SECTION 078200 - BOARD FIREPROOFING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following:

1. Non-combustible composite panel of fiber- reinforced cement, mechanically bonded


to punched steel sheets on both surfaces board fire proofing.

a. Application: Fire rated suspended ceiling assemblies to relevant details


indicated on Drawings.
b. Installation Spaces: Iconic Tower attic slabs inside refuge areas at floors shown
Drawings to have fire rated ceilings and where indicated on Drawings.

B. Related Sections include the following:

1. Division 07 Section "Thermal Insulation" for slag-wool-/rock-wool-fiber board and


blanket insulation.
2. Division 07 Section "Applied Fireproofing" for applied coatings.
3. Division 07 Section "Fire-Resistive Joint Systems" for joints in or between fire-
resistance-rated construction, at exterior curtain-wall/floor intersections, and in smoke
barriers.
4. Division 07 Section "Penetration Firestopping."
5. Division 09 painting Sections for field painting.

1.3 SUBMITTALS

A. General: Submit in compliance with Division 01 Section “Submittal Procedures.”

B. Product Data: For each type of product indicated.

C. Shop Drawings: Indicate construction and fixation details for each fire protection
application. Show interface with adjoining works and include structural calculations to
demonstrate the structural stability of each application.

D. Product Certificates: For each type of board fire protection, signed by product manufacturer.

E. Research/Evaluation Reports: For board fire protection.

F. Installer Qualifications as specified in this Section.

BOARD FIREPROOFING 078200 - Page 1 of 5


REV 00
Alamein Downtown Towers

1.4 LOCAL REGULATIONS AND CODES

A. Comply with applicable requirements of the laws, codes, and regulations of authorities
having jurisdiction.

1. Obtain necessary approvals from authorities having jurisdiction.


2. Comply with Egyptian Codes and Standards requirements and latest circulars.

1.5 QUALITY ASSURANCE

A. General: Comply with Division 01 Section “Quality Requirements.”

B. Source Limitations: Obtain board fire-protection materials through one source from a single
manufacturer.

C. Installer Qualifications: A qualified firm specializing in performing the work of this Section
with minimum three years documented experience and that is approved, authorized, or
licensed by the product manufacturer to install his product and that is eligible to receive
manufacturer's warranty. Include project names and addresses, names and addresses of
engineers and employers, and other information specified

D. Fire-Test-Response Characteristics: Provide board fire protection with the fire-test-response


characteristics indicated, as determined by testing identical products per test method
indicated below by UL or another testing and inspecting agency acceptable to Engineer.
Identify materials with appropriate markings of applicable testing and inspecting agency.

1. Surface-Burning Characteristics: ASTM E 84.


2. Fire-Resistance Ratings: ASTM E 119.
3. Combustion Characteristics: ASTM E 136 or BS 476.
4. Fire-resistance-rated assemblies are indicated by design designations from UL's "Fire
Resistance Directory" or from the listings of another qualified testing and inspecting
agency.
5. Products are identified with appropriate markings of applicable testing and inspecting
agency.
6. Fire Resistance Rating: As indicated on Drawings but not less than 2 (Two) hours.

E. Mockups: Apply mockups to verify selections made under sample Submittals and to
demonstrate aesthetic effects and qualities of materials and execution and to set quality
standard for fabrication and installation.

1. Locations of Mockups: As indicated on Drawings.


2. Extent of Mockups: Approximately 9 sq. m of surface for each product indicated.
3. Approval of mockups does not constitute approval of deviations from the Contract
Documents contained in mockups unless such deviations are specifically approved by
Engineer in writing.
4. Approved mockups may become part of the completed Work if undisturbed at time of
Substantial Completion.

F. Preinstallation Conference: Conduct conference at Project site to comply with requirements


in Division 01 Section "Project Management and Coordination." Review methods and
procedures related to board fire protection including, but not limited to, the following:

1. Review structural load limitations.

BOARD FIREPROOFING 078200 - Page 2 of 5


REV 00
Alamein Downtown Towers

2. Review and finalize construction schedule and verify availability of materials,


Installer's personnel, equipment, and facilities needed to make progress and avoid
delays.

1.6 COORDINATION

A. Coordinate installation of board fire protection with other construction specified in other
Sections to comply with the following:

1. Avoid unnecessary exposure of board fire protection to abrasion and other damage
likely to occur during construction operations subsequent to its application.
2. Do not install board fire protection on structural members until piping and other
construction behind fire-resistive materials have been completed, uninterrupted
coverage of fire-resistive materials can be provided, and the need for subsequent
cutting and patching of fire-resistive materials has been eliminated.
3. Expedite installation of board fire protection to minimize the time structural members
are exposed without fire-resistive materials.
4. Do not install enclosing or concealing construction until after board fire protection
has been applied and inspected by Engineer.

1.7 WARRANTY

A. Comply with Division 01 Section "Warranties".

B. Special Warranty: Manufacturer's standard form, signed by Contractor and by Installer, in


which manufacturer agrees to repair or replace board fireproofing that fail in materials or
workmanship within specified warranty period.

1. Warranty Period: Five years from date of Substantial Completion.

PART 2 - PRODUCTS

2.1 COMPOSITE STEEL FACED FIBER REINFORCED CEMENT PANEL

A. Description: Non-combustible composite panel of fiber reinforced cement, mechanically


bonded to punched steel sheets on both surfaces board fire proofing classified as ‘non-
combustible’ to BS 476: Part 4 and A1 to BS EN 13501-1.

1. Features:

a. Up to 240 minutes fire resistance.


b. Non-combustible to Class A to ASTM E 84 or BS 476: Part 4 and Euroclass
A1 to Clause 10 of BS EN 13501.
c. Resists high thermal shock such as high pressure water hoses: Test to a 3 bar
pressure hose (ASTM E119).
d. Withstands demanding environments, temperature extremes and hostile
elements.
e. Highly impact and moisture resistant.
f. Minimal smoke or toxic Gas in a fire.
g. Slim, space-saving profile.
h. Lightweight.
i. Mechanical or seismic vibration resistant.

BOARD FIREPROOFING 078200 - Page 3 of 5


REV 00
Alamein Downtown Towers

j. Good acoustic insulation performance.

2. Typical Properties:

a. Thickness: 9.5 mm.


b. Length: 2000, 2500 mm.
c. Width: 1200 mm.
d. Weight: 21 kg/m2@ 6% moisture content.
e. Surface spread of flame to BS 476: Part 7: 1987: Class 1.
f. Average Dry Flexural Strength: 84 N/mm2.
g. Finish: Galvanized.

B. Framing System:

1. Manufacturer’s proprietary, tested fire rated suspension ceiling system complying


with requirements specified in this Section comprising the following:

a. Metal Stud Ceiling Lining: 150 x 60 x 3 mm or 80 x 60 x 3 mm (dependent on


span) cold rolled steel channels at 1200 mm centers fixed to structure with steel
drop rods at 1.5 m centers, diameter of rods shall be as recommended by
manufacturer for ceiling configuration and fire rating duration. Channel
noggings at 2500 mm centers fixed to main channels.
b. Fire rated ceiling panels shall be screwed to underside of framework at
nominal 250 mm centers along board edges.
c. Fire Resistance: 240 minutes (integrity only).
d. Estimated Sound Reduction: Rw 30 (dB).
e. Nominal Weight: 27 kg/m2.
f. Rockwool insulation boards of 80 mm thick and 140 kg/m 3 shall be fitted over
the ceiling panels with overlapping joints between rockwool panels of at least
150 mm.
g. All fixings shall be non-combustible, and listed in the approval documents.
Expansion bolts used to fix framework shall be steel.

C. Ancillary Materials:

1. Composite panel fire rated ceiling assemblies shall be provided as a complete tested
and approved assemblies comprising all necessary ancillary materials including but
not limited to fire rated silicone, Intumescent mastic, cold smoke seal and any
materials that were used in fire-resistance-rated tested assemblies.

D. Performances: To satisfy requirements indicated on or construed from Fire Safety Drawings


and Authorities Having Jurisdiction.

E. Reference Manufacturer: Promat Durasteel or equal and approved.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Comply with manufacturer's written instructions for particular conditions of installation in


each case.

B. The system shall only be installed by manufacturer’s trained specialist licensed installers.

BOARD FIREPROOFING 078200 - Page 4 of 5


REV 00
Alamein Downtown Towers

C. Install board fire proofing to comply with requirements for thicknesses, number of courses
(layers), construction of joints and corners, and anchorage methods applicable to fire-
resistance-rated assemblies indicated.

3.2 PROTECTION

A. Coordinate installation of board fire protection with other construction to minimize cutting
into, or removal of, installed fire-resistive materials. As other construction is successively
completed, replace or repair board fire protection that has been cut away to facilitate this
other construction. Maintain complete coverage of full thickness on members and substrates
protected by board fire protection.

B. Provide final protection and maintain conditions in a manner acceptable to Installer,


manufacturer, and Engineer that ensure that board fire protection is without damage or
deterioration at time of Substantial Completion.

END OF SECTION 078200