Medium Voltage Distribution: N-Series Three-Phase Recloser With ADVC Controller
Medium Voltage Distribution: N-Series Three-Phase Recloser With ADVC Controller
Loop Automation
Restoring power to your customers in the shortest possible time is
the focus of Recloser Solutions’ Loop Automation Scheme.
Operation as a Sectionalizer
Reclosers and sectionalizers work together to further improve feeder
reliability. Using a separate RL-Series LBS/Sectionalizer, as part of
a feeder automation network, detects fault passage and
automatically isolates faulty sections of a network in conjunction with
upstream recloser operation. To accomplish this it senses the
three-phase current and voltage to count the number of recloser trip
operations. When the preprogrammed number of recloser
operations is reached, the controller opens the sectionalizer during
the recloser dead time to isolate the downstream fault.
recloser, plus the benefits of up-to-date design > A 630 A cable connection kit is provided as part of the standard package. Optional 250 A,
400 A, and 800 A cable kits are also available.
optimized for automation, remote control, and
monitoring, now or in the future, the N-Series ACR
Reduced Installation Costs
is a complete scalable solution.
> Simple Commissioning: Configuration of the unit is from the WSOS Software or the
operator interface.
The N-Series development was driven by customer
> All key components required for installation are included.
demand for improved return on capital investment in
the distribution network. After careful evaluation of
> Lightning arrester mounting, cable tail kit, and pole-mounting brackets are provided in the
standard package. An optional voltage transformer (VT) for auxiliary supply is available.
customer needs, the N-Series was developed to
> Schneider Electric ACRs are ideally suited as low-cost feeder circuit breakers in outdoor
achieve optimum performance and reliability, making primary substations. In this application, connection into the substation control system is
use of the latest available technology in vacuum simple and low cost.
interruption and microelectronics.
Reduced Operating Costs
In the past, distribution equipment such as reclosers > Reduce equipment damage through the integral protection relay, which provides fast
isolation of faults.
have been purchased only to support load growth.
Today, your customers, the electricity consumers, > The recloser constantly monitors line current and voltage without the need for additional
measurement devices. This data can then be used for forward planning and optimization of
are demanding reduced outages and lower prices. existing feeders.
At Schneider Electric, we are continually working to
> Reliable lifetime, low maintenance equipment reduces operational costs.
provide the advanced equipment needed for
tomorrow’s competitive electricity distribution system. DSA/SCADA Compatibility
When used with a compatible DSA or SCADA system, Schneider Electric ACRs support remote
By using our technologically advanced equipment, control and monitoring to provide the following advantages:
operating costs will be reduced and capital works
can be deferred through better management of
> Reduced travel time for line crews: information on fault current and recloser status values
transmitted to system control allows fast location of the faulted line section.
the existing plant. There will be a reduction in the
> This same information allows informed remote switching, reducing the affected area and
outage area; reductions can cause lost revenue. quickly restoring supply.
> ACRs can be configured and settings managed from system control without technicians
In addition to ACRs, the Schneider Electric family of having to visit each individual recloser in the field, with a consequent reduction in travelling
switchgear includes remotely controlled and monitored time and improved system integrity.
pole-mounted load break switches and sectionalizers,
as well as remote control and monitoring software. Increased Customer Satisfaction
> Reduced Customer Minutes Lost: Supply can be quickly restored to fault-free areas.
The Schneider Electric Switchgear and Controller
product ranges create a complete solution for
Deferred Capital Expenditures
distribution system automation (DSA). > Remotely controlled and monitored reclosers give an improved knowledge of a system and
provide better system control. Feeder and substation load can then be remotely managed,
improving utilization of your existing plant. Purchase of new plant can then most likely be
deferred for a considerable period of time.
Opening
Openingof ofthe
thecontacts
contactsisisachieved
achievedbybyreleasing aa
releasing controlled
controlledpulse
pulseof of
current from
current froma capacitor
a capacitor
through
throughthe thetrip
tripcoil.
coil.This
Thisattracts
attractsthe
thetrip
tripbar
bararmature,
armature, turning thethe
turning triptrip
barbar
andandreleasing thethe
releasing
1 12
latch.
latch.The
Theopening
openingspringspringand
andthe
thecontact
contactpressure
pressuresprings
springs accelerate
accelerate thethe
contacts
contacts open. A A
open.
flflexible
exible connection
connectionisisprovided
providedtotoallow
allowmovement
movement of of
thethe
contacts
contactsto to
occur.
occur.
Epoxy
Epoxy bushings
bushingsinsulate
insulatethe
themain
maincircuit
circuitconductors
conductors from thethe
from tank
tankand provide
and a double
provide a doubleO-ring
O-ring
2 seal.
seal. They
Theyalso
alsoprovide
providethe
thenecessary
necessaryinsulation
insulationandandsupport
support forfor
thethe
embedded
embedded capacitive
capacitive
13
voltage
voltagetransformers
transformers(CVT)
(CVT)andandfor
forthe
thecurrent
currenttransformers
transformers (CT).
(CT).The bushings
The areare
bushings DINDIN
47 47
636636
(threaded
(threadedoption)
option)and
andallow
allowthe
theconnection
connectionofof alternative
alternativecable
cableconnection
connectionelbows if desired.
elbows if desired.
Lightning
Lightningarrester
arrestermounting
mountingisisprovided
providedforforinstallation
installationconvenience.
convenience.
14
AA standard
standardkit kitfor
forfifield
eld fifitting
tting isissupplied
suppliedwith
withthe
thecircuit
circuitbreaker.
breaker.It It
contains
containssilicone
silicone bushing
bushing
boots
bootsand and9.85
9.85ft.ft.(3(3m)
m)lengths
lengthsofof.372
.372in.² (240
in.² (240mm²) aluminium
mm²) aluminiuminsulated water-tight
insulated water-tight cable
cable
tails
tails rated
ratedatat630
630A. A.This
Thisarrangement
arrangementresults
resultsinina arecloser
reclosersuitable
suitable forfor
connection
connection into an an
into
15 insulated
insulatedconductor
conductorsystem,system,orora abare
bareconductor
conductor system,
system, as as
appropriate.
appropriate. TheThefullyfully
insulated
insulated
systemprovides
system providesfreedom
freedomfrom fromfaults
faultscaused
causedbyby birds
birds andand other
other wildlife.
wildlife.
3
16 An
An auxiliary
auxiliary voltage
voltagesupply
supplyofof110,
110,220, oror
220, 240 volts
240 ACAC
volts is required to power
is required thethe
to power unitunit
and,and,
if if
4 necessary,
necessary, aa VT can be
voltage provided as
transformer a purchase
can option.
be provided as aThe ADVC is
purchase connected
option. by a control
The ADVC is
17 cable to the by
connected bottom of the
a control circuit
cable to breaker through
the bottom a rubber
of the covered through
circuit breaker plug/socket arrangement.
a rubber covered
5 plug/socket arrangement.
A clearly visible external pointer shows the contact position. The recloser can be tripped from
18 the ground
A clearly by a hookstick.
visible It can shows
external pointer then bethe
locked out by
contact opening
position. therecloser
The isolatingcan
switches located
be tripped from
6 on
thethe operator
ground by acontrol panel.
hookstick. These
It can switches
then are physically
be locked connected
out by opening in seriesswitches
the isolating with bothlocated
the
trip andoperator
on the close solenoids.
control panel. These switches are physically connected in series with both the
7 19 trip and close solenoids.
The ADVC interfaces to the recloser via the control cable and connects to the switch cable
20 entry module
The ADVC (SCEM) in
interfaces tothe
thebase of the
recloser viatank. The SCEM
the control cableuses
andnonvolatile
connectsmemory to store
to the switch all
cable
8 relevant calibration
entry module (SCEM) data,
in ratings,
the baseand number
of the tank.ofTheoperations.
SCEM usesThe non-volatile
SCEM also provides
memory the first all
to store
21 stage of electrical
relevant calibration isolation and shorting
data, ratings, electronics
and number to short theThe
of operations. CTsSCEM
and CVTs
alsoinprovides
the eventthe thefirst
9 control
stage ofcable is disconnected
electrical isolation and while current
shorting is flowing through
electronics to short the
the recloser.
CTs and CVTs in the event the
22 control cable is disconnected while current is flowing through the recloser.
10
11 23
24
Cross section of circuit breaker
Legend
1: Cable tails 13: DIN 47 636 bushings
2: Current transformer 14: Capacitive voltage
3: 316 grade stainless transformer (CVT)
steel tank 15: Lightning arrester
4: Air- or gas-filled tank and mountings
5: Flexible connection 16: Vacuum interrupter
6: Closing solenoid 17: Contacts
7: Opening spring 18: Pushrod
8: Mechanism plate 19: Contact pressure spring
9: Switch cable entry 20: Latch
module (SCEM) 21: Trip bar
10: Cable-entry cover 22: Trip bar armature
11: Cable to control cubicle 23: Trip coil
12: Silicone bushing boot 24: Manual trip lever
N-Series Automatic Circuit Recloser
A
A built-in
built-in microprocessor
microprocessor controlled
controlled power
power supply provides uninterrupted
supply provides uninterrupted operation
operation ofof not
not
only
only the
the circuit
circuit breaker and controller,
breaker and controller, but
but also
also the
the communications
communications radio
radio or
or modem.
modem. These
These
accessories are connected to a built-in user
user-programmable radio power
programmable radio power supply.
supply. Therefore
Therefore
no other power supplies are required for connection into into your SCADA
SCADA or distribution
distribution
automation
automation system.
system.
Due
Due toto careful
careful design
design,thetheefficiency
efficiencyofof
allall parts
parts is extremely
is extremely high,
high, allowing
allowing a battery
a battery holdhold-up
up timetime
hours.2.2 The
of up to 44 hours Thearchitecture
architectureused
usedhas hasthe
theadvantage
advantagethat that the
the circuit
circuit breaker
breaker operation
operation
is independent of of the
the high-voltage
high-voltagesupply,
supply,relying
relyingonona aset
setofof capacitors
capacitors charged
charged byby
thethe
auxiliary supply.
supply.
Due to sophisticated
Due to sophisticated power-supply-management
power-supply-managementtechniques,
techniques,aacircuit
circuitbreaker
breakeroperation
operation is is
always
always guaranteed when attempted
guaranteed when attemptedand
andalarms
alarmsare
areraised
raisedover
overthe
thetelemetry
telemetry when
when auxiliary
auxiliary
power is lost.
> ULTRA
> COMPACT
The table below outlines some of the differences between the two models.
ULTRA COMPACT
Enclosure 316 stainless steel 304 stainless steel
Door locking Three-point Two-point
Customer Side tray Side tray only
accessory tray Upper tray
Input/Output modules 8 inputs, 8 outputs N/A
Optional
Battery heater Optional N/A
Battery 7 Ah or 12 Ah 7 Ah
ADVC COMPACT (with setVUE) Temperature
Temperature range
Range -40 °F (-40 °C) to 122 °F (50 °C) -14 °F (-10 °C) to 122 °F (50 °C)
(with battery heater option)
Telemetry Interface
The Schneider Electric ACR can be interfaced to your SCADA system either through its built-in
V23 modem and a radio, or its RS232 ports and a modem of your choice. RS485 and Ethernet
TCP/IP are also available. A variable-voltage uninterruptible power supply is included for the
radio or modem, which can be mounted inside the communications cubicle. Many telemetry
protocols can be supported such as DNP3 and IEC 60870-5-101.
Computer Interface
WSOS isis an
WSOS an advanced
advanced personal-computer-based
personal-computer-basedsoftware
softwarepackage
packagetotoallow
allowoffl
off-line andonline
ine and on-line
programming,monitoring,
programming, monitoring,and
andcontrol
control of
of aa recloser
recloser via a USB port, RS232
RS232 port, or
or Ethernet.
Ethernet.
Remote Control
The ADVC offers an impressive list of communication ports for use in remote control applications:
Every controller
controller is
is programmed
programmed with with aa standard
standard confi guration of
configuration ofStatus
StatusLights
Lightsand
and
Quick Action
Action Keys
Keys — — text
text labels
labels are
are used
used to
to mark
mark the
the function
function of
of each.
each. These
These labels
labels are
are inserted
inserted intointo special
special pockets
pockets within
within thethe flexVUE
flexVUE operator
operator interface
interface andand
cancan
be be
changed in the fifield
eld if required.
A
A graphical panel configuration
graphical panel configuration tool
tool isis provided
providedas aspart
partofofthe
theWSOS
WSOS55software
softwarepackage
package
that
that will allow full
will allow full customization
customization ofof the
the flexVUE operatorinterface,
flexVUEoperator interface,ififrequired.
required.With
Withthe
the
tool
tool you
you can create your
can create your own
own logic
logicfunctions
functionsdriving
drivingthe
theStatus
StatusLights,
Lights,as aswell
wellasaschange
change
the
the actions linked to
actions linked to each
each Quick
Quick Action
ActionKey. Key.New
Newlabels
labelscan
canbebeprinted
printedfrom
fromthe
theWSOS
WSOS
template
template using standard office
using standard office paper,
paper,cut cutto
tosize,
size,and
andinserted
insertedinto
intothethecontroller.
controller.
WSOS
WSOS Version
Version 55 integrates
integrates the
theSchneider
SchneiderElectric
Electricfifield-proven, Windows®®-based
eld-proven, Windows -based
switchgear
switchgear operating
operatingsystem
systemandandits
itspowerful
powerfulfeatures
featuresand
andtools,
tools,developed
developedover overmany
many
years,
years, into
into aa modern
modern desktop.
desktop.The
The desktop
desktopincludes
includesthe
theSwitchgear
SwitchgearExplorer
Explorerto to
organize
organize your
your switchgear
switchgearthetheway
wayyou
youlike
likeititand
andthe
theLaunch
LaunchPadPadfor
forhandy
handylinks
linkstoto
Example of setting the Quick Action Keys
online
online help,
help, getting
getting started,
started,updates,
updates,andandmuch
muchmore.more.Controlling,
Controlling,confi guring, and
configuring, and
accessing
accessing valuable
valuable switchgear
switchgeardata
datafrom
fromlocal
a localor or
remote
remotelocations is now
locations even
is now eveneasier
easier
than
than before.
before.
Reclose Times
> First reclose time range: 0.5 – 180 sec.
> Second reclose time range: 2.0 – 180 sec.
> Third reclose time range: 2.0 – 180 sec.
> Timing resolution: 0.1 sec.
Trips to Lockout
Overcurrent and fault trips to lockout are selectable between 1 and 4. A separate setting is
available for sensitive ground fault and negative phase sequence.
Extremely inverse
Extremely inverse
> Three IEEE C37.112 inverse time curves: Moderately inverse
Very inverse
10
Extremely inverse
> 42 nonstandard
non-standardinverse
inversetime
timecurves:
curves: Refer to the Operating
Manual for a full listing
Instantaneous Protection
Instantaneous protection works by tripping the recloser if the line current exceeds the
1
Threshold
Maximum time
> Definite time resolution: 0.1 sec.
Modified curve
> SGF trip current setting resolution: 1A
> SGF operating time resolution: 0.1 sec.
Loss of Phase
WSOS offers a quick, easy way to configure the protection groups.
Loss of phase protection trips the recloser if phase-ground voltage on one or two phases falls
below a set voltage threshold for a set length of time.
Dead Lockout
Dead lockout prevents a reclose unless one or more of the source side or load side terminals
are live. If all terminals are dead then the controller goes to lockout.
Directional Protection
Directional
Distinct protection
protection for is distinct
faults protection
in the for faults
forward and in the
reverse forwardAand
direction. reverse
forward faultdirection.
may use a
A forward
different fault may use
time-current a different
curve time-current
and settings curvefault
to a reverse and (i.e.,
settings
thesetoare
a reverse fault
individually
(i.e., these are
selectable). individually
Both the forwardselectable).
protectionBoth
and the forward
reverse protection
protection areand reverseat
operating protection
the same time.
are operating
This at the same
is an additional time.This
protection is an additional protection feature.
feature.
Sequence Components
Negative-, positive-, and zero-phase sequence currents and voltages can be monitored
and logged.
In addition, the negative-phase sequence current protection can be used for detection of
low-level phase-to-phase faults in the presence of high-level, three-phase loads. Inverse time,
definite time, and instantaneous operation is available.
Under/Over-Frequency Protection
Trip Delay
Normal Frequency
Frequency
Count
Close Time
Under/over-frequency protection
Under/over-frequency protectiontrips
tripsthe
therecloser
recloserwhen
whenthe
thesystem
systemfrequency
frequencyexceeds
exceedsthe
the
Over Frequency
Trip setting under-and
under andover-frequency
over-frequencytrip
tripthreshold
threshold values;
values; frequency
frequency tripping
tripping range:
range: 45 – 65
65 Hz
Hz
Over Frequency
Normal restore
Trip at
this time Close at
this time > Frequency calculation: Once per cycle over a two-cycle period
Time
Nominal
> Number of under/over-frequency
Frequency
Axis
cycles before tripping: 2 – 1,000
> Accuracy: ±0.05 Hz
Under/over-frequency protection
> Under/Overvoltage Protection
When selected, and a nominal phase-to-ground system operating voltage is set, the
under/overvoltage protection works within a defined threshold above and below the
specified voltage.
> Undervoltage
Under voltagelower
lowerthreshold
thresholdrange:
range: 50% – 88%
> Overvoltage
Over voltageupper
upperthreshold
thresholdrange:
range: 112% – 150%
> Trip range (after x sec.): 0 – 300 sec.
> Phase logic:
t AND: when ALL phases deviate beyond thresholds
t OR: when ANY phase voltage deviates beyond the thresholds
t AVERAGE: when the numerical AVERAGE of all phase voltages deviates
beyond the threshold
Event History
> Maximum number of typical events stored in the event history: 30,000 events
Gas Pressure Measurement (SF6 or Dry Air “N-green” Option)
> Gas pressure display resolution: .725 psi (5 kPa)
> Gas pressure display accuracy: ± 1.45 psi (±10 kPa)
> Gas low alarm setting: 9.427 psi gauge @ 68 °F (65 kPa gauge @ 20 °C)
> Gas low alarm/interlock accuracy: ±1.45 psi (±10 kPa)
Optional radio
antenna (installed
by customer)
C Standard Lug
D
Torque both M10
Bolts to 32.5 lb./
ft. (44 Nm) using
ADVC Controller a .67 in (17 mm)
Socket
Boot
Control Cable
Bushing Palm
(Factory Fitted)
Bushing
Notes
(1) Details given in this illustration are subject to change without notice. For full details see the Installation Manual.
(2) Grounding connections are not shown and are to be in accordance with the Installation Manual.
(3) Recloser can be mounted closer to pole if lightning arresters are pole-mounted.
(4) Optional substation mounting frame available on request.
N-Series “N-green”
option
15 kV 27 kV 38 kV 38 kV 38 kV
12.5 kA 12.5 kA 12.5 kA 16 kA 16 kA
Ratings
Rated Maximum Voltage 15.5 kV 27 kV 38 kV 38 kV 38 kV
Rated Nominal Voltage (Phase to Ground)
Rated Continuous Current 800 A 800 A 800 A 800 A 800 A
Emergency Current (8 Hours) 850 A 850 A 850 A 850 A 850 A
Fault Make Capacity (RMS) 12.5 kA 12.5 kA 12.5 kA 16 kA 16 kA
Fault Make Capacity (Peak) 31.5 kA 31.5 kA 31.5 kA 40 kA 40 kA
Power Operating Time (Close/Open) 0.1/0.05 s 0.1/0.05 s 0.1/0.05 s 0.1/0.05 s 0.1/0.05 s
Mechanical Operations 10,000 10,000 10,000 10,000 10,000
Rated Full Load Operations 10,000 10,000 10,000 10,000 10,000
Short Time Current 12.5 kA 12.5 kA 12.5 kA 16 kA 16 kA
Breaking Capacity
Mainly Active (0.7pf) 800 A 800 A 800 A 800 A 800 A
Fault Break Capacity 12.5 kA 12.5 kA 12.5 kA 16 kA 16 kA
Cable Charging 25 A 40 A 40 A 40 A 40 A
Line Charging
Transformer Magnetizing 22 A 22 A 22 A 22 A 22 A
Capacitor Bank 250 A
Lightning Impulse Withstand Level
Phase to Phase
Phase to Ground 110 kV 150 kV 170 kV 170 kV 170 kV
Across Interrupter 110 kV 150 kV 170 kV 170 kV 170 kV
On Loss of SF6 /Dry Air 60 kV 70 kV 70 kV 70 kV 70 kV
Power Frequency Withstand Voltage
Phase to Ground 50 kV 60 kV 70 kV 70 kV 70 kV
Across Interrupter 50 kV 60 kV 70 kV 70 kV 70 kV
Service Conditions
Ambient Temperaturea (OF) -40 to 122 -40 to 122 -40 to 122 -40 to 122 -40 to 122
Ambient Temperaturea (OC) -40 to 50 -40 to 50 -40 to 50 -40 to 50 -40 to 50
Radiation (Max.) 1.1 kW/m 2
1.1 kW/m 2
1.1 kW/m 2
1.1 kW/m 2
1.1 kW/m2
Humidity 0 to 100% 0 to 100% 0 to 100% 0 to 100% 0 to 100%
b
Altitude Feet (Max.) 9,840 9,840 9,840 9,840 9,840
Altitude Meters (Max.) b 3,000 3,000 3,000 3,000 3,000
Net Weights
Circuit Breaker with Pole-Mount Bracket (lb./kg) 549/249 549/249 549/249 549/249 549/249
Control Cubicle with Control Cable (lb./kg) 90/41 90/41 90/41 90/41 90/41
Gross Weight of Crate (lb./kg) 891/404 891/404 891/404 891/404 891/404
External VT (lb./kg) 132/60 132/60 132/60 132/60 132/60
Crate Dimensions
Width (in./mm) 45.7/1,160 45.7/1,160 45.7/1,160 45.7/1,160 45.7/1,160
Depth (in./mm) 28.7/730 28.7/730 28.7/730 28.7/730 28.7/730
Height (in./mm) 64.6/1,640 64.6/1,640 64.6/1,640 64.6/1,640 64.6/1,640
a. Option when cubicle battery heater is fitted (-14 °F to 122 °F {-10 °C to 50 °C} without heater)
b. For altitudes above 1,000 m (3,280 feet), derate in accordance with ANSI C37.60 for reclosers (ANSI C37.63 for LBS)