Elmeasure Energy Process Monitor Energyprocess Programming Guide
Elmeasure Energy Process Monitor Energyprocess Programming Guide
com
Ph: +91 80 32904489
‘OLD’ register to store the previously cleared energy value. 5. LED INDICATION
Simultaneous sampling of Volts & Amps. LED Meaning LED
Meaning
Status Status
Universal Voltage Input Line to Line (50 to 550V AC) and Current M Mega Pulse
- Minus REV Reverse
secondary Input (0.05A to 6A).
K Kilo OLD Old Reading (Cleared readings)
Energy display programmable-counter based or resolution based. With digit “0” blinking
A
_________
80-300VDC
80-300VAC
15 Press DOWN key Programmable Range: 2 PT Primary (P.P) 415.0 100V- 999kV
0.5A to 6A Follow the same
(CT Secondary) 3 PT Secondary (P.S) 415.0 50V - 550V
procedure as explained in
(5.00 -default/factory set)
step-10 to 12. CT Primary (C.P)
4 5.000 0.5A - 99kA
16 Press DOWN key Arithmetic (Arth), 5 CT Secondary (C.S) 5.000 0.5A - 6A
Vector harmonics (UEC.H).
(Method of VA Selection). 6 VA selection (UA) UEC.H Arth (Arithmetic)/UECt(Vector)
Vector (UECt). Can be
selected using RIGHT & /UEC.H(vector harmonics)
DOWN key. 7 Analog Input 1Parameter(A.1) dISA Disable/0.t.1.V / 0.t.20mA/
17 Press DOWN key Analog Input 1 parameter. 4.t.20mA
Options: Disable/0.t.1.V / 8 Analog Input 2 Parameter(A.2) dISA 0.t.1.V/0.t.20mA/4.t.20mA
0.t.20mA/4.t.20mA
18 Press DOWN key Analog Input 1 Full Scale. 9 Baud rate (b) 9600 1200 to 19.2k
Range: 0.001 to 9999 Mega
10 Parity (P) Even Even/ Odd/ no
(Displays only when A1. is
selected) 11 Device Id (d) 1.000 1.000 to 247.0
19 Press DOWN key Analog Input 2 parameter
12 Reverse lock(r.L) no Yes/no
0.t.1.V/0.t.20mA/4.t.20mA
20 Press DOWN key Analog Input 2 Full Scale. 13 Password (PW) 1000 1000 to 9999
Range: 0.001 to 9999 Mega
(Displays only when A2. is 14 Energy (E) rESO rESO/COUπ
selected)
21 Press DOWN key 15 Starting Current (S.A) 0.08 0.020% to 10% of Fullscale
Defines the baud
(baud rate) rate. Option: 2400, 4800, 16 Energy Selection (E S.) Wh Wh/VAh
Communication speed. 9600, 19.20k. Options can
(9600 default /factory set) be changed using RIGHT &
DOWN keys.
as in step 10 to 12.
24 Press DOWN key Reverse lock (blocks energy
accumulation in case the
(Reverse lock)
CT polarity is reverse).
Option : NO/YES 90 mm Panel
52 mm