Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Characterstic Strength:: Annexure-Vc Structural Design of Combined Footing For Column

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 2

GMR Consulting Services Private Limited

ANNEXURE-VC
STRUCTURAL DESIGN OF COMBINED FOOTING FOR COLUMN

Characterstic strength:
Concrete, fck = 25 N/mm2
Allowable base pressure, qall = 1250 kN/m2
Steel, fy = 500 N/mm2
Section parameter: Depth of column, D = 600 mm
Width of column, W = 1200 mm

Location of Cloumn wrt to footing = Edge

Clear cover for tension reinf. = 50.0 mm


Dia. Of bar provided, d1 = 16.0 mm
Area of bar provided = 201 mm2

Design parameter: Staad Node 33


Load case 104
Factored Axial Load, P 2701.286 kN
Factored Major axis moment, Mx = 164.844 kNm
Factored Minor axis moment, Mz = 0 kNm
Partial load Factor = 1.5

Axial Load, P 1800.86 kN


Major axis moment, Mx = 109.90 kNm
Minor axis moment, Mz = 0.00 kNm
eccentricity due to moments
eccentricity, ex = 61 mm
eccentricity, ez = 0 mm
eccentricity due to column location
eccentricity, e'x = 0 mm
eccentricity, e'z = 800 mm

Footing Width provided, Lx = 4000 mm


Footing length provided, Lz = 2200 mm

Avg. base pressure at


P/A±6*P*ex/(Lx*A) Heel = 669.87 kN/m2
±6*P*ez/(Lz*A) Toe = -260.58 kN/m2

Depth of footing provided, Df= 850 mm


Effective depth provided, major axis = 792 mm
Effective depth provided, minor axis = 776 mm

Design for flexural reinforcement


For Mx' - Major axis
Interpolated base pressure at face of cloumn = 416.1 kN/m2
Maximum design moment at face of column = 597 kNm

Effective depth rqeuired = 285 mm OK


Ast. Required = 1770 mm2
Spacing required = 250 mm
Spacing provided = 200 mm OK
%Ast provided = 0.12 %

Check for one way shear


For major axis only
length D+d = 1392
Effective length for shear = 808 mm
Interpolated base pressure at d from face of col. = 81 kN/m2
Length under compression = 191.9 mm

Shear force = 46.71 kN


Design Shear Stresses = 0.01 N/mm2
b= 24.54
Permissible Stress (τc) = 0.29 N/mm2 OK

Check for two way/punching shear


Avg. Base pressure (considered) = 205 kN/m2
Design Shear force at d/2 from face of col.= 2213 kN
Design shear stress = 0.779 N/mm2
Limiting shear stress for two way shear = 1.25 N/mm2 OK
[ks*0.25*sqrt(fck)] where, ks = 2.500
(should not be >1)
Design Check of Rock anchors for tension
Length under tension = 616 mm
Width under tension = 4000 mm
Total force in tension = -321.1 kN (-) for tension
Dia. of rock anchors = 32 mm
Length of anchor = 3.5 m
Capacity of each anchor = 293.2 kN
No. of rock anchors required = 1.10
No. of rock anchors provided = 2 OK

P2 MZ P1

Column
X X MX X

LZ LZ
Z

P3
P4
LX

Bajoli Holi H.P.P.(180MW)


GMR Consulting Services Private Limited

ANNEXURE-VD
STRUCTURAL DESIGN OF COMBINED FOOTING FOR COLUMN

Characterstic strength:
Concrete, fck = 25 N/mm2
Allowable base pressure, qall = 1250 kN/m2
Steel, fy = 500 N/mm2
Section parameter: Depth of column, D = 600 mm
Width of column, W = 1200 mm

Location of Cloumn wrt to footing = Middle

Clear cover for tension reinf. = 50.0 mm


Dia. Of bar provided, d1 = 16.0 mm
Area of bar provided = 201 mm2

Design parameter: Staad Node 6884


Load case 102
Factored Axial Load, P 3728.298 kN
Factored Major axis moment, Mx = 233.598 kNm
Factored Minor axis moment, Mz = 0 kNm
Partial load Factor = 1.5

Axial Load, P 2486 kN


Major axis moment, Mx = 155.732 kNm
Minor axis moment, Mz = 0.000 kNm
eccentricity due to moments
eccentricity, ex = 62.6554 mm
eccentricity, ez = 0.0000 mm
eccentricity due to column location
eccentricity, e'x = 0 mm
eccentricity, e'z = 0 mm

Footing Width provided, Lx = 3000 mm


Footing length provided, Lz = 2200 mm

Avg. base pressure at


P/A±6*P*ex/(Lx*A) Heel = 423.79 kN/m2
±6*P*ez/(Lz*A) Toe = 329.40 kN/m2

Depth of footing provided, Df= 1000 mm


Effective depth provided, major axis = 942 mm
Effective depth provided, minor axis = 926 mm

Design for flexural reinforcement


For Mx' - Major axis
Interpolated base pressure at face of cloumn = 389.5 kN/m2
Maximum design moment at face of column = 586 kNm
Effective depth rqeuired = 282 mm OK
Ast. Required = 1450 mm2
Spacing required = 305 mm
Spacing provided = 200 mm OK
%Ast provided = 0.10 %

Check for one way shear


For major axis only
length D/2+d = 1242 mm
Effective length for shear = 0 mm
Interpolated base pressure at d from face of col. = 430 kN/m2

Shear force = 0.00 kN


Design Shear Stresses = 0.00 N/mm2
b= 28.87
Permissible Stress (τc) = 0.29 N/mm2 OK

Check for two way/punching shear


Avg. Base pressure (considered) = 377 kN/m2
Design Shear force at d/2 from face of col.= 1862 kN
Design shear stress = 0.361 N/mm2
Limiting shear stress for two way shear = 1.25 N/mm2 OK
[ks*0.25*sqrt(fck)] where, ks = 2.500
(should not be >1)

Z
P2 MZ P1

X X
MX Column LZ

Z
P3 P4
LX

Bajoli Holi H.P.P.(180MW)