm
Adopt d = 200 mm
Total D = 250 mm
Ast required = M
for moment σst x j x d
= 342.13 mm^2
Ast required = T
for tension σst
= 176.68 mm^2
Total Ast
required = 518.81 mm^2
Provide 12 mm dia bars @ 175 c/c spacing ( Verticle steel on liquid face)
(ii) At center
M= 3.83 kN.m
T= 22.97 kN (Tension on remote face)
Modified moment M-Tx
2.11 kN.m
Ast required = M
Page 9
Sheet2
Ast required = T
for tension σst
= 176.68 mm^2
Total Ast
required = 270.77 mm^2
Provide 10 mm dia bars @ 200 c/c spacing ( Verticle steel on remote face)
Total D = 250 mm
effective D = 125 mm
Distribution steel:
Min. Ast = 300 mm^2 for one zone (on each face)
Provide 10 mm dia bars @ 200 c/c spacing ( Horizontal steel on both face)
M = Q x b x d^2
Q= 1.8
d= 65.22 mm
Adopt d = 200 mm
Total D = 250 mm
Ast required = M
for moment σst x j x d
= 342.13 mm^2
Ast required = T
for tension σst
= 176.68 mm^2
Total Ast
required = 518.81 mm^2
Page 10
Sheet2
Provide 12 mm dia bars @ 175 c/c spacing ( Verticle steel on remote face)
(ii) At center
M= 3.83 kN.m
T= 22.97 kN (Tension on liquid face)
Ast required = M
for moment σst x j x d
= 171.07 mm^2
Ast required = T
for tension σst
= 176.68 mm^2
Total Ast
required = 347.75 mm^2
Provide 10 mm dia bars @ 200 c/c spacing ( Verticle steel on liquid face)
Total H = 4.9 m
or Downward pressure
< 1
Upward Pressure
Downward pressure
1) Weight of long walls = 145.31 kN
2) Weight of short walls = 116.25 kN providing all around projection of
3) Wight of bottom slab = 56.25 kN
4) Weight of soil on toe slab = 156.94 kN
Total Downward pressure = 474.75 kN
Page 11
Sheet2
Upward pressure for B.M. = 0 kN/m^2 (here, 0 is taken as no water surrounding the tank,
load transfer by wall per meter length of slab = weight of 1 m long wall
29.06 kN/m
M = Q x b x d^2
Q= 1.8
d= 145.94
Adopt d = 200
Total D = 250
Ast required = M
for moment σst x j x d
= 916.6 mm^2
Provide 12 mm dia bars @ 120 c/c spacing at face of bottom main direction
Ast required = M
for moment σst x j x d
= 1713.27 mm^2
Provide 20 mm dia bars @ 175 c/c spacing at center portion of bottom main dire
Page 12
Sheet2
Distribution steel:
Minimum reinforcement, pt (min) 0.24 %
Total D = 250 mm
effective D = 125 mm
Provide 10 mm dia bars @ 200 c/c spacing at top of slab both ways and
at bottom in secondary direction
Ast provided = 392.7 mm^2
X1 = 39.41 mm
X2 = -57 mm
M= 7.3
Icr = 142206137.4 mm^4
Page 13
Sheet2
Permissible stress
in steel
for HYSD bars 130 N/mm^2
Page 14
Sheet2
Page 15
Sheet2
Q factor
fy
415 500
2.76 2.66
3.45 3.33
4.14 3.99
Page 16
Sheet2
Page 17
Sheet2
Lm B
Plan
Page 18
Sheet2
Page 19
Sheet2
Page 20
Sheet2
Safe
Unsafe
Page 21
Sheet2
Page 22
Sheet2