Bartec Large Head 40mm

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Large Heads

Reference should be made to Dextra Manufacturing Design Guide, Methodology for Designing with Headed Reinforcement Anchors to Eurocode 2, Issue 2.
Input Data
Modify cells highlighted in green only

Nomimal Rebar Diameter (mm) 40


Rebar characteristic yield strength (Mpa) 500
Maximum aggregate size (mm) 20

Partial Factors of Safety:


γ c for Concrete 1.5 (EC2 Cl 2.4.2.4 The value of 1.5 is recomended in the core EC2 doc. )
γ s for Rebar 1.15 (EC2 Cl. 2.4.2.4 The value of 1.15 is recomended in the core EC2 doc.)

Coefficients:
αcc coefficient 1 (EC2 Cl. 3.1.6 The value of 1 is recommended in the core EC2 doc.)
αct coefficiant = 1 (EC2 Cl. 3.1.6 The valueof 1 is recommended in the core EC2 doc.)
n1 coefficient = 1 (EC2 Cl. 8.4.2 n1 = 1 for good bond conditions, n1 = 0.7 other cases)
n2 coefficient = 1
Bartec / Fortec Large Head
Head Data
Head Diameter, d HEAD = 130 mm d Head / d Bar = 3.25
Head thickness, t = 38 mm Area head / Area bar = 9.56

Head Capacity Check


For Full Capacity Head
Concrete f ck f cd σ sd d Head min. h min.
Grade (Mpa) (Mpa) (Mpa) (mm) (mm)
C20/25 20 13.3 137.8 259.8
C25/30 25 16.7 124.6 231.6
C30/37 30 20.0 114.9 210.6
C35/45 35 23.3 107.4 194.3
C40/50 40 26.7 101.5 181.1
C45/55 45 30.0 434.8 96.6 170.2
C50/60 50 33.3 92.5 160.9
C55/67 55 36.7 89.0 152.9
C60/75 60 40.0 86.0 145.9
C70/85 70 46.7 81.0 134.2
C80/95 80 53.3 77.1 124.7
Notes:
d Head min. in order to have a full capacity head
h min. for corresponding d Head min.
xxx Indicates that the actual head diameter is smaller than the minimum head diameter and therefore only partial head capacity can be utilised and rebar bond needs to be considered.
xxx Indicates that the actual head diameter is larger than the minimum head diameter.

Where d Head > d Head min. i.e. Full Head Bearing Capacity
Minimum Spacing Dimensions Confinment Rebar
Concrete f ck f cd σ sd X Rd h ab cb A B F2 A st min.
Grade (Mpa) (Mpa) (Mpa) (mm) (mm) (mm) (mm) (mm) (kN) (mm²)

C25/30 25 16.7 434.8 2.7 209.8 169.9 339.8 38 38 98.3 226.2


C30/37 30 20.0 434.8 2.3 154.0 142.0 284.0 38 38 98.3 226.2
C35/45 35 23.3 434.8 1.9 114.3 122.2 244.3 38 38 98.3 226.2
C40/50 40 26.7 434.8 1.7 84.7 107.3 214.7 38 38 98.3 226.2
C45/55 45 30.0 434.8 1.5 61.7 95.8 191.7 38 38 98.3 226.2
C50/60 50 33.3 434.8 1.4 43.4 86.7 173.4 38 38 98.3 226.2
C55/67 55 36.7 434.8 1.2 28.5 79.3 158.5 38 38 98.3 226.2
C60/75 60 40.0 434.8 1.1 16.2 73.1 146.2 38 38 98.3 226.2
C70/85 70 46.7 434.8 1.0 0.0 65.0 130.0 38 38 0.0 0.0
C80/95 80 53.3 434.8 1.0 0.0 65.0 130.0 38 38 0.0 0.0
Notes:
Ast should be distributed over the diverging stress region between 0.4h and h from the anchor head.

Arrangement to achieve full capacity, with minimum spacings

Notes:
For overlapping (staggered) heads, reference should be made to section 2.3.2 of the Design Guide
Minimum Spacings
Where d Head < d Head min. a contribution of rebar bond should be made
Minimum Spacing Dimensions Confinment Rebar Bond Contribution of Rebar
Concrete f ck f cd σ sd Head X Rd h ab cb A B F2 A st min. σ sd Bond f ctd* f bd l b,rqd l b,min l bd min**
Grade (Mpa) (Mpa) (Mpa) (mm) (mm) (mm) (mm) (mm) (kN) (mm²) (Mpa) (Mpa) (Mpa) (mm) (mm) (mm)
C20/25 20 13.3 382.5 3.0 243.2 186.6 373.2 38 38 86.5 226.2 52.3 1.0 2.25 232.4 400 400

Notes
*f ctd is limited to the value for C60/75
**Taken as the greater of l b,rqd and l b. α coeficients can be applied to l b as applicable in accordance with EC2 Cl.8.4.4. Thus l bd as tabulated is sometimes conservative.

Combined head anchorage and bond for Griptec heads