Structural Design Specs
Structural Design Specs
Structural Design Specs
LOCATION:Batan, Aklan
1.1.1 General
The purpose of this report is to document the basis of the Structural Design Criteria of the
Proposed Two-Storey Residential Building located in Batan, Aklan. Documented within this paper are the following:
The document provides a summary of the design concept criteria for the proposed structure to ensure that the
outcome of the design process is fit for the intended purpose.
The document is maintained with the latest information available for design analysis of the structure. The status
of each of the criteria is identified in the document. As design criteria are revised and/or confirmed, the document shall
be updated and re-issued accordingly.
1.1.2 Description
The proposed structure, in general, is conceived on the basis of conventional conventional Slab as Roofing
system with RC Beams and Concrete columns. The structural Design Criteria shall comply with the National Structural
Code of the Philippines, 2010 Edition, which is based on the internationally accepted codes, namely, UBC 1997 Code,
ACI 318-05, AISC, and ASCE 7-98. This design brief outlines the structural system, general structural analysis and
design methods.
The following Codes of Practice and Standards have been established to be appropriate for the proposed
structure:
I. GENERAL
A. Applicable Codes
A. Foundation System
The proposed structure will be designed complying with the NSCP 2010. The gross load bearing
capacity used is 120 Kpa. This shall provide sufficient support for the structure loading.
B. Framing System
The floor of the proposed structure will be supported by conventional reinforced concrete for foundation
and pedestal, RC for beams and columns and CONVENTIONAL CONCRETE for slab.
Foundation
i. Foundation f’c = 3,000.00 psi
ii. Slab on Grade f’c = 3,000.00 psi
Pedestals f’c = 3,000.00 psi
Slabs f’c = 3,000.00 psi
Masonry, Concrete blocks
Non-load bearing block fm’ = 650.00 psi
Load bearing block fm’ = 1,200.00 psi
Roof
Construction Dead Load
Slab - norrmal weight concrete 150.00 pcf
Wind Loads
Wind load for main structural elements shall be based on National Structural Code of the Philippines (NSCP) for
a basic wind velocity of 200 KPH in the absence of wind tunnel test results. The overall and interstory drift under wind
load will be limited to 0.0025H.
Figure 1: Wind Zone Map of the Philippines
Wind load will be calculated as per NSCP 2001:
Section 207: Wind Load
The structure is located at Zone II of the Wind Zone Map of the Philippines.
A basic wind speed (V) of 250 km/hr is to be considered.
Design wind pressure, p = q.GCp – qh.(GCpi)1.2
Where:
q = qz for windward wall at height z above ground,
qh for leeward wall, side walls and roof at mean roof height
G = given in Section 207.6.1 NSCP 2007
Cp = given in Figure 207-3 of NSCP 2007
GCpi = given in Table 207-4 of NSCP 2007
Velocity Pressure,qz = 47.3x10-6 Kz
Kzt V2
Iw
Kz = Refer to Table 207-3
Kzt = Refer to Section 207.5.5
V = in km/hr: Refer to Section 207.5.2
Iw = 1.0 (Special Occupancy)
Exposure Type B: Urban and suburban areas, wooded areas, or other terrain with numerous
closely spaced obstructions having the size of single-family dwellings or larger. Use of this
exposure category shall be limited to those areas for which terrain representative of Exposure B
prevails in the upwind direction for a distance of at least 0.5 km or 10 times the height of the
building or other structure, whichever is greater.
Internal Pressure Coefficients for Buildings, GCpi
The structure is located in typhoon-prone regions having a basic wind speed greater than or
equal to 250 km/hr
GCpi = +0.80
GCpi = -0.30
Load Combinations
1. Definitions:
D = Dead load
L = Live Load (net reduced live load after coefficient is applied), including roof live load
W = Wind load
E = Seismic load
H = loads due to weight and pressure of soil, water in soil, or other material.
UDSTL1 =D+L
UDSTL 2 = D + SDL + L
UDSTL 3 = D + SDL + 0.75(L+W)
UDSTL 4 = D + SDL + 0.75(L-W)
UDSTL 5 = D + SDL + W
UDSTL 6 = D + SDL – W
UDSTL 7 = 0.6D + 0.6SDL +W
UDSTL 8 = 0.6D + 0.6SDL –W
3. Concrete elements: factored loads and forces
The following combinations are from UBC-97:
U = 1.4D + 1.7L
U = 0.75 (1.4D + 1.7 L ± 1.7W)
U = 0.90D ± 1.3W
From UBC-97, Section 1612:
U = 1.2D + 1.0L ± 1.0E (for public assembly with LL > 4.9KPa and garages)
U = 1.2D + 0.5L ± 1.0E E = Eh + 0.20D
U = 0.9D ± 1.0E
V. Deflection Criteria
Lateral Deflection