DR-UPS40: 40A DC UPS Module
DR-UPS40: 40A DC UPS Module
DR-UPS40: 40A DC UPS Module
■ Features :
Battery controller for DIN Rail UPS system
Parallel connection to DC BUS
Suitable for 24V system up to 40A
Installed on DIN Rail TS35 / 7.5 or 15
Built-in battery test function
Battery polarity protection
Relay contact signal output and LED indicator for DC BUS OK,
Battery Fail, and Battery Discharge
Cooling by free air convection
3 years warranty
SPECIFICATION
MODEL DR-UPS40
DC INPUT / DC VOLTAGE (Typ.) Note.5 24 ~ 29V
DC BUS RATED CURRENT 40A
VOLTAGE RANGE (Typ.) 21 ~ 29V
BATTERY
CURRENT RANGE 0 ~ 40A
INPUT /
CHARGE CURRENT (Typ.) Note.4 2A
OUTPUT
EXTERNAL BATTERY (Typ.) 4 / 7 / 12AH / 24V
RELAY CONTACT RATING (max.) 30VDC, 1A
Relay contact : Short when DC voltage between 21~29V(±3%), relay contacts
DC BUS OK
LED(Green) : DC BUS OK : light ; DC BUS fail : dark
Short when battery voltage falls below 21.9V(±3%) or battery failure is observed through the battery test function, relay contacts
FUNCTION BATTERY FAIL Note.2
LED(Red) : Battery over-discharge warning or battery broken : light ; Battery OK : dark
Relay contact : Short when battery in discharge condition, relay contacts
BATTERY DISCHARGE
LED(Yellow):light : Battery discharging ; dark : Battery is not discharging or discharging current<2.0A
WORKING TEMP. -20 ~ +70℃
WORKING HUMIDITY 20 ~ 90% RH
ENVIRONMENT
STORAGE TEMP., HUMIDITY -20 ~ +85℃, 10 ~ 95% RH
VIBRATION Component : 10 ~ 500Hz, 2G 10min./1cycle, 60min. each X, Y, Z axes ; Mounting : Compliance to IEC600068-2-6
WITHSTAND VOLTAGE Terminal-Chassis :0.5KVAC, Relay Contacts-Terminal :0.5KVAC
SAFETY & ISOLATION RESISTANCE Terminal-Chassis :>100M Ohms / 500VDC / 25℃/ 70% RH
EMC
(Note 3) EMC EMISSION Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, heavy industry level, criteria A, EAC TP TC 020
MTBF 161.9K hrs min. MIL-HDBK-217F (25℃)
OTHERS DIMENSION 55.5*125.2*100mm (W*H*D)
PACKING 0.55Kg; 20pcs/12Kg/1.29CUFT
NOTE 1. All parameters NOT specially mentioned are measured at rated load and 25℃ of ambient temperature.
2. Battery fail will only function at UPS mode with battery connected. Every 25 seconds, unit will send out test signal through "Battery Fail" relay contact and
LED indicator once the battery is fail.
3. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
4. Battery charging will be in progress when DC input > battery voltage.
5. DR-UPS40 will be in operation when DC input is applied at the beginning.
6. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
100
125.2
LED TB2
1 1
2
2
55.5
3
TB1 4
3 5
6
4
2 BATTERY INPUT -
3 DC INPUT -
4 DC INPUT +
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Terminal Pin No. Assignment (TB2)
Pin No. Assignment
1 BAT DISC 1
2 BAT DISC 2
3 BAT FAIL 1
4 BAT FAIL 2
5 DC OK 1
6 DC OK 2
LOAD 25Ax2
100
+
+
24V
BAT. BATTERY 80
TEST
CHARGE
INPUT CIRCUIT
POWER LIMIT 60
SUPPLY
LOAD (%)
40
DETECTION 20
CIRCUIT
-20 0 10 20 30 45 50 60 70 (VERTICAL)
DC BAT BAT
OK FAIL DISCHARGE
AMBIENT TEMPERATURE (℃)
DR-UPS40
24V PSU
Battery 24V/40A max. Load
BAT DC
+ - - +
- + + - + -
DR-UPS40 DR-RDN20
24V
Battery PSUA PSUB Load
BAT DC
+ - - + Vout Vin
+ - - - B+ A+
- + + - + - + -