Liebert STS (10A & 16A) : Power Redundancy For One-Way Power Supply

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

AC Power

for Business-Critical Continuity™

Liebert STS (10A & 16A)


Power Redundancy for One-way Power Supply

The STS is a kind of single-pole automatic transfer device with the capacity of 10 / 16A. It performs the core functions of detection
and transfer in the dual-bus system composed of two ways of AC power, and is used in the high-end uninterruptible power supply
applications that require high power supply reliability.

Features
„ The key component in the system, the auxiliary
power, adopts redundancy design to ensure
that the equipment can still operate normally
upon the failure of one single power.
„ Full DSP control ensures strong data processing
capacity and improves the system reliability.
„ Advanced power-off detection method enables
quick judgment of power-off failure.
„ Powerful communication function realizes
the remote management through SNMP card
(option)
Redundancy
The main power and the standby power can
directly connect to the STS on the rack, and the
STS can provide redundancy control on the power.
Once the main power fails, it will automatically
switch to the standby power.

Reliability
The STS adopts the control technology of“First
Disconnect Then Connect”
„ If one-way power fails, the STS can ensure
the uninterruptible power supply to the
equipment through the other way of power.
„ Once short circuit occurs, the STS can
ensure that the failure will not extend
to the standby power, and thus ensure
the uninterruptible power supply to the
equipment.

The Liebert STS Is Ideally Suited For:


„ Computer equipment rooms
„ Internet data centers
„ Telecom & financial data centers
„ Industrial process control centers
Liebert STS Specifications
Model Number 02352247 02352244 02352190
Input
Input Connectors C14 x 2 IEC309 x 2 IEC-C20 x 2
Rated Voltage 220 /230VAC
Rated Frequency 50 / 60Hz
Voltage Range 150 to 300VAC
Frequency Range 50 / 60Hz ± 5Hz
Voltage Distortion < 10%
Output
Output Connectors C13 x 6 C13 x 6 + C19 x 1
Power Factor 0.75 to 1 lead or lag
Overload Capacity 125% for 30 minutes
Efficiency 99%
Transfer
Number of Poles 2 poles
Automatic Transfer Interval < 6ms typical, < 11ms max
Environmental Parameters
Operating temperature 0 to 40°C
Storage temperature -40 to 70°C
Relative humidity 5 to 95%; no condensation
Elevation 3000m
Mechanical Parameters
Dimension H × W × D (mm) 44 × 430 × 250
Net weight of standard equipment 4.5kg
Gross weight with options 5kg