Setup: Deep Sea Electronics Dse857 Usb - Rs485 Converter Installation Instructions
Setup: Deep Sea Electronics Dse857 Usb - Rs485 Converter Installation Instructions
Setup: Deep Sea Electronics Dse857 Usb - Rs485 Converter Installation Instructions
ISSUE 1
DSE857 USB – RS485 CO NVERTER
I NSTALLATIO N I NSTRUCTIO NS
DSE857 USB – RS485 converter is designed to allow DSE controllers with a USB port to be
connected to an industry standard RS485 Modbus RTU master system. This enables (for
example) DSE controllers with USB ports to communicate with a Building Management System
(BMS) or PLC with HMI using Modbus RTU over RS485.
SETUP
DSE Configuration Suite PC Software is used in conjunction with an RS485 port on the
PC/Laptop. This allows the convertor to be setup as required by the Modbus RTU Master system.
For information in regards to setting up the Host DSE Controller, refer to the relevant
Configuration Suite PC Software Manual which can be found on our website:
www.deepseaplc.com.
Factory Settings
Baud Rate Modbus Slave ID
19200 10
USAGE
The host DSE controller has addressable registers as defined in the DSEGencomm Document.
This and other DSEGencomm training documents are available from DSE Technical Support
upon request from support@deepseaplc.com.
DIMENSIONS
Parameter Description
Overall Size 35 mm x 96.9 mm x 102.2 mm
(1.34” x 3.81” x 4.02”)
Mounting Type DIN rail EN 50022 35 mm type only
Indoor Use Only
Maximum Ambient Operating 50 ºC
Temperature (122 ºF)