(TDB) EHS Split For Europe (50Hz, HP) Ver.2.1 - 211112

Download as pdf or txt
Download as pdf or txt
You are on page 1of 80

EHS

Technical
Data Book
EHS Split for Europe
(50Hz, HP)

Model : Outdoor unit (AE****XED**/EU)


Hydro unit (AE****NYD**/EU)
History

Version Modification Date Remark

Ver.1.0 Released EHS Split for Europe TDB (R410A, 50Hz, HP) 21.04.14

Ver.1.1 Updated the dimensional drawing page 21.04.21

Ver.2.0 Updated some formats (Specification, Drawing) 21.08.27

Ver.2.1 Modified some contents including R32 line up 21.11.12


Nomenclature
Outdoor Unit

Model Name

AE 160 A X E D E H EU
(1) (2) (3) (4) (5) (6) (7) (8) Buyer

(1) Classification (5) Feature 1

AC CAC E Split
AM DVM T TDM
AJ FJM (Free Joint Multi) Y MONO
AE EHS

(6) Feature 2

(2) Capacity D Deluxe


P Premium
X 1/10 kW (3 digits)

(7) Rating Voltage


(3) Version
A 115V, 60hz, 1Ф
R 2019 B 220V, 60Hz, 1Ф
A 2021 C 208~230V, 60Hz, 1Ф
D 200~220V, 50Hz, 1Ф
E 220~240V, 50Hz, 1Ф
(4) Product Type F 208~230V, 60Hz, 3Ф
G 380~415V, 50Hz, 3Ф
S SET (NASA)
N Indoor Unit (NASA)
X Outdoor Unit (NASA)
A SET (Non NASA)
(8) Mode
B Indoor Unit (Non NASA)
C Outdoor Unit (Non NASA) H Heat Pump (R410A)
G Heat Pump (R32)
Nomenclature
Hydro unit

Model Name

AE 160 A N Y D E H EU
(1) (2) (3) (4) (5) (6) (7) (8) Buyer

(1) Classification (5) Product Notation

AC CAC Y Hydro Unit (Wall Mounted)


AM DVM
AJ FJM (Free Joint Multi)
AE EHS
(6) Feature

D Standard

(2) Capacity

x Liter (3 digits)

(7) Rating Voltage


A 115V, 60hz, 1Ф
(3) Version B 220V, 60Hz, 1Ф
C 208~230V, 60Hz, 1Ф
R 2019 D 200~220V, 50Hz, 1Ф
A 2021 E 220~240V, 50Hz, 1Ф
F 208~230V, 60Hz, 3Ф
G 380~415V, 50Hz, 3Ф
(4) Product Type

S SET (NASA)
N Indoor Unit (NASA)
(8) Mode
X Outdoor Unit (NASA)
A SET (Non NASA) H Heat Pump (R410A)
B Indoor Unit (Non NASA) G Heat Pump (R32)
C Outdoor Unit (Non NASA)
Features & Benefits
Overview

Optimized Seasonal Efficiency

EHS Split delivers efficient performance in all


seasons. Heating performance is optimized
according to the actual operating temperature. It
provides outstanding efficiency with ECO-friendly
design.

Flexibility

EHS split is a versatile system with under


floor heating, hot water and radiator. Our
Hydro Unit can be compatible with a wide
range of additional products such as
thermostats, solar panels and back-up
boilers.

High Reliability

EHS Split includes a number of


improvements that together create
superior performance. The low-noise fan
and Silent Mode at night ensure a
meaningful presence. Our EHS system
creates the perfect living condition.
Contents

1. Line-up 7
1-1. Outdoor Units 7
1-2. Hydro unit 7

2. Outdoor Units 8
2-1. Specifications 8
2-2. Electrical characteristics 16
2-3. Dimensional drawing 17
2-4. Electrical wiring diagram 20
2-5. Sound data 25
2-6. Operation range 27
2-7. Piping diagram 29
2-8. Capacity table 31
2-9. Capacity correction 36

3. Hydro unit 37
3-1. Specifications 37
3-2. Dimensional drawing 39
3-3. Electrical wiring diagram 42
3-4. Sound data 44
3-5. Piping diagram 46

4. Installation 47
47
61
1. Line-up
1-1. Outdoor Units

Capacity 4/6 kW (R32) 9 kW (R32) 12/16 kW (R410A)

Image

AE040RXEDEG/EU AE120AXEDEH/EU
1phase AE090RXEDEG/EU
AE060RXEDEG/EU AE160AXEDEH/EU
Model
AE120AXEDGH/EU
3phase AE090RXEDGG/EU
AE160AXEDGH/EU

1-2. Hydro unit

1phase 3phase

AE090RNYDEG/EU AE090RNYDGG/EU
Model
AE160ANYDEH/EU AE160ANYDGH/EU

Hydro Unit
2. Outdoor Units
2-1. Specifications

Model Name Indoor Unit AE090RNYDEG/EU AE090RNYDEG/EU


Outdoor Unit AE040RXEDEG/EU AE060RXEDEG/EU
Mode - Heat Pump (A2W) Heat Pump (A2W)
Performance Nominal Capacity Heating kW 4.40 6.00
(A7/W35) *1 Btu/h 15,000 20,500
Cooling kW 5.00 6.50
Btu/h 17,100 22,200
Power Input Heating 0.85 1.22
kW
(Nominal) Cooling 1.09 1.47
Current Input Heating 3.90 5.60
A
(Nominal) Cooling 4.90 6.70
COP (Nominal Heating) W/W 5.20 4.92
EER (Nominal Cooling) W/W 4.59 4.42
SCOP (35℃) W/W 4.58 4.58
SEER - 4.40 4.73
Performance Capacity Heating W 4,200 5,600
*2
(A7/W45) COP W/W 3.85 3.71
Performance Capacity Heating W 3,900 5,200
(A7/W55) *3 COP W/W 2.95 2.87
Performance Capacity Heating W 4,200 5,200
(A2/W35) *4 COP W/W 3.82 3.51
Performance Capacity Heating W 4,600 5,500
(A-7/W35) *5 COP W/W 2.97 2.75
System Field Wiring MCA A 16.0 16.0
MFA A 20.0 20.0
Water Connections Water Flow Rate (Heating / Cooling) LPM 12.7/14.4 17.3/18.8
Water Pressure (Max) bar 3 3
Water Pipe Inlet Φ, inch BSPP male 1 1/4" BSPP male 1 1/4"
Outlet Φ, inch BSPP male 1 1/4" BSPP male 1 1/4"
Leaving Water Heating °C 15~65 15~65
Temperature Cooling °C 5~25 5~25
Refrigerant Liquid Pipe Quantity EA 1 1
Connections Type - Flare connection Flare connection
Φ, mm 6.35 6.35
Φ, inch 1/4" 1/4"
Liquid Pipe Quantity EA 1 1
Type - Flare connection Flare connection
Φ, mm 15.88 15.88
Φ, inch 5/8" 5/8"
Installation Limitation Max. Length m 30 30
Max. Height m 20 20
Chargeless Length m 15 15
Operating Temp. Heating (A2W) *6 ℃ -25~35 -25~35
Range Cooling (A2W) ℃ 10~46 10~46
D.Hot Water (A2W) *7 ℃ -25~43 -25~43
Power Supply V, Hz, Φ 220~240, 50, 1 220~240, 50, 1
Compressor Type - BLDC Twin Rotary BLDC Twin Rotary
Model - UB4TN8200FE4SS UB4TN8200FE4SS
Oil Type - POE POE
Quantity EA 1 1
Output W 1623 1623
Starting method - Inverter driven Inverter driven
Heat exchanger Length mm 906.8 906.8
Rows Quantity EA 2 2
Fin pitch mm 1.5 1.5
Passes Quantity EA 4 4
Face area m² 0.53 0.53
Outdoor Unit
Stages Quantity EA 28 28
Tube type - Φ7 Φ7
Fin Type - Corrugate Corrugate
Treatment - NGS NGS
Condenser Size - 2RX28S 2RX28S
Motor Type (Model) - YMAP095AE01A1 YMAP095AE01A1
Quantity EA 1 1
CODE No - DB31-00658D DB31-00658D
Fan Type - Propeller Fan Propeller Fan
Discharge direction - Horizontal Horizontal
Air Flow Rate Heating m³/min 40 43
Cooling m³/min 40 43
2. Outdoor Units
2-1. Specifications

Model Name Indoor Unit AE090RNYDEG/EU AE090RNYDEG/EU


Outdoor Unit AE040RXEDEG/EU AE060RXEDEG/EU
Fan motor Quantity EA 1 1
Model - Brushless DC motor Brushless DC motor
Output W 68W 68W
Drive - Direct drive Direct drive
Speed Heating rpm 740 800
Cooling rpm 740 800
4-Way Valve Type (Model) SHF-7H-34U SHF-7H-34U
Base Heater Power Input W N/A N/A
Sound Sound Pressure Heating dB(A) 44 47
Cooling dB(A) 46 47
Night Mode dB(A) - 35
Sound Power Heating dB(A) 58 60
Outdoor Unit
Cooling dB(A) 61 62
Casing Color - Earth brown Earth brown
Material - Poweder coated Galvanised steel Poweder coated Galvanised steel
Packing Material - EPS/BOX EPS/BOX
Weight kg 3.0 3.0
External Dimension Net Weight kg 46.5 46.5
Shipping Weight kg 49.5 49.5
Net Dimensions (WxHxD) mm 880 x 638 x 310 880 x 638 x 310
Shipping Dimensions (WxHxD) mm 1,023 x 742 x413 1,023 x 742 x413
Refrigerant Type - R32 R32
Control Method - EEV EEV
Factory Charging g / tCO2e 1,200 / 0.81 1,200 / 0.81

NOTE
• Specifications may be subject to change without prior notice.
*1) A2W Condition *1 : (Heating) Water In/Out 30℃/35℃, Outdoor Air 7℃DB/6℃WB;
(Cooling) Water In/Out 23℃/18℃, Outdoor Air 35℃DB.
*2) A2W Condition *2 : (Heating) Water In/Out 40℃/45℃, Outdoor Air 7℃DB
*3) A2W Condition *3 : (Heating) Water In/Out 47℃/55℃, Outdoor Air 7℃DB
*4) A2W Condition *4 : (Heating) Water In/Out 30℃/35℃, Outdoor Air 2℃DB
*5) A2W Condition *5 : (Heating) Water In/Out 30℃/35℃, Outdoor Air -7℃DB
*7) The system is operated in (-25°C ≤ Outdoor temp. < -20°C) condition, but no guarantee of capacity.
*8) The system is operated by only Booster Heater in special condition (35 °C < Outdoor temp. ≤ 43°C).
• *9) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- Sound pressure level in Night Mode is measured 3m away from front side of outdoor unit.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted Sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• Select wire size based on the value of MCA
• These products contain R32 (GWP=675) which is fluorinated greenhouse gas.
2. Outdoor Units
2-1. Specifications

Model Name Indoor Unit AE090RNYDEG/EU AE090RNYDGG/EU


Outdoor Unit AE090RXEDEG/EU AE090RXEDGG/EU
Mode - Heat Pump (A2W) Heat Pump (A2W)
Performance Nominal Capacity Heating kW 9.00 9.00
(A7/W35) *1 Btu/h 30,700 30,700
Cooling kW 8.70 8.70
Btu/h 29,700 29,700
Power Input Heating 1.87 1.87
kW
(Nominal) Cooling 2.11 2.11
Current Input Heating 8.60 3.00
A
(Nominal) Cooling 9.70 3.40
COP (Nominal Heating) W/W 4.81 4.81
EER (Nominal Cooling) W/W 4.12 4.12
SCOP (35℃) W/W 4.45 4.45
SEER - 5.09 5.09
Performance Capacity Heating W 8,600 8,600
*4
(A7/W45) COP W/W 3.69 3.69
Performance Capacity Heating W 8,000 8,000
(A7/W55) *5 COP W/W 2.93 2.93
Performance Capacity Heating W 7,700 7,700
(A2/W35) *2 COP W/W 3.41 3.41
Performance Capacity Heating W 7,900 7,900
(A-7/W35) *3 COP W/W 2.72 2.72
System Field Wiring MCA A 22.0 10.0
MFA A 27.5 16.1
Water Connections Water Flow Rate (Heating / Cooling) LPM 26/25.1 26/25.1
Water Pressure (Max) bar 3 3
Water Pipe Inlet Φ, inch BSPP male 1 1/4" BSPP male 1 1/4"
Outlet Φ, inch BSPP male 1 1/4" BSPP male 1 1/4"
Leaving Water Heating °C 15~65 15~65
Temperature Cooling °C 5~25 5~25
Refrigerant Liquid Pipe Quantity EA 1 1
Connections Type - Flare connection Flare connection
Φ, mm 6.35 6.35
Φ, inch 1/4" 1/4"
Liquid Pipe Quantity EA 1 1
Type - Flare connection Flare connection
Φ, mm 15.88 15.88
Φ, inch 5/8" 5/8"
Installation Limitation Max. Length m 35 35
Max. Height m 20 20
Chargeless Length m 15 15
*6
Operating Temp. Heating (A2W) ℃ -25~35 -25~35
Range Cooling (A2W) ℃ 10~46 10~46
D.Hot Water (A2W) *7 ℃ -25~43 -25~43
Power Supply V, Hz, Φ 220~240, 50, 1 380~415, 50, 3
Compressor Type - BLDC Twin Rotary BLDC Twin Rotary
Model - UB8TN8265FJWSG UB8TN8265FJWSG
Oil Type - POE POE
Quantity EA 1 1
Output W 2078 2078
Starting method - Inverter driven Inverter driven
Heat exchanger Length mm 950 950
Rows Quantity EA 2 2
Fin pitch mm 1.5 1.5
Passes Quantity EA 8 8
Face area m² 0.92 0.92
Outdoor Unit
Stages Quantity EA 46 46
Tube type - Φ7 Φ7
Fin Type - Wide Louver Wide Louver
Treatment - Anti Salt Anti Salt
Condenser Size - 2RX46S 2RX46S
Motor Type (Model) - FMDC531SSA FMDC531SSA
Quantity EA 1 1
CODE No - DB31-00579A DB31-00579A
Fan Type - Propeller Fan Propeller Fan
Discharge direction - Horizontal Horizontal
Air Flow Rate Heating m³/min 66 66
Cooling m³/min 66 66
2. Outdoor Units
2-1. Specifications

Model Name Indoor Unit AE090RNYDEG/EU AE090RNYDGG/EU


Outdoor Unit AE090RXEDEG/EU AE090RXEDGG/EU
Fan motor Quantity EA 1 1
Model - Brushless DC motor Brushless DC motor
Output W 125W 125W
Drive - Direct drive Direct drive
Speed Heating rpm 780 780
Cooling rpm 780 780
4-Way Valve Type (Model) SHF-11H SHF-11H
Base Heater Power Input W 150 150
Sound Sound Pressure Heating dB(A) 49 49
Cooling dB(A) 49 49
Night Mode dB(A) 35 35
Sound Power Heating dB(A) 64 64
Outdoor Unit
Cooling dB(A) 63 63
Casing Color - Earth brown Earth brown
Material - Poweder coated Electro galvanized steel Poweder coated Electro galvanized steel
Packing Material - EPS/BOX EPS/BOX
Weight kg 8.5 8.5
External Dimension Net Weight kg 73.0 72.0
Shipping Weight kg 81.5 80.5
Net Dimensions (WxHxD) mm 940 x 998 x 330 940 x 998 x 330
Shipping Dimensions (WxHxD) mm 995 x 1,178 x 426 995 x 1,178 x 426
Refrigerant Type - R32 R32
Control Method - EEV EEV
Factory Charging g / tCO2e 1,400/ 0.95 1,400/ 0.95

NOTE
• Specifications may be subject to change without prior notice.
*1) A2W Condition *1 : (Heating) Water In/Out 30℃/35℃, Outdoor Air 7℃DB/6℃WB;
(Cooling) Water In/Out 23℃/18℃, Outdoor Air 35℃DB.
*2) A2W Condition *2 : (Heating) Water In/Out 40℃/45℃, Outdoor Air 7℃DB
*3) A2W Condition *3 : (Heating) Water In/Out 47℃/55℃, Outdoor Air 7℃DB
*4) A2W Condition *4 : (Heating) Water In/Out 30℃/35℃, Outdoor Air 2℃DB
*5) A2W Condition *5 : (Heating) Water In/Out 30℃/35℃, Outdoor Air -7℃DB
*7) The system is operated in (-25°C ≤ Outdoor temp. < -20°C) condition, but no guarantee of capacity.
*8) The system is operated by only Booster Heater in special condition (35 °C < Outdoor temp. ≤ 43°C).
• *9) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- Sound pressure level in Night Mode is measured 3m away from front side of outdoor unit.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted Sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• Select wire size based on the value of MCA
• These products contain R32 (GWP=675) which is fluorinated greenhouse gas.
2. Outdoor Units
2-1. Specifications
Model Indoor Unit AE160ANYDEH/EU AE160ANYDEH/EU
Name Outdoor Unit AE120AXEDEH/EU AE160AXEDEH/EU
Mode - Heat Pump (A2W) Heat Pump (A2W)
Performance Nominal Capacity Heating W 12,000 16,000
(A7/W35) *1 Btu/h 40,900 54,600
Cooling W 12,000 15,000
Btu/h 40,900 51,200
Power Input Heating 2,590 3,760
(Nominal) W
Cooling 3,100 4,140
Current Input Heating 11.70 16.90
(Nominal) A
Cooling 14.00 18.60
COP (Nominal Heating) W/W 4.63 4.26
EER (Nominal Cooling) W/W 3.87 3.62
Eco design 35℃ P-design H W 13.00 14.00
SCOP W/W 4.59 4.46
GRADE - A+++ A+++
55℃ P-design H W 12.50 14.00
SCOP W/W 3.12 3.09
GRADE - A+ A+
SEER - 4.45 4.39
Performance Capacity Heating W 11,500 15,300
(A7/W45) *2 COP W/W 3.56 3.37
Performance Capacity Heating W 11,000 14,600
(A7/W55) *3 COP W/W 2.89 2.74
Performance Capacity Heating W 11000 13700
(A2/W35) *4 COP W/W 3.48 3.26
Performance Capacity Heating W 11,300 13,800
System (A-7/W35) *5 COP W/W 2.76 2.53
Performance Capacity Cooling W 9,000 11,200
(A35/W7) *6 EER W/W 2.90 2.80
Field MCA A 28.0 32.0
Wiring MFA A 35.0 40.0
Water Connections Water Flow LPM 35/35 46/44
Water Pressure (Max) bar 3 3
Water Pipe Inlet Φ, inch BSPP male 1 1/4" BSPP male 1 1/4"
Outlet Φ, inch BSPP male 1 1/4" BSPP male 1 1/4"
Leaving Heating °C 15~55 15~55
Water Cooling °C 5~25 5~25
Refrigerant Liquid Pipe Quantity EA 1 1
Connections Type - Flare connection Flare connection
Φ, mm 9.52 9.52
Φ, inch 3/8 3/8
Gas Pipe Quantity EA 1 1
Type - Flare connection Flare connection
Φ, mm 15.88 15.88
Φ, inch 5/8 5/8
Installation Max. Length m 50 50
Limitation Max. Height m 30 30
Chargeless Length m 15 15
Operating Heating (A2W) *7 ℃ -25~35 -25~35
Temp. Cooling (A2W) ℃ 10~46 10~46
Range
DHW (A2W) *8 ℃ -25~43 -25~43
Power Supply V, Hz, Φ 220~240, 50, 1 220~240, 50, 1
Compressor Type - BLDC Twin Rotary BLDC Twin Rotary
Model - UG5TK5450FJX UG5TK5450FJX
Oil Type - PVE/1700 PVE/1700
Quantity EA 1 1
Output W 3423 3423
Starting method - Inverter driven Inverter driven
Motor Output Crankcase heater W 55 55
Outdoor Unit Heat exchanger Length mm 950 950
Rows Quantity EA 2 2
Fin pitch mm 1.5 1.5
Passes Quantity EA 10 10
Face area m² 1.32 1.32
Stages Quantity EA 66 66
Tube type - Φ7.94 Φ7.94
Fin Type - G-Fin G-Fin
Treatment - Anti Salt Anti Salt
2. Outdoor Units
2-1. Specifications
Model Indoor Unit AE160ANYDEH/EU AE160ANYDEH/EU
Name Outdoor Unit AE120AXEDEH/EU AE160AXEDEH/EU
Condenser Size - 2RX66S 2RX66S
Motor Type (Model) - FMDC531SSA FMDC531SSA
Quantity EA 2 2
CODE No - DB31-00579A DB31-00579A
Fan Type - Propeller Fan Propeller Fan
Discharge direction - Horizontal Horizontal
Air Flow Rate Heating m³/min 99 108
Cooling m³/min 99 108
Fan motor Quantity EA 2 2
Model - Brushless DC motor Brushless DC motor
Output W 125W x 2 125W x 2
Drive - Direct drive Direct drive
Speed Heating rpm 650 750
Cooling rpm 650 750
4-Way Valve Type (Model) - SHF-20D-46 SHF-20D-46
Outdoor Unit Base Heater Power Input W 150 150
Sound *9 Sound Pressure Cooling dB(A) 50 54
Heating dB(A) 50 52
Sound Power Cooling dB(A) 64 69
Heating dB(A) 64 66
Casing Color - Earth brown Earth brown
Material - Poweder coated Electro galvanized steel Poweder coated Electro galvanized steel
Packing Material - EPS/BOX EPS/BOX
Weight kg 9.5 9.5
External Dimension Net Weight kg 100.5 100.5
Shipping Weight kg 110.0 110.0
Net Dimensions (WxHxD) mm 940 x 1,420 x 330 940 x 1,420 x 330
Shipping Dimensions mm 995 x 1,598 x 426 995 x 1,598 x 426
Refrigerant Type - R410A R410A
Control Method - EEV EEV
Factory Charging *10 g / tCO2e 2,980 2,980

NOTE
• Specifications may be subject to change without prior notice.
*1) A2W Condition *1 : (Heating) Water In/Out 30℃/35℃, Outdoor Air 7℃DB/6℃WB;
(Cooling) Water In/Out 23℃/18℃, Outdoor Air 35℃DB.
*2) A2W Condition *2 : (Heating) Water In/Out 40℃/45℃, Outdoor Air 7℃DB
*3) A2W Condition *3 : (Heating) Water In/Out 47℃/55℃, Outdoor Air 7℃DB
*4) A2W Condition *4 : (Heating) Water In/Out 30℃/35℃, Outdoor Air 2℃DB
*5) A2W Condition *5 : (Heating) Water In/Out 30℃/35℃, Outdoor Air -7℃DB
*6) A2W Condition *6 : (Cooling) Water In/Out 12℃/7℃, Outdoor Air 35℃DB
*7) The system is operated in (-25°C ≤ Outdoor temp. < -20°C) condition, but no guarantee of capacity.
*8) The system is operated by only Booster Heater in special condition (35 °C < Outdoor temp. ≤ 43°C).
• *9) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- Sound pressure level in Night Mode is measured 3m away from front side of outdoor unit.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted Sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• Select wire size based on the value of MCA
• These products contain R32 (GWP=675) which is fluorinated greenhouse gas.
2. Outdoor Units
2-1. Specifications
Model Indoor Unit AE160ANYDGH/EU AE160ANYDGH/EU
Name Outdoor Unit AE120AXEDGH/EU AE160AXEDGH/EU
Mode - Heat Pump (A2W) Heat Pump (A2W)
Performance Nominal Capacity Heating W 12,000 16,000
(A7/W35) *1 Btu/h 40,900 54,600
Cooling W 12,000 15,000
Btu/h 40,900 51,200
Power Input Heating 2,590 3,760
(Nominal) W
Cooling 3,100 4,140
Current Input Heating 4.10 5.70
(Nominal) A
Cooling 4.70 6.20
COP (Nominal Heating) W/W 4.63 4.26
EER (Nominal Cooling) W/W 3.87 3.62
Eco design 35℃ P-design H W 13.00 14.00
SCOP W/W 4.59 4.46
GRADE - A+++ A+++
55℃ P-design H W 12.50 14.00
SCOP W/W 3.12 3.09
GRADE - A+ A+
SEER - 4.45 4.39
Performance Capacity Heating W 11,500 15,300
(A7/W45) *2 COP W/W 3.56 3.37
Performance Capacity Heating W 11,000 14,600
(A7/W55) *3 COP W/W 2.89 2.74
Performance Capacity Heating W 11000 13700
(A2/W35) *4 COP W/W 3.48 3.26
Performance Capacity Heating W 11,300 13,800
System (A-7/W35) *5 COP W/W 2.76 2.53
Performance Capacity Cooling W 9,000 11,200
(A35/W7) *6 EER W/W 2.90 2.80
Field MCA A 10.0 12.0
Wiring MFA A 16.1 16.1
Water Connections Water Flow LPM 35/35 46/44
Water Pressure (Max) bar 3 3
Water Pipe Inlet Φ, inch BSPP male 1 1/4" BSPP male 1 1/4"
Outlet Φ, inch BSPP male 1 1/4" BSPP male 1 1/4"
Leaving Heating °C 15~55 15~55
Water Cooling °C 5~25 5~25
Refrigerant Liquid Pipe Quantity EA 1 1
Connections Type - Flare connection Flare connection
Φ, mm 9.52 9.52
Φ, inch 3/8 3/8
Gas Pipe Quantity EA 1 1
Type - Flare connection Flare connection
Φ, mm 15.88 15.88
Φ, inch 5/8 5/8
Installation Max. Length m 50 50
Limitation Max. Height m 30 30
Chargeless Length m 15 15
Operating Heating (A2W) *7 ℃ -25~35 -25~35
Temp. Cooling (A2W) ℃ 10~46 10~46
Range
DHW (A2W) *8 ℃ -25~43 -25~43
Power Supply V, Hz, Φ 380~415, 50, 3 380~415, 50, 3
Compressor Type - BLDC Twin Rotary BLDC Twin Rotary
Model - UG5TK5450FJX UG5TK5450FJX
Oil Type - PVE/1700 PVE/1700
Quantity EA 1 1
Output W 3423 3423
Starting method - Inverter driven Inverter driven
Motor Output Crankcase heater W 55 55
Outdoor Unit Heat exchanger Length mm 950 950
Rows Quantity EA 2 2
Fin pitch mm 1.5 1.5
Passes Quantity EA 10 10
Face area m² 1.32 1.32
Stages Quantity EA 66 66
Tube type - Φ7.94 Φ7.94
Fin Type - G-Fin G-Fin
Treatment - Anti Salt Anti Salt
2. Outdoor Units
2-1. Specifications
Model Indoor Unit AE160ANYDGH/EU AE160ANYDGH/EU
Name Outdoor Unit AE120AXEDGH/EU AE160AXEDGH/EU
Condenser Size - 2RX66S 2RX66S
Motor Type (Model) - FMDC531SSA FMDC531SSA
Quantity EA 2 2
CODE No - DB31-00579A DB31-00579A
Fan Type - Propeller Fan Propeller Fan
Discharge direction - Horizontal Horizontal
Air Flow Rate Heating m³/min 99 108
Cooling m³/min 99 108
Fan motor Quantity EA 2 2
Model - Brushless DC motor Brushless DC motor
Output W 125W x 2 125W x 2
Drive - Direct drive Direct drive
Speed Heating rpm 650 750
Cooling rpm 650 750
4-Way Valve Type (Model) - SHF-20D-46 SHF-20D-46
Outdoor Unit Base Heater Power Input W 150 150
Sound *9 Sound Pressure Cooling dB(A) 50 54
Heating dB(A) 50 52
Sound Power Cooling dB(A) 64 69
Heating dB(A) 64 66
Casing Color - Earth brown Earth brown
Material - Poweder coated Electro galvanized steel Poweder coated Electro galvanized steel
Packing Material - EPS/BOX EPS/BOX
Weight kg 9.5 9.5
External Dimension Net Weight kg 99.5 99.5
Shipping Weight kg 109.0 109.0
Net Dimensions (WxHxD) mm 940 x 1,420 x 330 940 x 1,420 x 330
Shipping Dimensions mm 995 x 1,598 x 426 995 x 1,598 x 426
Refrigerant Type - R410A R410A
Control Method - EEV EEV
Factory Charging *10 g / tCO2e 2,980 2,980

NOTE
• Specifications may be subject to change without prior notice.
*1) A2W Condition *1 : (Heating) Water In/Out 30℃/35℃, Outdoor Air 7℃DB/6℃WB;
(Cooling) Water In/Out 23℃/18℃, Outdoor Air 35℃DB.
*2) A2W Condition *2 : (Heating) Water In/Out 40℃/45℃, Outdoor Air 7℃DB
*3) A2W Condition *3 : (Heating) Water In/Out 47℃/55℃, Outdoor Air 7℃DB
*4) A2W Condition *4 : (Heating) Water In/Out 30℃/35℃, Outdoor Air 2℃DB
*5) A2W Condition *5 : (Heating) Water In/Out 30℃/35℃, Outdoor Air -7℃DB
*6) A2W Condition *6 : (Cooling) Water In/Out 12℃/7℃, Outdoor Air 35℃DB
*7) The system is operated in (-25°C ≤ Outdoor temp. < -20°C) condition, but no guarantee of capacity.
*8) The system is operated by only Booster Heater in special condition (35 °C < Outdoor temp. ≤ 43°C).
• *9) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- Sound pressure level in Night Mode is measured 3m away from front side of outdoor unit.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted Sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• Select wire size based on the value of MCA
• These products contain R32 (GWP=675) which is fluorinated greenhouse gas.
2. Outdoor Units
2-2. Electrical characteristics

Voltage Range Nominal Running


Power Supply Current [A]
Capacity [V] Current [A]
Model
[kW] Min. Max.
Φ # Hz Voltage Cooling Heating MCA MFA
(-10%) (+10%)
4 AE040RXEDEG/EU 1 2 50 220~240 198 264 3.9 4.9 16.0 20.0
6 AE060RXEDEG/EU 1 2 50 220~240 198 264 5.6 6.7 16.0 20.0
9 AE090RXEDEG/EU 1 2 50 220~240 198 264 8.6 9.7 22.0 27.5
9 AE090RXEDGG/EU 3 4 50 380~415 342 456 3.0 3.4 10.0 16.1
12 AE120AXEDEH/EU 1 2 50 220~240 198 264 14.0 11.7 28.0 35.0
12 AE120AXEDGH/EU 3 4 50 380~415 342 456 4.7 4.1 10.0 16.1
16 AE160AXEDEH/EU 1 2 50 220~240 198 264 18.6 16.9 32.0 40.0
16 AE160AXEDGH/EU 3 4 50 380~415 342 456 6.2 5.7 12.0 16.1

NOTE
•• MCA : Mimium circuit amperes
•• MFA : Maximum fuse amperes
•• Select wire size based on the value of MCA
2. Outdoor Units
2-3. Dimensional drawing

AE040RXEDEG/EU, AE060RXEDEG/EU
Unit : mm

50 610 12

23
364

310
638

880 54 .1
2. Outdoor Units
2-3. Dimensional drawing

AE090RXEDEG/EU, AE090RXEDGG/EU
Unit : mm

620

384
360
330

940
973

998
2. Outdoor Units
2-3. Dimensional drawing

AE120AXEDEH/EU, AE120AXEDGH/EU, AE160AXEDEH/EU, AE160AXEDGH/EU


Unit : mm

620
330

384
360
940
1395

1420
2. Outdoor Units
2-4. Electrical wiring diagram
AE040RXEDEG/EU, AE060RXEDEG/EU

M BLDC BLDC FAN MOTOR COMP COMPRESSOR


OUT-TH Thermistor OUT(10K) DIS-TH Thermistor DISCHARGE(200K)
COND-TH Thermistor COND(10K) OLP-TH Thermistor OLP(200K)

NOTE
1. This wiring diagram applies only to the Outdoor unit.
2. Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue, grn: green
3. or connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
4. Protective earth(SCREW)
2. Outdoor Units
2-4. Electrical wiring diagram
AE090RXEDEG/EU

M BLDC BLDC FAN MOTOR COMP COMPRESSOR


Comm Communication OUT-Temp Thermistor OUT(10K)
COND-Temp Thermistor COND(10K) DISCHARGE-Temp Thermistor DISCHARGE(200K)
OLP-Temp Thermistor OLP(200K) SUCTION-TEMP Thermistor SUCTION(10K)

NOTE
1. This wiring diagram applies only to the Outdoor unit.
2. Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue, grn: green
3. or connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
4. Protective earth(SCREW)
2. Outdoor Units
2-4. Electrical wiring diagram
AE090RXEDGG/EU

M BLDC BLDC FAN MOTOR COMP COMPRESSOR


Comm Communication OUT-Temp Thermistor OUT(10K)
COND-Temp Thermistor COND(10K) DISCHARGE-Temp Thermistor DISCHARGE(200K)
OLP-Temp Thermistor OLP(200K) SUCTION-TEMP Thermistor SUCTION(10K)

NOTE
1. This wiring diagram applies only to the Outdoor unit.
2. Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue, grn: green
3. or connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
4. Protective earth(SCREW)
2. Outdoor Units
2-4. Electrical wiring diagram
AE120AXEDEH/EU, AE160AXEDEH/EU

MAIN PBA Printed circuit board(MAIN) INVERTER PBA Printed circuit board(INVERTER)
EMI PBA Printed circuit board(EMI) M BLDC Motor for Outdoor Fan
EEV Electronic expansion valve COMP Compressor
OUT-TEMP Thermistor - Ambient COND-TEMP Thermistor - Cond
DISCHARGE-
Thermistor - Discharge pipe OLP-TEMP Thermistor - OLP
TEMP
SUCTION-TEMP Thermistor - Suction pipe D_TUBE-TEMP Thermistor – D_tube
WATER_OUT Thermistor - Water Out WATER_IN Thermistor - Water In

NOTE
1. This wiring diagram applies only to the Outdoor unit.
2. Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue, grn: green
3. For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
4. Protective earth(SCREW)
2. Outdoor Units
2-4. Electrical wiring diagram
AE120AXEDGH/EU, AE160AXEDGH/EU

MAIN PBA Printed circuit board(MAIN) INVERTER PBA Printed circuit board(INVERTER)
EMI PBA Printed circuit board(EMI) M BLDC Motor for Outdoor Fan
EEV Electronic expansion valve COMP Compressor
OUT-TEMP Thermistor - Ambient COND-TEMP Thermistor - Cond
DISCHARGE-
Thermistor - Discharge pipe OLP-TEMP Thermistor - OLP
TEMP
SUCTION-TEMP Thermistor - Suction pipe D_TUBE-TEMP Thermistor – D_tube
WATER_OUT Thermistor - Water Out WATER_IN Thermistor - Water In

NOTE
1. This wiring diagram applies only to the Outdoor unit.
2. Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue, grn: green
3. For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
4. Protective earth(SCREW)
2. Outdoor Units
2-5. Sound data

Sound Pressure level


Unit: dB(A)

1m Model Cooling Heating


Microphone
AE040RXEDEG/EU 44 46

AE060RXEDEG/EU 47 47
1.5m

AE090RXEDEG/EU 49 49
Front
AE090RXEDGG/EU 49 49

• NR Curve
1) AE040RXEDEG/EU 2) AE060RXEDEG/EU
70 NR 75 70 70 NR 75 70
65 NR 70 65 65 NR 70 65
60 NR 65 60 60 NR 65 60
55 NR 60 55 55 NR 60 55
Cooling
Heating Heating
50 50 50 50
Sound Pressure Level (dB)

Sound Pressure Level (dB)

Cooling NR 55 NR 55
45 NR 50 45 45 NR 50 45
40 40 40 40
NR 45 NR 45
35 35 35 35
NR 40 NR 40
30 30 30 30
NR 35 NR 35
25 25 25 25
NR 30 NR 30
20 20 20 20
NR 25 NR 25
15 Hearing 15 15 Hearing 15
threshold NR 20 threshold NR 20
10 10 10 10
NR 15 NR 15
5 5 5 5
0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)

3) AE090RXEDEG/EU 4) AE090RXEDGG/EU

70 NR 75 70 70 NR 75 70
65 NR 70 65 65 NR 70 65
60 Cooling NR 65 60 60 Cooling NR 65 60
55 NR 60 55 55 NR 60 55
Heating Heating
50 50 50 50
Sound Pressure Level (dB)

NR 55
Sound Pressure Level (dB)

NR 55
45 NR 50 45 45 NR 50 45
40 40 40 40
NR 45 NR 45
35 35 35 35
NR 40 NR 40
30 30 30 30
NR 35 NR 35
25 25 25 25
NR 30 NR 30
20 20 20 20
NR 25 NR 25
15 Hearing 15 Hearing
15 15
threshold NR 20 threshold NR 20
10 10 10 10
NR 15 NR 15
5 5 5 5
0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
2. Outdoor Units
2-5. Sound data

Sound Pressure level


Unit: dB(A)

1m Model Cooling Heating


Microphone
AE120AXEDEH/EU 50 50

AE120AXEDGH/EU 50 50
1.5m

AE160AXEDEH/EU 54 52
Front
AE160AXEDGH/EU 54 52

• NR Curve
1) AE120AXEDEH/EU 2) AE120AXEDGH/EU

3) AE160AXEDEH/EU 4) AE160AXEDGH/EU
2. Out
utdoor
door Units
2-6. Operation range
AE040/060/090RXED*G (R32)

1) Cooling 2) Heating

46 35
Outdoor temp. (℃, DB)

Outdoor temp. (℃, DB)


Operation of outdoor unit possible,
but no guarantee of capacity in this
24
condition.

Operation of outdoor unit possible,


10 but backup heater is recommended.
-5

10 -20
-25
60
5 25 15 20 25 40 50 65
Leaving water temp. ( ℃) Leaving water temp. ( ℃)
Water Temp. (℃) Water Flow Rates (LPM) Air Temp. (℃, DB/WB)
MONO Outdoor Unit
Min Std Max Min Std Max Min Std Max

Cooling 5 - 25
Controller
Heating 15 - 65
Inlet - 23 (12*2) 30
Cooling 10/- 35/24 46/28
Outlet 5 18 (7*2) 25
12 (7 )
*1
Δ 5℃ 58 (48 ) *1
Inlet 5 30 (40*2) -
Heating -25/- 7/6 35/24
Outlet 25 (15*3) 35 (45*2) 65

*1) Model : AE040RXEDEG


AE060RXEDEG
AE090RXEDEG
AE090RXEDGG
*2) Eurovent Test Condition #2
*3) Back up heater operation.

3) DHW (Domestic Hot Water Tank)

※ Special condition( 35℃ < Outdoor temp. ≤ 43℃) is operated by only Booster Heater.
SAMSUNG doesn’t supply DHW for EHS Split.
Since it is a reference data, you have to check DHW operation range for yours.
2. Outdoor Units
2-6. Operation range
AE120/160AXED*H (R410A)

1) Cooling 2) Heating

46 35
Outdoor temp. (℃, DB)

Outdoor temp. (℃, DB)


Operation of outdoor unit possible,
but no guarantee of capacity in this
24 condition.

Operation of outdoor unit possible,


-10 but backup heater is recommended.

-20
10 -25

5 25 15 20 25 37 43 55
Leaving water temp. (℃) Leaving water temp. (℃)

Water Temp. (℃) Water Flow Rates (LPM) Air Temp. (℃, DB/WB)
MONO Outdoor Unit
Min Std Max Min Std Max Min Std Max
Cooling 5 - 25
Controller
Heating 15 - 55
Inlet - 23 (12*1) 30
Cooling 10/- 35/24 46/28
Outlet 5 18 (7*1) 25
12 Δ 5℃ 58
Inlet 5 30 (40*1) - 7/6
Heating -25/- 35/24
Outlet 25 (15*3) 35 (45*1) 55 (-7/-8*2)

*1) Eurovent Test Condition #2


*2) NF PAC Low Temp. Heating Condition.
*3) Back up heater operation.

ation
& No guarantee of capacity

3) DHW (Domestic Hot Water Tank)

20 25 37 43 55
g water temp. (℃)

※ Special condition( 35℃ < Outdoor temp. ≤ 43℃) is operated by only Booster Heater.
SAMSUNG doesn’t supply DHW for EHS Split.
Since it is a reference data, you have to check DHW operation range for yours.
2. Outdoor Units
2-7. Piping diagram

AE040/060RXEDEG (R32)

Outdoor Fan Motor1 (OFM1)

Heat Exchanger - Thermistor -


Main(HX_M) Ambient
(T_A)

Solenoid Valve-
4Way (V_4W)

Muffler
Electronic
Expansion Valve -
Main
(E_M)
Pressute Switch
Thermistor -
Discharge pipe
(T_D)
Thermistor -
Compressor
Top
(T_CT)

Accumulator
(AC)
Compressor
(COMP)

AE090RXED*G (R32)

Outdoor Fan Motor1 (OFM1)

Heat Exchanger - Thermistor -


Main(HX_M) Ambient
(T_A)

Solenoid Valve-
4Way (V_4W)

Pressute Switch
Electronic
Expansion Valve -
Main
Muffler (E_M)

Thermistor -
Discharge pipe
(T_D)
Thermistor -
Compressor
Top
(T_CT)

Accumulator
(AC)
Compressor
(COMP)
2. Outdoor Units
2-7. Piping diagram

AE120/160AXED*H (R410A)

Outdoor Fan Motor1 (OFM1)

Charge Port

Heat Exchanger - Thermistor -


Main(HX_M) Ambient
(T_A)

Solenoid Valve-
4Way (V_4W)

Muffler
Electronic
Expansion Valve -
Main
(E_M)
Pressute Switch
Thermistor -
Discharge pipe
(T_D)
Thermistor -
Compressor
Top
(T_CT)

Accumulator
(AC)
Compressor
(COMP)
2. Outdoor Units
2-8. Capacity table
1) Maximum Heating Capacity (Peak Value)
LWT (Leaving Water Temp.), Tamb (Ambient T emp.), HC (Heating Capacity), PI (Power input)
LWT 25 30 35 40 45 50 55 60 65
(℃)
Tamb HC PI HC PI HC PI HC PI HC PI HC PI HC PI HC PI HC PI
(℃) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
-20 3.76 1.21 3.65 1.30 3.48 1.46 3.34 1.56 3.21 1.72
-15 4.32 1.29 4.20 1.39 4.00 1.56 3.89 1.66 3.77 1.76 3.66 1.84
-10 4.97 1.34 4.83 1.44 4.60 1.62 4.46 1.73 4.32 1.84 4.19 1.93 3.89 2.12
AE040RXEDEG -7 5.18 1.34 5.03 1.44 4.79 1.61 4.69 1.82 4.59 2.03 4.40 2.11 4.22 2.19
-2 5.40 1.25 5.25 1.34 5.00 1.51 4.81 1.65 4.62 1.80 4.39 1.89 4.16 1.98 3.94 2.18
2 5.27 1.06 5.13 1.14 4.88 1.28 4.61 1.35 4.34 1.43 4.12 1.60 3.91 1.78 3.70 1.89
7 4.75 0.70 4.62 0.75 4.40 0.85 4.30 0.97 4.20 1.09 4.05 1.21 3.90 1.32 3.76 1.38 3.62 1.44
10 5.19 0.71 5.05 0.76 4.81 0.85 4.71 0.97 4.61 1.10 4.38 1.23 4.15 1.37 3.94 1.41 3.74 1.46
15 5.92 0.72 5.76 0.77 5.48 0.87 5.39 0.97 5.30 1.11 5.03 1.25 4.77 1.38 4.53 1.43 4.29 1.47
20 6.65 0.73 6.47 0.78 6.16 0.88 6.07 0.99 5.98 1.12 5.68 1.26 5.39 1.40 5.12 1.44 4.85 1.48
LWT 25 30 35 40 45 50 55 60 65
(℃)
Tamb HC PI HC PI HC PI HC PI HC PI HC PI HC PI HC PI HC PI
(℃) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
-20 4.69 1.63 4.56 1.75 4.35 1.97 4.18 2.10 4.01 2.32
-15 5.40 1.74 5.25 1.87 5.00 2.10 4.86 2.23 4.72 2.36 4.58 2.48
-10 5.89 1.82 5.72 1.95 5.45 2.19 5.29 2.34 5.12 2.48 4.97 2.60 4.61 2.85
AE060RXEDEG -7 6.19 1.73 6.02 1.85 5.73 2.08 5.61 2.35 5.49 2.62 5.27 2.79 5.05 2.96
-2 6.57 1.64 6.38 1.76 6.08 1.98 5.85 2.17 5.62 2.37 5.34 2.66 5.06 2.96 4.79 3.29
2 6.53 1.43 6.35 1.53 6.05 1.72 5.71 1.82 5.37 1.92 5.11 2.16 4.84 2.40 4.58 2.55
7 6.48 1.01 6.30 1.09 6.00 1.22 5.70 1.37 5.40 1.51 5.10 1.66 4.80 1.81 4.53 1.88 4.27 1.95
10 7.08 1.02 6.88 1.10 6.55 1.23 6.30 1.38 6.04 1.53 5.74 1.73 5.43 1.92 5.16 1.98 4.89 2.04
15 8.08 1.04 7.85 1.11 7.48 1.25 7.29 1.39 7.10 1.57 6.74 1.77 6.39 1.97 6.07 2.03 5.75 2.09
20 9.07 1.05 8.82 1.13 8.40 1.27 8.28 1.42 8.16 1.61 7.75 1.81 7.34 2.01 6.98 2.08 6.61 2.14
LWT 25 30 35 40 45 50 55 60 65
(℃)
Tamb HC PI HC PI HC PI HC PI HC PI HC PI HC PI HC PI HC PI
(℃) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
-20 6.90 2.28 6.71 2.44 6.39 2.74 6.14 2.93 5.90 3.23
-15 7.94 2.43 7.72 2.61 7.35 2.93 7.14 3.11 6.94 3.30 6.73 3.46
-10 8.64 2.57 8.40 2.76 8.00 3.10 7.76 3.28 7.52 3.46 7.29 3.63 6.77 3.98
AE090RXED*G -7 8.89 2.51 8.64 2.69 8.23 3.02 8.05 3.41 7.88 3.80 7.56 4.04 7.25 4.29
-2 9.57 2.43 9.31 2.61 8.86 2.93 8.53 3.22 8.19 3.50 7.78 3.94 7.37 4.38 6.98 4.87
2 9.67 2.18 9.40 2.34 8.95 2.63 8.46 2.78 7.96 2.93 7.56 3.30 7.16 3.66 6.79 3.89
7 9.72 1.55 9.45 1.66 9.00 1.87 8.80 2.10 8.60 2.33 8.30 2.53 8.00 2.73 7.72 2.96 7.44 3.20
10 10.62 1.57 10.32 1.68 9.83 1.89 9.64 2.12 9.44 2.36 8.97 2.66 8.50 2.95 8.07 3.05 7.65 3.14
15 12.11 1.59 11.78 1.70 11.22 1.91 11.03 2.13 10.84 2.42 10.30 2.72 9.76 3.02 9.27 3.11 8.78 3.21
20 13.61 1.61 13.23 1.73 12.60 1.94 12.42 2.18 12.24 2.47 11.63 2.78 11.02 3.09 10.47 3.18 9.91 3.28

1. Heating capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for heated water range
△t = 3~8°C
2. Cooling capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for chilled water range
△t = 3~8°C
3. ower input : Power input is according to Eurovent rating standard OM-3-2015.
4. eak value : Tested without defrost operation in accordance with EN14511
※ The eal capacity would be changed according to the install environment.
2. Outdoor Units
2-8. Capacity table
1) Maximum Heating Capacity (Peak Value)
AE120AXED*H/EU LWT (Leaving Water Temp.), Tamb (Ambient T emp.), HC (Heating Capacity), PI (Power input)
LWT(℃) 25 30 35 40 45 50 55
Tamb(℃) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW)
-20 9.28 3.19 9.02 3.42 8.59 3.84 8.27 4.10 7.93 4.52
-15 10.46 3.54 10.17 3.79 9.69 4.26 9.51 4.53 9.43 4.71 9.14 4.93
-10 12.96 4.17 12.60 4.35 12.00 4.87 11.64 4.95 11.28 5.08 10.94 5.35 10.15 5.77
-7 12.71 4.14 12.36 4.31 11.77 4.87 11.52 5.18 11.27 5.67 10.82 5.53 10.37 5.52
-2 13.68 3.42 13.30 3.67 12.67 4.13 12.19 4.53 11.70 4.93 11.12 5.55 10.53 6.16
2 13.81 3.05 13.43 3.27 12.79 3.67 12.08 3.89 11.37 4.10 10.80 4.61 10.23 5.12
7 12.96 2.15 12.60 2.36 12.00 2.59 11.75 2.97 11.50 3.23 11.26 3.60 11.01 3.83
10 13.88 2.21 13.48 2.38 12.85 2.66 12.60 3.00 12.36 3.34 11.74 3.75 11.12 4.17
15 15.83 2.24 15.39 2.41 14.65 2.70 14.42 3.01 14.18 3.42 13.47 3.85 12.76 4.26
20 18.14 2.23 17.64 2.39 16.80 2.69 16.56 3.02 16.32 3.42 15.50 3.85 14.69 4.28

AE160AXED*H/EU
LWT(℃) 25 30 35 40 45 50 55
Tamb(℃) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW)
-20 12.08 4.65 11.74 4.99 11.18 5.61 10.75 5.97 10.32 6.59
-15 13.61 4.91 13.23 5.27 12.61 5.92 12.37 6.30 12.27 6.54 11.90 6.87
-10 16.85 5.64 16.38 5.93 15.60 6.70 15.13 6.93 14.66 7.04 14.22 7.47 13.20 7.97
-7 15.53 5.51 15.09 5.71 14.38 6.48 14.07 6.87 13.76 7.64 13.21 7.49 12.66 7.33
-2 16.88 4.55 16.41 4.88 15.63 5.48 15.03 6.02 14.43 6.55 13.71 7.37 12.98 8.19
2 17.20 4.05 16.73 4.35 15.93 4.88 15.05 5.17 14.16 5.45 13.45 6.13 12.74 6.81
7 17.28 3.12 16.80 3.42 16.00 3.76 15.65 4.23 15.30 4.54 14.95 5.03 14.60 5.32
10 18.50 3.21 17.98 3.45 17.13 3.87 16.79 4.30 16.45 4.73 15.63 5.32 14.81 5.92
15 21.10 3.25 20.52 3.49 19.54 3.93 19.22 4.35 18.89 4.90 17.94 5.51 17.00 6.12
20 24.19 3.24 23.52 3.47 22.40 3.90 22.08 4.39 21.76 4.97 20.67 5.59 19.58 6.21

1. Heating capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for heated water range
△t = 3~8°C
2. Cooling capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for chilled water range
△t = 3~8°C
3. ower input : Power input is according to Eurovent rating standard OM-3-2015.
4. eak value : Tested without defrost operation in accordance with EN14511
※ The eal capacity would be changed according to the install environment.
2. Outdoor Units
2-8. Capacity table
2) Maximum Heating Capacity (Integrated Value)
LWT (Leaving Water Temp.), Tamb (Ambient T emp.), HC (Heating Capacity), PI (Power input)
LWT 25 30 35 40 45 50 55 60 65
(℃)
Tamb HC PI HC PI HC PI HC PI HC PI HC PI HC PI HC PI HC PI
(℃) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
-20 3.76 1.21 3.65 1.30 3.48 1.46 3.34 1.56 3.21 1.72
-15 4.28 1.28 4.16 1.37 3.96 1.54 3.85 1.64 3.74 1.74 3.62 1.82
-10 4.87 1.32 4.73 1.41 4.51 1.59 4.37 1.70 4.24 1.81 4.11 1.90 3.81 2.08
AE040RXEDEG -7 4.97 1.29 4.83 1.38 4.60 1.55 4.50 1.75 4.40 1.95 4.23 2.03 4.05 2.10
-2 4.75 1.10 4.62 1.18 4.40 1.33 4.23 1.46 4.07 1.59 3.87 1.67 3.66 1.75 3.47 1.92
2 4.54 0.91 4.41 0.98 4.20 1.10 3.97 1.16 3.73 1.23 3.55 1.38 3.36 1.53 3.18 1.70
7 4.75 0.70 4.62 0.75 4.40 0.85 4.30 0.97 4.20 1.09 4.05 1.21 3.90 1.32 3.76 1.38 3.62 1.44
10 5.19 0.71 5.05 0.76 4.81 0.85 4.71 0.97 4.61 1.10 4.38 1.23 4.15 1.37 3.94 1.41 3.74 1.46
15 5.92 0.72 5.76 0.77 5.48 0.87 5.39 0.97 5.30 1.11 5.03 1.25 4.77 1.38 4.53 1.43 4.29 1.47
20 6.65 0.73 6.47 0.78 6.16 0.88 6.07 0.99 5.98 1.12 5.68 1.26 5.39 1.40 5.12 1.44 4.85 1.48
LWT 25 30 35 40 45 50 55 60 65
(℃)
Tamb HC PI HC PI HC PI HC PI HC PI HC PI HC PI HC PI HC PI
(℃) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
-20 4.69 1.63 4.56 1.75 4.35 1.97 4.18 2.10 4.01 2.32
-15 5.35 1.73 5.20 1.85 4.95 2.08 4.81 2.21 4.67 2.34 4.53 2.46
-10 5.77 1.78 5.61 1.91 5.34 2.15 5.18 2.29 5.02 2.43 4.87 2.55 4.52 2.80
AE060RXEDEG -7 5.94 1.66 5.78 1.78 5.50 2.00 5.38 2.26 5.27 2.51 5.05 2.68 4.84 2.84
-2 5.78 1.44 5.62 1.55 5.35 1.74 5.15 1.91 4.94 2.08 4.70 2.34 4.45 2.60 4.22 2.89
2 5.62 1.23 5.46 1.32 5.20 1.48 4.91 1.57 4.62 1.65 4.39 1.86 4.16 2.06 3.94 2.29
7 6.48 1.01 6.30 1.09 6.00 1.22 5.70 1.37 5.40 1.51 5.10 1.66 4.80 1.81 4.53 1.88 4.27 1.95
10 7.08 1.02 6.88 1.10 6.55 1.23 6.30 1.38 6.04 1.53 5.74 1.73 5.43 1.92 5.16 1.98 4.89 2.04
15 8.08 1.04 7.85 1.11 7.48 1.25 7.29 1.39 7.10 1.57 6.74 1.77 6.39 1.97 6.07 2.03 5.75 2.09
20 9.07 1.05 8.82 1.13 8.40 1.27 8.28 1.42 8.16 1.61 7.75 1.81 7.34 2.01 6.98 2.08 6.61 2.14
LWT 25 30 35 40 45 50 55 60 65
(℃)
Tamb HC PI HC PI HC PI HC PI HC PI HC PI HC PI HC PI HC PI
(℃) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
-20 6.90 2.28 6.71 2.44 6.39 2.74 6.14 2.93 5.90 3.23
-15 7.86 2.41 7.64 2.58 7.28 2.90 7.07 3.08 6.87 3.26 6.66 3.43
-10 8.47 2.52 8.23 2.70 7.84 3.04 7.60 3.21 7.37 3.39 7.15 3.56 6.63 3.90
AE090RXED*G -7 8.53 2.41 8.30 2.58 7.90 2.90 7.73 3.27 7.56 3.65 7.26 3.88 6.96 4.12
-2 8.42 2.14 8.19 2.30 7.80 2.58 7.50 2.83 7.20 3.08 6.84 3.47 6.48 3.85 6.14 4.28
2 8.32 1.88 8.09 2.01 7.70 2.26 7.27 2.39 6.84 2.52 6.50 2.84 6.16 3.15 5.84 3.50
7 9.72 1.55 9.45 1.66 9.00 1.87 8.80 2.10 8.60 2.33 8.30 2.53 8.00 2.73 7.72 2.96 7.44 3.20
10 10.62 1.57 10.32 1.68 9.83 1.89 9.64 2.12 9.44 2.36 8.97 2.66 8.50 2.95 8.07 3.05 7.65 3.14
15 12.11 1.59 11.78 1.70 11.22 1.91 11.03 2.13 10.84 2.42 10.30 2.72 9.76 3.02 9.27 3.11 8.78 3.21
20 13.61 1.61 13.23 1.73 12.60 1.94 12.42 2.18 12.24 2.47 11.63 2.78 11.02 3.09 10.47 3.18 9.91 3.28

1. Heating capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for heated water range
△t = 3~8°C
2. Cooling capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for chilled water range
△t = 3~8°C
3. ower input : Power input is according to Eurovent rating standard OM-3-2015.
4. eak value : Tested without defrost operation in accordance with EN14511
※ The eal capacity would be changed according to the install environment.
2. Outdoor Units
2-8. Capacity table
2) Maximum Heating Capacity (Integrated Value)
AE120AXED*H/EU LWT (Leaving Water Temp.), Tamb (Ambient T emp.), HC (Heating Capacity), PI (Power input)
LWT(℃) 25 30 35 40 45 50 55
Tamb(℃) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW)
-20 9.28 3.19 9.02 3.42 8.59 3.84 8.27 4.10 7.93 4.52
-15 10.46 3.54 10.17 3.79 9.69 4.26 9.51 4.53 9.43 4.71 9.14 4.93
-10 12.07 3.91 11.73 4.19 11.17 4.71 11.18 4.87 10.83 4.99 10.51 5.23 9.75 5.62
-7 11.59 4.01 11.28 4.20 11.07 4.72 11.06 5.09 10.82 5.56 10.38 5.48 9.95 5.30
-2 11.44 3.31 11.12 3.49 10.59 3.81 10.72 4.30 10.30 4.69 9.78 5.12 9.27 5.58
2 11.64 2.75 11.32 2.95 10.78 3.32 10.39 3.51 9.78 3.70 9.29 4.17 8.80 4.54
7 12.96 2.15 12.60 2.36 12.00 2.59 11.75 2.97 11.50 3.23 11.26 3.60 11.01 3.83
10 13.88 2.21 13.48 2.38 12.85 2.66 12.60 3.00 12.36 3.34 11.74 3.75 11.12 4.17
15 15.83 2.24 15.39 2.41 14.65 2.70 14.42 3.01 14.18 3.42 13.47 3.85 12.76 4.26
20 18.14 2.23 17.64 2.39 16.80 2.69 16.56 3.02 16.32 3.42 15.50 3.85 14.69 4.28

AE160AXED*H/EU
LWT(℃) 25 30 35 40 45 50 55
Tamb(℃) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW)
-20 12.08 4.65 11.74 4.99 11.18 5.61 10.75 5.97 10.32 6.59
-15 13.61 4.91 13.23 5.27 12.61 5.92 12.37 6.30 12.27 6.54 11.90 6.87
-10 15.68 5.46 15.25 5.85 14.53 6.58 14.53 6.79 14.08 6.93 13.66 7.28 12.54 7.82
-7 14.16 5.33 13.77 5.58 13.52 6.27 13.51 6.77 13.21 7.40 12.68 7.30 11.79 7.04
-2 14.11 4.40 13.72 4.63 13.06 5.07 13.22 5.72 12.70 6.23 12.06 6.81 11.09 7.43
2 14.50 3.66 14.10 3.93 13.43 4.41 12.94 4.66 12.18 4.91 11.57 5.53 10.63 6.04
7 17.28 3.12 16.80 3.42 16.00 3.76 15.65 4.23 15.30 4.54 14.95 5.03 14.60 5.32
10 18.50 3.21 17.98 3.45 17.13 3.87 16.79 4.30 16.45 4.73 15.63 5.32 14.81 5.92
15 21.10 3.25 20.52 3.49 19.54 3.93 19.22 4.35 18.89 4.90 17.94 5.51 17.00 6.12
20 24.19 3.24 23.52 3.47 22.40 3.90 22.08 4.39 21.76 4.97 20.67 5.59 19.58 6.21

1. Heating capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for heated water range
△t = 3~8°C
2. Cooling capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for chilled water range
△t = 3~8°C
3. ower input : Power input is according to Eurovent rating standard OM-3-2015.
4. eak value : Tested without defrost operation in accordance with EN14511
※ The eal capacity would be changed according to the install environment.
2. Outdoor Units
2-8. Capacity table
3) Cooling Capacity
LWT (Leaving Water Temp.), Tamb (Ambient Temp.), CC (Cooling Capacity), PI (Power input)
LWT (℃) 7 10 13 15 18 25
Tamb (℃) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW)
10 3.99 0.83 4.37 0.82 4.76 0.82 5.15 0.82 5.54 0.81 6.09 0.83
AE040RXEDEG 20 3.83 0.94 4.21 0.93 4.58 0.93 4.95 0.93 5.33 0.92 5.86 0.94
30 3.68 1.05 4.04 1.04 4.39 1.04 4.75 1.03 5.11 1.03 5.62 1.05
35 3.60 1.11 3.95 1.11 4.30 1.10 4.65 1.10 5.00 1.09 5.50 1.11
46 3.43 1.23 3.76 1.22 4.10 1.22 4.43 1.21 4.77 1.20 5.24 1.23
LWT (℃) 7 10 13 15 18 25
Tamb (℃) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW)
10 5.20 1.07 5.70 1.08 6.20 1.08 6.70 1.09 7.20 1.10 7.92 1.12
AE060RXEDEG 20 5.01 1.22 5.48 1.22 5.96 1.23 6.44 1.24 6.92 1.24 7.61 1.27
30 4.80 1.36 5.26 1.37 5.72 1.37 6.18 1.38 6.64 1.39 7.31 1.42
35 4.70 1.44 5.15 1.45 5.60 1.46 6.05 1.46 6.50 1.47 7.15 1.50
46 4.48 1.59 4.91 1.60 5.34 1.61 5.77 1.62 6.19 1.62 6.81 1.66
LWT (℃) 7 10 13 15 18 25
Tamb (℃) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW)
10 7.20 1.45 7.80 1.48 8.41 1.51 9.02 1.54 9.63 1.57 10.59 1.60
AE090RXED*G 20 6.92 1.65 7.51 1.68 8.09 1.72 8.68 1.75 9.27 1.78 10.19 1.82
30 6.64 1.84 7.21 1.88 7.77 1.92 8.33 1.96 8.89 1.99 9.78 2.03
35 6.50 1.95 7.05 1.99 7.60 2.03 8.15 2.07 8.70 2.11 9.57 2.15
46 6.19 2.15 6.72 2.20 7.24 2.24 7.77 2.29 8.29 2.33 9.12 2.38

AE120AXED*H/EU
LWT(℃) 7 10 13 15 18 25
Tamb(℃) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW)
10 11.95 1.98 12.77 1.99 13.58 2.00 14.13 2.01 14.95 2.02 16.86 2.06
20 10.77 2.44 11.59 2.45 12.40 2.46 12.95 2.47 13.77 2.48 15.68 2.52
30 9.59 2.96 10.41 2.95 11.23 2.95 11.77 3.00 12.59 3.03 14.50 3.04
35 9.00 3.10 9.52 3.32 10.32 3.44 10.84 3.44 12.00 3.10 13.49 3.76
46 7.47 4.55 8.26 4.56 9.06 4.78 9.59 4.78 10.37 4.56 12.22 4.55
AE160AXED*H/EU
LWT(℃) 7 10 13 15 18 25
Tamb(℃) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW) HC(kW) PI(kW)
10 14.74 2.85 15.77 2.91 16.81 2.97 17.50 3.00 18.54 3.03 20.96 3.12
20 13.32 3.33 14.36 3.39 15.39 3.45 16.09 3.49 17.12 3.54 19.54 3.63
30 11.91 3.84 12.94 3.87 13.98 3.89 14.67 3.99 15.71 4.06 18.13 4.17
35 11.20 4.00 11.87 4.29 12.87 4.49 13.53 4.50 15.00 4.14 16.89 5.07
46 9.35 5.70 10.35 5.73 11.37 6.06 12.03 6.10 13.03 5.86 15.37 5.95

1. Heating capacity is according to Eurovent rating standard OM-3-2015 and valid for heated water range △t = 3~8°C
2. Cooling capacity is according to Eurovent rating standard OM-3-2015 and valid for chilled water range △t = 3~8°C
3. Power input is total of indoor and outdoor unit, according to Eurovent rating standard OM-3-2015.
※ The real capacity would be changed according to the install environment.
2. Outdoor Units
2-9. Capacity correction

AE040/060RXEDEG (R32)

1) Heating 2) Cooling

AE090RXED*G (R32)
1) Heating 2) Cooling

AE120/160AXED*H (R410A)
1) Heating 2) Cooling

O O
D D
U U

IDU IDU

IDU IDU

O O
D D
U U
3. Hydro Unit
3-1. Specifications

Model Name Indoor Unit AE090RNYDEG/EU AE090RNYDGG/EU


Power Supply Φ, #, V, Hz 1, 2, 50, 220~240 3, 4, 50, 380~415
Water Pump Type (Model Name) - Centrifurugal (UPM3 25-7.5) Centrifurugal (UPM3 25-7.5)
Motor Input W 60 60
Number of Unit EA 1 1
Flow Switch Type (Model Name) - FLOW SENSOR FLOW SENSOR
Min. flow rates LPM 7 ± 1.5 7 ± 1.5
Electric Heater W 4,000 6,000
Expansion Vessel Liter 8 8
Pressure Relief Valve bar 2.9 2.9
Air Purge Valve Ф, inch BSPP male 3/8" BSPP male 3/8"
Service Valve Ф, inch BSPP male 1 1/4" BSPP male 1 1/4"
Hydro Unit
Sound Pressure Heating Std
Sound *1 dB(A) 26 26
Cooling Std dB(A) 26 26
Sound Power Heating Std dB(A) 40 40
External Net Weight kg 45.0 46.5
Dimension
Shipping Weight kg 55.0 56.0
Net Dimensions (WxHxD) mm 510 x 850 x 315 510 x 850 x 315
Shipping Dimensions (WxHxD) mm 564 x 1,024 x 426 564 x 1,024 x 426
External Control Back up Boiler - AC 230V (Max 10mA) AC 230V (Max 10mA)
Room Thermostat - AC 230V (Max 22mA) AC 230V (Max 22mA)
Solar Pump - AC 230V (Max 10mA) AC 230V (Max 10mA)
Valves, 2 or 3way - AC 230V (Max 22mA) AC 230V (Max 22mA)

*1) Sound level was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
3. Hydro Unit
3-1. Specifications

Model Name Indoor Unit AE160ANYDEH/EU AE160ANYDGH/EU


Power Supply V, Hz, Φ 220~240, 50, 1 380~415, 50, 3
Field Wiring Hydro Unit MAX INPUT kW 6.20 6.20
MCA A 27.9 9.3
MFA A 34.9 11.6
Water Pump Type (Model Name) Centrifurugal Centrifurugal
-
(Stratos 25 1-9) (Stratos 25 1-9)
Rated Current A 0.9 0.9
Motor Input W 90 90
Number of Unit EA 1 1
Flow SENSOR Type (Model Name) - FLOW SENSOR FLOW SENSOR
Min. flow rates LPM 12 12
Electric Heater W 6,000 6,000
Expansion Vessel Liter 8 8

Hydro Unit Pressure Relief Valve bar 2.9 2.9


Air Purge Valve Ф, inch BSPP male 3/8 BSPP male 3/8
Service Valve Ф, inch BSPP male 1 1/4 BSPP male 1 1/4
Sound *1 Sound Heating
dB(A) 30 30
Pressure
Sound Power Heating dB(A) 44 44
External Net Weight kg 45.0 46.5
Dimension
Shipping Weight kg 55.0 56.0
Net Dimensions (WxHxD) mm 510 x 850 x 315 510 x 850 x 315
Shipping Dimensions
(WxHxD) mm 564 x 1,024 x 426 564 x 1,024 x 426

External Control Back up Boiler - AC 230V (Max 10mA) AC 230V (Max 10mA)
Room Thermostat - AC 230V (Max 22mA) AC 230V (Max 22mA)
Solar Pump - AC 230V (Max 10mA) AC 230V (Max 10mA)
Valves, 2 or 3way - AC 230V (Max 22mA) AC 230V (Max 22mA)

*1) Sound level was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
3. Hydro Unit
3-2. Dimensional drawing

Unit : mm

② ①
OUT IN

NO Name Description

1 Refrigerant Gas pipe Ø15.88


2 Refrigerant liquid pipe Ø9.52
3 Water Pipe (Outlet/Inlet) -
4 Drain Holes -
3. Hydro Unit
3-2. Dimensional drawing

Main components (AE090RNYD*G/EU)






③ ⑲

⑤ ⑱



⑨ ⑮

⑩ ⑬
⑪ ⑫

No. Name Note


① Air vent 3/8” BSPP male 3/8”
② Backup heater thermal fuse Thermal cut out 94 °C (+0, -6 °C)
③ Backup heater thermostat Disc . 75 °C ±4 °C
④ Backup Heater Element Incoloy 800, 4/6 kW, 230 V AC 50 Hz
⑤ Drain Hose
⑥ Flow Sensor 5~80L/min
⑦ Water pump 1P-230 V-50 Hz, 26LPM x 43kPa
⑧ Manometer ø48, 0~4bar
⑨ Water outlet pipe BSPP male 1 1/4"
⑩ Drain valves
⑪ Service valve (L) BSPP male, 1-1/4”
⑫ Service valve (R) BSPP male, 1-1/4”
⑬ Water inlet pipe BSPP male 1 1/4"
⑭ Refrigerant pipe Ø6 .35(1/4")
⑮ Refrigerant pipe ø15 .88 (5/8”)
⑯ Wired Remote Controller
⑰ Expansion Vessel 8 Liter, Pre-charge gas : 0 .1 MPa, N2, BSPP male, 3/8”
⑱ Plate heat exchanger
⑲ LED display
⑳ Control box
㉑ Pressure relief valve 0 .3 MPa, BSPP 1/2”
3. Hydro Unit
3-2. Dimensional drawing

Main components (AE160ANYD*H/EU)






③ ⑲

⑤ ⑱



⑨ ⑮

⑩ ⑬
⑪ ⑫

No. Name Note


① Air vent 3/8” BSPP male 3/8”
② Backup heater thermal fuse Thermal cut out 94 °C (+0, -6 °C)
③ Backup heater thermostat Disc . 65 °C ±4 °C
④ Backup Heater Element Incoloy , 6 kW, 230 V AC 50 Hz or 6kW 400V AC 50Hz
⑤ Drain Hose
⑥ Flow Sensor 5~80L/min
⑦ Water pump 1P-230 V-50 Hz, 46 LPM x 54 kPa
⑧ Manometer ø48, 0~4bar
⑨ Water outlet pipe BSPP male 1 1/4"
⑩ Drain valves
⑪ Service valve (L) BSPP male, 1-1/4”
⑫ Service valve (R) BSPP male, 1-1/4”
⑬ Water inlet pipe BSPP male 1 1/4"
⑭ Refrigerant pipe ø9 .52(3/8")
⑮ Refrigerant pipe ø15 .88 (5/8”)
⑯ Wired Remote Controller
⑰ Expansion Vessel 8 Liter, Pre-charge gas : 0 .1 MPa, N2, BSPP male, 3/8”
⑱ Plate heat exchanger
⑲ LED display
⑳ Control box
㉑ Pressure relief valve 0 .3 MPa, BSPP 1/2”
3. Hydro Unit
3-3. Electrical wiring diagram

AE090RNYDEG/EU, AE160ANYDEH/EU

HEATER Thermistor HEATER EVA-OUT Thermistor EVA-OUT


EVA-IN Thermistor EVA-IN(10K) WATER-OUT Thermistor WATER-OUT(10K)
WATER-IN Thermistor WATER-IN(10K) WATER TANK Thermistor WATER TANK(200K)
MIXING Thermistor MIXING VALVE(10K) ROOM Thermistor - Indoor Room
SIG/GND Signal/Ground ELCB Earth Leakage Circuit Breaker
WIRED
M/C Magnetic Contactor Wired Remote Controller
REMOCON
EEV Electronic expansion valve
STEP MOTOR STEP MOTOR

NOTE
1. This wiring diagram applies only to the Indoor unit.
2. Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue, grn: green
3. For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
4. Protective earth(SCREW)
3. Hydro Unit
3-3. Electrical wiring diagram

AE090RNYDGG/EU, AE160ANYDGH/EU

HEATER Thermistor HEATER EVA-OUT Thermistor EVA-OUT


EVA-IN Thermistor EVA-IN(10K) WATER-OUT Thermistor WATER-OUT(10K)
WATER-IN Thermistor WATER-IN(10K) WATER TANK Thermistor WATER TANK(200K)
MIXING Thermistor MIXING VALVE(10K) ROOM Thermistor - Indoor Room
SIG/GND Signal/Ground ELCB Earth Leakage Circuit Breaker
WIRED
M/C Magnetic Contactor Wired Remote Controller
REMOCON
EEV Electronic expansion valve
STEP MOTOR STEP MOTOR

NOTE
1. This wiring diagram applies only to the Indoor unit.
2. Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue, grn: green
3. For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
4. Protective earth(SCREW)
3. Hydro Unit
3-4. Sound data

Sound Pressure level

Unit: dB(A)

Model Heating
1m
AE160ANYDEH/EU 30
Microphone Front AE160ANYDGH/EU 30

• NR Curve
1) AE160ANYDEH/EU 2) AE160ANYDGH/EU
80 NR 85 80 80 NR 85 80
75 NR 80 75 75 NR 80 75
70 NR 75 70 70 NR 75 70
65 NR 70 65 65 NR 70 65
Sound Pr essur e Level (dB)

Sound Pr essur e Level (dB)


60 NR 65 60 60 NR 65 60
55 NR 60 55 55 NR 60 55
50 NR 55 50 50 NR 55 50
Heat Heat
45 NR 50 45 45 NR 50 45
40 40 40 40
NR 45 NR 45
35 35 35 35
NR 40 NR 40
30 30 30 30
NR 35 NR 35
25 25 25 25
NR 30 NR 30
20 20 20 20
NR 25 NR 25
15 15 15 15
NR 20 NR 20
10 10 10 10
NR 15 NR 15
5 5 5 5
0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)

NOTE
• Specifications may be subject to change without prior notice.
• Sound Pressure Level
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A weighted sound pressure level
- Reference acoustic pressure 0 dB = 20μPa
3. Hydro Unit
3-4. Sound data

Sound Power level

NOTE Model Power (dBA)

• Specifications may be subject to change without prior notice AE160ANYDEH/EU 44


- Sound power level is an absolute value that a sound source
generates. AE160ANYDGH/EU 44

- dBA = A-weighted sound power level.


- Reference power : 1pW.
- Measured according to ISO 3741.

1) AE160ANYDEH/EU 2) AE160ANYDGH/EU
80 NR 85 80 80 NR 85 80
75 75 75 75
NR 80 NR 80
70 70 70 70
NR 75 NR 75
65 65 65 65
NR 70 NR 70
60 60 60 60
Sound Power Level (dB)

Sound Power Level (dB)


NR 65 NR 65
55 55 55 55
NR 60 NR 60
50 50 50 50
NR 55 Heat NR 55
45 45 Heat
45 45
NR 50 NR 50
40 40 40 40
NR 45 NR 45
35 35 35 35
NR 40 NR 40
30 30 30 30
NR 35 NR 35
25 25 25 25
NR 30 NR 30
20 20 20 20
NR 25 NR 25
15 15 15 15
NR 20 NR 20
10 10 10 10
5 NR 15 5 5 NR 15 5
0 0 0 0
125 250 500 1000 2000 4000 8000 A 125 250 500 1000 2000 4000 8000 A
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
3. Hydro Unit
3-5. Piping diagram

No. Description No. Description

① Water Pipe Service Valve (R) ⑪ Water Pipe Service Valve (L)

② Strainer ⑫ Water Temp. Sensor 1

③ Flow Sensor ⑬ Water Temp. Sensor 2

④ Heat Changer ⑭ Water Temp. Sensor 3

⑤ Backup Heater

⑥ Pressure Relief Valve

⑦ Air-vent

⑧ Variable Speed water pump

⑨ Expansion Tank

⑩ Manometer
4. Installation
Hydro unit
Application 1: Space heating

Outdoor Indoor

Room Controller
Zone Control
45°C
Supply Header

Return Header

Radiators or Convectors

Water
pump #2
Our Supply Range
Tw2_z2

Water
pump #1 35°C
Supply Header
Tw2_z1

Return Header
Under-Floor Heating Coils
Outdoor unit
Hydro Unit Balancing Vessel

Application 2: Space heating + water heating

Outdoor Indoor

Room Controller
Zone Control
45°C
Supply Header

Return Header

Radiators or Convectors
DHW Tank
Water
pump #2
Our Supply Range
Tw2_z2

Water
pump #1 35°C
Supply Header
Tw2_z1

Return Header
Under-Floor Heating Coils
Outdoor unit
Hydro Unit Balancing Vessel

Application 3: Hybrid application(backup boiler and solar panel connected)

Outdoor Box for Solar Solar thermal Panel Indoor


/ DHW control *)
Back up Boiler Operation
So
lar
Pa
ne
l

Solar Pump
Room Controller
Zone Control
45°C Supply Header
Return Header

Radiators or Convectors

Water
Our Supply Range pump #2
DHW Tank
Tw2_z2

Water
pump #1 35°C
Supply Header
Tw2_z1

Return Header

Under-Floor Heating Coils


Balancing Vessel
Outdoor unit
Hydro Unit *) We control only the on / off signal of backup boiler according to outdoor temperature .
Backup boiler should be installed with own device according to the field condition .
4. Installation
Hydro unit

Installation of the indoor unit


The indoor unit should be installed indoors and meet the following conditions .
Installation site should be sheltered from frost .
In area with suitable space for servicing .
A place with adequate ventilation .
Where there is no risk of leakage of flammable gases .
There is a provision for condensate drain and pressure relief valve blow-off .
The wall for installation is a flat, vertical and non-combustible wall, capable of supporting the operation weight of the unit .

Installation space
Ensure to leave the appropriate space as indicated in the drawing .
Installation site should be secured with adequate ventilation so that the components of hydro unit will not be damaged from overheating .

(Unit : mm )
200

300 ≥350

500
≥1200

Before installing the indoor unit, fix the pattern sheet on the wall . This sheet has a function to take correct position for the wall mounting bracket and screws .

Pattern Sheet

Refrigerant pipe work


For all guide lines, specifications regarding refrigerant pipe work between the indoor unit and the outdoor unit, please follow
the outdoor unit installation manual .
Tightening
Gas pipe (O .D .) Liquid pipe (O .D .) Final Torque
Torque

Indoor unit 15 .88 mm (5/8 inch) 9 .52 mm (3/8 inch) 400 kg∙cm 450 kg∙cm Liquid Gas
pipe pipe

Outdoor unit 15 .88 mm (5/8 inch) 9 .52 mm (3/8 inch) 700 kg∙cm 750 kg∙cm

WATER WATER
• When connecting the refrigerant pipes, always use 2 wrenches/spanners for tightening or loosening nuts . If not, OUTLET INLET
CAUTION piping connections can be damaged .
4. Installation
Hydro unit

Water pipe work


The hydro unit is equipped with components listed on the table below .
The hot and cold water supply connections are clearly marked on the unit with labels . And service valves are provided . Whole water plumbing system including Hydro
unit shall be installed by a qualified technician and must comply with all relevant European and national regulations .
Allowable water pressure of hydro unit is maximum 3 .0bar .
2 service valves are provided with the Hydro unit . To facilitate service and maintenance work, install R-Type service valve at the water inlet of the hydro unit and
L-Type service valve at the water outlet of the hydro unit .
An air-vent valve is integrated on the hydro unit . Please check that air-vent valve is not overtightened so the air-vent
valve can release any air out of the system during system operation .


No. Name Tightening Torque


① 1 .25” BSPP 350 ~ 380 kgf•cm 34 ~ 37 N•m
② 3/8” BSPP 120 ~ 150 kgf•cm 12 ~ 15 N•m

⑦ ③ Pressure relief valve 120 ~ 150 kgf•cm 12 ~ 15 N•m


Hydro unit
④ Air-vent valve 120 ~ 150 kgf•cm 12 ~ 15 N•m

⑤ Manometer 92~ 102 kgf•cm 9 ~ 10 N•m
⑥ Flow Sensor O-ring type O-ring type
① ⑦ Strainer 350 ~ 380 kgf•cm 34 ~ 37 N•m
4. Installation
Hydro unit

ESP(External Static Pressure) Diagram (R32)


The illustration below shows the external static pressure of the unit depending on the water flow and the pump setting .
ESP [kPa]
90

80

70

60

50
43
40

30
20

10

0
10 15 20 2526 30 35 40 4546 50 Flow [l/min]
Water flow rate : 26 LPM

If the pressure loss of total system is over 43 kPa , additional water pump should be installed in series .
Otherwise, the flow rate might be decreased, causing insufficient heating or cooling .
When the ESP is not enough, additional pump should be installed . In this case, install the PWM control external type pump
(Heating type) additionally .

ESP(External Static Pressure) Diagram (R410A)


The illustration below shows the external static pressure of the unit depending on the water flow and the pump setting .
ESP [kPa]
90

80

70

60

50
43
40

30
20

10

0
10 15 20 2526 30 35 40 4546 50 Flow [l/min]
Water flow rate : 46 LPM

If the pressure loss of total system is over 20kPa, additional water pump should be installed in series .
Otherwise, the flow rate might decreased, causing insufficient heating or cooling .
When ESP is not enough, additional pump should be installed . In this case, install the PWM control external type pump
(Heating type) additionally .
4. Installation
Hydro unit

Connection guide of additional pump


Case 1) INV. pump
Connect the PWM control external type pump to PWM terminal block and power cable to the external contact terminal .
The maximum number of additional pump installation is one inverter pumps (Input power 100W) .
1 . Power supply (For additional INV . Pump) 2 . PWM control (For additional INV . Pump only), refer to page 24, 25

Reference (GND)

B1 B6 PWM signal (SIG)


Live additional pump
Neutral additional pump

• If there is wrong wiring between PWM and reference, INV . Water Pump may not work or wrong operation .
CAUTION

PWM characteristic curve


Max .
Speed

PWM input signal(%)

The additional pump should be the same type of product as the above graph .
Recommendation
WILO STRATOS PARA 25/1-9 (Heating Type)

Case 2) AC pump
Only a single additional AC pump is is allowed .
1 . Power supply (AC Pump)

B8: Live additional pump


B7: Neutral additional pump

Neutral additional pump

PCB Live additional pump

Terminal block B7 B8

Pump

Power L M/C
N

• The maximum allowable current that this terminal block can supply for the additional water pump is 0 .1 A .
CAUTION
4. Installation
Hydro unit

Setting the pre-pressure of the expansion vessel


When it is required to change the default pre-pressure of the expansion vessel(1 bar), keep in mind the following guidelines:
ffUse only dry nitrogen to set the expansion vessel pre-pressure .
ffInappropriate setting of the expansion vessel pre-pressure will lead to malfunction of the system . Therefore, the pre-
pressure should only be adjusted by a licensed installer .
Expansion Vessel capacity (Liter)
14 .00
12 .00

10 .00 Norminal
8 .00
Operation range
[Lit]

6 .00

4 .00

2 .00

0 .00
50 100 150 200 250 300 350 400
Water volume (Litre) in total system including pipes

• Water volume of total system for reliable performance is minimum 20 liters(R32), 50 liters(R410A) .
CAUTION

Water volume
Installation height
differencea)
< 220 Litres > 220 Litres

Actions required:
• Pre-pressure must be decreased, calculate
according to “Calculating the pre-pressure of
< 7 m No pre-pressure adjustment required .
the expansion vessel” .
• Check if the water volume is lower than
maximum allowed water volume

Actions required:
• Pre-pressure must be increased, calculate
the appropriate value following by
Expansion vessel of the unit too small for the
> 7 m “Calculating the pre-pressure of the
installation .
expansion vessel” .
• Check if the water volume is lower than
maximum allowed water volume

a) Installation height difference: height difference(m) between the highest point of the water circuit and the indoor unit . If
the indoor unit is located at the highest point of the installation, the installation height is considered 0 m .
Calculating the pre-pressure of the expansion vessel
The pre-pressure(Pg) to be set depends on the maximum installation height difference(H) and is calculated as below:
Pg=(H/10+0 .3) bar
4. Installation
Hydro unit

Torque requirements

C-BOX: SINGLE PHASE C-BOX: 3 PHASE

Tightening torque
Screw size Part Terminal code Remarks
(N·m)
M3 0 .5~0 .75 20P Terminal Block 1~20 Digital input/output
Magnetic contactor 2P AC 220V-240V power
-
Single phase input/output
Magnetic contactor 3P AC 380V-415V power
-
3phase input/output
ELCB 2P AC 220V-240V power
-
Single phase input/output
ELCB 4P AC 380V-415V power
-
3 phase input/output
M5 2 .0~2 .9
AC220-240V Power
1(L), 2(N)
Terminal block 4P output
Single phase
L, N AC220-240V Power input

AC220-240V Power
1(L), 2(N)
Terminal block 6P output
3 phase AC 380V-415V power
L1(R), L2(S), L3(T), N
input

Grounding work
ffGrounding must be done by a qualified installer for your safety .

Grounding the power cable


ffThe standard of grounding may vary according to the rated voltage and installation place of a heat pump .
ffGround the power cable according to the following .
Installation place
High humidity Average humidity Low humidity
Power condition

Perform the grounding Perform the grounding work 3 if


Electrical potential of lower than 150V
work 3 . Note 1) possible for your safety . Note 1)

Must perform the grounding work 3 . Note 1)


Electrical potential of higher than 150V
(In case of installing circuit breaker)

❋ Note 1) Grounding work 3


• Grounding must be done by your installation specialist .
• Check if the grounding resistance is lower than 100 Ω .
When installing a circuit breaker that can cut the electric circuit in case of a short circuit, the allowable grounding resistance can be 30~500 Ω .
4. Installation
Hydro unit

Checking correct grounding


If the power distribution circuit does not have a grounding or the grounding does not comply with specifications, an grounding electrode must be installed . The
corresponding accessories are not supplied with the Air to Water Heat pump .
1 . Select an grounding electrode that complies with the specifications given in the illustration .
Carbon Steel core 50 cm
plastic Terminal M4
30 cm
PVC-insulated green/ To grounding
yellow wire screw

2 . Connect the flexible hose to the flexible hose port .


ffIn damp hard soil rather than loose sandy or gravel soil that has a higher grounding resistance .
ffAway from underground structures or facilities, such as gas pipes, water pipes, telephone lines and underground cables .
ffAt least two metres away from a lightening conductor grounding electrode and its cable .

• The grounding wire for the telephone line cannot be used to ground the Air to Water Heat pump .
NOTE

3 . Finish wrapping insulating tape around the rest of the pipes leading to the outdoor unit .
4 . Install a green/yellow coloured grounding wire :
ffIf the grounding wire is too short, connect an extension lead, in a mechanical way and wrapping it with insulating tape (do not bury the connection) .
ffSecure the grounding wire in position with staples .

• If the grounding electrode is installed in an area of heavy traffic, its wire must be connected securely .
NOTE

5 . Carefully check the installation, by measuring the grounding resistance with a ground resistance tester . If the resistance is above required level,
drive the electrode deeper into the ground or increase the number of grounding electrodes .
6 . Connect the grounding wire to the electrical component box inside of the outdoor unit .

Connection of the power supply and communication cable

No. of Max.
Model Description Thickness Supply Scope
wires A
4 .0mm2 ↑
1 Phase main 2+ Field supply (220-
18 .6A H05RN-F or
power ground 240Vac, Input)
H07RN-F
AE090RNYDEG
0 .75mm2 ↑
Field wiring
Communication 2 0 .1A H05RN-F or
(7Vdc, data)
H07RN-F
4+ 2 .5mm2 ↑ Field supply (380-
3 Phase power 9 .2 A
ground H07RN-F 415Vac, Input)
AE090RNYDGG 0 .75mm2 ↑
Field wiring
Communication 2 0 .1A H05RN-F or
(7Vdc, data)
H07RN-F

No. of
Model Description Max. A Thickness Supply Scope
wires
4 .0mm2 ↑
1 Phase main 2+ Field supply (220-
27 .9 A H05RN-F or
power ground 240Vac, Input)
H07RN-F
AE160ANYDEH
0 .75mm2 ↑
Field wiring
Communication 2 0 .1 A H05RN-F or
(7Vdc, data)
H07RN-F
4+ 2 .5mm2 ↑ Field supply (380-
3 Phase power 9 .3 A
ground H07RN-F 415Vac, Input)
AE160ANYDGH 0 .75mm2 ↑
Field wiring
Communication 2 0 .1 A H05RN-F or
(7Vdc, data)
H07RN-F
* When you use inlet hole through the cabinet top positions for power/communication wires, please fix the wire by using mount tie of the cabinet right .
4. Installation
Hydro unit
2 wires for communication cable

Circuit breaker

Communication cable between


indoor and outdoor units Communication
cable
Earth
F4

F3
CONTROL-KIT PBA
V2

V1
1 2 1 2
F2

F1

TB-A TB-A1 TB-C

Hydro unit

Communication cable connection

F4

F3
CONTROL-KIT PBA
V2

V1
1 2 1 2
F2

F1

TB-A TB-A1 TB-C

1 . 1 phase product
1Φ, 220-240Vac

Distribution board

MCCB + ELB
or
ELCB

1L 2N L N

grounding

L N

1 phase AC
POWER-IN
1 phase AC POWER
220~240V~

grounding
2 . 3 phase product
3Φ, 380-415Vac

Distribution board

MCCB + ELB
or
ELCB

grounding 1L 2N L1(R) L2(S) L3(T) N

L1(R) L2(S) L3(T) N

3 phse AC POWER 3 phase AC


POWER-IN
380~415V~

grounding

• If the supply cable is damaged, it must be replaced by a special cable or assembly available from the
CAUTION manufacturer or installer .
• Circuit Breaker (ELCB, ELB, MCCB etc .) for outdoor and indoor units shall be installed by installers because they
are not sub-parts in the units . But you don't need to install for hydro unit (Built-in ELCB) . ❋ ELCB : Earth leakage circuit breaker
• It cause damage to chassis, PCB parts if the main power is not connected correctly . You should make certain that R, ELB : Earth leakage breaker
S, T is connected correctly before turning on the main power . (3 phase models only) MCCB : Molded case circuit breaker
4. Installation
Hydro unit

Connecting the power terminal


ffConnect the cables to the terminal board using the solderless ring terminal .
ffUse certified and reliable cables .
ffConnect the cables with the torque chart as below .
ffIf the terminal is loose, fire may occur caused by arc . If the terminal is connected too firmly, the terminal may be damaged .
ffExternal force should not be applied to the terminal block and wires .
ffThe cable ties to fasten the wire should be an incombustible material, V0 or above . (The cable ties should be used to
fasten the power wire and they are supplied with the unit .)

Solderless terminal Cable tie

Thin cable
Thick cable

Separate the solderless terminal up and down to prevent it being get


loosen . Place the thin cable upward and the thick cable downward . Secure
the power cable with the cable tie .

Tightening Torque (kgf • cm)


M3 5~7 .5
M5 20 ~ 30

Connection of the backup heater power supply


• Do not use a power supply shared by other appliances . Each components for outdoor unit, indoor unit, backup
CAUTION heater and booster heater has the dedicated power supply .

Model Heater capacity (kW) ELCB capacity (A)


AE090RNYDEG 4 30
AE090RNYDGG 6 20
AE160ANYDEH 6 40
AE160ANYDGH 6 20

❋ Circuit Breaker(ELCB, ELB, MCCB etc .)s written above are already included in the hydro unit .
ELCB : Earth leakage circuit breaker
ELB : Earth leakage breaker
MCCB : Molded case circuit breaker

1 phase 3 phase Booster heater (DHW)

1L 2N L N

DHW Tank

1 Phase 1 Phase 3 Phase


ELCB ELCB ELCB
4. Installation
Hydro unit

Connection of the thermostat


Description No. of wires Max. current Thickness Supply Scope
> 0 .75 mm2, H05RN-F or Field supply (220-240V~,
Room Thermostat 4 22mA
H07RH-F Input)
1 . Before the installation, hydro unit should be turned off .
2 . Using the appropriate equipment to correct position of terminal block as shown on the diagram .
B19: Neutral (N)
B20 : Live (L) 3 . Determine the thermostat type .
B21 : THERMOSTAT01_COOLING (C1) - Normal OPEN or Normal CLOSED .
B22 : THERMOSTAT01_HEATING (H1) - Contact signal must be “ L “ . When installing two thermostats,
B23 : THERMOSTAT02_COOLING (C2)
B24 : THERMOSTAT02_HEATING (H2) thermostat2 is prior to thermostat1 .

N L C1 H1 N L C2 H2
• Product will not operate when signal for cooling and
CAUTION heating mode is inputted at the same time .
THERMOSTAT01 THERMOSTAT02

Connection of the 2-way valve


Description No. of wires Min. / Max. current Thickness Supply Scope
Motorized 2-way valve to shut off > 0 .75 mm2, H05RN-F or Field supply (220-240V~,
2+ground 10mA / 50mA
UFH loops during cooling . H07RH-F Output)
2-way motorized valve
ffWhen outlet water temperature reach to lower than 16 °C in cooling mode, UFH loops will be closed .
B9 : 2WAY1 (L1) B14 : 2WAY2 (L2)
B10 : 2WAY1 (L2) B13 : 2WAY2 (L1) ff220-240V~
B11 : Neutral (N) B12 : Live (L) ff2 wires(Normal Open or Normal Close)
* Connection of 2 wires 2-way valve 1 . Before the installation, hydro unit should be turned off .
2 . Using the appropriate equipment to correct position of terminal block as shown on the diagram .
Normal
Open type
Normal
closed type
3 . Determine the motorized valve type .

In case of normal open type In case of normal closed type


- When it closes -When it opens -When it opens - When it closes
- Normal OPEN or Normal CLOSED .

N L1 N L2
• There are 2 types of 2-way valve, normal open type and
CAUTION normal closed type . Make sure to connect terminals
Mixing
Tank
Floor
Heating
Mixing
Tank
Floor
Heating
Mixing
Tank
Floor
Heating
Mixing
Tank
Floor
Heating
to right positions of terminal block . As detailed on the
2Way Valve 2Way Valve wiring diagram and illustrations above .

Connection of the water pump for 2-zone control (FSV 4061=1)


ffZone1 water pump connection: B10(L1) + B11(N)
ffZone2 water pump connection: B14(L1) + B15(N)

Zone2
Tw2_z2

Balancing
vessel

Radiator

Zone1

M Tw2_z1

Under Floor

• There are 2 types of 2-way valve, normal open type and normal closed type . Make sure to connect terminals to
CAUTION
right positions of terminal block . As detailed on the wiring diagram and illustrations above .
• To use the zone control (FSV #4016=1), set the thermostat control option (FSV #2091 & #2092) to "0" for disabling
it .
4. Installation
Hydro unit

B11 - Neutral AC power output for Zone1 water pump control signal B15 - Neutral AC power output for Zone2 water pump control signal
B10 - Live AC power output for Zone1 water pump control signal B14 - Live AC power output for Zone2 water pump control signal

Neutral additional pump Neutral additional pump

PCB Live additional pump Live additional pump


PCB

Terminal block B11 B10 Terminal block B15 B14

Pump Pump

Power L M/C Power L M/C


N N

• The maximum allowable current that this terminal block can supply for the additional water pump is 50mA .
CAUTION

Connection of the 3-way valve


Description No. of wires Mini. / Max. current Thickness Supply Scope
Diverting type 3way > 0 .75 mm2, H05RN-F or Field supply (220-240V~,
4 10mA / 50mA
valve H07RN-F Input)

Status L1 L2 3-way diverting valve for water tank


A ffWhen cooling operating mode, floor heating loops will
OFF ON be closed .
B15 : Neutral (N)
(Initial)
B18 : 3WAY (L2)
B16 : Live (L) B17 : 3WAY (L1) B ON OFF
ff220-240V~
1 . Before the installation, hydro unit should be turned off .
Field Setting Valve (#3071) “0” Field Setting Valve (#3071) “1” 2 . Using the appropriate equipment to correct position of
Floor heating as default DHW tank as default terminal block as shown on the diagram .
A A 3 . Make sure what type of 3 way V/V you use .
FLOOR FLOOR
HEATING HEATING

HYDRO HYDRO
UNIT UNIT

3WAY V/V 3WAY V/V

DHW DHW
TANK TANK

B FLOOR
B FLOOR
HEATING HEATING

HYDRO HYDRO
UNIT UNIT

3WAY V/V 3WAY V/V

DHW DHW
TANK TANK
4. Installation
Hydro unit

Connection of the back-up boiler


Description No. of wires Mini. / Max. current Thickness Supply Scope
0 .75mm2 H05RN-F or Field supply (220-240V~,
Back-up Boiler 2+ground 10mA / 50mA
H07RN-F Input)

1 . Before the installation, hydro unit should be turned off .


2 . Using the appropriate equipment to correct position of terminal
B5 : Neutral (N) block as shown on the diagram .
B4 : Back-up boiler (L)
When it set back up
3 . Make sure EXT-CTRL signal of back up boiler must be 230Vac .
When it order to back up
boiler on the hydro unit boiler operates (relay on) - Do not connect supply power of back up boiler directly .
(relay off ) ❋ Heat pump does not work when the Back-up boiler operates .
L N L N

Boiler Boiler

Connecting for external contact functions


Screw size Tightening torque (N·m) Part Terminal code
M3 0 .5~0 .75 20P Terminal block 1~20

Connecting external sensors for zone control

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

ZONE1
Flow
Temp .
[Tw2_z1]
(103)

ZONE2 ZONE2
Room Flow
Temp .
Temp . [Tw2_z2]
(103) (103)

• When connecting sensors, use a Thermistor with the specifications of 10 kΩ at 25 °C, B constant = 3435 k .
CAUTION
4. Installation
Hydro unit

Connecting for smart grid ready control

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Connection terminal Connection terminal for


for SG READY Signal 1 SG READY Signal 2

SG READY Signal 2
SG READY Signal 1

SG READY Signal 1 SG READY Signal 2 Product operation


Short Open Forced thermo off operation
Open Open Normal operation
Open Short Heating / DHW setting temperature 1step-up operation
Short Short Heating / DHW setting temperature 2step-up operation

• These parts are optional and not included with the product .
CAUTION • Maker sure to connect to non-power on/off contacts .
4. Installation
Outdoor unit

Deciding on where to install the outdoor unit


Decide the installation location regarding the following condition and obtain the user’s approval .
f The outdoor unit must not be placed on its side or upside down, as the compressor lubrication oil will run into the cooling circuit and seriously damage the unit .
f Choose a location that is dry and sunny, but not exposed to direct sunlight or strong winds .
f Do not block any passageways or thoroughfares .
f Choose a location where the noise of the Air to Water Heat Pump when running and the discharged air do not disturb any neighbours .
f Choose a position that enables the pipes and cables to be easily connected to the other hydrauric system .
f Install the outdoor unit on a flat, stable surface that can support its weight and does not generate any unnecessary noise and vibration .
f Position the outdoor unit so that the air flow directly stream towards the open area .
f Place the outdoor unit where there are no plants and animals because they may cause malfunction of outdoor unit .
f Maintain sufficient clearance around the outdoor unit, especially from a radio, computer, stereo system, etc .

Installation Guide at the seashore


Make sure to follow below guides when installing at the seashore .
1 . Do not install the product in a place where it is directly exposed to sea water and sea breeze .
- Make sure to install the product behind a structure (such as building) that can block see breeze .
- Even when it is inevitable to install the product in seashore, make sure that product is not directly exposed to sea breeze by installing a protection wall .
2 . Consider that the salinity particles clinging to the external panels should be sufficiently washed out .
3 . Because the residual water at the bottom of the outdoor unit significantly promotes corrosion, make sure that the slope does not disturb drainage .
- Keep the floor level so that rain does not accumulate .
- Be careful not to block the drain hole due to foreign substance
4 . When product is installed in seashore, periodically clean it with water to remove attached salinity .
5 . Make sure to install the product in a place that provides smooth water drainage . Especially, ensure that the base part has good drainage .
6 . If the product is damaged during the installation or maintenance, make sure to repair it .
7 . Check the condition of the product periodically .
- Check the installation site every 3 months and perform anti-corrosion treatment such as R-Pro supplied by SAMSUNG (Code : MOK-220SA) or commercial water
repellent grease and wax, etc ., based on the product condition .
- When the product is to be shut down for a long period of time, such as off-peak hours, take appropriate measures like covering the product .
8 . If the product installed within 500m of seashore, special anti-corrosion treatment is required .
❋ Please contact your local SAMSUNG representative for further details .

Outdoor
Sea breeze unit

Sea

Protection wall Outdoor


unit
Outdoor
Sea breeze unit
Sea breeze

Sea
Sea

Protection wall should be constructed with a solid material that can block the
sea breeze and the height and width of the wall should be 1 .5 times larger
than the size of the outdoor unit . (You must secure more than 700mm of space
between the protection wall and the outdoor unit for air circulation .)

• Depending on the condition of power supply, unstable power or voltage may cause malfunction of the parts or
CAUTION control system . (At the ship or places using power supply from electric generator, etc) .

f Do not install the Air to Water Heat Pump in following places .


• The place where there is mineral oil or arsenic acid . There is a chance that parts may get damaged due to burned resin . The capacity of the heat exchanger may
reduce or the Air to Water Heat pump may be out of order .
• The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet . The copper pipe or connection pipe may corrode and
refrigerant may leak .
• The place where there is a danger of existing combustible gas, carbon fiber or flammable dust . The place where thinner or gasoline is handled .
• This device must be installed according to the national electrical rules .
CAUTION • With an outdoor unit having net weight upper than 60 kg, we suggest do not install it suspended on wall, but
considering floor standing one .
4. Installation
Outdoor unit

f If the outdoor unit is installed at a height, ensure that its base is firmly fixed in position .
f Make sure that the water dripping from the drain hose runs away correctly and safely .
f When you install the outdoor unit at wayside, you should install it above 2 m height or make sure that the heat from the outdoor unit shouldn't be in direct contact
with passersby . (The ground for application :The revision of regulation for facility in building by the law of the Ministry of Construction and Transportation .

Moving the Outdoor Unit by Wire Rope


Wire rope
Fasten the outdoor unit by two 8 m or longer wire ropes as shown at the figure . To prevent from damage or
scratches, insert a piece of cloth between the outdoor unit and rope, then move the unit . Plate protection
❋ The appearance of the unit may be different from the picture depending on the model . cloth

Space requirements for outdoor unit


When installing 1 outdoor unit

(Unit : mm)
300 or more

1,500 or more

❋ When the air outlet is opposite the wall ❋ When the air outlet is towards the wall
300 or more

1,500 or more

2,000 or more

300 or more 600 or more

❋ When 3 sides of the outdoor unit are blocked by the ❋ The upper part of the outdoor unit and the air outlet
wall is towards the wall
600 or more

300 or more

300 or more
1,500 or more

❋ The upper part of the outdoor unit and the air outlet ❋ When front and rear side of the outdoor unit is
is opposite the wall towards the wall
4. Installation
Outdoor unit

When installing more than 1 outdoor unit

(Unit : mm)

1500 or more
❋ When the air outlet is towards the wall

300 or more

300 or more 600 or more 600 or more 600 or more

❋ When 3 sides of the outdoor unit are blocked by the wall


300 or more
500 or
more
300 or
more

300 or more
500 or
more
1500 or more

600 or more 600 or more

❋ When front and rear side of the outdoor unit is towards the wall ❋ The upper part of the outdoor unit and the
air outlet is opposite the wall

1500 or more 600 or more 3000 or more 3000 or more 300 or more

❋ When front and rear side of the outdoor unit is towards the wall

• The units must be installed according to distances declared, in order to permit accessibility from each side, either
CAUTION to guarantee correct operation of maintenance or repairing products . The unit’s parts must be reachable and
removable completely under safety condition (for people or things) .

Outdoor unit installation


The outdoor unit must be installed on a rigid and stable base to avoid any increase in the noise level and vibration,
particularly if the outdoor unit is to be installed in a location exposed to strong winds or at a height, the unit must be fixed to
an appropriate support(wall or ground) .
f Fix the outdoor unit with anchor bolts .

• The anchor bolt must be 20 mm or higher from the base AE090RXED*G/EU
AE040/060RXEDEG/EU (Unit : mm) AE120/160AXED*H/EU
NOTE surface . (Unit : mm)
Anchor bolt hole
Anchor bolt hole

• When tightening the anchor bolt, tighten the rubber


washer to prevent the outdoor unit bolt connection part
310

340

364

CAUTION
328

344

384

from corroding .
• Make a drain outlet around the base for outdoor unit
drainage . 660
620
• If the outdoor unit is installed on the roof, you have to 880
940

check the ceiling strength and waterproof the unit . Rubber leg
4. Installation
Outdoor unit

Electrical connections
Overall system configuration
Connection of the power cable (1 phase 2 wires)
Distribution board Outdoor unit Hydro unit
1 phase 1 phase 1 phase
2 wires 2 wires 2 wires
220- 220- 220-
240 V ~ 240 V ~ 240 V ~
Or
ELCB MCCB+ DHW tank
ELB

Earth
Earth Earth
Communication cable

• Install cabinet panel near the outdoor unit for the convenience of service and emergency operation off .
CAUTION • Make sure to install the circuit breaker with the over-current and electric leakage protection .

Connection of the power cable (3 phase 4 wires)


Distribution board Outdoor unit Hydro unit
3phase 3phase 3phase
4wires 4wires 4wires
380 - 380 - 380 -
415 V~ 415 V~ 415 V~
Or
ELCB MCCB+ DHW tank
ELB

Earth
Earth Earth
Communication cable

• Install cabinet panel near the outdoor unit for the convenience of service and emergency operation off .
CAUTION • Make sure to install the circuit breaker with the over-current and electric leakage protection .

Connecting the cable


Power cable specifications
1 phase

Rated Voltage Range MCA MFA


Outdoor unit
Hz Volts Min Max Min. Circuit Amps. Max. Fuse Amps.
AE040RXEDEG 50 220-240 198 264 16 A 20 A
AE060RXEDEG 50 220-240 198 264 16 A 20 A
AE090RXEDEG 50 220-240 198 264 22 A 27.5 A
AE120AXEDEH 50 220-240 198 264 28 A 35 A
AE160AXEDEH 50 220-240 198 264 32 A 40 A

f The power cable is not supplied with Air to Water Heat pump .
f Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (Code
designation IEC:60245 IEC 57 / CENELEC:H05RN-F)
f This Equipment complies with IEC 61000-3-12 .
4. Installation
Outdoor unit

3 Phase

Rated Voltage Range MCA MFA


Outdoor unit
Hz Volts Min Max Min. Circuit Amps. Max. Fuse Amps.
AE090RXEDGG 50 380-415 342 457 10 A 16 .1 A
AE120AXEDGH 50 380-415 342 457 10 A 16 .1 A
AE160AXEDGH 50 380-415 342 457 12 A 16 .1 A
f The power cable is not supplied with Air to Water Heat pump .
f Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (Code designation IEC:60245 IEC 66 /
CENELEC:H07RN-F)
f This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to 3 .3[MVA] at the interface point between the user's
supply and the public system . It is the responsibility of the installer or user of the equipment to ensure, by consultation with distribution network operator if
necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to 3 .3[MVA] .

Connecting the cable


Specification of connection cables (common in use)
Power supply Max/Min(V) Communation cable
1Φ, 220-240 V, 50 Hz
±10 % 0 .75~1 .5 mm², 2 wires
3Φ, 380-415 V, 50 Hz

f For Power Cable, use the grade H07RN-F or H05RN-F materials .

When installing the indoor unit, outdoor unit use the double shielded (Tape
aluminum / polyester braid + copper ) cable of FROHH2R type .

AE040/060RXEDEG

1-phase terminal block spec

AC power : M4 screw Communication : M4 screw


13.1 11.4

L N

10.1 10.1
4. Installation
Outdoor unit

AE090RXED*G

1-phase terminal block spec

AC power : M5 screw Communication : M4 screw

L N

17
10.1

13

3-phase terminal block spec

AC power : M4 screw Communication : M4 screw

1(L) 2(N) L1(R) L2(S) L3(T) N

10.1
9.8 14.19

AE120/160AXED*H

1-phase terminal block spec

AC power : M5 screw Communication : M4 screw

1(L) 2(N) L N

15 12 6 .7
9 .7

3-phase terminal block spec

AC power : M4 screw Communication : M4 screw

1(L) 2(N) L1(R) L2(S) L3(T) N

9 .95 11 .55 6 .7
9 .7
4. Installation
Outdoor unit

AE040/060RXEDEG

Wiring diagram of power cable


When using ELB/MCCB for 1 phase

Power Supply Electrical component box

MCCB
L N

ELB

Cable tie

Cable
clamp

Main power cable Communication


cable
Hydro unit

❋ The appearance of the unit may be different from the picture depending on the model .

• You should connect the power cable into the power cable terminal and fasten it with a clamp .
CAUTION • The unbalanced power must be maintained within 2 % of supply rating .
- If the power is unbalanced greatly, it may shorten the life of the condenser . If the unbalanced power is
exceeded over 4 % of supply rating, the indoor unit is protected, stopped and the error mode indicates .
• To protect the product from water and possible shock, you should keep the power cable and the connection cord of
the indoor and outdoor units within ducts . (with appropriate IP rating and material selection for your application)
• Ensure that main supply connection is made through a switch that disconnects all poles, with contact gap of a
least 3 mm .
• Devices disconnected from the power supply should be completely disconnected in the condition of
overvoltage category .
• Keep distances of 50 mm or more between power cable and communication cable .

1 phase 2 wires
1 phase

Circuit
breaker Earth cable
(U-Trap)

Power cable

Communication cable between Hydro


unit and outdoor units Communication
cable
Earth
Hydro unit

• When removing the outer cover of the power cable, use the appropriate tools to prevent damaging the inner
CAUTION cover .
• Make sure to place the outer cover of the power cable and the communication cable, at least 20 mm into the
electrical parts .
• Communication wiring should be done separately from the power cable and other communication cables .
4. Installation
Outdoor unit

AE090RXED*G

Wiring diagram of power cable


When using ELB for 1 phase and 3 phase
f1 phase

L N

Cable tie

Power Supply Electrical component box


Cable
MCCB clamp
+
ELB
Main power cable Communication
cable
ELCB
f3 phase

1(L) 2(N) L1(R) L2(S) L3(T) N

Hydro unit NOT USE

❋ The appearance of the unit may be Cable tie


different from the picture depending on Cable clamp
the model.

3 Phase 4 Wires power Communication


cable (AC 380-415 V) cable

• You should connect the power cable into the power cable terminal and fasten it with a clamp.
CAUTION • The unbalanced power must be maintained within 2 % of supply rating.
- If the power is unbalanced greatly, it may shorten the life of the condenser. If the unbalanced power is
exceeded over 4 % of supply rating, the indoor unit is protected, stopped and the error mode indicates.
• To protect the product from water and possible shock, you should keep the power cable and the connection cord of
the indoor and outdoor units within ducts. (with appropriate IP rating and material selection for your application)
• Ensure that main supply connection is made through a switch that disconnects all poles, with contact gap of a
least 3 mm.
• Devices disconnected from the power supply should be completely disconnected in the condition of
overvoltage category.
• Keep distances of 50 mm or more between power cable and communication cable.
4. Installation
Outdoor unit

AE120/160AXED*H

1 phase 2 wires
1 phase

Circuit
breaker Earth cable
(U-Trap)

Power cable

Communication cable between Hydro


unit and outdoor units Communication
cable
Earth
Hydro unit

• When removing the outer cover of the power cable, use the appropriate tools to prevent damaging the inner
CAUTION cover.
• Make sure to place the outer cover of the power cable and the communication cable, at least 20 mm into the
electrical parts.
• Communication wiring should be done separately from the power cable and other communication cables.

3 phase 4 wires

3 phase

Circuit
breaker 1(L) 2(N) L1(R) L2(S) L3(T) N
Earth cable
(U-Trap)
NOT USE

Power cable

Communication cable between Hydro and


outdoor units

Earth Communication
cable

Hydro unit

• When removing the outer cover of the power cable, use the appropriate tools to prevent damaging the inner
CAUTION cover.
• Make sure to place the outer cover of the power cable and the communication cable, at least 20 mm into the
electrical parts.
• Communication wiring should be done separately from the power cable and other communication cables.
4. Installation
Outdoor unit

Wiring diagram of power cable


When using ELB for 1 phase and 3 phase
f 1 phase

L N

Cable tie

Power Supply Electrical component box


Cable
MCCB+ELB clamp

Main power cable Communication


cable
ELCB
f 3 phase

1(L) 2(N) L1(R) L2(S) L3(T) N

Hydro unit NOT USE

❋ The appearance of the unit may be Cable tie


different from the picture depending on Cable clamp
the model .

3 Phase 4 Wires power Communication


cable (AC 380-415 V) cable

• You should connect the power cable into the power cable terminal and fasten it with a clamp .
CAUTION • The unbalanced power must be maintained within 2 % of supply rating .
- If the power is unbalanced greatly, it may shorten the life of the condenser . If the unbalanced power is
exceeded over 4 % of supply rating, the indoor unit is protected, stopped and the error mode indicates .
• To protect the product from water and possible shock, you should keep the power cable and the connection
cord of the indoor and outdoor units within ducts . (with appropriate IP rating and material selection for your
application)
• Ensure that main supply connection is made through a switch that disconnects all poles, with contact gap of a
least 3 mm .
• Devices disconnected from the power supply should be completely disconnected in the condition of
overvoltage category .
• Keep distances of 50 mm or more between power cable and communication cable .
4. Installation
Outdoor unit

Connecting the cable


1 phase 2 wires
1 phase

Circuit
breaker Earth cable
(U-Trap)

Power cable

Communication cable between Hydro


unit and outdoor units Communication
cable
Earth
Hydro unit

• When removing the outer cover of the power cable, use the appropriate tools to prevent damaging the inner
CAUTION cover .
• Make sure to place the outer cover of the power cable and the communication cable, at least 20 mm into the
electrical parts .
• Communication wiring should be done separately from the power cable and other communication cables .

3 phase 4 wires

3 phase

Circuit
breaker 1(L) 2(N) L1(R) L2(S) L3(T) N
Earth cable
(U-Trap)
NOT USE

Power cable

Communication cable between Hydro and


outdoor units

Earth Communication
cable

Hydro unit

• When removing the outer cover of the power cable, use the appropriate tools to prevent damaging the inner
CAUTION cover .
• Make sure to place the outer cover of the power cable and the communication cable, at least 20 mm into the
electrical parts .
• Communication wiring should be done separately from the power cable and other communication cables .
4. Installation
Outdoor unit

Connecting the power terminal


f Connect the cables to the terminal board using the compressed ring terminal .
f Connect the rated cables only .
f Connect using a wrench which is able to apply the rated torque to the screws .
f If the terminal is loose, fire may occur caused by arc . If the terminal is connected too firmly, the terminal may be
damaged .
Tightening Torque (kgf.cm)
M4 12~18
M5 20~30

Installing the earth wire


f Earthing must be done by your installation specialist for your safety .
f Use the earth wire by referring to the specification of the electric cable for the outdoor unit .

Earthing the power cable


f The standard of earthing may vary according to the rated voltage and installation place of the Air to Water Heat Pump .
f Earth the power cable according to the following .

Installation place
High humidity Average humidity Low humidity
Power condition
Perform the earthing work 3 if
Electrical potential of lower than 150 V Perform the earthing work 3 . Note 1)
possible for your safety . Note 1)
Must perform the earthing work 3 . Note 1)
Electrical potential of higher than 150 V
(In case of installing circuit breaker)

❋ Note 1) Earthing work 3


- Earthing must be done by your installation specialist .
- Check if the earthing resistance is lower than 100Ω . When installing a circuit breaker that can cut the electric circuit in
case of a short circuit, the allowable earthing resistance can be 30~500Ω .
f When using the terminal for earthing only f When using earthing of the switchboard

Earth Distribution
terminal Board

Refrigerant piping work


fInstall the refrigerant pipe within the maximum allowable length, difference in height and length of after the first branch pipe.
fThe pressure of the R-32 is high.
Use only rated refrigerant pipe and follow the installation method.
fUse clean refrigerant pipe Where there is no harmful ion, oxide, dust, iron content or moisture.
fUse adequate tools and accessories for R-32.

Manifold gauge • Use manifold gauge only for R-32 to prevent the inflow of foreign substances.
• Use vacuum pump with check valve to prevent pump oil from flowing backward while the vacuum
Vacuum pump pump is stopped.
• Use the vacuum pump that the vacuum induction is available up to 5Torr. (-100.7kPa)
Flare nut • Use only flare nut supplied with the product.

f Install the refrigerant pipe within the maximum allowable length, difference in height and length of after the first branch pipe.
f The pressure of the R-410A is high .
Use only rated refrigerant pipe and follow the installation method .
f Use clean refrigerant pipe Where there is no harmful ion, oxide, dust, iron content or moisture .
f Use adequate tools and accessories for R-410A .

Manifold gauge • Use manifold gauge only for R-410A to prevent the inflow of foreign substances .
• Use vacuum pump with check valve to prevent pump oil from flowing backward while the vacuum
Vacuum pump pump is stopped .
• Use the vacuum pump that the vacuum induction is available up to 5Torr . (-100 .7kPa)
Flare nut • Use only flare nut supplied with the product .
4. Installation
Outdoor unit

Allowable length of the refrigerant pipe and the installation examples


Outdoor unit

AE040/060RXEDEG

Item Example Remarks


Maximum allowable Outdoor unit Less than
Total length a ≤ 30 m
length of pipe ~ Hydro unit 30 m
If outdoor unit
Maximum allowable Outdoor unit
Less than 20 m H1 is located lower
height ~ Hydro unit
position H1 ≤15 m
Additional refrigerant calculation R=Basic charge + additional charge by the piping length

AE090RXED*G
Item Example Remarks
Maximum allowable Outdoor unit Less than
Total length a ≤ 35 m
length of pipe ~ Hydro unit 35 m
If outdoor unit
Maximum allowable Outdoor unit
Less than 20 m H1 is located lower
height ~ Hydro unit
position H1 ≤15 m
Additional refrigerant calculation R=Basic charge + additional charge by the piping length

Contact the manufacturer if the length should exceed .


ffBecause your air conditioner contains R-32 refrigerant, make sure that it is installed, operated, and stored it in a room
whose floor area is larger than the minimum required floor area specified in the following table:
Minimum required room area (A,m²)
m (kg) Ceiling-mounted Wall-mounted Floor-standing
≤ 1 .842 No requirement
1 .843 3 .64 4 .45 28 .9
1 .9 3 .75 4 .58 30 .7
2 .0 3 .95 4 .83 34 .0
2 .2 4 .34 5 .31 41 .2
2 .4 4 .74 5 .79 49 .0
2 .6 5 .13 6 .39 57 .5
2 .8 5 .53 7 .41 66 .7
3 .0 5 .92 8 .51 76 .6
3 .2 6 .48 9 .68 87 .2
3 .4 7 .32 10 .9 98 .4
3 .6 8 .20 12 .3 110
3 .8 9 .14 13 .7 123
4 .0 10 .1 15 .1 136
4 .2 11 .2 16 .7 150
4 .4 12 .3 18 .3 165
4 .6 13 .4 20 .0 180
4 .8 14 .6 21 .8 196
5 .0 15 .8 23 .6 213
- m : Total refrigerant charge in the system
- A : Minimum required floor area
ffIMPORTANT: it’s mandatory to consider either the table above or taking into consideration the local law regarding the
minimum living space of the premises .
ffMinimum installation height of indoor unit is 0 .6 m for floor mounted, 1 .8 m for wall, 2 .2 m for ceiling .
4. Installation
Outdoor unit

Selecting the refrigerant pipe


Outer Minimum
Liquid side Gas side
Outdoor unit capacity (kW) diameter thickness Temper grade
(mm) (mm)
(mm) (mm)
AE040RXEDEG ø6 .35 ø15 .88 ø 6 .35 0 .7
AE060RXEDEG ø6 .35 ø15 .88 ø 9 .52 0 .7
C1220T-0
AE090RXEDEG ø6 .35 ø15 .88 ø12 .70 0 .8
AE090RXEDGG ø6 .35 ø15 .88 ø15 .88 1 .0
ø15 .88 0 .8
ffInstall refrigerant pipe depending on the outdoor unit C1220T-1/2H OR
capacity . ø19 .05 0 .9
C1220T-H
ffMake sure to use C1220T-1/2H (Semi-hard) pipe for more ø22 .23 0 .9
than Ø19 .05 mm . In case of using C1220T-O (Soft) pipe for ❋ Temper grade and minimum thickness of the
Ø19 .05 mm, pipe may be broken, which can result in an injury . refrigerant pipe

AE120/160AXED*H

Allowable length of the refrigerant pipe and the installation examples


Outdoor unit

Item Example Remarks


Maximum
allowable Outdoor unit Less than
Total length a ≤ 50 m
length of ~ Hydro unit 50 m
pipe
If outdoor unit
Maximum
Outdoor unit is located lower
allowable Less than 30 m H1
~ Hydro unit position H1
height
≤15 m
Additional refrigerant
R=Basic charge + additional charge by the piping length
calculation
Contact the manufacturer if the length should exceed .

Selecting the refrigerant pipe


Outer Minimum
Liquid side Gas side
Outdoor unit capacity (kW) diameter thickness Temper grade
(mm) (mm)
(mm) (mm)
AE120AXEDEH ø 6 .35 0 .7
AE120AXEDGH ø 9 .52 0 .7
ø9 .52 ø15 .88 C1220T-0
AE160AXEDEH ø12 .70 0 .8
AE160AXEDGH ø15 .88 1 .0
f Install refrigerant pipe depending on the outdoor unit ø15 .88 0 .8
capacity . C1220T-1/2H OR
ø19 .05 0 .9
C1220T-H
f Make sure to use C1220T-1/2H (Semi-hard) pipe for more ø22 .23 0 .9
than Ø19 .05 mm . In case of using C1220T-O (Soft) pipe
for Ø19 .05 mm, pipe may be broken, which can result in ❋ Temper grade and minimum thickness of the
an injury . refrigerant pipe
4. Installation
Outdoor unit

Refrigerant piping work


Selecting the insulator of the refrigerant pipe
f According to pipes size, insulate pipes on gas and liquid side by selecting appropriate insulations .
f Standard condition is under a temperature of 30 °C and a humidity of 85 % . If the units are installed in extreme weather conditions, select the insulator by table below .
Thickness of insulator
Normal High humidity
Pipe type Pipe diameter (mm) Remarks
(Under 30 °C, 85 %) (Over 30 °C, 85 %)
EPDM, NBR
ø6 .35~ø19 .05 9 9
Liquid
ø12 .70~ø19 .05 13 13
ø6 .35 13 19 The material shall has
ø9 .52 heat resistant over
Gas ø12 .70 120 °C
19 25
ø15 .88
ø19 .05

• Install the insulation not to be get wider and use the adhesives on the connection part of it to prevent moisture entering .
CAUTION • Wind the refrigerant pipe with insulation tape if it is exposed to outside sunlight .
• Install the refrigerant pipe respecting that the insulation does not get thinner on the bent part or hanger of pipe .

Selecting additional refrigerant charge


❋ Basic charge
The basic amount of refrigerant for outdoor unit charged in factory is:

Outdoor unit (Series) Factory charge(kg)


AE040RXEDEG
1 .2
AE060RXEDEG
AE090RXEDEG
1 .4
AE090RXEDGG

❋ Charge additional refrigerant according to the total length of the pipe .


Each factory charging values are determined according to basic pipe length 15 m .
When extra pipe length are required, additional charging works must be implemented as describes below .

Refrigerant Charging
❋ Additional charging amount is determined based on liquid pipe specifications .

Outdoor unit of liquid ø6 .35


Additional charging (g) 20 g/m

Additional Charge(g) = (L1-15)*20

• L1: Total length of liquid pipe Ø 6 .35(m)_Model : AE040/060RXEDEG


NOTE • L1: Total length of liquid pipe Ø 6.35(m)_Model : ✴✴090✴✴

Ex) Total length of liquid pipe =20 m


Φ 6 .35 = (20m-15m) x 20g/m = 100 g (Model : AE040/060RXEDEG)

Precautions on adding the R-32 refrigerant


In addition to the conventional charging procedure, . the following requirements shall be kept .
ffMake sure that contamination by other refrigerants does not occur for charging .
ffTo minimize the amount of refrigerant, keep the hoses and lines as short as possible .
ffThe cylinders shall be kept upright .
ffMake sure that the refrigeration system is earthed before charging .
ffLabel the system after charging, if necessary .
ffExtreme care is required not to overcharge the system .
ffBefore recharging, the pressure shall be checked with nitrogen blowing .
ffAfter charging, check for leakage before commissioning .
ffBe sure to check for leakage before leaving the work area .
4. Installation
Outdoor unit

Charging refrigerant
ffMeasure the quantity of the refrigerant according to the length of the liquid side pipe . Add quantity of the refrigerant
using a scale .

Important information: regulation regarding the refrigerant used


This product contains fluorinated greenhouse gases . Do not vent gases into the atmosphere .

• Inform user if the system contains 5 tCO2e or more of fluorinated greenhouse gases . In this case, it must be checked
CAUTION for leakage at least once every 12 months, according to regulation No . 517/2014 . This activity must be covered by
qualified personnel only . In the case of the situation above, the installer (or authorized person with responsibility for
final check) must provide a maintenance book, with all the information recorded, according to REGULATION (EU) No .
517/2014 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 April 2014 on fluorinated greenhouse gases .

Please fill in the following indelible ink on the refrigerant charge label supplied
with this product on and on this manual . Indoor unit R-32
GWP = 675
ff① The factory refrigerant charge of the product .
ff② The additional refrigerant amount charged in the field . ②
ff①+② The total refrigerant charge . d ①

a . Factory refrigerant charge of the product: See unit name plate . Outdoor unit
NOTE b . Additional refrigerant amount charged in the field . (Refer
to the above information for the quantity of refrigerant Unit kg tCO2e
replenishment .) ①, a
c . Total refrigerant charge . ②, b
d . Refrigerant cylinder and manifold for charging . ① + ②, c

Refrigerant type GWP value


R-32 675
❋ GWP: Global Warming Potential
❋ Calculating tCO2e: kg x GWP/1000

ffBefore charging, check whether the refrigerant cylinder has a siphon attached or not and position the cylinder accordingly .
Charging using a cylinder with a Charging using a cylinder
siphon attached without a siphon attached
Charge the liquid refrigerant with Charge the liquid refrigerant with
the cylinder in upright position . the cylinder in up-side-down
position .

• The filled-out label must be adhered in the proximity of the product charging port (e .g . onto the inside of the
CAUTION stop valve cover) .
• Make sure that the total refrigerant charge does not exceed (A), the maximum refrigerant charge, which is
calculated in the following formula: Maximum refrigerant charge (A)= factory refrigerant charge (B) + maximum
additional refrigerant charge due to piping extension (C) .
• Here below, the summary table with refrigerant charge limits for each products .

Model A B C (Unit : g)
AE040/060RXEDEG 1,500 1,200 300
AE090RXED** 1,800 1,400 400
4. Installation
Outdoor unit

Adding refrigerant
fMeasure the quantity of the refrigerant depending on the length of the liquid side pipe. Add fixed quantity of the
refrigerant using a scale.
❋ Adding refrigerants in cooling conditions
Manifold gauge
Suction charging
High Outdoor unit
Low pressure pressure
side side
Gas side Liquid side

Service valve
Scale

❋ Adding refrigerants in heating conditions


Manifold gauge
Outdoor Suction charging
High unit
Low pressure
pressure side
side Gas side Liquid side

Service valve
Scale

fConnect the manifold gauge and purge the manifold gauge.


fOpen the manifold gauge valve of the liquid side service valve and add the liquid refrigerant.
fIf you cannot fully recharge the additional refrigerant while the outdoor unit is stopped, use the key on the outdoor unit
PCB to recharge the remaining refrigerant.
fAdding the cooling refrigerant
1) Press the function key for adding refrigerant in cooling mode.
2) After 20 minutes of operation, open the valve on gas side.
3) Open the valve for low pressure side on the manifold gauge to recharge the remaining refrigerant.

Refrigerant piping work


fAdding the heating refrigerant
1) When recharging the heating refrigerant, connect the low pressure pipe from manifold gage to the suction charging
port.
2) Press the function key for adding refrigerant in heating mode.
3) After 20 minutes of operation, open the valve on suction charge port.
4) Open the valve for low pressure side on the manifold gage to recharge the remaining refrigerant.

• Open the gas side and liquid side service valve completely after charging the refrigerant. (If you operate the Air
CAUTION to Water Heat Pump with the service valve closed, the important parts may be damaged.)
4. Installation
Outdoor unit

Selecting additional refrigerant charge


❋ Basic charge
The basic amount of refrigerant for outdoor unit charged in factory is:

Outdoor unit (Series) Factory charge(kg)


AE120AXEDEH
AE120AXEDGH
2 .98
AE160AXEDEH
AE160AXEDGH

❋ Charge additional refrigerant according to the total length of the pipe .


Each factory charging values are determined according to basic pipe length 15 m .
When extra pipe length are required, additional charging works must be implemented as describes below .

Refrigerant Charging
❋ Additional charging amount is determined based on liquid pipe specifications .

Outdoor unit of liquid ø9 .52


Additional charging (g) 50 g/m

Additional Charge(g) = (L1-15)*50

• L1: Total length of liquid pipe Ø 9 .52(m)_Model : TT120/160TT


NOTE

Ex) Total length of liquid pipe =20 m


Φ 9 .52 = (20m-15m) x 50g/m = 250 g (Model : TT120/160TT)

Charging refrigerant
f The R-410A refrigerant is blended refrigerant . Add only liquid refrigerant .
f Measure the quantity of the refrigerant according to the length of the liquid side pipe . Add quantity of the refrigerant using a scale .

Important information: regulation regarding the refrigerant used


This product contains fluorinated greenhouse gases . Do not vent gases into the atmosphere .

• Inform user if the system contains 5 tCO2e or more of fluorinated greenhouse gases . In this case, it must be
CAUTION checked for leakage at least once every 12 months, according to regulation No . 517/2014 . This activity must be
covered by qualified personnel only . In the case of the situation above, the installer (or authorized person with
responsibility for final check) must provide a maintenance book, with all the information recorded, according
to REGULATION (EU) No . 517/2014 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 April 2014 on
fluorinated greenhouse gases .

Please fill in the following indelible ink on the refrigerant charge label supplied
Indoor unit
with this product on and on this manual .
f ① The factory refrigerant charge of the product .
f ② The additional refrigerant amount charged in the field . ②
f ①+② The total refrigerant charge . d ①

a . Factory refrigerant charge of the product: See unit name Outdoor unit
NOTE plate .
b . Additional refrigerant amount charged in the field . Unit kg tCO2e
(Refer to the above information for the quantity of
refrigerant replenishment .) ①, a
c . Total refrigerant charge . ②, b
d . Refrigerant cylinder and manifold for charging . ① + ②, c

Refrigerant type GWP value


R-410A 2088

❋ GWP: Global Warming Potential


❋ Calculating tCO2e: kg x GWP/1000
4. Installation
Outdoor unit

f Before charging, check whether the refrigerant cylinder has a siphon attached or not and position the cylinder accordingly .
Charging using a cylinder with a Charging using a cylinder
siphon attached without a siphon attached
Charge the liquid refrigerant with Charge the liquid refrigerant with
the cylinder in upright position . the cylinder in up-side-down
position .

Adding refrigerant
f The R-410A refrigerant is blended refrigerant . Add only liquid refrigerant .
f Measure the quantity of the refrigerant depending on the length of the liquid side pipe . Add fixed quantity of the refrigerant using a scale .
❋ Adding refrigerants in cooling conditions
Manifold gauge
Suction charging
High Outdoor unit
Low pressure pressure
side side
Gas side Liquid side

Service valve
Scale

❋ Adding refrigerants in heating conditions


Manifold gauge
Outdoor Suction charging
unit
Low High pressure
pressure side
side Gas side Liquid side

Service valve
Scale

f Connect the manifold gauge and purge the manifold gauge .


f Open the manifold gauge valve of the liquid side service valve and add the liquid refrigerant .
f If you cannot fully recharge the additional refrigerant while the outdoor unit is stopped, use the key on the outdoor unit PCB to recharge the remaining refrigerant .
f Adding the cooling refrigerant
1) Press the function key for adding refrigerant in cooling mode .
2) After 20 minutes of operation, open the valve on gas side .
3) Open the valve for low pressure side on the manifold gauge to recharge the remaining refrigerant .
f Adding the heating refrigerant
1) When recharging the heating refrigerant, connect the low pressure pipe from manifold gage to the suction charging port .
2) Press the function key for adding refrigerant in heating mode .
3) After 20 minutes of operation, open the valve on suction charge port .
4) Open the valve for low pressure side on the manifold gage to recharge the remaining refrigerant .

• Open the gas side and liquid side service valve completely after charging the refrigerant . (If you operate the Air
CAUTION to Water Heat Pump with the service valve closed, the important parts may be damaged .)
2021.11
Ver.2.1

Samsung Electronics Co., LTD.


Head Office (Suwon Korea) 129, Samsung-Ro, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 16677
Website : www.samsung.com, https://partnerhub.samsung.com Email : airconditioner@samsung.com
Images and data in this book may subject to change without prior notice.