Elmeasure Energy Process Monitor Energyprocess Programming Guide

This document provides a programming guide for an EPM 5110 energy meter. It includes: 1. An overview of the meter's key features such as true RMS measurement, energy accumulation, and a user configurable password. 2. Details on the meter's unique features like a 1 row 6 digit display and parameters shown for phases. 3. A wiring diagram showing the meter's voltage and current connections. 4. Steps for entering the meter's configuration mode through the front panel to set up parameters.

Uploaded by

saqib ghouri
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views

Elmeasure Energy Process Monitor Energyprocess Programming Guide

This document provides a programming guide for an EPM 5110 energy meter. It includes: 1. An overview of the meter's key features such as true RMS measurement, energy accumulation, and a user configurable password. 2. Details on the meter's unique features like a 1 row 6 digit display and parameters shown for phases. 3. A wiring diagram showing the meter's voltage and current connections. 4. Steps for entering the meter's configuration mode through the front panel to set up parameters.

Uploaded by

saqib ghouri
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

support@elmeasure.

com
Ph: +91 80 32904489

HO & Unit -1 : Unit -2 :


47-P, Hardware Park, KIADB, Goutham Garden, No.4,
Huvinayakanahalli Bengaluru - 562149 Veerapandi, Coimbatore - 641 019
Karnataka INDIA. Tamilnadu INDIA
PROGRAMMING GUIDE
Sales Offices :
BENGALURU CHENNAI COIMBATORE MUMBAI DELHI HYDERABAD USA UAE EPM 5110
PG/EPM/V0/1117 www.elmeasure.com

1. FEATURES 4. KEY FUNCTIONS


Key In SET (Programming) mode In RUN (Measurement) mode
Universal Auxiliary supply (80V to 300V AC/DC)
Right/UP To select the value and accept the value To scroll pages in upward direction
True RMS measurement. (it act as a Right key in programming to look at different parameters.
mode)
Active Energy, positive energy accumulation DOWN To edit the value/system types To scroll pages in downward
downward in edit mode and scroll direction to look at different
User configurable (Editable) password through the parameters. parameters

‘OLD’ register to store the previously cleared energy value. 5. LED INDICATION
Simultaneous sampling of Volts & Amps. LED Meaning LED
Meaning
Status Status
Universal Voltage Input Line to Line (50 to 550V AC) and Current M Mega Pulse
- Minus REV Reverse
secondary Input (0.05A to 6A).
K Kilo OLD Old Reading (Cleared readings)

2. UNIQUE FEATURES Communication

1 row 6 digit display for readability. 6. ENTERING CONFIGURATION (SETUP) MODE


To configure the setup parameters through front panel, the following steps can be
Parameters (VLL, VLn, A, F, W, VA, Wh, PF, Load hour) along with followed.
Step Actions Display Reads Range/Options/Comments
respective R, Y and B Phases.
1 Press RIGHT &
Auto-scaling of kilo, mega, & decimal point. DOWN keys together to
enter SETUP
Energy selection : Wh/VAh 2 Press DOWN key

Energy display programmable-counter based or resolution based. With digit “0” blinking

Energy resetting at 999999KVAh x Multiplication factor.

4. WIRING DIAGRAM (ITF) 3 Press DOWN key to If any other password is


decrement the first digit already set press RIGHT and
RS 485
to “9” sequentially come first digit “1” blinking. DOWN key to reach the
to digit 1. right password
U
X

A
_________
80-300VDC
80-300VAC

4 Press RIGHT key Defines the clearing


Single phase S1 AR S2 S1 AY S2 S1AB S2 VR VY VB N four times to accept the option for the meter
connection password. display CLr
S1 S2
R
CLEAR Mode : Press RIGHT key for CLEAR Mode
N
LINE DELIVERED RECEIVED LOAD
5 Press RIGHT key Option : (YES) /(NO)
Y (for clearing )
RS 485
Options can be changed by
N (for not clearing)
pressing DOWN key. Display
U
X

will prompt to 'y' or 'n' while


_________
80-300VDC
80-300VAC

pressing DOWN key.


S1 AR S2 S1 AY S2 S1 AB S2 VR VY VB N
Delta connection (2E) 6 Press RIGHT key
3Phase 3 wire system To accept the edited
Displays xxxx LL
option.
R
(Clear Mode ends here)
S1 S2
Y
B
SETUP Mode : Press DOWN key for SETUP Mode
S1 S2
N
LINE DELIVERED RECEIVED LOAD 7 Press DOWN key Defines the power system
configuration.
display StAr.EL
RS 485
Options: STAR /DELTA/1.
Phase
U
X

8 Press RIGHT key Press RIGHT key to


_________
80-300VDC
80-300VAC

accept the mode.


Star connection (3E) S1 AR S2 S1 AY S2 S1 AB S2 VR VY VB
StAr/ dELt/ 1.Phase, selected
N
mode blinks. Options can be
3Phase 4wire system
changed by pressing DOWN key.
R
S1 S2
S1 S2
Y 9 Press DOWN key Programmable Range:
B
S1 S2
N 100V to 999kV
LINE DELIVERED RECEIVED LOAD XXXX P.P (PT Primary)
(415.00 -default/factory set)
10 Press RIGHT key 27 Press DOWN key Energy value format i.e.,
the energy accumulated in
First digit blinking can be edited
the meter to be displayed
using DOWN key.
in Resolution or Counter
11 Press RIGHT key to format. Option: resolution/
accept the edited value counter
Second digit blinking, can be
for first digit.
edited using DOWN key. Press
28 Press DOWN key Starting current value to be
RIGHT key to accept the edited
displayed in the meter
value. Continue the same Starting Current Range: (0.02% to 10% of
method till fourth digit.
full scale)
12 Press Right key to Eg: To set 11.00kV
29 Press DOWN key Energy Selection.
accept the value. Set first four digits (1100)
Decimal point blinking. Can be set Option : Wh/VAh
at appropriate location using DOWN as explained above keep
30 Press DOWN key blinking. If “n”(no) is selected then
key. Ascertain the correct scale pressing DOWN key to
Meter enters into RUN
(Mega/Kilo) is selected. Mega/Kilo place decimal point at mode without affecting any
31 Press RIGHT key to
is placed on the right hand side of appropriate location. edited Values in the setup
store the changes done
the display by Letter M/K. Press USE RIGHT/DOWN key.. Displays XXXX LL (Setup
RIGHT key to accept the edited value. Mode ends here and
13 Press DOWN key Programmable Range: returns to Run mode).
50V to 550V Follow the Once the required parameter is programmed press the DOWN key continuously till it reaches
(PT Secondary)
same procedure as SAVE page.
(415.00 -default/factory set)
explained in step-10 to 12.
14 Press DOWN key Programmable Range:
0.5A to 99kA Follow the 7. The List of parameters can be configured and the range is given
(CT Secondary) below
same procedure as
(5.00 -default/factory set)
explained in step-10 to 12.
Sl. Parameter Default Range / Options
No. Setup
1 Connection mode(EL) STAR STAR/ DELTA/ 1.Phase

15 Press DOWN key Programmable Range: 2 PT Primary (P.P) 415.0 100V- 999kV
0.5A to 6A Follow the same
(CT Secondary) 3 PT Secondary (P.S) 415.0 50V - 550V
procedure as explained in
(5.00 -default/factory set)
step-10 to 12. CT Primary (C.P)
4 5.000 0.5A - 99kA
16 Press DOWN key Arithmetic (Arth), 5 CT Secondary (C.S) 5.000 0.5A - 6A
Vector harmonics (UEC.H).
(Method of VA Selection). 6 VA selection (UA) UEC.H Arth (Arithmetic)/UECt(Vector)
Vector (UECt). Can be
selected using RIGHT & /UEC.H(vector harmonics)
DOWN key. 7 Analog Input 1Parameter(A.1) dISA Disable/0.t.1.V / 0.t.20mA/
17 Press DOWN key Analog Input 1 parameter. 4.t.20mA
Options: Disable/0.t.1.V / 8 Analog Input 2 Parameter(A.2) dISA 0.t.1.V/0.t.20mA/4.t.20mA
0.t.20mA/4.t.20mA
18 Press DOWN key Analog Input 1 Full Scale. 9 Baud rate (b) 9600 1200 to 19.2k
Range: 0.001 to 9999 Mega
10 Parity (P) Even Even/ Odd/ no
(Displays only when A1. is
selected) 11 Device Id (d) 1.000 1.000 to 247.0
19 Press DOWN key Analog Input 2 parameter
12 Reverse lock(r.L) no Yes/no
0.t.1.V/0.t.20mA/4.t.20mA
20 Press DOWN key Analog Input 2 Full Scale. 13 Password (PW) 1000 1000 to 9999
Range: 0.001 to 9999 Mega
(Displays only when A2. is 14 Energy (E) rESO rESO/COUπ
selected)
21 Press DOWN key 15 Starting Current (S.A) 0.08 0.020% to 10% of Fullscale
Defines the baud
(baud rate) rate. Option: 2400, 4800, 16 Energy Selection (E S.) Wh Wh/VAh
Communication speed. 9600, 19.20k. Options can
(9600 default /factory set) be changed using RIGHT &
DOWN keys.

22 Press DOWN key Internal 8. Enabling and disabling of Auto scrolling


communication error check
(Parity check) Enabling auto scrolling: Press UP key continuously for 5 seconds or until display
EUEn (even)/odd(odd)/no
(no parity). Options can be
shows EnAb for scrolling.
changed using RIGHT & Disabling auto scrolling: Press any key (UP/DOWN), display show dISA and returns to
DOWN keys. normal mode.
23 Press DOWN key Defines the (ID)
communications 9. Mechanical Specification:
(device ID) identification number. Dimension Bezel: Panel Cutout:
Range : 1 to 247 Can be set
using RIGHT & DOWN keys
96 x 96 mm (Depth 50mm behind Bezel) 90+2 +2
-0 x 90 -0 mm

as in step 10 to 12.
24 Press DOWN key Reverse lock (blocks energy
accumulation in case the
(Reverse lock)
CT polarity is reverse).
Option : NO/YES 90 mm Panel
52 mm

25 Press DOWN key Range: 1000-9999.


90 mm

CAUTION: memorize the


(Password user Password. Use the same
definable). Password for next time.
Instruments will reject
other Passwords.
Clamp +2
26 Press RIGHT key to view CAUTION: Password 90-0 mm
the password can be reset only at the
factory. Can be set using
RIGHT & DOWN keys as in
step 10 to 12.