Air System Sizing Summary For 1. WAITING AREA
Air System Sizing Summary For 1. WAITING AREA
WAITING AREA
Project Name: OFFICE BUILDING 10/19/2021
Prepared by: MALAYSIA FRANCE INSTITUTE 04:21PM
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
1. WAITING AREA 1 34.7 Jun 1700 3049 0.0 265.0 11.51
1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 502 L/s
TABLE 1.1.A. Component Loads For Space "1. WAITING AREA" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 33.0 °C / 25.3 °C HEATING OA DB / WB 21.7 °C / 15.2 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 55 m² 11195 - 55 m² - -
Wall Transmission 44 m² 1742 - 44 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 55 m² 2724 - 55 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3710 W 3326 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1375 - 0 0 -
People 169 8740 5949 0 0 0
Infiltration - 2420 4296 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 3152 1024 0% 0 0
>> Total Zone Loads - 34674 11269 - 0 0
TABLE 1.1.B. Envelope Loads For Space "1. WAITING AREA" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²·K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 15 2.014 - 674 - 0
WINDOW 1 28 6.208 0.881 1362 5141 0
W EXPOSURE
WALL 29 2.014 - 1068 - 0
WINDOW 1 28 6.208 0.881 1362 6054 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.1 26.8 53 617.9 13118.4 9212.6 0.0 0.0 0.0
0100 26.6 26.8 54 569.4 12101.7 8479.8 0.0 0.0 0.0
0200 26.2 26.8 54 521.8 11138.7 7764.1 0.0 0.0 0.0
0300 25.8 26.8 55 478.4 10274.1 7112.1 0.0 0.0 0.0
0400 25.5 26.8 56 439.3 9504.5 6524.7 0.0 0.0 0.0
0500 25.4 26.8 56 407.6 8876.7 6049.8 0.0 0.0 0.0
0600 25.6 26.8 57 386.6 8438.9 5736.4 0.0 0.0 0.0
0700 26.1 26.8 57 382.0 8275.0 5667.0 0.0 0.0 0.0
0800 26.9 24.6 55 3049.2 19382.1 24320.6 0.0 0.0 0.0
0900 28.1 24.4 55 3049.2 21067.8 25541.9 0.0 0.0 0.0
1000 29.4 24.5 55 3049.2 22778.1 26357.0 0.0 0.0 0.0
1100 30.9 24.7 55 3049.2 24551.4 26837.7 0.0 0.0 0.0
1200 32.4 24.5 55 3049.2 26228.1 28847.9 0.0 0.0 0.0
1300 33.5 24.4 55 3049.2 27729.2 30528.6 0.0 0.0 0.0
1400 34.2 24.7 55 3049.2 29768.6 30878.7 0.0 0.0 0.0
1500 34.4 24.8 55 3049.2 31928.4 32648.9 0.0 0.0 0.0
1600 34.2 24.8 55 3049.2 33599.1 34224.5 0.0 0.0 0.0
1700 33.5 24.6 55 3049.2 34450.0 35415.6 0.0 0.0 0.0
1800 32.6 27.0 49 1089.8 23622.2 16412.2 0.0 0.0 0.0
1900 31.4 26.9 50 925.6 20010.5 13891.1 0.0 0.0 0.0
2000 30.2 26.9 51 862.9 18476.9 12931.8 0.0 0.0 0.0
2100 29.2 26.9 51 796.6 16959.1 11921.3 0.0 0.0 0.0
2200 28.3 26.9 52 731.1 15522.6 10926.8 0.0 0.0 0.0
2300 27.6 26.8 52 671.8 14242.0 10026.7 0.0 0.0 0.0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.9 W/(L/s)
Site Altitude = 21.9 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.9 W/(L/s)
Site Altitude = 21.9 m
0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )