P3u en M I006 Iec Web
P3u en M I006 Iec Web
P3u en M I006 Iec Web
www.schneider-electric.com
Table of Contents Universal Relays P3U10, P3U20 and P3U30
Table of Contents
1 About this manual.........................................................................11
1.1 Purpose...........................................................................................................11
1.2 Related documents......................................................................................... 11
1.3 Abbreviations and terms................................................................................. 12
2 Product introduction..................................................................... 18
2.1 Warranty..........................................................................................................18
2.2 Product overview............................................................................................ 18
2.3 Product selection guide...................................................................................19
2.4 Access to device configuration....................................................................... 28
2.4.1 User accounts.......................................................................................28
2.4.2 Logging on via the front panel.............................................................. 28
2.4.3 HTTP and FTP logon details................................................................ 29
2.4.4 Password management........................................................................ 29
2.4.5 Password restoring............................................................................... 30
2.5 Front panel......................................................................................................31
2.5.1 Push-buttons.........................................................................................31
2.5.2 LED indicators...................................................................................... 32
2.5.3 Controlling the alarm screen.................................................................33
2.5.4 Accessing operating levels................................................................... 33
2.5.5 Adjusting the LCD contrast................................................................... 33
2.5.6 Testing the LEDs and LCD screen........................................................33
2.5.7 Controlling an object with selective control...........................................34
2.5.8 Controlling an object with direct control................................................ 34
2.5.9 Menus................................................................................................... 34
2.5.9.1 Moving in the menus .............................................................. 36
2.5.9.2 Local panel messages.............................................................37
2.6 Easergy Pro setting and configuration tool..................................................... 37
2.7 Low-power instrument transformers............................................................... 38
3 Measurement functions................................................................39
3.1 Primary, secondary and per unit scaling......................................................... 46
3.1.1 Frequency adaptation mode................................................................. 51
3.1.2 Current scaling......................................................................................52
3.1.3 Voltage scaling for analog module........................................................54
3.2 Measurements for protection functions...........................................................57
3.3 RMS values.....................................................................................................58
3.4 Harmonics and total harmonic distortion (THD)..............................................58
3.5 Demand values............................................................................................... 59
3.6 Minimum and maximum values...................................................................... 60
3.7 Maximum values of the last 31 days and 12 months...................................... 62
3.8 Memory management of measurements........................................................ 64
P3U/en M/I006 3
Universal Relays P3U10, P3U20 and P3U30 Table of Contents
4 Control functions.......................................................................... 68
4.1 Digital outputs................................................................................................. 68
4.2 Digital inputs................................................................................................... 70
4.3 Virtual inputs and outputs................................................................................74
4.4 Matrix.............................................................................................................. 80
4.4.1 Output matrix........................................................................................ 80
4.4.2 Blocking matrix..................................................................................... 81
4.4.3 Object block matrix............................................................................... 82
4.4.4 Auto-recloser matrix..............................................................................83
4.5 Releasing latches............................................................................................83
4.5.1 Releasing latches using Easergy Pro................................................... 83
4.5.2 Releasing latches using buttons and local panel display......................84
4.5.3 Releasing latches using F1 or F2 buttons............................................ 84
4.6 Controllable objects........................................................................................ 85
4.6.1 Object control with digital inputs........................................................... 86
4.6.2 Local or remote selection......................................................................86
4.6.3 Object control with I and O buttons.......................................................87
4.6.4 Object control with F1 and F2...............................................................87
4.7 Logic functions................................................................................................ 89
4.8 Local panel......................................................................................................96
4.8.1 Mimic view............................................................................................ 96
4.8.2 Local panel configuration......................................................................99
5 Protection functions....................................................................105
5.1 Current transformer requirements for overcurrent elements.........................105
5.1.1 CT requirements when settings are unknown.................................... 106
5.1.2 Principle for calculating the saturation current in class P................... 106
5.1.3 Examples of calculating the saturation current in class P...................106
5.1.4 Principle for calculating the saturation current in class PX................. 107
5.1.5 Examples of calculating the saturation current in class PX................ 108
5.2 Maximum number of protection stages in one application............................108
5.3 General features of protection stages...........................................................108
5.4 Application modes.........................................................................................115
5.5 Current protection function dependencies.................................................... 116
5.6 Dependent operate time................................................................................116
5.6.1 Standard dependent delays using IEC, IEEE, IEEE2 and RI curves.. 118
5.6.2 Free parameterization using IEC, IEEE and IEEE2 curves................ 139
5.6.3 Programmable dependent time curves...............................................140
5.7 Synchrocheck (ANSI 25)...............................................................................142
5.8 Undervoltage (ANSI 27)................................................................................146
5.9 Directional power (ANSI 32) ........................................................................ 149
5.10 Phase undercurrent (ANSI 37)....................................................................150
5.11 Broken conductor (ANSI 46BC) ................................................................. 151
5.12 Negative sequence overcurrent (ANSI 46) ................................................ 153
4 P3U/en M/I006
Table of Contents Universal Relays P3U10, P3U20 and P3U30
P3U/en M/I006 5
Universal Relays P3U10, P3U20 and P3U30 Table of Contents
9 Installation.................................................................................. 340
9.1 Checking the consignment............................................................................340
9.2 Product identification.....................................................................................340
9.3 Storage......................................................................................................... 341
9.4 Mounting....................................................................................................... 341
9.5 Connections.................................................................................................. 344
9.5.1 Rear panel.......................................................................................... 345
9.5.2 Auxiliary voltage..................................................................................360
9.5.3 Local port............................................................................................ 361
9.5.4 Connection data..................................................................................362
9.5.5 External option modules..................................................................... 370
9.5.5.1 VSE-001 fiber-optic interface module....................................370
6 P3U/en M/I006
Table of Contents Universal Relays P3U10, P3U20 and P3U30
11 Maintenance............................................................................. 426
11.1 Preventive maintenance..............................................................................426
11.2 Periodic testing............................................................................................427
11.3 Hardware cleaning...................................................................................... 427
11.4 System status messages............................................................................ 427
11.5 Spare parts..................................................................................................427
11.6 Self-supervision...........................................................................................427
11.6.1 Diagnostics........................................................................................428
13 Firmware revision.....................................................................434
P3U/en M/I006 7
Universal Relays P3U10, P3U20 and P3U30 Legal information
Legal information
The Schneider Electric brand and any registered trademarks of Schneider Electric
Industries SAS referred to in this guide are the sole property of Schneider Electric
SA and its subsidiaries. They may not be used for any purpose without the
owner's permission, given in writing. This guide and its content are protected,
within the meaning of the French intellectual property code (Code de la propriété
intellectuelle français, referred to hereafter as "the Code"), under the laws of
copyright covering texts, drawings and models, as well as by trademark law. You
agree not to reproduce, other than for your own personal, noncommercial use as
defined in the Code, all or part of this guide on any medium whatsoever without
Schneider Electric's permission, given in writing. You also agree not to establish
any hypertext links to this guide or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the guide or its
content, except for a non-exclusive license to consult it on an "as is" basis, at your
own risk. All other rights are reserved.
As standards, specifications and designs change from time to time, please ask for
confirmation of the information given in this publication.
8 P3U/en M/I006
Safety information Universal Relays P3U10, P3U20 and P3U30
Safety information
Important information
Read these instructions carefully and look at the equipment to become familiar
with the device before trying to install, operate, service or maintain it.
The following special messages may appear throughout this publication or on the
equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result
in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could
result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Please note
Protective grounding
The user is responsible for compliance with all the existing international and
national electrical codes concerning protective grounding of any device.
P3U/en M/I006 9
Universal Relays P3U10, P3U20 and P3U30 EU directive and UKCA regulations compliance
10 P3U/en M/I006
1 About this manual Universal Relays P3U10, P3U20 and P3U30
1.1 Purpose
This document contains instructions on the installation, commissioning and
operation of Easergy P3U10, P3U20 and P3U30.
This document is intended for persons who are experts on electrical power
engineering, and it covers the relay models as described by the order code.
Related topics
12.1 Order codes
Document Identification1)
P3U/en M/I006 11
Universal Relays P3U10, P3U20 and P3U30 1 About this manual
Document Identification1)
A standardization organization
CB Circuit breaker
CM Common mode
CT Current transformer
12 P3U/en M/I006
1 About this manual Universal Relays P3U10, P3U20 and P3U30
DI Digital input
DM Differential mode
DO Digital output
DT Definite time
Eth packets per second limit Use this to set the maximum transmitted
packet limit in each second by the Easergy
P3 device. The recommended setting is 75.
P3U/en M/I006 13
Universal Relays P3U10, P3U20 and P3U30 1 About this manual
IN Nominal current
An international standardization
organisation
14 P3U/en M/I006
1 About this manual Universal Relays P3U10, P3U20 and P3U30
P Active power
Unit = [W]
PF Power factor
P3U/en M/I006 15
Universal Relays P3U10, P3U20 and P3U30 1 About this manual
pu Per unit
Q Reactive power
Unit = [var]
RH Relative humidity
S Apparent power
Unit = [VA]
16 P3U/en M/I006
1 About this manual Universal Relays P3U10, P3U20 and P3U30
UN Nominal voltage
VI Virtual input
VO Virtual output
VT Voltage transformer
P3U/en M/I006 17
Universal Relays P3U10, P3U20 and P3U30 2 Product introduction
2 Product introduction
2.1 Warranty
This product has a standard warranty of 2 years.
Ask your local Schneider Electric representative about our optional 10-year
warranty. Local conditions and availability apply.
User interface
Easergy P3U10, P3U20 and P3U30 include all the essential protection functions
needed to protect feeders and motors in distribution networks of utilities, industry
and power plants for all level of voltage below 132 kV. Further, the relay includes
several programmable functions, such as trip circuit supervision and circuit
breaker protection and communication protocols for various protection and
communication situations.
Protection functions
Virtual injection
18 P3U/en M/I006
2 Product introduction Universal Relays P3U10, P3U20 and P3U30
Robust hardware
P3U/en M/I006 19
Universal Relays P3U10, P3U20 and P3U30 2 Product introduction
Table 3 - Applications
Voltage – – –
Feeder P3F30
w.
directional
–
P3L30
w. line diff. &
P3U30 distance
with
Transformer directional P3T32
o/c – with
P3U10 P3U20
with voltage differential
protection
Motor P3M32
P3M30 with
differential
Generator P3G32
P3G30 with
differential
Measuring Phase current 1/5A CT (x3) 1/5A CT (x3) or 1/5A CT (x3) or 1/5A CT (x6)
inputs LPCT (x3) LPCT (x3)2)
Output – 0 or 4 3) 0 or 4 3)
20 P3U/en M/I006
2 Product introduction Universal Relays P3U10, P3U20 and P3U30
Communication
IRIG/B ■ ■ ■
Ethernet – ■ ■ ■
IEC 60870-5-101 – ■ ■ ■ ■
IEC 60870-5-103 – ■ ■ ■ ■
DNP3 Over – ■ ■ ■ ■
Ethernet
Modbus serial – ■ ■ ■ ■
Modbus TCP/IP – ■ ■ ■ ■
Ethernet/IP – ■ ■ ■ ■
Profibus DP – ■ ■ ■ ■
SPAbus – ■ ■ ■ ■
Redundancy RSTP – ■ ■ ■ ■
protocols
PRP – ■ ■ ■ ■
Others
Logic Matrix ■ ■
Logic equations ■ ■
P3U/en M/I006 21
Universal Relays P3U10, P3U20 and P3U30 2 Product introduction
Withdrawability (Pluggable ■ –
connector)
Remote UMI – ■
NOTE: The numbers in the following tables represent the amount of stages
available for each Easergy P3 type.
Protection functions ANSI Feeder Feeder P3U30 Motor P3U10/20 Motor P3U30
code P3U10/20
Synchronization check5) 25 – 2 – 2
Undervoltage 27 – 3 – 3
Directional power 32 – 2 – 2
Phase undercurrent 37 1 1 1 1
Negative sequence 46 – – 2 2
overcurrent (motor,
generator)
Negative sequence 47 – 3 – 3
overvoltage protection
Thermal overload 49 1 1 1 1
SOTF 50HS 1 1 1 1
Voltage-dependent 51V – 1 – 1
overcurrent
Overvoltage 59 – 3 – 3
22 P3U/en M/I006
2 Product introduction Universal Relays P3U10, P3U20 and P3U30
Protection functions ANSI Feeder Feeder P3U30 Motor P3U10/20 Motor P3U30
code P3U10/20
CT supervision 60 1 1 1 1
VT supervision 60FL – 1 – 1
Directional phase 67 – 4 – 4
overcurrent
Auto-Recloser 79 5 5 – –
Lockout 86 1 1 1 1
Programmable stages 99 8 8 8 8
Programmable curves – 3 3 3 3
Setting groups 8) – 4 4 4 4
5) The availability depends on the selected voltage measurement mode (in the Scaling setting view in Easergy Pro)
6) Using external RTD module
7) Capacitor bank unbalance protection is connected to the earth fault overcurrent input and shares two stages with the earth fault
overcurrent protection.
8) Not all protection functions have 4 setting groups. See details in the manual.
Protection functions ANSI P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
code
Distance 21 – 1 – – – – –
Under-impedance 21G – – – – 2 2 –
Overfluxing 24 – – – – 1 1 1
Synchronization check9) 25 2 2 2 2 2 2 2
P3U/en M/I006 23
Universal Relays P3U10, P3U20 and P3U30 2 Product introduction
Protection functions ANSI P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
code
Undervoltage 27 3 3 3 3 3 3 3
Directional power 32 2 2 2 2 2 2 –
Phase undercurrent 37 – – 1 1 – – –
Loss of field 40 – – – – 1 1 –
Under-reactance 21/40 – – – – 2 2 –
Negative sequence 46 – – 2 2 2 2 2
overcurrent (motor,
generator)
Negative sequence 47 3 3 3 3 3 3 3
overvoltage protection
Thermal overload 49 1 1 1 1 1 1 1
SOTF 50HS 1 1 1 1 1 1 1
Voltage-dependent 51V 1 1 – – 1 1 –
overcurrent
Overvoltage 59 3 3 3 3 3 3 3
CT supervision 60 1 1 1 1 1 2 2
VT supervision 60FL 1 1 1 1 1 1 1
24 P3U/en M/I006
2 Product introduction Universal Relays P3U10, P3U20 and P3U30
Protection functions ANSI P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
code
Directional phase 67 4 4 4 4 4 4 4
overcurrent
Auto-Recloser 79 5 5 – – – – –
Over or under frequency 81 2/2 2/2 2/2 2/2 2/2 2/2 2/2
Lockout 86 1 1 1 1 1 1 1
Programmable stages 99 8 8 8 8 8 8 8
Programmable curves – 3 3 3 3 3 3 3
overcurrent protection.
12) Not all protection functions have 4 setting groups. See details in the manual.
P3U/en M/I006 25
Universal Relays P3U10, P3U20 and P3U30 2 Product introduction
Control functions P3U10/ P3U30 P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
20
Switchgear monitoring – – 2 2 2 2 2 2 2
only
Programmable switchgear ■ ■ ■ ■ ■ ■ ■ ■ ■
interlocking
Local/remote function ■ ■ ■ ■ ■ ■ ■ ■ ■
Function keys 2 2 2 2 2 2 2 2 2
Table 8 - Measurements
Measurement P3U10/ P3U30 P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
20
Frequency ■ ■ ■ ■ ■ ■ ■ ■ ■
Fundamental frequency – ■ ■ ■ ■ ■ ■ ■ ■
voltage values
Fundamental frequency – ■ ■ ■ ■ ■ ■ ■ ■
active, reactive and
apparent power values
Power factor – ■ ■ ■ ■ ■ ■ ■ ■
26 P3U/en M/I006
2 Product introduction Universal Relays P3U10, P3U20 and P3U30
Measurement P3U10/ P3U30 P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
20
Harmonic values of – ■ ■ ■ ■ ■ ■ ■ ■
voltage and THD
Logs and Records P3U10/ P3U30 P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
20
Disturbance record ■ ■ ■ ■ ■ ■ ■ ■ ■
P3U/en M/I006 27
Universal Relays P3U10, P3U20 and P3U30 2 Product introduction
P3U10/
Monitoring functions P3U30 P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
20
Relay monitoring ■ ■ ■ ■ ■ ■ ■ ■ ■
NOTE: To log on via the front panel, you need a password that consists of
letters, digits, or other characters in the scope of ASCII 0x21~0x7E.
1. Press and on the front panel. The Enter password view opens.
28 P3U/en M/I006
2 Product introduction Universal Relays P3U10, P3U20 and P3U30
Select a digit value using , and if the password is longer than one digit,
move to the next digit position using .
NOTE: There are 16 digit positions in the Enter password view. Enter the
password starting from the first digit position.
For example, if the password is 2, you can enter 2***, **2*, ***2, or 0002
to log on.
Related topics
2.4.4 Password management
You can log on to the HTTP server and FTP using these user names and
passwords.
HTTP conf 2
FTP conf 2
NOTICE
CYBERSECURITY HAZARD
To improve cybersecurity:
• Change all passwords from their default values when taking the protection
device into use.
• Change all passwords regularly.
• Ensure a minimum level of password complexity according to common
password guidelines.
P3U/en M/I006 29
Universal Relays P3U10, P3U20 and P3U30 2 Product introduction
You can change the password for the operator or configurator user accounts in
the General > Device info setting view in Easergy Pro.
The password can contain letters, digits or other characters in the scope of ASCII
0x21~0x7E. However, the new password cannot be any of the default passwords
(digits 0–4 or 9999).
Follow these guidelines to improve the password complexity and thus device
security:
• Use a password of minimum 8 characters.
• Use alphabetic (uppercase and lowercase) and numeric characters in addition
to symbols.
• Avoid character repetition, number or letter sequences and keyboard patterns.
• Do not use any personal information, such as birthday, name, etc.
• Do not use the same password for different user accounts.
• Do not reuse old passwords.
Also, all users must be aware of the best practices concerning passwords
including:
• not sharing personal passwords
• not displaying passwords during password entry
• not transmitting passwords in email or by other means
• not saving the passwords on PCs or other devices
• no written passwords on any supports
• regularly reminding users about the best practices concerning passwords
Related topics
2.4.2 Logging on via the front panel
If you have lost or forgotten all passwords, contact Schneider Electric to restore
the default passwords.
30 P3U/en M/I006
2 Product introduction Universal Relays P3U10, P3U20 and P3U30
G
B E
2.5.1 Push-buttons
Symbol Function
P3U/en M/I006 31
Universal Relays P3U10, P3U20 and P3U30 2 Product introduction
Symbol Function
14) The default names of the function buttons are Function button 1 and 2. You can change the names
of the buttons in the Control > Names for function buttons setting view.
When the relay is powered, the power LED is green. During normal use, the
service LED is not active, it activates only when an error occurs or the relay is not
operating correctly. Should this happen, contact your local representative for
further guidance. The service LED and watchdog contact are assigned to work
together. Hardwire the status output into the substation's automation system for
alarm purposes.
To customize the LED texts on the front panel for the user-configurable LEDs, the
text may be created using a template and then printed. The printed text may be
placed in the pockets beside the LEDs.
You can also customize the LED texts that are shown on the screen for active
LEDs via Easergy Pro.
32 P3U/en M/I006
2 Product introduction Universal Relays P3U10, P3U20 and P3U30
You can enable or disable the alarm screen either via the relay's local display or
using Easergy Pro:
NOTE: By nature, the LCD display changes its contrast depending on the
ambient temperature. The display may become dark or unreadable at low
temperatures. However, this condition does not affect the proper operation of
the protection or other functions.
You can start the test sequence in any main menu window.
1. Press .
2. Press .
P3U/en M/I006 33
Universal Relays P3U10, P3U20 and P3U30 2 Product introduction
The relay tests the LCD screen and the functionality of all LEDs.
Prerequisite: You have logged in with the correct password and enabled selective
control in the Objects setting view.
– Press to cancel.
• Press to open an object.
– Press to cancel.
Prerequisite: You have logged in with the correct password and enabled direct
control in the Objects setting view.
When direct control is enabled, the control operation is done without confirmation.
• Press to close an object.
• Press to open an object.
2.5.9 Menus
This section gives an overview of the menus that you can access via the device's
front panel.
Press the right arrow to access more measurements in the main menu.
34 P3U/en M/I006
2 Product introduction Universal Relays P3U10, P3U20 and P3U30
P3U/en M/I006 35
Universal Relays P3U10, P3U20 and P3U30 2 Product introduction
OK
ISTART setting
OK OK
36 P3U/en M/I006
2 Product introduction Universal Relays P3U10, P3U20 and P3U30
• To go back to the first menu item in the main menu, press for at least three
seconds.
NOTE: To enter the parameter edit mode, enter the password. When the
value is in edit mode, its background is dark.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC
FLASH
• General
• Measurements
• Inputs/outputs
• Protection
• Matrix
• Logs
• Communication
The contents of the tabs depend on the relay type and the selected application
mode.
Easergy Pro stores the relay configuration in a setting file. The configuration of
one physical relay is saved in one setting file. The configurations can be printed
out and saved for later use.
P3U/en M/I006 37
Universal Relays P3U10, P3U20 and P3U30 2 Product introduction
NOTICE
HAZARD OF EQUIPMENT DAMAGE
Using LPITs has many benefits compared to using tranditional CTs or VTs:
• improved personal safety during testing and operation
• one LPCT replaces the dedicated measurement CTs and protection CTs
• the LPCT primary rating is no longer to be as close as possible to the nominal
current
• time and money savings during project planning and execution
• reduced environmental impact because of reduced instrument transformer
size
LPITs compliant with the standards IEC 60044 and IEC 61869 can be connected
to the LPIT inputs of Easergy P3 devices.
38 P3U/en M/I006
3 Measurement functions Universal Relays P3U10, P3U20 and P3U30
3 Measurement functions
Easergy P3 has various amounts of analog inputs depending on the model in use.
Table 16 introduces directly measured and calculated quantities for the power
system monitoring. Also see 2.3 Product selection guide.
The relay has two operational modes: feeder and motor. In the feeder mode, the
secondary currents are proportional to the CT primary values whereas in the
motor mode, all protection stages use the motor's nominal current values.
±3 % for range
0.1–0.3xPN
±3 % for range
0.1–0.3xQN
±3 % for range
0.1–0.3xSN
P3U/en M/I006 39
Universal Relays P3U10, P3U20 and P3U30 3 Measurement functions
I > 1.5 x IN ±3 % of
value
40 P3U/en M/I006
3 Measurement functions Universal Relays P3U10, P3U20 and P3U30
±3 % for range
0.1–0.3xPN
±3 % for range
0.1-0.3xQN
±3 % for range
0.1–0.3xSN
P3U/en M/I006 41
Universal Relays P3U10, P3U20 and P3U30 3 Measurement functions
I > 1.5 x IN ±3 % of
value
42 P3U/en M/I006
3 Measurement functions Universal Relays P3U10, P3U20 and P3U30
±3 % for range
0.1–0.3xPN
±3 % for range
0.1–0.3xQN
±3 % for range
0.1–0.3xSN
P3U/en M/I006 43
Universal Relays P3U10, P3U20 and P3U30 3 Measurement functions
I > 1.5 x IN ±3 % of
value
±3 % for range
0.1–0.3xPN
±3 % for range
0.1–0.3xQN
±3 % for range
0.1–0.3xSN
44 P3U/en M/I006
3 Measurement functions Universal Relays P3U10, P3U20 and P3U30
I > 1.5 x IN ±3 % of
value
P3U/en M/I006 45
Universal Relays P3U10, P3U20 and P3U30 3 Measurement functions
The scaling is done using the rated values of VTs and CTs or LPVTs and LPCTs
depending on the selected model order option.
Scaling settings
Parameter Description
Nominal input (IL Rated value of the phase current input. The given thermal
side) withstand, burden and impedance are based on this value.
46 P3U/en M/I006
3 Measurement functions Universal Relays P3U10, P3U20 and P3U30
Parameter Description
I01 CT primary Primary current value of the earth fault I01 overcurrent transformer
I01 CT secondary Secondary current value of the earth fault I01 overcurrent
transformer
Nominal I01 input Selectable nominal input rating for the earth fault overcurrent
input. Select either 5A or 1A depending on which Io input is used.
The given thermal withstand, burden and impedance are based
on this value.
Frequency adaptation Parameter used to set the system frequency. There are three
mode modes available: manual, auto and fixed. For more information,
see 3.1.1 Frequency adaptation mode.
Adapted frequency When the frequency adaption mode is set to manual, you can set
the frequency in the Adapted frequency field, and it is not be
updated even if the measured frequency is different.
Angle memory Time setting for the directional overcurrent stage to keep the
duration phase angle fixed if the system voltage collapses
Table 19 - Phase current and earth fault overcurrent scaling parameters – LPIT
P3U/en M/I006 47
Universal Relays P3U10, P3U20 and P3U30 3 Measurement functions
LPVT rated primary All measurements are scaled by the 50–500 000 V
voltage LPVT rated primary voltage and LPVT
rated secondary voltage setting.
48 P3U/en M/I006
3 Measurement functions Universal Relays P3U10, P3U20 and P3U30
Nominal I01 input Selectable nominal input rating for the 1.0 A / 5.0 A
earth fault overcurrent input. Select
either 5 A or 1 A depending on which I0
input is used. The given thermal
withstand, burden and impedance are
based on this value.
Nominal I02 input Selectable nominal input rating for the 0.2 A / 1.0 A
earth fault overcurrent input. Select
either 1 A or 0.2 A depending on which
I0 input is used. The given thermal
withstand, burden and impedance are
based on this value.
Voltage The device can be connected either to U0, 3LN, 3LN/LNy, 3LN
measurement mode zero-sequence voltage or line-to-neutral +Uo, LN+U0/y/z
voltage. Set the voltage measurement
mode according to the type of
connection used.
P3U/en M/I006 49
Universal Relays P3U10, P3U20 and P3U30 3 Measurement functions
50 P3U/en M/I006
3 Measurement functions Universal Relays P3U10, P3U20 and P3U30
The scaling equations presented in 3.1.2 Current scaling and 3.1.3 Voltage
scaling for analog module are useful when doing secondary testing.
You can set the system frequency in General > Scaling in Easergy Pro.
• Manual: When the adaption mode is set to manual, you can set the frequency
in the Adapted frequency field, and it will not be updated even if the
measured frequency is different. However, the relay monitors the system
P3U/en M/I006 51
Universal Relays P3U10, P3U20 and P3U30 3 Measurement functions
frequency internally and adapts to the new frequency even if the frequency
has been set manually.
• Auto: The network frequency is automatically updated when the relay has
measured the voltage for approximately 45 seconds. The Adapted frequency
field is updated even if it has been set previously. The frequency is measured
from the voltage signals.
LN+U0/y/z UL1 U1
In P310 and P320 relays, the frequency adaptation is taken from the
measured currents.
• Fixed: The frequency is not updated based on the measured voltage and only
the set value is used. This mode is recommended to be used for the line-
differential function.
NOTE: The rated value of the relay's current input, for example 5 A or 1 A,
does not have any effect on the scaling equations, but it defines the
measurement range and the maximum allowed continuous current. See Table
143 for details.
Current (CT)
primary → secondary
CTSEC
I SEC = I PRI ⋅
CTPRI
For earth fault overcurrent to input I0, use the corresponding CTPRI and CTSEC
values. For earth fault stages using I0 Calc signals, use the phase current CT
values for CTPRI and CTSEC.
Examples
1. Secondary to primary
52 P3U/en M/I006
3 Measurement functions Universal Relays P3U10, P3U20 and P3U30
CT = 500 / 5
Current to the relay's input is 4 A.
=> Primary current is IPRI = 4 x 500 / 5 = 400 A
2. Primary to secondary
CT = 500 / 5
The relay displays IPRI = 400 A
=> Injected current is ISEC = 400 x 5 / 500 = 4 A
1 pu = 1 x IMODE = 100%, where IMODE is the rated current according to the mode.
See 1.3 Abbreviations and terms.
Examples
CT = 750 / 5
Current injected to the relay's inputs is 7 A.
Per unit current is IPU = 7 / 5 = 1.4 pu = 140%
CT = 750/5
IN or IMOT = 525 A
Current injected to the relay's inputs is 7 A.
Per unit current is IPU = 7 x 750 / (5 x 525) = 2.00 pu = 2.00 x (IN or I MOT )
= 200%
CT = 750 / 5
The relay setting is 2 pu = 200%.
Secondary current is ISEC = 2 x 5 = 10 A
CT = 750 / 5
IN or IMOT = 525 A
P3U/en M/I006 53
Universal Relays P3U10, P3U20 and P3U30 3 Measurement functions
Input is I0.
CT0 = 50 / 1
Current injected to the relay's input is 30 mA.
Per unit current is IPU = 0.03 / 1 = 0.03 pu = 3%
Input is I0.
CT0 = 50 / 1
The relay setting is 0.03 pu = 3%.
Secondary current is ISEC = 0.03 x 1 = 30 mA
Input is I0 Calc.
CT = 750 / 5
Currents injected to the relay's IL1 input is 0.5 A.
IL2 = IL3 = 0.
Per unit current is IPU = 0.5 / 5 = 0.1 pu = 10%
Input is I0 Calc.
CT = 750 / 5
The relay setting is 0.1 pu = 10%.
If IL2 = IL3 = 0, then secondary current to IL1 is ISEC = 0.1 x 5 = 0.5 A
54 P3U/en M/I006
3 Measurement functions Universal Relays P3U10, P3U20 and P3U30
primary → VTSEC U VT
U SEC = U PRI ⋅ U SEC = PRI ⋅ SEC
secondary VTPRI 3 VTPRI
Examples
VT = 12000/110
Voltage connected to the relay's input UA or UB is 100 V.
=> Primary voltage is UPRI = 100x12000/110 = 10909 V.
VT = 12000/110
Three phase symmetric voltages connected to the relay's inputs UA, UB
and UC are 57.7 V.
=> Primary voltage is UPRI = √3 x58x12000/110 = 10902 V
VT = 12000/110
The relay displays UPRI = 10910 V.
=> Secondary voltage is USEC = 10910x110/12000 = 100 V
VT = 12000/110
The relay displays U12 = U23 = U31 = 10910 V.
=> Symmetric secondary voltages at UA, UB and UC are USEC = 10910/√3
x110/12000 = 57.7 V.
P3U/en M/I006 55
Universal Relays P3U10, P3U20 and P3U30 3 Measurement functions
Examples
VT = 12000/110
Voltage connected to the relay's input UA or UB is 110 V.
=> Per unit voltage is UPU = 110/110 = 1.00 pu = 1.00 x UN = 100%
VT = 12000/110
Three symmetric phase-to-neutral voltages connected to the relay's inputs
UA, UB and UC are 63.5 V
=> Per unit voltage is UPU = √3 x63.5/110x12000/11000 = 1.00 pu = 1.00 x
UN = 100%
VT = 12000/110
The relay displays 1.00 pu = 100%.
=> Secondary voltage is USEC = 1.00 x 110 x 11000/12000 = 100.8 V
VT = 12000/110
UN = 11000 V
The relay displays 1.00 pu = 100%.
=> Three symmetric phase-to-neutral voltages connected to the relay 's
inputs UA,UB and UC are USEC = 1.00 x 110/√3 x 11000/12000 = 58.2 V
56 P3U/en M/I006
3 Measurement functions Universal Relays P3U10, P3U20 and P3U30
U 0 SEC VTSEC 3
Examples
VT = 12000/110
Voltage connected to the relay's input UA is 38.1 V, while UA = UB = 0.
=> Per unit voltage is UPU = (38.1+0+0)/(√3 x110) = 0.20 pu = 20%
VT = 12000/110
The relay displays U0 = 20%.
=> If UB = UC = 0, then secondary voltages at UA is USEC = √3 x0.2x110 =
38.1 V
P3U/en M/I006 57
Universal Relays P3U10, P3U20 and P3U30 3 Measurement functions
Load = 0%
100
-5
IL2
-10
All the direct measurements and most protection functions are based on
fundamental frequency values.
The relay calculates the RMS value of each phase current. The minimum and
maximum RMS values are recorded and stored (see 3.6 Minimum and maximum
values).
I RMS = I f 1 + I f 2 + ... + I f 15
2 2 2
RMS voltages
The relay calculates the RMS value of each voltage input. The minimum and the
maximum of RMS values are recorded and stored (see 3.6 Minimum and
maximum values).
U RMS = U f 1 + U f 2 + ... + U f 15
2 2 2
58 P3U/en M/I006
3 Measurement functions Universal Relays P3U10, P3U20 and P3U30
Equation 1
15
∑f
i =2
i
2
THD =
h1
f1 = Fundamental value
f2– 15 = Harmonics
Example
f1 = 100 A, f3 = 10 A, f7 = 3 A, f11 = 8 A
10 2 + 3 2 + 8 2
THD = = 13.2%
100
For reference, the RMS value is:
P3U/en M/I006 59
Universal Relays P3U10, P3U20 and P3U30 3 Measurement functions
RMS values
60 P3U/en M/I006
3 Measurement functions Universal Relays P3U10, P3U20 and P3U30
IL1 RMS, IL2 RMS, IL3 RMS Phase current, RMS value
f Frequency
P3U/en M/I006 61
Universal Relays P3U10, P3U20 and P3U30 3 Measurement functions
Table 27 - Parameters
NOTE: The saving process starts every 30 minutes and it takes a while. If the
relay's auxiliary supply power is switched off before all values have been
saved, the old values remain for the unsaved ones.
Corresponding time stamps are stored for the last 31 days. The registered values
are listed in Table 28.
62 P3U/en M/I006
3 Measurement functions Universal Relays P3U10, P3U20 and P3U30
I0 X Earth fault
overcurrent
S X Apparent X X
power
P X X Active power X X
Q X X Reactive X X
power
The timebase can be a value from one cycle to one minute. Also a demand value
can be used as the timebase and its value can be set between 10 and 60
minutes. The demand value menu is located under the Measurements view.
Table 29 - Parameters of the day and month registers
P3U/en M/I006 63
Universal Relays P3U10, P3U20 and P3U30 3 Measurement functions
Frequency x
64 P3U/en M/I006
3 Measurement functions Universal Relays P3U10, P3U20 and P3U30
Power factor x
Active energy x
Reactive energy x
P3U/en M/I006 65
Universal Relays P3U10, P3U20 and P3U30 3 Measurement functions
Events x x
Disturbance record x x
+90°
II I
ind +cap
cos = cos = +
PF = + PF =
V REF 0°
III I IV
cap +ind
cos = cos = +
PF = PF = +
Q
+90°
II cap +ind I
cos = cos = +
PF = PF = +
S
P 0°
III IV
ind +cap
cos = cos = +
PF = + PF =
66 P3U/en M/I006
3 Measurement functions Universal Relays P3U10, P3U20 and P3U30
• Positive sequence 1
• Negative sequence 2
• Zero sequence 0
S 0 1 1 1 S A
S = 1 1 a a S B
2
1 3
S 2 1 a 2 a S C
1 3
a = 1∠120° = − + j
2 2
, a phase rotating constant
P3U/en M/I006 67
Universal Relays P3U10, P3U20 and P3U30 4 Control functions
4 Control functions
Any internal signal can be connected to the digital outputs in the Matrix > Output
matrix setting view. A digital output can be configured as latched or non-latched.
The digital output connections are configured either through the Easergy Pro
setting tool or the relay's menus. Horizontal lines represent inputs and vertical
lines outputs. When the crossing line of the horizontal input signal and vertical
output line is touched, the connection changes in the following sequence:
The position of the contact can be checked in the Output matrix and Relays
setting views. A digital output can be configured as latched or non-latched.
Latched relay contacts can be set free by pressing the “enter” key of the relay or
by releasing from the Easergy Pro setting tool.
The difference between trip contacts and signal contacts is the DC breaking
capacity. The contacts are single pole single throw (SPST) normal open (NO)
type, except signal relay A1 which has a changeover contact single pole double
throw (SPDT).
Programming matrix
68 P3U/en M/I006
4 Control functions Universal Relays P3U10, P3U20 and P3U30
NOTE: Logic outputs are assigned automatically in the output matrix as well
when logic is built.
Trip contact status can be viewed and forced to operate in the Relays setting
view.
Power supply card outputs are not visible in the Relay config setting view.
P3U/en M/I006 69
Universal Relays P3U10, P3U20 and P3U30 4 Control functions
The polarity normal open (NO) / normal closed (NC) and a delay can be
configured according to the application by using the front panel or Easergy Pro.
Digital inputs can be used in many operations. The status of the input can be
checked in the Output matrix and Digital inputs setting views. The digital inputs
make it possible to change group, block/enable/disable functions, to program
logics, indicate object status, etc.
The digital inputs require an external control voltage (ac or dc). The digital inputs
are activated after the activation voltage is exceeded. Deactivation follows when
the voltage drops below threshold limit.
Digital inputs can be connected, latched or unlatched to trip contacts or other
similar purpose in Output matrix setting view.
70 P3U/en M/I006
4 Control functions Universal Relays P3U10, P3U20 and P3U30
Digital inputs can be viewed, named and changed between NO/NC in the Digital
inputs and Names for digital inputs setting views.
P3U/en M/I006 71
Universal Relays P3U10, P3U20 and P3U30 4 Control functions
All essential information on digital inputs can be found in the same location in the
Digital inputs setting view. DI on/off events and alarm display (pop-up) can be
enabled and disabled in Digital inputs setting view. Individual operation counters
are located in the same view as well.
Label and description texts can be edited with Easergy Pro according to the
demand. Labels are the short parameter names used on the local panel and
descriptions are the longer names used by Easergy Pro.
Digital input delay determines the activation and de-activation delay for the input.
Figure 20shows how the digital input behaves when the delay is set to 1 second.
1
VOLTAGE
0
1
DIGITAL INPUT
0
Input Number of
DI1 – DI16
digital input.
72 P3U/en M/I006
4 Control functions Universal Relays P3U10, P3U20 and P3U30
For normal
closed contacts
(NC)
Active edge is 1
>0
P3U/en M/I006 73
Universal Relays P3U10, P3U20 and P3U30 4 Control functions
Default is "DI1 –
DIx". x is the
maximum
number of the
digital input.
x is the
maximum
number of the
digital input.
23) Set = An editable parameter (password needed).
Virtual inputs can be used in many operations. The status of the input can be
checked in the Matrix > Output matrix and Control > Virtual inputs setting
views. The status is also visible on local mimic display, if so selected. Virtual
inputs can be selected to be operated with the function buttons F1 and F2, the
local mimic or simply by using the virtual input menu. Virtual inputs have similar
functions as digital inputs: they enable changing groups, block/enable/disable
functions, to program logics and other similar to digital inputs.
Number of outputs 20
Virtual inputs and outputs can be used for many purposes in the Output matrix
setting view.
74 P3U/en M/I006
4 Control functions Universal Relays P3U10, P3U20 and P3U30
Virtual inputs
The virtual inputs can be viewed, named and controlled in the Control > Virtual
inputs setting view.
P3U/en M/I006 75
Universal Relays P3U10, P3U20 and P3U30 4 Control functions
76 P3U/en M/I006
4 Control functions Universal Relays P3U10, P3U20 and P3U30
Off
Default is "VIn",
n = 1–20
P3U/en M/I006 77
Universal Relays P3U10, P3U20 and P3U30 4 Control functions
Virtual outputs
In Easergy Pro, the Virtual outputs setting view is located under Control.
78 P3U/en M/I006
4 Control functions Universal Relays P3U10, P3U20 and P3U30
Off
P3U/en M/I006 79
Universal Relays P3U10, P3U20 and P3U30 4 Control functions
4.4 Matrix
The relay has several matrices that are used for configuring the relay:
• Output matrix used to link protection stage signals, digital inputs, virtual
inputs, function buttons, object control, logic output, relay's internal alarms,
GOOSE signals and release latch signals to outputs, disturbance recorder trig
input and virtual outputs
• Block matrix used to block protection stages
• Object block matrix used to inhibit object control
• Auto-recloser matrix used to control auto-recloser
• Arc matrix used to control current and light signals to arc stages and arc
stages to the high-speed outputs
Virtual
inputs
Digital n
inputs
n Output relays Virtual
optional
DI delay and indicators outputs
n
and
inversion n
Output contacts
With the output matrix, the output signals of the various protection stages, digital
inputs, logic outputs and other internal signals can be connected to the digital
outputs, virtual outputs and so on.
There are general-purpose LED indicators – "A", "B", "C" to ”H” – available for
customer-specific indications on the front panel. Their usage is define in a
separate output matrix.
There are two LED indicators specified for keys F1 and F2. The triggering of the
disturbance recorder (DR) and virtual outputs are configurable in the output
matrix.
There is a common "release all latches" signal to release all the latched relays.
This release signal resets all the latched digital outputs and indicators. The reset
signal can be given via a digital input, via front panel or remotely through
80 P3U/en M/I006
4 Control functions Universal Relays P3U10, P3U20 and P3U30
Trip and alarm relays together with virtual outputs can be assigned in the output
matrix. Also automatic triggering of disturbance recorder is done in the output
matrix.
The Blocked status becomes visible only when the stage is about to activate.
P3U/en M/I006 81
Universal Relays P3U10, P3U20 and P3U30 4 Control functions
Figure 31 - Result for the I> stage when the DI is active and the stage exceeds its
current start value
NOTICE
RISK OF NUISANCE TRIPPING
The object block matrix is used to link digital inputs, virtual inputs, function
buttons, protection stage outputs, logic outputs, alarm signals and GOOSE
signals to inhibit the control of objects, that is, circuit breakers, isolators and
earthing switches.
Typical signals to inhibit controlling of the objects like circuit breaker are:
• protection stage activation
• statuses of other objects
• interlocking made with logic
• GOOSE signals
82 P3U/en M/I006
4 Control functions Universal Relays P3U10, P3U20 and P3U30
These and other signals are linked to objects in the object block matrix.
There are also event-type signals that do not block objects as they are on only for
a short time, for example "Object1" open and "Object1 close" signals.
The auto-recloser matrix is used to link digital inputs, virtual inputs, protection
stage outputs, object statuses, logic outputs, alarm signals and GOOSE signals to
control the auto-recloser. For more information, see 5.35 Auto-recloser function
(ANSI 79).
2. From the Easergy Pro toolbar, select Device > Release all latches.
Alternatively, go to Control > Release latches, and click the Release button.
P3U/en M/I006 83
Universal Relays P3U10, P3U20 and P3U30 4 Control functions
1. Press .
2. Press .
You can use the function buttons F1 or F2 to release all latches after configuring
this function in Easergy Pro.
After this, pressing the F1 button on the relay’s front panel releases all
latches.
NOTE: The latch release signal can be activated only if the latched
output is active.
84 P3U/en M/I006
4 Control functions Universal Relays P3U10, P3U20 and P3U30
Object states
Open
Close
Undefined (11)
Max ctrl pulse length 0.02–600 s Pulse length for open and
close commands. Control
pulse stops once object
changes its state
P3U/en M/I006 85
Universal Relays P3U10, P3U20 and P3U30 4 Control functions
If changing the states takes longer than the time defined by the “Max ctrl pulse
length” setting, the object is inoperative and the “Object failure” matrix signal is
set. Also, an undefined event is generated. “Completion timeout” is only used for
the ready indication. If “DI for ‘obj ready’” is not set, the completion timeout has no
meaning.
These signals send control pulse when an object is controlled by digital input,
remote bus, auto-reclose etc.
Objects can be controlled with digital inputs, virtual inputs or virtual outputs. There
are four settings for each object:
Setting Active
If the relay is in local control state, the remote control inputs are ignored and vice
versa. An object is controlled when a rising edge is detected from the selected
input. The length of digital input pulse should be at least 60 ms.
In local mode, digital outputs can be controlled via the front panel but they cannot
be controlled via a remote serial communication interface.
In remote mode, digital outputs cannot be controlled via a front panel but they can
be controlled via a remote serial communication interface.
The local or remote mode can be selected by using the front panel or via one
selectable digital input. The digital input is normally used to change a whole
station to local or remote mode. You can select the L/R digital input in the Control
> Objects setting view in Easergy Pro.
86 P3U/en M/I006
4 Control functions Universal Relays P3U10, P3U20 and P3U30
The relay also has dedicated control buttons for objects. (I) stands for object
closing and (O) controls object open command internally. Control buttons are
configured in the Control > Objects setting view.
Button
opens selected
object if
password is
enabled
Control
operation is
done without
confirmation
P3U/en M/I006 87
Universal Relays P3U10, P3U20 and P3U30 4 Control functions
You can configure the button funtions in the Control > Function buttons setting
view in Easergy Pro.
If ObjCtrl has been selected under Selected control, the selected object is
shown under Selected object. Otherwise, this column is empty.
When selecting ObjCtrl, link the function button to the appropriate object in the
Control > Objects setting view.
88 P3U/en M/I006
4 Control functions Universal Relays P3U10, P3U20 and P3U30
Logic functions No. of gates Max. no. of input Max. no. of logic
reserved gates outputs
AND 1
OR 1
XOR 1
AND+OR 2
32
CT (Count+Reset) 2
(An input gate can 20
INVAND 2
include any number
INVOR 2 of inputs.)
OR+AND 2
RS (Reset+Set) 2
The logic is operational as long the memory consumption of the inputs, gates or
outputs remains individually below or equal to 100%.
P3U/en M/I006 89
Universal Relays P3U10, P3U20 and P3U30 4 Control functions
Truth tables
AND In Out
A Y
0 0
1 1
In Out
A Y
0 1
1 0
In Out
A B Y
0 1 0
1 0 0
1 1 1
0 0 0
In Out
A B Y
0 1 1
1 0 1
1 1 0
0 0 1
AND+OR In Out
A B Y
0 0 0
1 1 1
1 0 1
0 1 1
90 P3U/en M/I006
4 Control functions Universal Relays P3U10, P3U20 and P3U30
CT (Count+Reset) In Out
A B Y Y
1 3 0
1 3 0
1 3 1
1 3 0
INVAND In Out
A B Y
0 0 0
1 0 1
1 1 0
0 1 0
INVOR In Out
A B Y
0 0 1
1 1 1
1 0 1
0 1 0
P3U/en M/I006 91
Universal Relays P3U10, P3U20 and P3U30 4 Control functions
OR In Out
A B Y
0 0 0
1 1 1
1 0 1
0 1 1
In Out
A B Y
0 0 1
1 1 0
1 0 0
0 1 0
In Out
A B C Y
0 0 0 1
1 1 0 1
1 0 0 1
0 1 0 1
1 1 1 1
In Out
A B C Y
0 0 0 1
1 0 0 0
1 1 0 0
0 1 0 0
1 1 1 0
92 P3U/en M/I006
4 Control functions Universal Relays P3U10, P3U20 and P3U30
OR+AND In Out
A B Y
0 0 0
1 1 1
1 0 0
0 1 0
RS (Reset+Set) In Out
A B Y
Set Reset Y
1 0 1
0 0 128)
0 0 029)
X 1 030)
28) Output = 1 (latched), if
previous state was 1, 0, 1.
29) Output = 0, if previous state
was X, 1, 0.
30) Output = 0, if RESET = 1
P3U/en M/I006 93
Universal Relays P3U10, P3U20 and P3U30 4 Control functions
RS_D (Set+D+Load+Reset) A B C D Y
0 0 0 0 031)
1 X X 0 1
1 X X 1 0
0 1 0 0 0
0 1 1 0 1
0 1 1 1 032)
31) Initial
state
32) Thestate remains 1 until
Reset is set active
X = Any state
XOR In Out
A B C Y
0 0 0 0
0 0 1 1
0 1 0 1
0 1 1 0
1 0 0 1
1 0 1 0
1 1 0 0
1 1 1 1
After you have selected the required logic gate in Easergy Pro, you can change
the function of the gate in the Element properties window by clicking the gate.
94 P3U/en M/I006
4 Control functions Universal Relays P3U10, P3U20 and P3U30
Table 42 - Settings available for the logical gates depending on the selected
element
Property Description
Element properties
OFF delay Time delay for how long the gate remain
active even the logical condition is reset
Inputs
P3U/en M/I006 95
Universal Relays P3U10, P3U20 and P3U30 4 Control functions
Property Description
All the main menus are located on the left side of the display. To get to a
submenu, move up and down the main menus.
The mimic view is set as the local panel's main view as default. You can modify
the mimic according to the application or disable it, if it is not needed, via the
Easergy Pro setting tool.
You can modify the mimic in the General > Mimic setting view in Easergy Pro
and disable the mimic view in the General > Local panel conf setting view.
NOTE: The mimic itself or the local mimic settings cannot be modified via the
local panel.
96 P3U/en M/I006
4 Control functions Universal Relays P3U10, P3U20 and P3U30
C A B F I
G
D
H F J
E
I
A. To clear an object or drawing, first point an F. The remote/local selection defines whether
empty square (A) with the mouse. Then point the certain actions are granted or not. In remote
object item with the mouse. The color of the object state, it is not possible to locally enable or
item turns red. To clear the whole mimic, click on disable auto-reclosing or to control objects. The
the empty area. remote/local state can be changed in Control >
Objects.
B. Text tool G. Creates auto-reclosing on/off selection to
mimic.
C. To move an existing drawing or object, point it H. Creates virtual input activation on the local
with the mouse. The color turns green. Hold down mimic view.
the left mouse button and move the object.
D. Different type of configurable objects. The I. Describes the relay's location. Text comes
object's number corresponds to the number in from the relay info menu.
Control > Objects.
E. Some predefined drawings. J. Up to six configurable measurements.
P3U/en M/I006 97
Universal Relays P3U10, P3U20 and P3U30 4 Control functions
98 P3U/en M/I006
4 Control functions Universal Relays P3U10, P3U20 and P3U30
f, P, Q, S, P.F.
CosPhi
ARStart,
ARFaill,
ARShot1–5
IFLT
Starts, Trips
I0Calc
IL1–IL3da, IL
fSYNC, USYNC
IL1–IL3Min,
IL1–IL3Max,
IL1–IL3daMax
VAI1–VAI5
ExtAI1–633)
Set = Settable.
You can modify the local panel configuration in the General > Local panel conf
setting view in Easergy Pro.
P3U/en M/I006 99
Universal Relays P3U10, P3U20 and P3U30 4 Control functions
f, P, Q, S, P.F.
CosPhi
ARStart,
ARFaill,
ARShot1–5
IFLT
Starts, Trips
I0 Calc
IL
IL1–3da
IL1–3 max
IL1–3 min
IL1–3daMax
Pda, Qda,
Sda
T
fSYNC,
USYNC
VAI1–5
ExtAI1–635)
SetGrp
When selected,
the mimic is the
local panel's
default main
view. When
unselected, the
measurement
view is the
default main
view.
5 Protection functions
Each protection stage can independently be enabled or disabled according to the
requirements of the intended application.
The condition to be fulfilled by the CT saturation current (Isat) depends on the type
of overcurrent protection operate time.
IDMT Isat > 1.5 x the curve value which is the smallest of these two values:
• Isc max., maximum installation short-circuit current
• 20 x Is (IDMT curve dynamic range)
A B
t t
I I
Is Isat Is Isat
C D
The method for calculating the saturation current depends on the CT accuracy
class.
Table 46 - CT requirements
For 5 A: Vk > 150 x (Rct + Rw); for example: 150 x 0.53 = 79.5 V
If the resistance Rct is known, it is possible to calculate the actual CT ALF which
takes account of the actual CT load. The saturation current equals the actual ALF
x Inp.
Equation 2
To have an ALF of at least 20, that is, a saturation current of 20 x Inp = 2 kA, the
load resistance Rw of the CT must be less than Equation 3.
Equation 3
VAct 2.5
Rw, max = 2 = = 0.1Ω
Ins 52
This represents 12 m (39 ft) of wire with cross-section 2.5 mm² (AWG 14) for a
resistance per unit length of approximately 8 Ω/km (2.4 mΩ/ft). For an installation
with 50 m (164 ft) of wiring with section 2.5 mm² (AWG 14), Rw = 0.4 Ω.
Equation 4
Equation 5
Vk Inp
Isat = ×
Rct + Rw Ins
CT Vk Rct Rw Saturation
Transformati current
on ratio
The individual protection stage and total load status can be found in the
Protection > Protection stage status setting view in the Easergy Pro setting
tool.
Setting groups are controlled by using digital inputs, function keys or virtual
inputs, via the front panel or custom logic. When none of the assigned inputs are
active, the setting group is defined by the parameter ‘SetGrp no control state’.
When controlled input activates, the corresponding setting group is activated as
well. If the control signal of the setting group is lost, the setting “Keep last” forces
the last active group into use. If multiple inputs are active at the same time, the
active setting group is defined by ‘SetGrp priority’. By using virtual I/O, the active
setting group can be controlled using the local panel display, any communication
protocol or the built-in programmable logic functions. All protection stages have
four setting groups.
Example
Any digital input can be used to control setting groups but in this example, DI1,
DI2, DI3 and DI4 are chosen to control setting groups 1 to 4. This setting is done
with the parameter “Set group x DI control” where x refers to the desired setting
group.
Use the 'SetGrp common change' parameter to force all protection stages to
group 1, 2, 3 or 4. The control becomes active if there is no local control in the
protection stage. You can activate this parameter using Easergy Pro.
Assuming that DI2 and DI3 are active at the same time and SetGrp priority is set
to “1 to 4”, setting group 2 becomes active. If SetGrp priority is reversed, that is,
set to “4 to 1”, the setting group 3 becomes active.
• Ok = ‘-‘
The stage is idle and is measuring the analog quantity for the protection. No
power system fault detected.
• Blocked
The blocking reason may be an active signal via the block matrix from other
stages, the programmable logic or any digital input. Some stages also have built-
in blocking logic. For more details about the block matrix, see 4.4.2 Blocking
matrix.
Each protection stage has start and trip counters that are incremented when the
stage starts or trips. The start and trip counters are reset on relay reboot.
There is a "Forcing flag" parameter which, when activated, allows forcing the
status of any protection stage to be "start" or "trip" for half a second. By using this
forcing feature, current or voltage injection is not necessary to check the output
matrix configuration, to check the wiring from the digital outputs to the circuit
breaker and also to check that communication protocols are correctly transferring
event information to a SCADA system.
After testing, the forcing flag is automatically reset five minutes after the last local
panel push button activity.
The force flag also enables forcing the digital outputs and the optional mA
outputs.
The force flag can be found in the Device/Test > Relays setting view.
Every protection stage has two internal binary output signals: start and trip. The
start signal is issued when a fault has been detected. The trip signal is issued
after the configured operation delay unless the fault disappears before the end of
the delay time.
Start level
> Start
Output matrix
Using the output matrix, you can connect the internal start and trip signals to the
digital outputs and indicators. For more details, see 4.4.1 Output matrix.
Blocking
Any protection function can be blocked with internal and external signals using
the block matrix (4.4.2 Blocking matrix). Internal signals are for example logic
outputs and start and trip signals from other stages and external signals are for
example digital and virtual inputs as well as GOOSE signals.
Some protection stages have also built-in blocking functions. For example under-
frequency protection has built-in under-voltage blocking to avoid tripping when the
voltage is off.
When a protection stage is blocked, it does not trip if a fault condition is detected.
If blocking is activated during the operation delay, the delay counting is frozen
until the blocking goes off or the start reason, that is the fault condition,
disappears. If the stage is already tripping, the blocking has no effect.
Use 100 ms safety margin delay when the downstream relay’s protection start
signal is hardwired to interlock protection stages at the upstream relay.
The operate time in the dependent time mode is dependent on the magnitude of
the injected signal. The bigger the signal, the faster the stage issues a trip signal
and vice versa. The tripping time calculation resets if the injected quantity drops
below the start level.
IDMT DT
t (s)
If (A)
The operate time in the definite time mode is fixed by the Operation delay
setting. The timer starts when the protection stage activates and counts until the
set time has elapsed. After that, the stage issues a trip command. Should the
protection stage reset before the definite time operation has elapsed, then the
stage resets.
By default, the definite time delay cannot be set to zero because the value
contains processing time of the function and operate time of the output contact.
This means that the time indicated in the Definite time setting view is the actual
operate time of the function. Use the Accept zero delay setting in the protection
stage setting view to accept the zero setting for definite time function. In this case,
the minimum operate time of the function must be tested separately.
Overshoot time
Overshoot time is the time the protection device needs to notice that a fault has
been cleared during the operate time delay. This parameter is important when
grading the operate time delay settings between devices.
tFAULT
tRET < 50 ms
TRIP CONTACTS
If the delay setting would be slightly shorter, an unselective trip might occur (the
dash line pulse).
For example, when there is a big fault in an outgoing feeder, it might start both the
incoming and outgoing feeder relay. However, the fault must be cleared by the
outgoing feeder relay and the incoming feeder relay must not trip. Although the
operating delay setting of the incoming feeder is more than at the outgoing feeder,
the incoming feeder might still trip if the operate time difference is not big enough.
The difference must be more than the overshoot time of the incoming feeder relay
plus the operate time of the outgoing feeder circuit breaker.
Figure 50 shows an overvoltage fault seen by the incoming feeder when the
outgoing feeder clears the fault. If the operation delay setting would be slightly
shorter or if the fault duration would be slightly longer than in the figure, an
unselective trip might happen (the dashed 40 ms pulse in the figure). In Easergy
P3 devices, the overshoot time is less than 50 ms.
Reset time
Figure 51 shows an example of reset time, that is, release delay when the relay is
clearing an overcurrent fault. When the relay’s trip contacts are closed, the circuit
breaker (CB) starts to open. After the CB contacts are open, the fault current still
flows through an arc between the opened contacts. The current is finally cut off
when the arc extinguishes at the next zero crossing of the current. This is the start
moment of the reset delay. After the reset delay the trip contacts and start contact
are opened unless latching is configured. The precise reset time depends on the
fault size; after a big fault, the reset time is longer. The reset time also depends
on the specific protection stage.
The maximum reset time for each stage is specified under the characteristics of
every protection function. For most stages, it is less than 95 ms.
tSET
tCB
tRESET
TRIP CONTACTS
Reset time is the time it takes the trip or start relay contacts to open after the fault
has been cleared.
Start level
> Start
Start level
< Start
Time grading
When a fault occurs, the protection scheme only needs to trip circuit breakers
whose operation is required to isolate the fault. This selective tripping is also
called discrimination or protection coordination and is typically achived by time
grading. Protection systems in successive zones are arranged to operate in times
that are graded through the sequence of equipment so that upon the occurrence
of a fault, although a number of protections devices respond, only those relevant
to the faulty zone complete the tripping function.
δt TC m Tm δt
time
Δt
There is detailed information available on the last eight faults for each protection
stage. The recorded values are specific for the protection stages and can contain
information like time stamp, fault value, elapsed delay, fault current, fault voltage,
phase angle and setting group.
NOTE: The recorded values are lost if the relay power is switched off.
Squelch limit
Current inputs have a squelch limit (noise filter) at 0.005 x IN. When the
measured signal goes below this threshold level, the signal is forced to zero.
NOTE: If ICALC is used to measure the residual current, the squelch limit for
the ICALC signal is same as for the phase currents. The I0 setting range begins
at the level of phase currents' squelch limit. This can cause instability if the
minimum setting is used with the I0 CALC mode.
The application mode can be changed with Easergy Pro software or from CONF
menu of the relay. Changing the application mode requires configurator password.
Dependent delay means that the operate time depends on the measured real
time process values during a fault. For example, with an overcurrent stage using
dependent delay, a bigger a fault current gives faster operation. The alternative to
dependent delay is definite delay. With definite delay, a preset time is used and
the operate time does not depend on the size of a fault.
Some protection functions have their own specific type of dependent delay.
Details of these dedicated dependent delays are described with the appropriate
protection function.
Operation modes
There are three operation modes to use the dependent time characteristics:
• Standard delays
selecting a curve family (IEC, IEEE, IEEE2) and defining one's own
parameters for the selected delay formula. This mode is activated by setting
delay type to ‘Parameters’, and then editing the delay function parameters A –
E. See 5.6.2 Free parameterization using IEC, IEEE and IEEE2 curves.
• Fully programmable dependent delay characteristics
CAUTION
HAZARD OF NON-OPERATION
The relay shows a graph of the currently used dependent delay on the local panel
display. The up and down keys can be used for zooming. Also the delays at 20 x
ISET, 4 x ISET and 2 x ISET are shown.
If there are any errors in the dependent delay configuration, the appropriate
protection stage uses the definite time delay.
There is a signal ‘Setting Error’ available in the output matrix that indicates
different situations:
3. There are errors in formula parameters A – E, and the relay is not able to
build the delay curve.
4. There are errors in the programmable curve configuration, and the relay is not
able to interpolate values between the given points.
Limitations
Table 48 - Maximum measured secondary currents and settings for phase and
earth fault overcurrent inputs
I0 = 5 A 50 A 2.5 A
I0 = 1 A 10 A 0.5 A
1. Example of limitation
CT = 750 / 5
For overcurrent stage I>, Table 48 gives 12.5 A. Thus, the maximum setting
the for I> stage giving full dependent delay range is 12.5 A / 5 A = 2.5 xIN =
1875 APrimary.
For earth fault stage I0>, Table 48 gives 0.5 A. Thus, the maximum setting for
the I0> stage giving full dependent delay range is 0.5 A / 1 A = 0.5 xI0N = 50
APrimary.
2. Example of limitation
CT = 750 / 5
For overcurrent stage I>, Table 48 gives 12.5 A. Thus, the maximum setting
giving full dependent delay range is 12.5 A / 4 A = 3.13 x IMOT = 1875 APrimary.
For earth fault stage I0>, Table 48 gives 12.5 A. Thus, the maximum setting
for the I0> stage giving full dependent delay range is 12.5 A / 5 A = 2.5 x I0N =
1875 APrimary.
5.6.1 Standard dependent delays using IEC, IEEE, IEEE2 and RI curves
The available standard dependent delays are divided in four categories called
dependent curve families: IEC, IEEE, IEEE2 and RI. Each category contains a set
of different delay types according to Table 49.
The dependent time setting error signal activates if the delay category is changed
and the old delay type does not exist in the new category. See 5.6 Dependent
operate time for more details.
Limitations
The minimum definite time delay starts when the measured value is twenty times
the setting, at the latest. However, there are limitations at high setting values due
to the measurement range. See 5.6 Dependent operate time for more details.
Table 49 - Available standard delay families and the available delay types within
each family
DT Definite X
time
NI Normal X X
inverse
VI Very X X X
inverse
EI Extremely X X X
inverse
MI Moderately X X
inverse
RI Old ASEA X
type
The operate time depends on the measured value and other parameters
according to Equation 6. Actually this equation can only be used to draw graphs
or when the measured value I is constant during the fault. A modified version is
implemented in the relay for real time usage.
Equation 6
kA
t= B
I
− 1
I START
I = Measured value
There are three different dependent delay types according to IEC 60255-3,
Normal inverse (NI), Extremely inverse (EI), Very inverse (VI) and a VI extension.
In addition, there is a de facto standard Long time inverse (LTI).
Parameter
Delay type
A B
EI Extremely inverse 80 2
k = 0.50
I = 4 pu (constant current)
IPICKUP = 2 pu
A = 0.14
B = 0.02
Equation 7
0.50 ⋅ 0.14
t= 0.02
= 5. 0
4
−1
2
The operate time in this example is five seconds. The same result can be read
from Figure 55.
IEC NI
B inverseDelayIEC_NI
IEC EI
B inverseDelayIEC_EI
IEC VI
B inverseDelayIEC_VI
IEC LTI
B inverseDelayIEC_LTI
There are three different delay types according to IEEE Std C37.112-1996 (MI, VI,
EI) and many de facto versions according to Table 51. The IEEE standard defines
dependent delay for both trip and release operations. However, in the Easergy P3
relay only the trip time is dependent according to the standard but the reset time
is constant.
The operate delay depends on the measured value and other parameters
according to Equation 8. Actually, this equation can only be used to draw graphs
or when the measured value I is constant during the fault. A modified version is
implemented in the relay for real-time usage.
Equation 8
A
t=k C
+ B
I − 1
I START
k = User’s multiplier
I = Measured value
A B C
k = 0.50
I = 4 pu
IPICKUP = 2 pu
A = 0.0515
B = 0.114
C = 0.02
Equation 9
t = 0.50 ⋅ 0.0515
+ 0.1140 = 1.9
4 0.02
−1
2
The operate time in this example is 1.9 seconds. The same result can be read
from Figure 62.
IEEE LTI
B inverseDelayIEEE1_LTI
IEEE LTVI
B inverseDelayIEEE1_LTVI
IEEE LTEI
B inverseDelayIEEE1_LTEI
IEEE MI
B inverseDelayIEEE1_MI
IEEE STI
B inverseDelayIEEE1 STI
IEEE STEI
B inverseDelayIEEE1 STEI
Before the year 1996 and ANSI standard C37.112 microprocessor relays were
using equations approximating the behavior of various induction disc type relays.
A quite popular approximation is Equation 10 which in Easergy P3 relays is called
IEEE2. Another name could be IAC because the old General Electric IAC relays
have been modeled using the same equation.
There are four different delay types according to Table 52. The old
electromechanical induction disc relays have dependent delay for both trip and
release operations. However, in Easergy P3 relays, only the trip time is
dependent and the reset time is constant.
The operate delay depends on the measured value and other parameters
according to Equation 10. Actually, this equation can only be used to draw graphs
or when the measured value I is constant during the fault. A modified version is
implemented in the relay for real-time usage.
Equation 10
B D E
t = k A + + + 3
I 2
− C I − C I − C
I START I START
I
START
k = User’s multiplier
I = Measured value
Parameter
Delay type
A B C D E
k = 0.50
I = 4 pu
ISTART = 2 pu
A = 0.1735
B = 0.6791
C = 0.8
D = -0.08
E = 0.127
Equation 11
0.6791 − 0.08 0.127
t = 0.5 ⋅ 0.1735 + + + = 0.38
4 4
2
4
3
− 0.8 − 0.8 − 0.8
2 2 2
The operate time in this example is 0.38 seconds. The same result can be read
from Figure 65.
IEEE2 MI
B inverseDelayIEEE2_MI
IEEE2 NI
B inverseDelayIEEE2_NI
IEEE2 VI
B inverseDelayIEEE2_VI
IEEE2 EI
B inverseDelayIEEE2_EI
These two dependent delay types have their origin in old ASEA (nowadays ABB)
earth fault relays.
The operate delay of types RI and RXIDG depends on the measured value and
other parameters according to Equation 12 and Equation 13. Actually, these
equations can only be used to draw graphs or when the measured value I is
constant during the fault. Modified versions are implemented in the relay for real-
time usage.
Equation 12 Equation 13
k I
t RI = t RXIDG = 5.8 − 1.35 ln
0.236 k I START
0.339 −
I
I START
k = User’s multiplier
I = Measured value
k = 0.50
I = 4 pu
ISTART = 2 pu
Equation 14
0.5
t RI = = 2.3
0.236
0.339 −
4
2
The operate time in this example is 2.3 seconds. The same result can be read
from Figure 69.
k = 0.50
I = 4 pu
ISTART = 2 pu
Equation 15
4
t RXIDG = 5.8 − 1.35 ln = 3.9
0.5 ⋅ 2
The operate time in this example is 3.9 seconds. The same result can be read
from Figure 70.
RI
B inverseDelayRI
This mode is activated by the setting delay type to ‘Parameters’, and then editing
the delay function constants, that is, the parameters A – E. The idea is to use the
standard equations with one’s own constants instead of the standardized
constants as in the previous chapter.
k = 0.50
I = 4 pu
ISTART = 2 pu
A = 0.2078
B = 0.8630
C = 0.8000
D = - 0.4180
E = 0.1947
Equation 16
0.8630 − 0.4180 0.1947
t = 0.5 ⋅ 0.2078 + + + = 0.37
4 4
2
4
3
− 0.8 − 0.8 − 0.8
2 2 2
The resulting time/current characteristic of this example matches quite well the
characteristic of the old electromechanical IAC51 induction disc relay.
The dependent time setting error signal actives if interpolation with the given
parameters is not possible. See 5.6 Dependent operate time for more details.
Limitations
The minimum definite time delay starts at the latest when the measured value is
twenty times the setting. However, there are limitations at high setting values due
to the measurement range. See 5.6 Dependent operate time for more details.
Programming dependent time curves requires Easergy Pro setting tool and
rebooting the unit.
The [current, time] curve points are programmed using Easergy Pro PC program.
There are some rules for defining the curve points:
• the configuration must begin from the topmost line
• the line order must be as follows: the smallest current (longest operate time)
on the top and the largest current (shortest operate time) on the bottom
• all unused lines (on the bottom) should be filled with [1.00 0.00s]
1 1.00 10.00 s
2 2.00 6.50 s
3 5.00 4.00 s
4 10.00 3.00 s
5 20.00 2.00 s
6 40.00 1.00 s
7 1.00 0.00 s
8 1.00 0.00 s
9 1.00 0.00 s
10 1.00 0.00 s
11 1.00 0.00 s
12 1.00 0.00 s
13 1.00 0.00 s
14 1.00 0.00 s
15 1.00 0.00 s
16 1.00 0.00 s
The dependent time setting error signal activates if interpolation with the given
points fails. See 5.6 Dependent operate time for more details.
Limitations
The minimum definite time delay starts at the latest when the measured value is
twenty times the setting. However, there are limitations at high setting values due
to the measurement range. See 5.6 Dependent operate time for more details.
P3U10
P3U20
P3U30 x x
Description
The relay includes a function that checks the synchronism before giving or
enabling the circuit breaker close command. The function monitors the voltage
amplitude, frequency and phase angle difference between two voltages. Since
there are two stages available, it is possible to monitor three voltages. The
voltages can be busbar and line or busbar and busbar (bus coupler).
Close
Request
cmd
Side 2 f1 = f2
φ1 = φ2 & & CB close
Register
U1 event
U2 & ≥1 Sync OK
The synchrocheck stage includes two separate synchronism criteria that can be
used separately or combined:
• voltage only
• voltage, frequency, and phase
The voltage check simply compares voltage conditions of the supervised objects.
The supervised object is considered dead (not energized) when the measured
voltage is below the Udead setting limit. Similarly, the supervised object is
considered live (energized) when the measured voltage is above the Ulive setting
limit. Based on the measured voltage conditions and the selected voltage check
criteria, synchronism is declared.
When the network sections to be connected are part of the same network, the
frequency and phase are the same. Therefore, the voltage check criteria is safe to
use without frequency and phase check.
The frequency and phase check compares the voltages, frequency and phase of
the supervised objects. Synchronism is declared if the voltages are above the
Ulive limit and all three difference criteria are within the given limits. This
synchronism check is dynamic by nature, and the object close command is given
at a certain moment of time, depending on the selected mode of operation.
When two networks are running at slightly different frequencies, there is also a
phase difference between these two networks. Because of the different frequency,
the phase angle tends to rotate. The time for one cycle depends on the frequency
difference. The stress for electrical components is lowest when two networks are
connected at zero phase difference.
In the “Sync” mode, the circuit breaker closing is aimed at the moment of zero
phase difference. Therefore, the close command is advanced by the time defined
by the CB close time setting. In the “Async” mode, the circuit breaker closing is
aimed at the moment when the synchronism conditions are met, that is, when the
phase difference is within the given phase difference limit.
When two networks with different frequencies are to be connected, the request
timeout setting must be long enough to allow the synchronism criteria to be met.
For example, if the frequency difference is 0.1 Hz, the synchronism criteria is met
only once in ten seconds.
The synchrocheck stage starts from an object close command that generates a
request to close the selected circuit breaker when the synchronism conditions are
met. The synchrocheck stage provides a "request" signal that is active from the
stage start until the synchronism conditions are met or the request timeout has
elapsed. When the synchronism conditions are not met within the request
timeout, a “fail” pulse is generated. The fail pulse has a fixed length of 200 ms.
When the synchronism conditions are met in a timely manner, the object close
command is initiated for the selected object. This signal is purely internal and not
available outside the synchrocheck stage. When the synchronism conditions are
met, the “OK” signal is always active. The activation of the bypass input bybasses
the synchronism check and declares synchronism at all times.
The request, OK, and fail signals are available in the output matrix.
The synchronized circuit breaker close execution order is shown in Figure 72.
1 2 3
A B C
4 5
A. Synchrocheck stage
B. Object
C. Circuit breaker (physical)
2. Synchronism declared
4. Sync fail signal if request timeout elapsed before synchronism conditions met
A B
1
C D
1. Sync request
2. Sync OK
A. The object close command given (mimic or bus) actually only makes a sync request.
B. The sync request ends when the synchronism conditions are met and CB command is given or
if the request timeout elapsed.
C. If the request timeout elapsed before synchronism conditions are met, sync fail pulse is
generated.
D. Normal object close operation
3LN+LLy 1
3LN+LNy 1
2LL+U0+LLy 1
2LL+U0+LNy 1
LL+U0+LLy+LLz 2
LN+U0+LNy+LNz 2
3LN+LLy 1
3LN+LNy 1
LL+U0+LLy+LLz 2
LN+U0+LNy+LNz 2
The voltage used for synchrochecking is always line-to-line voltage U12 even
when UL1 is measured. The sychrocheck stage 1 always compares U12 with U12y.
The compared voltages for the stage 2 can be selected (U12/U12y, U12/U12z,
U12y/U12z). See 9.7 Voltage measurement modes.
Characteristics
Voltage check mode (UMODE) DD; DL; LD; DD/DL; DD/LD; DL/LD;
DD/DL/LD 41) 42) 43) 44)
Inaccuracy:
- voltage ±3% UN
limit setting).
43) L means that the side must be “live” when closing (live = The voltage is higher than the live voltage
limit setting).
44) Example: DL mode for stage 1: The U12 side must be “dead” and the U12y side must be “live”.
P3U10
P3U20
P3U30 x x
Description
As all the protection stages, the undervoltage function can be blocked with any
internal or external signal using the block matrix. For example if the secondary
voltage of one of the measuring transformers disappears because of a fuse failure
(See the voltage transformer supervision function in 6.8 Voltage transformer
supervision (ANSI 60FL)). The blocking signal can also be a signal from the
custom logic (see 4.7 Logic functions).
The stages can be blocked with a separate low-limit setting. With this setting, the
particular stage is blocked when the biggest of the three line-to-line voltages
drops below the given limit. The idea is to avoid unwanted tripping when the
voltage is switched off. If the operate time is less than 0.08 s, the blocking level
setting should not be less than 15% for the blocking action to be fast enough. The
self blocking can be disabled by setting the low-voltage block limit equal to zero.
A
K K K
I
B
C
J J
H J
D
G
L L F
D. Block limit
E. U< undervoltage state
F. Time
G. The maximum of the three line-to-line voltages ULLmax is below the block limit. This is not
regarded as an undervoltage situation.
H. The voltage ULLmax is above the block limit but below the start level. This is an undervoltage
situation.
I. The voltage is OK because it is above the start limit.
J. This is an undervoltage situation.
K. The voltage is OK.
L. The voltage ULLmax is under the block limit and this is not regarded as an undervoltage
situation.
There are three separately adjustable stages: U<, U<< and U<<<. All these
stages can be configured for the definite time (DT) operation characteristic.
Setting groups
Characteristics
Inaccuracy:
Inaccuracy:
Inaccuracy:
P3U10
P3U20
P3U30 x x
Description
The directional power function can be used, for example, to disconnect a motor if
the supply voltage is lost and thus prevent power generation by the motor. It can
also be used to detect loss of load of a motor.
The directional power function is sensitive to active power. For the directional
power function, the start value is negative. For the underpower function, a positive
start value is used. Whenever the active power goes under the start value, the
stage starts and issues a start signal. If the fault situation stays on longer than the
delay setting, a trip signal is issued.
The start setting range is from -200% to +200% of the nominal shaft power PM. If
the PM value is not known, set it equal to the machine’s nominal power. The
directional power stages use this value as reference for 1.00 per unit.
There are two identical stages available with independent setting parameters.
Setting groups
Characteristics
Inaccuracy: -
P3U10 x x
P3U20 x x
P3U30 x x
Description
The undercurrent stage protects rather the relay driven by the motor, for example
a submersible pump, than the motor itself.
Setting groups
Characteristics
Accuracy: -
NOTE: Stage Blocking is functional when all phase currents are below the
block limit.
P3U10 x
P3U20 x
P3U30 x
Description
The purpose of the unbalance stage is to detect unbalanced load conditions, for
example a broken conductor of a heavy-loaded overhead line if there is no earth
fault. The operation of the unbalanced load function is based on the negative
phase sequence component I2 related to the positive phase sequence component
I1. This is calculated from the phase currents using the method of symmetrical
components. The function requires that the measuring inputs are connected
correctly so that the rotation direction of the phase currents are as in 9.5.7
Connection examples. The unbalance protection has definite time operation
characteristic.
Equation 17
I2
K2 =
I1
Equation 18
, a phasor rotating constant
1 3
a = 1∠120° = − + j
2 2
Characteristics
Settings:
Inaccuracy: -
P3U10 x
P3U20 x
P3U30 x
Description
Equation 19
K1
T= 2
I2
− K 22
I MOT
T = Operate time
K1 = Delay multiplier
Example
K1 = 15 s
K2 = 5 % = 0.05 x IMOT
15
t= 2
= 300.4
0.229
− 0.05
2
1
If more than one definite time delay stages are needed for negative sequence
overcurrent protection, the freely programmable stages can be used (5.39
Programmable stages (ANSI 99)).
500 K2 = 2 % K 2 = 40 % K 2 = 70 %
200
100 K1 = 50 s
A 50
K2 = 2 % K 2 = 40 % K 2 = 70 %
20
10
5
K1 = 1 s
2
1
0 20 40 60 80 100
B
Setting groups
Characteristics
Inaccuracy:
NOTE: The stage is operational when all secondary currents are above 250
mA.
P3U10 x
P3U20 x
P3U30 x
Description
The incorrect phase sequence detection prevents the motor from being started to
wrong direction, thus protecting the load.
When the ratio between negative and positive sequence current exceeds 80%
and the average of three phase currents exceeds 0.2 x IMOT in the start-up
situation, the phase sequence stage starts and trips 100 ms after start-up.
Setting groups
Characteristics
Setting: 80 % (fixed)
NOTE: Stage is blocked when motor has been running for 2 seconds.
Stage is operational only when least one of the currents is above 0.2 x IMOT
P3U10
P3U20
P3U30 x x
Description
This protection stage can be used to detect voltage unbalance and phase
reversal situations. It calculates the fundamental frequency value of the negative
sequence component U2 based on the measured voltages (for calculation of U2,
see 3.10 Symmetrical components).
Whenever the negative sequence voltage U2 raises above the user's start setting
of a particular stage, this stage starts, and a start signal is issued. If the fault
situation remains on longer than the user's operate time delay setting, a trip signal
is issued.
Like all the protection stages, the negative sequence overvoltage can be blocked
with any internal or external signal using the block matrix, for example, if the
secondary voltage of one of the measuring transformers disappears because of a
fuse failure (See VT supervision function in 6.8 Voltage transformer supervision
(ANSI 60FL)).
The blocking signal can also be a signal from the user's logic (see 4.7 Logic
functions).
There are three separately adjustable stages: U2>, U2>>, and U2>>>. Both stages
can be configured for the definite time (DT) operation characteristic.
Setting groups
There are four settings groups available for all stages. Switching between setting
groups can be controlled by digital inputs, virtual inputs (mimic display,
communication, logic) and manually.
Characteristics
Inaccuracy:
P3U10 x
P3U20 x
P3U30 x
Description
The motor start-up supervision IST> protects the motor against prolonged direct-
on-line (DOL) starts caused by, for example, a stalled rotor, too high inertia of the
load or too low voltage. It measures the fundamental frequency component of the
phase currents.
The IST> stage can be configured for definite operate time or dependent operate
time characteristic. For a weak voltage supply, the dependent characteristic is
useful allowing more start time when a voltage drop decreases the start current
and increases the start time. Equation 20 defines the dependent operate time.
Figure 76 shows an example of the dependent characteristic.
Tstart
If the measured current is less than the specified start current ISTART, the operate
time is longer than the specified start time TSTART and vice versa.
Equation 20
2
I
T = START TSTART
I MEAS
ISTART = Rated start current of the motor “Nom motor start current IMOTST. The
default setting is 6.00xIMOT.
TSTART = Maximum allowed start time “Inv. time coefficient” k> for the motor at
rated voltage
The start setting “Motor start detection current” IST > is the start detection level of
the start current. When the current has been less than 10% of IMOT and then
within 200 milliseconds exceeds the setting IST >, the motor start-up supervision
stage starts to count the operate time TSTART. When the current drops below 120
% x IMOT, the motor start-up supervision stage releases. The motor start-up
supervision is only active during the starting of the motor.
Block diagram
Istlohko
Im1
Im2 MAX > ts tr
& G
Im3
& H
A t
>1 I
& H
B C D E F
• Motor stopped: the motor average current is less than 10% of the motor
nominal current (IMOT).
• Motor starting: To reach the starting position, the motor has to be stopped for
at least 500 ms before starting. The average motor current has to increase
above the motor start detection current (setting value) within 200 ms. The
motor remains starting as long as the terms for turning into running condition
are not fulfilled.
• Motor running: The motor can change to the running position from both
stopped and starting position. The low limit for motor running is 20% and the
high limit 120% of IMOT.
The motor status can be viewed via Easergy Pro software or via the device's front
panel (Mstat). The starting and running statuses can be found on the output and
block matrix. Therefore, it is possible to use these signals for tripping or indication
and for blocking purposes.
The default value for the motor start detection is six times the motor nominal
value. The motor current is
IL1+IL2+IL3
3
G
A
B H
C
E
D
F
Soft start
Frequency converter drives and soft starter applications do not initiate the motor
start signal because of the low current during motor start. The motor changes
directly from stopped to running position when the current increases to a certain
level.
IL1+IL2+IL3
3
F
A
B
D
C
E
Setting groups
Characteristics
Setting range: -
Inaccuracy: -
NOTE: Motor stopped and running limits are based on the average of three
phase currents.
P3U10 x P3U10 x
P3U20 x P3U20 x
P3U30 x P3U30 x
Description
The thermal overload function (ANSI 49F) protects cables in the feeder mode
against excessive heating.
The thermal overload function (ANSI 49M) protects the motor in the motor mode
against excessive heating.
Thermal model
The temperature is calculated using RMS values of phase currents and a thermal
model according IEC60255-149. The RMS values are calculated using harmonic
components up to the 15th.
Trip time:
I 2 − IP
2
t = τ ⋅ ln
I 2 − a2
Alarm (alarm 60% = 0.6):
a = k ⋅ kΘ ⋅ I MODE ⋅ alarm
Trip:
a = k ⋅ kΘ ⋅ I MODE
Reset time:
2
I
t = τ ⋅ Cτ ⋅ ln 2 P 2
a −I
Trip release:
a = 0.95 × k × I MODE
T = Operate time
I =Measured RMS phase current (the max. value of three phase currents)
Ip = Preload current, I P = θ × k × I MODE (If temperature rise is 120% -> θ = 1.2). This
parameter is the memory of the algorithm and corresponds to the actual
temperature rise.
If the motor's fan is stopped, the cooling is slower than with an active fan.
Therefore, there is a coefficient Cτ for thermal constant available to be used as
cooling time constant when the current is less than 0.3 x IMOT.
The trip level is determined by the maximum allowed continuous current IMAX
corresponding to the 100% temperature rise ΘTRIP for example the heat
capacitance of the motor (ANSI 49M) or cable (ANSI 49F). IMAX depends of the
given service factor k and ambient temperature ΘAMB and settings IMAX40 and
IMAX70 according the following equation.
I MAX = k ⋅ kΘ ⋅ I MODE
k
1.2
IMAX40
1.0
0.8 IMAX70
0.6
10 20 30 40 50 60 70 80 (°C)
AMB
When the relay is switched on, an initial temperature rise of 70% is used.
Depending on the actual current, the calculated temperature rise then starts to
approach the final value.
Alarm function
The thermal overload stage is provided with a separately settable alarm function.
When the alarm limit is reached, the stage activates its start signal.
Θoverload
Θmax
Θalarm
Reset ratio=95%
Θp
Settings:
τ = 30 minutes
k = 1.06
Θalarm = 90%
Alarm
Trip
45 min
IP = 0.85*IN
Time
100 min 200 min 300 min 400 min 500 min
Setting groups
Characteristics
P3U10 x x
P3U20 x x
P3U30 x x
Description
The circuit breaker failure protection stage (CBFP) can be used to operate any
upstream circuit breaker (CB) if the programmed output matrix signals, selected
to control the main breaker, have not disappeared within a given time after the
initial command. The supervised output contact is defined by the “Monitored Trip
Relay” setting. An alternative output contact of the relay must be used for this
backup control selected in the Output matrix setting view.
The CBFP operation is based on the supervision of the signal to the selected
output contact and the time. The following output matrix signals, when
programmed into use, start the CBFP function:
• protection functions
• control functions
• supporting functions
• GOOSE signals (through communication)
If the signal is longer than the CBFP stage’s operate time, the stage activates
another output contact defined in the Output matrix setting view. The output
contact remains activated until the signal resets. The CBFP stage supervises all
the signals assigned to the same selected output contact.
In Figure 84, both the trip and CBFP start signals activate simultaneously (left
picture). If T> trip fails to control the CB through T1, the CBFP activates T3 after
the breaker failure operate time.
Figure 84 - Trip and CBFP start signals in the Output matrix view
NOTE: For the CBFP, always select the ”Connected” crossing symbol in the
Output matrix setting view.
Characteristics
Inaccuracy:
P3U10 x x
P3U20 x x
P3U30 x x
Easergy P3 has two identical Breaker failure 1 (ANSI 50BF) and Breaker failure 2
(ANSI 50BF) stages.
Description
Power system protection should always have some sort of backup protection
available. Backup protection is intended to operate when a power system fault is
not cleared or an abnormal condition is not detected in the required time because
of a failure or the inability of the primary protection to operate or failure of the
appropriate circuit breakers to trip. Backup protection may be local or remote.
Circuit breaker failure protection (CBFP) is part of the local backup protection.
CBFP provides a backup trip signal to an upstream circuit breaker (CB) when the
CB nearest to fault fails to clear fault current. The CB may fail to operate for
several reasons, for example burnt open coil or a flashover in the CB.
Two separate stages are provided to enable re-trip and CBFP trip commands.
The first stage can be used to give re-trip command (for example to control
second/backup open coil of the main CB) while the second stage can give
dedicated CBFP trip command to an upstream circuit breaker. Select the required
outputs for re-trip and CBFP trip through the output matrix.
Block diagram
A I
IL1
IL2 Imax > &
& J
IL3
I0 > & ≥ t K
B
C & & J
D
&
E
F G H
CBFP operation
The CBFP function can be enabled and disabled with the Enable for BF2
selection. The CBFP function activates when any of the selected start signals
becomes and stays active.
The CBFP operation can be temporarily blocked by the stage block signal from
the block matrix. When the stage is blocked by the block signal, the stage timer
stops but it does not reset. The stage timer continues its operation when the block
signal is disabled. When the block signal is active, the stage output signals are
disabled.
Condition selectors
The CBFP function has four condition selectors that can be used separately or all
together to activate and reset the CBFP function.
The four condition selectors are almost identical. The only difference is that
condition selectors 1 and 2 are for all protection functions that benefit from zero-
current detection for resetting the CBFP as described in section Zero-current
detector, and selectors 3 and 4 are for all the protection functions that do not
benefit from zero-current detection for CBFP.
Figure 87 - Start signal and reset condition setting view for Condition 1
Separate zero-current detection with dedicated start settings exists for phase
overcurrent and earth fault overcurrent signals. Zero-current detection is
independent of the protection stages.
The condition criteria, available signals and reset conditions are listed in Table 68.
NOTE: The start signal can be selected for each condition in advance from
the pull-down menu even if the concerned stage is not enabled. For the CBFP
activation, the concerned stage must be enabled from the protection stage
menu and the stage has to start to activate the CBFP start signal.
Condition 1 I>, I>>, I>>>, Iv>, I2>, dI>, Reset by CB status: DI1 –
dI>>, Iφ>, Iφ>>, Iφ>>>, DIx (1, F1, F2, VI1-20,
Iφ>>>>, T>, If2>, X<, X<<, VO1–20, GOOSE_NI1–64,
I’>, I’>>, If5, SOTF POC1–16, Obj1-8Op
In addition to the selection of the start signal, the CBFP reset condition needs to
be selected.
If no reset conditions are selected, the stage uses Reset by monitored stage as
the reset condition. This prevents a situation where the stage never releases.
The reset condition Reset by CB status is useful if the current is already zero
when the CB is opened (for example unloaded CB).
When more than one selection criteria are selected, AND condition is used, for
example “zero current detection” AND “object open”. See Figure 86 for details.
Stage timer
The operate delay timer is started by a signal activated by the monitored stages
(condition selectors). The operate time delay is a settable parameter. When the
given time delay has elapsed, the stage provides a trip signal through the output
matrix and the event codes.
Zero-current detector
The setting range of the zero-current detector is always associated with the CT
nominal value, even in case of motor and transformer protection. The setting
range minimum depends on the relay accuracy. Instead of zero, a small minimum
value can be accepted. See Table 69.
CBFP coordination
The CBFP delay setting has to be coordinated according to the CB operation time
and the reset time of protection stages monitored by the CBFP function as
described in Figure 89.
B
C E F
D G
A
H I
Characteristics
Zero-current detection:
Inaccuracy:
P3U10 x x
P3U20 x x
P3U30 x x
Description
The switch-on-to-fault (SOTF) protection function offers fast protection when the
circuit breaker (CB) is closed manually against a faulty line. Overcurrent-based
protection does not clear the fault until the intended time delay has elapsed.
SOTF gives a trip signal without additional time delay if the CB is closed and a
fault is detected after closing the CB.
E
A
G
B
C
F
D
A. Start setting
B. Maximum of IL1, IL2, IL3
C. Low limit 0.02 x IN
D. SOTF trip
E. Switch-on-to-fault does not activate if the CB has not been in open position before the fault.
Open CB detection is noticed from the highest phase current value which has to be under a fixed
low-limit threshold (0.02 x IN). Opening of the CB can be detected also with digital inputs (Dead
line detection input = DI1 – DIx, VI1 – VIx). The default detection input is based on the current
threshold, so the dead line detection input parameter has value “–“.
F. Dead line detection delay defines how long the CB has to be open so that the SOTF function is
active. If the set time delay is not fulfilled and the highest phase current value (maximum of IL1, IL2,
IL3) rises over the start setting, the SOTF does not operate.
G.If the highest phase current value of IL1, IL2, IL3 goes successfully under the low limit and rises to
a value between the low limit and the start value, then if the highest phase current value rises over
the start setting value before the set SOTF active after CB closure time delay has elapsed, the
SOTF trips. If this time delay is exceeded, the SOTF does not trip even if the start setting value is
exceeded.
Setting groups
Characteristics
P3U10 x x
P3U20 x x
P3U30 x x
Description
Block diagram
3vlsblock
Im1
Im2 MAX > ts tr
& H
Im3
& I
A t
>1 J
& I
B C D E F G
A. Block F. Multiplier
B. Setting I>s G. Enable events
C. Delay H. Start
D. Definite / dependent time I. Register event
E. Dependent time characteristics J. Trip
Figure 92 - Block diagram of the three-phase overcurrent stage I>> and I>>>
3vIssblock
Im1
Im2 MAX > & E
Im3 ts tr
& F
A
t
G
& F
B C D
A. Block E. Start
B. Setting I>>s F. Register event
C. Delay G. Trip
D. Enable events
There are three separately adjustable overcurrent stages: I>, I>> and I>>>. The
first stage I> can be configured for definite time (DT) or dependent operate time
(IDMT) characteristic. The stages I>> and I>>> have definite time operation
characteristic. By using the definite delay type and setting the delay to its
minimum, an instantaneous (ANSI 50) operation is obtained.
Figure 91 shows a functional block diagram of the I> overcurrent stage with
definite time and dependent time operate time. Figure 92 shows a functional block
diagram of the I>> and I>>> overcurrent stages with definite time operation delay.
Dependent operate time means that the operate time depends on the amount the
measured current exceeds the start setting. The bigger the fault current is, the
faster is the operation. The dependent time delay types are described in 5.6
Dependent operate time. The relay shows the currently used dependent operate
time curve graph on the local panel display.
The maximum measured secondary current is 50 x IN. This limits the scope of
dependent curves with high start settings. See 5.6 Dependent operate time for
more information.
The I> and I>> (50/51) overcurrent protection stages have a setting parameter to
include harmonics. When this setting is activated, the overcurrent stage
calculates the sum of the base frequency and all measured harmonics. This
feature is used to determine the signal's true root mean square value to detect the
signal's real heating factor. The operate time is 5 ms more when harmonics are
included in the measurement. Activate the "Include harmonics" setting if the
overcurrent protection is used for thermal protection and the content of the
harmonics is known to exist in the power system.
Setting groups
Characteristics
IDMT function:
- RI curve 0.025–20.0
0.025–20.0
Inaccuracy:
Moderately Inverse
Inaccuracy:
±3% of the set value or 5 mA secondary
- Starting
±1% or ±25 ms
- operate time
51) This
is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in Easergy Pro to accept the zero operate time setting for the DT function.
Inaccuracy:
52) This
is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in Easergy Pro to accept the zero operate time setting for the DT function.
P3U10 x x
P3U20 x x
P3U30 x x
Description
Block diagram
i0s1
A > & I
ts tr
& J
B t
>1 K
& J
C D E F G H
A. I0 G. Multiplier
B. Block H. Enable events
C. Setting I0>s I. Start
D. Delay J. Register event
E. Definite / inverse time K. Trip
F. Inverse time characteristics
Figure 94 - Block diagram of the earth fault stages overcurrent I0>>, I0>>>,
I0>>>>, I0>>>>>
I0ssblock
A > ts tr
& F
& G
B
t
H
& G
C D E
A. I0 E. Enable events
B. Block F. Start
C. Setting I0>>s G. Register event
D. Delay H. Trip
Each stage can be connected to supervise any of the following inputs and signals:
• Input I0 for all networks other than solidly earthed.
• Calculated signal I0 Calc for solidly and low-impedance earthed networks.. I0
Calc = IL1 + IL2 + IL3.
Short earth faults make the protection to start but do not cause a trip. A short fault
means one cycle or more.
When starting happens often enough, transient intermittent faults can be cleared
using the intermittent time setting.
When a new start happens within the set intermittent time, the operation delay
counter is not cleared between adjacent faults, and finally the stage trips.
There are five separately adjustable earth fault overcurrent stages: I0>, I0>>,
I0>>>, I0>>>> and I0>>>>>. The first stage I0> can be configured for definite time
(DT) or dependent time operation characteristic (IDMT). The other stages have
definite time operation characteristic. By using the definite delay type and setting
the delay to its minimum, an instantaneous (ANSI 50N) operation is obtained.
Using the directional earth fault overcurrent stages (5.31 Directional earth fault
overcurrent (ANSI 67N)) in nondirectional mode, three more stages with
dependent operate time delay are available for nondirectional earth fault
overcurrent protection.
Dependent delay means that the operate time depends on the amount the
measured current exceeds the start setting. The bigger the fault current is, the
faster is the operation. Accomplished dependent delays are available for the I0>
stage. The relay shows a scaleable graph of the configured delay on the local
panel display.
The maximum measured secondary earth fault overcurrent is 10 x I0N and the
maximum measured phase current is 50 x IN. This limits the scope of dependent
curves with high start settings.
Setting groups
Characteristics
IDMT function:
0.025–20.0, except
Inaccuracy:
Moderately Inverse
Inaccuracy:
Inaccuracy:
The earth fault overcurrent stage (ANSI 50N/51N) and directional earth fault
overcurrent stage (ANSI 67N) have an inbuilt detection algorithm to detect a faulty
phase. This algorithm is meant to be used in radial-operated distribution
networks. The faulty phase detection can be used in solidly-earthed, impedance-
earthed or resonant-earthed networks.
Operation
The faulty phase detection starts from the earth fault stage trip. At the moment of
stage start, the phase currents measured prior to start are registered and stored
as prior-to-fault currents. At the moment of trip, phase currents are registered
again. Finally, faulty phase detection algorithm is performed by comparing prior-
to-fault currents to fault currents. The algorithm also uses positive sequence
current and negative sequence current to detect faulty phase.
The detected faulty phase is registered in the protection stage fault log (and also
in the event list and alarm screen). Faulty phase is also indicated by a line alarm
and line fault signals in the output matrix.
Possible detections of faulty phases are L1-N, L2-N, L3-N, L1-L2-N, L1-L3-N, L2-
L3-N, L1-L2-L3-N, and REV. If the relay protection coordination is incorrect, REV
indication is given in case of a relay sympathetic trip to a reverse fault.
P3U10 x x
P3U20 x x
P3U30 x x
NOTE: Configure the capacitor bank unbalance protection through the earth
fault overcurrent stages I0>>> and I0>>>>.
Description
The relay enables capacitor, filter and reactor bank protection. The capacitor
unbalance protection requires an IL1 current to polarize the unbalance
measurement. Use the earth fault overcurrent input for the unbalance current
measurement of a double-wye connected unearthed bank.
As the capacitor elements are not identical and have acceptable tolerances, there
is a natural unbalance current between the starpoints of the capacitor banks. This
natural unbalance current can be compensated to tune the protection sensitive
against real faults inside the capacitor banks.
X1:1
IL1
X1
X1:2
X1:3
IL2
X1:4
X1:5
IL3
X1:6
X1:7
Io 5A
X1:8
X1:9
Io 1A
X1:10
Compensation method
This feature is implemented to the stage I0>>>>, while the other stage I0>>> can
still function as normal unbalance protection stage with the compensation
method. Normally, the I0>>>> could be set as an alarming stage while stage I0>>>
trips the circuit breaker.
The stage I 0>>>> should be set based on the calculated unbalance current
change of one faulty element. You can calculate this using the following formula:
Equation 21
U L− N U L− N
−
(2 ⋅ π ⋅ f ⋅ C1 ) −1 (2 ⋅ π ⋅ f ⋅ C2 ) −1
3I 0 =
3
90
3I0
A
180 0
B
270
If there is an element failure in the bank, the algorithm checks the phase angle of
the unbalance current related to the phase angle of the phase current IL1. Based
on this angle, the algorithm can increase the corresponding faulty elements
counter (there are six counters).
Easergy P3 H I
G C
A B
F D
E
You can set for the stage I0>>>> the allowed number of faulty elements. For
example, if set to three elements, the fourth fault element will issue the trip signal.
The fault location is used with internal fused capacitor and filter banks. There is
no need to use it with fuseless or external fused capacitor and filter banks, nor
with the reactor banks.
Application example
12kV A
I B
I0
Characteristics
Inaccuracy:
– via the Easergy P3 device's front panel: go to the I0>>>> menu, scroll
right to 1 SET 50N/51N, and select Location for CMode.
– via the device's front panel: go to the I0>>>> menu, scroll right to SET2
50N/51N, and select Get for SaveBal.
Equation 22
U L− N U L− N
−
(2 ⋅ π ⋅ f ⋅ C1 ) −1
(2 ⋅ π ⋅ f ⋅ C 2 ) −1
3I 0 =
3
6928 6928
−
(2 ⋅ π ⋅ 50 ⋅ 43.81 ⋅ 10 −6 ) −1 (2 ⋅ π ⋅ 50 ⋅ 43.81 ⋅ 10 −6 ) −1
3I 0 =
3
3I 0 = 1.37 A
Failure of one element inside the bank on the left branch causes
approximately 1.37 ampere unbalance current at the star point. On the right
branch, there are two capacitor units in parallel, and therefore, a failure of one
element causes only 0.69 ampere unbalance. A different start value for each
branch is necessary. Set the start value to 80% of the calculated value.
4. Test the operation of the unbalance protection.
0.80
0.60
0.40
0.20
0.00
Conduct testing by injecting current to channels IL1 and I01 of the device. In
the example above, 0.69 A primary current is injected to the I01 channel. I01 is
leading the phase current IL1 by 60 degrees. This means the fault has to be
on the right branch and in phase 2. Compensation happens automatically
after the set operate time until the allowed total amount of failed units is
exceeded (Max. allowed faults). In this application, the fourth failed element
would cause the stage to trip.
P3U10 x
P3U20 x
P3U30 x
Description
The locked rotor protection stage Ilr> measures the fundamental frequency
component of the phase currents and calculates the average of the measured
three phase currents (= phase current IL).
The locked rotor stage protects the motor when too heavy load or a mechanical
failure of the motor causes rotor jam during the motor running condition.
The stage's start setting is relative to the motor's nominal starting current. The
nominal starting current can be configured in the Motor start-up supervision stage
(ANSI 48).
The locked rotor stage can be configured for definite time or dependent time
operation characteristic. Equation 23 defines the dependent operate time.
Equation 23
2
I
T = START k
IMEAS
When the calculated average phase current IL exceeds the defined start setting,
the locked rotor protection stage starts operation delay calculation. The stage
releases when the average phase current IL drops below the start setting. The
stage operation is automatically blocked when the motor status is “starting”. For
details of the criteria for motor status, see Motor status view.
Block diagram
Figure 103 - Block diagram of the locked rotor protection stage Ilr>
Im1
Im2 AVG > & I
Im3
& J
A
t
>1 K
& J
B C D E F G H
Setting groups
Characteristics
Inaccuracy: -
P3U10
P3U20
P3U30 x x
Description
The voltage-dependent overcurrent stage IV> is typically used for generator short-
circuit protection in applications where the static excitation system of the
generator is fed only from the generator terminals. Other possible applications are
conditions where the fault current level depends on the sources feeding the fault.
In close-by short circuits, the fault current rapidly decreases, thus jeopardizing the
operation of the high-set short circuit protection. The operation can be secured
using the voltage-dependent overcurrent function.
When the generator terminal or busbar voltage falls below the set voltage level,
the start current level of the overcurrent stage IV> also starts falling linearly
controlled by the control voltage according to the characteristic curve.
When the setting parameters are selected according to Figure 105, the function is
said to be voltage-controlled.
The voltage setting parameters UX1 and UX2 are proportional to the rated voltage
of the generator or busbar. They define the voltage limits, within which the start
current of the overcurrent unit is restrained. The multipliers IY1 and IY2 are used
for setting the area of change of the start level of the overcurrent function in
proportion to the UX1 and UX2 settings.
Setting groups
Characteristics
Settings:
Inaccuracy:
P3U10
P3U20
P3U30 x x
Description
Overvoltage protection is used to detect too high system voltages or to check that
there is sufficient voltage to authorize a source transfer.
The overvoltage function measures the fundamental frequency component of the
line-to-line voltages regardless of the voltage measurement mode (see 9.7
Voltage measurement modes). By using line-to-line voltages any line-to-neutral
over-voltages during earth faults have no effect. (The earth fault protection
functions take care of earth faults.) Whenever any of these three line-to-line
voltages exceeds the start setting of a particular stage, this stage starts and a
start signal is issued. If the fault situation remains on longer than the operate time
delay setting, a trip signal is issued.
In solidly earthed, four-wire networks with loads between phase and neutral
voltages, overvoltage protection may be needed for line-to-neutral voltages, too.
In such applications, the programmable stages can be used. 5.39 Programmable
stages (ANSI 99).
There are three separately adjustable stages: U>, U>> and U>>>. All the stages
can be configured for the definite time (DT) operation characteristic.
The U> stage has a settable reset delay that enables detecting intermittent faults.
This means that the time counter of the protection function does not reset
immediately after the fault is cleared, but resets after the release delay has
elapsed. If the fault appears again before the release delay time has elapsed, the
delay counter continues from the previous value. This means that the function
eventually trips if faults are occurring often enough.
Configurable hysteresis
The dead band is 3% by default. This means that an overvoltage fault is regarded
as a fault until the voltage drops below 97% of the start setting. In a sensitive
alarm application, a smaller hysteresis is needed. For example, if the start setting
is about only 2% above the normal voltage level, the hysteresis must be less than
2%. Otherwise, the stage does not release after fault.
Block diagram
Figure 106 - Block diagram of the three-phase overvoltage stages U>, U>> and
U>>>
3vus
Um1
Um2 MAX > & G
Um3 ts tr
& H
A
t
I
& H
B C D E F
Setting groups
Characteristics
Inaccuracy:
Inaccuracy:
60) This
is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in Easergy Pro to accept the zero operate time setting for the DT function.
Inaccuracy:
P3U10 x
P3U20 x
P3U30 x
Description
Especially in filter applications, there are harmonics and depending on the phase
angles the harmonics can increase the peak voltage. This stage calculates the
worst-case overvoltage in per-unit values using the Equation 24 (IEC 60871-1).
Harmonics up to 15th are taken into account.
Equation 24
15
XC In
UC =
U CLN
∑n
n =1
where
Equation 25
1
XC =
2πfC
c = Single phase capacitance between phase and starpoint. This is the setting
value CSET.
Equation 24 gives the maximum possible voltage, while the actual voltage
depends on the phase angles of the involved harmonics.
Equation 26
Q N = 2πf N U CLN
2
C SET
Equation 27
C SET = C NamePlate
Figure 107 - Capacitor bank built of three single-phase units connected in wye (III
Y). Each capacitor is 100 µF and this value is also used as the setting value.
UcFig1
UN = 10 kV
f = 50 Hz
CSET = 100 μF
Q = 3.14 Mvar
Equation 28
C SET = 2C AB
CAB is the name plate capacitance which is equal to capacitance between phases
A and B.
UN = 10 kV
f = 50 Hz
UN = 10 kV
Q50Hz = 3.14 Mvar
Q60Hz = 3.77 Mvar
CSET = 100 μF CAB = 50 μF
CAB = 50 μF 3 x 100 μF
Q = 3.14 Mvar
The capacitor bank is built of three separate 100 µF capacitors connected in wye
(Y). The rated voltage of the capacitors is 8000 V, the measured frequency is
50.04 Hz and the rated frequency is 50 Hz.
IL1 = 181 A
2% = 3.62 A
7% = 12.67 A
5% = 9.05 A
QN = 2011 kvar
The phases L2 and L3 are calculated similarly. The highest of the three values is
compared to the start setting.
Setting groups
Characteristics
Inaccuracy:
- Time ±1% or ±1 s
P3U10 x x
P3U20 x x
P3U30 x x
Description
Whenever the measured value exceeds the start setting of a particular stage, this
stage starts and a start signal is issued. If the fault situation remains on longer
than the operate time delay setting, a trip signal is issued.
There are three separately adjustable stages: U0>, U0>> and U0>>>. All stages
can be configured for the definite time (DT) operation characteristic.
Block diagram
Figure 109 - Block diagram of the neutral voltage displacement stages U0>, U0>>,
U0>>>
U0sblock
A > ts tr
& G
& H
B
t
I
& H
C D E F
A. U0 F. Enable events
B. Blocking G. Start
C. Setting U0>s H. Register event
D. Release delay I. Trip
E. Delay
Setting groups
Characteristics
Inaccuracy:
Inaccuracy:
Inaccuracy:
P3U10 x
P3U20 x
P3U30 x
Description
The simplest way to start an asynchronous motor is just to switch the stator
windings to the supply voltages. However, every such start heats up the motor
considerably because the initial currents are significantly above the rated current.
If the motor manufacturer has defined the maximum number of starts within an
hour or the minimum time between two consecutive starts, this stage is easy to
apply to prevent too frequent starts.
When the current has been less than 10 % of the motor nominal current and then
exceeds the value Motor start detection current of IST> (Motor start-up supervision
stage, ANSI 48), the situation is recognized as a motor start. After the recognition
of the motor start, if the current drops to less than 10 % of the motor nominal
current, the stage considers the motor to be stopped.
The motor restart inhibition stage provides an N> alarm signal when the second
last start has been done and remains active until the maximum amount of motor
starts have been reached or one hour of time has passed.
The N> motor start inhibit signal activates after starting the motor and remains
active a period of time that is defined for parameter Min time between motor
starts. After the given time has passed, the inhibit signal returns to inactive state.
When the stage's start counter reaches the value defined for Max. motor starts/
hour, the N> motor start inhibit signal activates and remains active until one hour
has passed.
Set the parameter Def. elap time from motor start to 120 min if the ANSI 66
stage is required to give permission to start the motor immediately after the relay
is powered. If this setting is 0 min, the motor is not started until the Min time
between motor starts delay has elapsed.
The motor restart inhibition stage's correlation to the output contacts is defined in
the output matrix menu. See 4.4.1 Output matrix.
Figure 110 shows an application for preventing too frequent starting using the N>
stage. Closed coil wire has been connected through the normal close (NC)
contact of the signal relay A1, and A1 is controlled with the N> start inhibit signal.
Whenever the N> motor start inhibit signal becomes active, it prevents circuit
breaker closing.
Figure 110 - Application for preventing too frequent starting using the N> stage
+ +
- -
STOP Open Close START
Coil Coil
M
+
Easergy P3
Output matrix
T1 A1
I> start
I> trip
N> alar m
N> motor start inhibi t
Setting groups
Characteristics
Settings: -
- Min. time between motor starts 62) 0.0–100 min. (step 0.1 min)
P3U10
P3U20
P3U30 x x
Description
The stages are sensitive to the amplitude of the highest fundamental frequency
current of the three measured phase currents.
A typical characteristic is shown in Figure 111. The base angle setting is -30°. The
stage starts if the tip of the three phase current phasor gets into the grey area.
NOTE: If the maximum possible earth fault current is greater than the used
most sensitive directional overcurrent setting, connect the relay to the line-to-
neutral voltages instead of line-to-line voltages to get the right direction for
earth faults, too. For networks having the maximum possible earth fault
current less than the over current setting, use 67N, the directional earth fault
stages.
Voltage memory
Im +90°
2°
-ind. +cap.
SET
VALUE
0° +res.
-res. ILOAD Re
TRIP AREA
-cap. +ind.
-90° ldir_angle2
Directional+back-up mode works the same way as the directional mode, but it has
undirectional backup protection in case a close-up fault forces all voltages to
about zero. After the angle memory hold time, the direction would be lost.
Basically the directional+backup mode is required when operate time is set longer
than voltage memory setting and no other undirectional back-up protection is in
use.
Figure 112 - Difference between directional mode and non-directional mode. The
grey area is the trip region.
+90° +90°
-ind. +cap. -ind. +cap.
2°
DIRECTIONAL NON-DIRECTIONAL
SET SET
VALUE 0° VALUE 0°
-res. +res. -res. +res.
BASE ANGLE= 0°
-90° -90°
Figure 113 - Bi-directional application with two stages Iφ> and Iφ>>
+90°
-ind. +cap.
4°
Iφ>> TRIP AREA
SET SET
VALUE VALUE 0°
-res. +res.
BASE ANGLE= 0°
-cap. +ind.
When any of the three phase currents exceeds the setting value and, in
directional mode, the phase angle including the base angle is within the active
±88° wide sector, the stage starts and issues a start signal. If this fault situation
remains on longer than the delay setting, a trip signal is issued.
There are four separately adjustable stages available:Iφ>, Iφ>>, Iφ>>> and
Iφ>>>>.
Stages Iφ> and Iφ>> can be configured for definite time or dependent time
characteristic. See 5.6 Dependent operate time for details of the available
dependent delays.
Stages Iφ>>> and Iφ>>>> have definite time (DT) operation delay. The relay
shows a scaleable graph of the configured delay on the local panel display.
The maximum measured secondary current is 50 x IN. This limits the scope of
dependent curves with high start settings. See 5.6 Dependent operate time for
more information.
Setting groups
Characteristics
Mode Directional/Directional+BackUp
IDMT function:
0.025–20.0, except
Inaccuracy:
- Starting (rated value IN= 1–5A) ±3% of the set value or ±0.5% of the rated
value
- Angle
±2° U>5 V
±30° U= 0.1–5.0 V
- Operate time at definite time function
±1% or ±25 ms
- Operate time at IDMT function
±5% or at least ±30 ms63)
63) This is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in Easergy Pro to accept the zero operate time setting for the DT function.
64) EI = Extremely Inverse, NI = Normal Inverse, VI = Very Inverse, LTI = Long Time Inverse, MI=
Moderately Inverse
Mode Directional/Directional+BackUp
Inaccuracy:
- Starting (rated value IN= 1 – 5A) ±3% of the set value or ±0.5% of the rated
value
- Angle
±2° U> 5 V
±30° U = 0.1–5.0 V
- Operate time at definite time function
±1% or ±25 ms
65) This
is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in Easergy Pro to accept the zero operate time setting for the DT function.
P3U10 x x
P3U20 x x
P3U30 x x
Description
The earth fault protection is adapted for various network earth systems.
Polarization
This mode consists of two sub modes, Res and Cap. A digital signal can be
used to dynamically switch between these two submodes. When the digital
input is active (DI = 1), Cap mode is in use and when the digital input is
inactive (DI = 0), Res mode is in use. This feature can be used with
compensated networks when the Petersen coil is temporarily switched off.
◦ Res
This mode is used with networks earthed with a small resistance. In this
context, "small" means that a fault current may be more than the rated phase
currents. The trip area has a shape of a sector as drawn in Figure 116. The
base angle is usually set to zero degrees or slightly on the lagging inductive
side (negative angle).
• Undir
This mode makes the stage equal to the undirectional stage I0>. The phase
angle and U0 amplitude setting are discarded. Only the amplitude of the
selected I0 input is supervised.
Each stage can be connected to supervise any of the following inputs and signals:
Short earth faults make the protection start but does not cause a trip. A short fault
means one cycle or more. For shorter than 1 ms transient type of intermittent
earth faults in compensated networks, there is a dedicated stage I0INT> 67NI.
When starting happens often enough, such intermittent faults can be cleared
using the intermittent time setting.
When a new start happens within the set intermittent time, the operation delay
counter is not cleared between adjacent faults and finally the stage trips.
There are three separately adjustable stages: I0φ>, I0φ>> and I0φ>>>. All the
stages can be configured for definite time delay (DT) or dependent time delay
operate time.
Accomplished dependent delays are available for all stages I0φ>, I0φ>> and
I0φ>>>.
The relay shows a scalable graph of the configured delay on the local panel
display.
The maximum measured secondary earth fault overcurrent is 10 x I0N and the
maximum measured phase current is 50 x IN. This limits the scope of dependent
curves with high start settings.
Block diagram
Figure 114 - Block diagram of the directional earth fault overcurrent stages I0φ>,
I0φ>>, I0φ>>>
I0fiisblock
A Isinφ
Icosφ
> & I
& J
B
C K
> t
& J
D E F G H
A. I0 G. Delay
B. Block H. Enable events
C. U0 I. Start
D. Choise Icosφ (Res) / Isinφ (Cap) J. Register event
E. Setting Iφ > s K. Trip
F. Setting I0 > s
+90º
CAP
Iosin φ
I0φ>
I0
RES
φ
0º
Iocos φ -U0
I0φ>
Res mode can be used with compensated networks. Cap mode is used with unearthed networks.
I0
TRIP AREA +152º +32º
I0φ> 120º
70º 0º 0º
-U0 120º -U0
70º I0φ>
-15º
I0
TRIP AREA
-85º -88º
IoDir_SectorAdj
The drawn I0 phasor is inside the trip area. The angle offset and half sector size are user’s
parameters.
Setting groups
Characteristics
I0φ>>: I0 or I0 Calc
Mode Non-directional/Sector/ResCap
IDMT function:
0.025–20.0, except
Inaccuracy:
- Starting U0 & I0 (rated value In= 1–5A) ±3% of the set value or ±0.3% of the rated
value
- Starting U0 & I0 (Peak Mode when, rated ±5% of the set value or ±2% of the rated
value I0n= 1–10A) value (Sine wave <65 Hz)
- Starting U0 & I0 (I0 Calc) ±3% of the set value or ±0.5% of the rated
value
else ±20°
Moderately Inverse
Mode Non-directional/Sector/ResCap
IDMT function:
0.05–20.0, except
Inaccuracy:
- Starting U0 & I0 (rated value In= 1 – 5A) ±3% of the set value or ±0.3% of the rated
value
- Starting U0 & I0 (Peak Mode when, rated ±5% of the set value or ±2% of the rated
value I0n= 1 – 10A) value (Sine wave <65 Hz)
- Starting U0 & I0 (I0 Calc) ±3% of the set value or ±0.5% of the rated
value
else ±20°
Moderately Inverse
The earth fault overcurrent stage (ANSI 50N/51N) and directional earth fault
overcurrent stage (ANSI 67N) have an inbuilt detection algorithm to detect a faulty
phase. This algorithm is meant to be used in radial-operated distribution
networks. The faulty phase detection can be used in solidly-earthed, impedance-
earthed or resonant-earthed networks.
Operation
The faulty phase detection starts from the earth fault stage trip. At the moment of
stage start, the phase currents measured prior to start are registered and stored
as prior-to-fault currents. At the moment of trip, phase currents are registered
again. Finally, faulty phase detection algorithm is performed by comparing prior-
to-fault currents to fault currents. The algorithm also uses positive sequence
current and negative sequence current to detect faulty phase.
The detected faulty phase is registered in the protection stage fault log (and also
in the event list and alarm screen). Faulty phase is also indicated by a line alarm
and line fault signals in the output matrix.
Possible detections of faulty phases are L1-N, L2-N, L3-N, L1-L2-N, L1-L3-N, L2-
L3-N, L1-L2-L3-N, and REV. If the relay protection coordination is incorrect, REV
indication is given in case of a relay sympathetic trip to a reverse fault.
P3U10 x
P3U20 x
P3U30 x
Description
The directional transient intermittent earth fault protection is used to detect short
transient intermittent faults in compensated cable networks. The transient faults
are self-extinguished at some zero crossing of the transient part of the fault
current IFault and the fault duration is typically only 0.1 ms – 1 ms. Such short
intermittent faults can not be correctly recognized by normal directional earth fault
function using only the fundamental frequency components of I0 and U0.
Although a single transient fault usually self extinguishes within less than one
millisecond, in most cases a new fault happens when the phase-to-earth voltage
of the faulty phase has recovered.
Figure 117 - Typical phase-to-earth voltages, earth fault overcurrent of the faulty
feeder and the neutral voltage displacement voltage U0 during two transient earth
faults in phase L1. In this case, the network is compensated.
EFtransientFig3
UL1
UL2
UL3
I0
U0
Direction algorithm
The function is sensitive to the instantaneous sampled values of the earth fault
overcurrent and neutral voltage displacement voltage. The neutral displacement
voltage can be measured directly with a broken delta transformer or derived from
the measured phase voltages.
I0 start sensitivity
The sampling time interval of the relay is 625 μs at 50 Hz (32 samples/cycle). The
I0 current spikes can be quite short compared to this sampling interval.
Fortunately, the current spikes in cable networks are high and while the anti-alias
filter of the relay attenuates the amplitude, the filter also makes the pulses wider.
Thus, when the current pulses are high enough, it is possible to detect pulses that
have a duration of less than twenty percent of the sampling interval. Although the
measured amplitude can be only a fraction of the actual peak amplitude, it does
not disturb the direction detection because the algorithm is more sensitive to the
sign and timing of the I0 transient than to the absolute amplitude of the transient.
Although the sensitivity of the I0 start is not critical, there is a selection between
two fixed settings values of I0. A sensitive start setting can be used in small
networks with lower residual current.
The transient intermittent earth fault current stage I0INT> should always be used
together with the normal directional earth fault overcurrent protection stages I0φ>,
I0φ>>. The transient stage I0INT> may in worst case detect the start of a steady
earth fault in wrong direction but does not trip because the peak value of a steady
state sine wave I0 signal must also exceed the corresponding base frequency
component's peak value to make the I0INT> to trip.
The operate time of the transient stage I0INT> should be lower than the settings of
any directional earth fault overcurrent stage to avoid any unnecessary trip from
the I0φ>, I0φ>> stages .The start signal of the I0INT> stage can be also used to
block I0φ>, I0φ>> stages of all parallel feeders.
Auto reclosing
The start signal of any I0φ> stage initiating auto reclosing (AR) can be used to
block the I0INT> stage to avoid the I0INT> stage with a long intermittent setting to
interfere with the AR cycle in the middle of discrimination time.
Usually the I0INT> stage itself is not used to initiate any AR. For transient faults,
the AR does not help because the fault phenomena itself already includes
repeating self-extinguishing.
• operation delay
• required amount of peaks
• residual voltage limit
• intermittent time
All requirements need to be satisfied before the stage issues a trip signal. Also,
the residual voltage requirement needs to be satisfied at the moment of trip.
There is also a settable reset delay: to ensure that the stage does not release
before the circuit breaker has operated. The setting range for the required amount
of peaks is 1–20 s and the setting range for the operational delay is 0.02–300 s.
The reset delay setting range is 0.06–300 s. The intermittent time setting is 0.01–
300 s. If, for example, the setting for peaks is set to 2 and the setting for operation
delay to 160 ms and intermittent time to 200 ms, then the function starts
calculating the operation delay from the first peak and after the second peak in 80
ms peak amount criteria is satisfied and when 160 ms comes full, the operate
time criteria is satisfied and the stage issues trip (Figure 118). If the second peak
does not come before the operational delay comes full, the stage is released after
the intermittent time has come full. But if the second peak comes after the operate
time has come full but still inside intermittent time, then a trip is issued instantly
(Figure 119). If the intermittent time comes full before the operation delay comes
full, the stage is released (Figure 120). There are a of couple limitations to avoid
completely incorrect settings. The algorithm assumes that peaks cannot come
more often than 10 ms, so if the peak amount is set to 10, then the operation
delay does not accept a value smaller than 100 ms and also, if the operational
delay is set to 40 ms, then it is not possible to set a peak amount setting higher
than 4. This is not fail proof but prohibits the usage of settings that can never be
satisfied.
Figure 118 - Set peak amount is satisfied and operate time comes full inside
intermittent time setting. Stage issues a trip.
Uo
Io
Figure 119 - Peak amount is not satisfied when operation delay comes full but last
required peak comes during intermittent time. Stage issues instant trip when peak
amount comes satisfied.
Uo
Io
Figure 120 - Peak amount is satisfied but intermittent time comes full before
operate time comes full. Stage is released.
Uo
Io
Block diagram
Figure 121 - Block diagram of the directional transient intermittent earth fault
stage I0INT>
i0tBlock
A
I0 I0
O
B P > L
& P
C
DIV
D >
R n M Q
U0 U0
G H I J K
Setting groups
Characteristics
Reverse
Inaccuracy:
- Time transients
P3U10 x x
P3U20 x x
P3U30 x x
Description
This stage can be used to block other stages and to indicate possible primary
faults in the power distribution network. The ratio between the second harmonic
component and the fundamental frequency component is measured on all the
phase currents. When the ratio in any phase exceeds the setting value, the stage
gives a start signal. After a settable delay, the stage gives a trip signal.
The start and trip signals can be used for blocking the other stages.
The trip delay is irrelevant if only the start signal is used for blocking.
The trip delay of the stages to be blocked must be more than 60 ms to ensure a
proper blocking.
Block diagram
2ndHarm
Im1
Im2 MAX > & E
Im3 ts tr
& F
A
t
G
& F
B C D
A. Block E. Start
B. Setting 2nd harmonics F. Register event
C. Delay G. Trip
D. Enable events
Characteristics
Settings:
Inaccuracy:
P3U10 x x
P3U20 x x
P3U30 x x
Description
The ratio between the fifth harmonic component and the fundamental frequency
component is measured on all the phase currents. When the ratio in any phase
exceeds the setting value, the stage activates a start signal. After a settable delay,
the stage operates and activates a trip signal.
The trip delay of the stages to be blocked must be more than 60 ms to ensure a
proper blocking.
Characteristics
Settings:
Inaccuracy:
P3U10 x
P3U20 x
P3U30 x
Description
The AR function uses the object control function to control objects. All other object
control methods are in simultaneous use, including object failure monitoring. If the
circuit breaker (CB) control fails or another function controls the CB, the AR
sequence stops.
Purpose
Normal protection functions detect the fault and then trigger the AR function. After
tripping the circuit breaker, the AR function can reclose the CB. Normally, the first
reclose (or shot) is so short in time that consumers cannot notice anything.
However, the fault is cleared and the feeder will continue in normal service.
AR working principles
Even though the basic principle of AR is very simple, there are a lot of different
timers and parameters that have to be set.
In Easergy P3 relays, there are five shots. A shot consists of open time (so called
“dead” time) and closed time (so called “burning” time or discrimination time). A
high-speed shot means that the dead time is less than one second. The time-
delayed shot means longer dead times up to two to three minutes.
There are four AR lines for each shot (1–5). Enable the desired line (AR1‑4) to
trig the required shot. If none of the AR lines are selected but the AR function is
enabled, the AR makes a final trip. A line means an initialization signal for AR.
Normally, start or trip signals of protection functions are used to initiate an AR
sequence. Each AR line has a priority. AR1 has the highest and AR4 has the
lowest priority. This means that if two lines are initiated at the same time, AR
follows only the highest priority line. A very typical configuration of the lines is that
the instantaneous overcurrent stage initiates the AR1 line, time-delayed
overcurrent stage the AR2 line and earth fault protection use lines AR3 and AR4.
The AR matrix in Figure 123 describes the start and trip signals forwarded to the
AR function
A B C D E F G H I
M
|>>s
|>t
|>s
J N On
0...300 s 0...300 s
On
0...300 s 0...300 s 0...300 s 0...300 s P
O
Off 0...300 s 0...300 s
On
K
Q R
A. AR matrix J. Shot 1
B. Ready (wait for AR request) K. Shot 2
C. Enable L. Shot 3...5
D. Start delay M. Critical
E. Open CB N. AR 1
F. Dead time O. AR 2
G. Close CB P. Reclaim time succeeded. Move back to shot 1.
H. Discrimination time Q. If critical signal is activated during discrimination time, make final
trip
I. Reclaim time R. If new AR request is activated during reclaim time, continue on
next shot
After the start delay, the CB is opened if it is closed. When the CB opens, a dead
time timer is started. Each shot from 1 to 5 has its own dead time setting.
After the dead time, the CB is closed and a discrimination time timer is started.
Each shot from 1 to 5 has its own discrimination time setting. If a critical signal is
activated during the discrimination time, the AR function makes a final trip. The
CB opens and the AR sequence is locked. Closing the CB manually clears the
“locked” state.
After the discrimination time has elapsed, the reclaim time timer starts. If any AR
signal is activated during the reclaim time or the discrimination time, the AR
function moves to the next shot. The reclaim time setting is common for every
shot.
If the reclaim time runs out, the AR sequence is successfully executed and the
AR function moves to ready state and waits for a new AR request in shot 1.
Configure the protection stage’s start signal to initiate the AR function. A trip
signal from the protection stage can be used as a backup. If something fails in the
AR function, the trip signal opens the CB. The delay setting for the protection
stage should be longer than the AR start delay and discrimination time.
Manual closing
When CB is closed manually with the local panel, remote bus, digital inputs etc,
the reclaim state is activated. Within the reclaim time, all AR requests are ignored.
The protection stages take care of tripping. Trip signals of protection stages must
be connected to a trip relay in the output matrix.
Manual opening
Manual CB open command during AR sequence stops the sequence and leaves
the CB open.
This reclaim time setting defines reclaim time between different shots during a
sequence and also the reclaim time after manual closing.
• Use shot-specific reclaim time: Yes
This Reclaim time setting defines the reclaim time only for manual control.
The reclaim time between different shots is defined by shot-specific reclaim
time settings.
AR shots blocking
Each AR shot can be blocked with a digital input, virtual input or virtual output.
The blocking input is selected with the Block setting. When selected input is
active, the shot is blocked. A blocked shot is treated like it does not exist and AR
sequence jumps over it. If the last shot in use is blocked, any AR request during
reclaiming of the previous shot causes the final tripping.
Starting AR sequence
Each AR request has its own separate starting delay counter. The AR whose
starting delay has elapsed first is selected. If more than one delay elapses at the
same time, an AR request of the highest priority is selected. AR1 has the highest
priority and AR4 has the lowest priority. First shot is selected according to the AR
request. Next AR opens the CB and starts counting dead time.
Each AR request line can be enabled to any combination of the five shots. For
example, making a sequence of Shot 2 and Shot 4 for AR request 1 is done by
enabling AR1 only for those two shots.
Critical AR request
A critical AR request stops the AR sequence and causes final tripping. The critical
request is ignored when the AR sequence is not running.
The critical request is accepted during dead time and discrimination time.
When a starting delay has elapsed, an active signal is set for the first shot. If
successful reclosing is executed at the end of the shot, the active signal is reset
after the reclaim time. If the reclosing was not successful or a new fault appears
during the reclaim time, the active signal is reset for the current shot and an active
signal is set for the next shot (if there are any shots left before the final trip).
This signal indicates dead time. The signal is set after CB is opend. When dead
time ends, the signal is reset and CB is closed.
There are five final trip signals in the matrix, one for each AR request (1 to 4 and
1 critical). When a final trip is generated, one of these signals is set according to
the AR request which caused the final tripping. The final trip signal stays active for
0.5 seconds and then resets automatically.
DI to block AR setting
This setting is useful with an external synchro-check relay. This setting only
affects re-closing the CB. Re-closing can be blocked with a digital input, virtual
input or virtual output. When the blocking input is active, CB is not closed until the
blocking input becomes inactive again. When blocking becomes inactive, the CB
is controlled close immediately.
Figure 124 - Example sequence of two shots. After shot 2, the fault is cleared.
Discrimination
Discrimination
Dead Time2
Dead Time1
Start delay1
Reclaim
time1
time2
time
I> setting
Current
Open command
CB
Close command
CB
CBclose
state
CBopen
state
1. The current exceeds the I> setting; the start delay from shot 1 starts.
4. The dead time from shot 1 runs out; a CloseCB controlling output closes.
5. The CB closes. The CloseCB controlling output opens, and the discrimination
time from shot 1 starts. The current is still over the I> setting.
6. The discrimination time from the shot 1 runs out; the OpenCB relay output
closes.
7. The CB opens. The dead time from shot 2 starts, and the OpenCB relay
output opens.
8. The dead time from shot 2 runs out; the CloseCB controlling output closes.
9. The CB closes. The CloseCB controlling output opens, and the discrimination
time from shot 2 starts. The current is now under I> setting.
10. Reclaim time starts. After the reclaim time the AR sequence is successfully
executed. The AR function moves to wait for a new AR request in shot 1.
P3U10
P3U20
P3U30 x x
Description
Frequency protection is used for load sharing, loss of power system detection and
as a backup protection for overspeeding.
The frequency function measures the frequency from the two first voltage inputs.
At least one of these two inputs must have a voltage connected to be able to
measure the frequency. Whenever the frequency crosses the start setting of a
particular stage, this stage starts, and a start signal is issued. If the fault remains
on longer than the operating delay setting, a trip signal is issued. For situations
where no voltage is present, an adapted frequency is used.
The underfrequency stages are blocked when the biggest of the three line-to-line
voltages is below the low-voltage block limit setting. With this common setting,
LVBlk, all stages in underfrequency mode are blocked when the voltage drops
below the given limit. The idea is to avoid purposeless alarms when the voltage is
off.
When the biggest of the three line-to-line voltages has been below the block limit,
the underfrequency stages are blocked until the start setting has been reached.
There are four separately adjustable frequency stages: f><, f>><<, f<, f<<. The
two first stages can be configured for either overfrequency or underfrequency
usage. So totally four underfrequency stages can be in use simultaneously. Using
the programmable stages even more can be implemented (chapter 5.39
Programmable stages (ANSI 99)). All the stages have definite operate time delay
(DT).
Setting groups
Characteristics
Inaccuracy:
NOTE: If the relay restarts for some reason, there is no trip even if the
frequency is below the set limit during the start-up (Start and trip is blocked).
To cancel this block, frequency has to rise above the set limit.
Table 96 - Underfrequency f<, f<< (81L)
Inaccuracy:
P3U10
P3U20
P3U30 x x
Description
The rate of change of frequency (ROCOF or df/dt) function is used for fast load
shedding, to speed up operate time in overfrequency and underfrequency
situations and to detect loss of grid. For example, a centralized dedicated load
shedding relay can be omitted and replaced with distributed load shedding, if all
outgoing feeders are equipped with Easergy P3 relays.
A special application for ROCOF is to detect loss of grid (loss of mains, islanding).
The more the remaining load differs from the load before the loss of grid, the
better the ROCOF function detects the situation.
Load switching and fault situations may generate change in frequency. A load
drop may increase the frequency and increasing load may decrease the
frequency, at least for a while. The frequency may also oscillate after the initial
change. After a while, the control system of any local generator may drive the
frequency back to the original value. However, in case of a heavy short-circuit
fault or if the new load exceeds the generating capacity, the average frequency
keeps on decreasing.
Figure 125 - An example of definite time df/dt operate time. At 0.6 s, which is the
delay setting, the average slope exceeds the setting 0.5 Hz/s and a trip signal is
generated.
FREQUENCY ROCOF1_v3
(Hz)
Settings:
df/dt = 0.5 Hz/s
1. t = 0.60 s
0
Hz 0.5
/s Hz tMin = 0.60 s
/s
0.7
2.0
5H
Hz
z/s TIME
/s
(s)
START
TRIP
ROCOF implementation
The ROCOF function is sensitive to the absolute average value of the time
derivate of the measured frequency |df/dt|. Whenever the measured frequency
slope |df/dt| exceeds the setting value for 80 ms time, the ROCOF stage starts
and issues a start signal after an additional 60 ms delay. If the average |df/dt|,
since the start moment, still exceeds the setting, when the operation delay has
elapsed, a trip signal is issued. In this definite time mode the second delay
parameter "minimum delay, tMIN" must be equal to the operation delay parameter
"t".
If the frequency is stable for about 80 ms and the time t has already elapsed
without a trip, the stage resets.
One difference between the overfrequency and underfrequency and the df/dt
function is the speed. Often a df/dt function can predict an overfrequency or
underfrequency situation and is thus faster than a simple overfrequency or
underfrequency function. However, in most cases, standard overfrequency and
underfrequency stages must be used together with ROCOF to ensure tripping
also if the frequency drift is slower than the slope setting of ROCOF.
Figure 125 shows an example where the df/dt start value is 0.5 Hz/s and the
delay settings are t = 0.60 s and tMIN = 0.60 s. Equal times t = tMIN gives a definite
time delay characteristic. Although the frequency slope fluctuates, the stage does
not release but continues to calculate the average slope since the initial start. At
the defined operate time, t = 0.6 s, the average slope is 0.75 Hz/s. This exceeds
the setting, and the stage trips.
At slope settings less than 0.7 Hz/s, the fastest possible operate time is limited
according to the Figure 126.
Figure 126 - At very sensitive slope settings the fastest possible operate time is
limited.
ROCOF5_v3
Fastest possible operation time setting (s)
By setting the second delay parameter tMIN smaller than the operate time delay t,
a dependent type of operate time characteristic is achieved.
Figure 128 shows one example, where the frequency behavior is the same as in
the first figure, but the tMIN setting is 0.15 s instead of being equal to t. The
operate time depends on the measured average slope according to the following
equation:
Equation 29
s SET ⋅ t SET
t TRIP =
s
The minimum operate time is always limited by the setting parameter tMIN. In the
example, the fastest operate time, 0.15 s, is achieved when the slope is 2 Hz/s or
more. The leftmost curve in Figure 127 shows the dependent characteristics with
the same settings as in Figure 128.
ROCOF6_v3
Operation time (s)
Figure 128 - An example of dependent df/dt operate time. The time to trip will be
0.3 s, although the setting is 0.6 s, because the average slope 1 Hz/s is steeper
than the setting value 0.5 Hz/s.
FREQUENCY ROCOF3_v3
(Hz)
50.0 Settings:
df/dt = 0.5 Hz/s
t = 0.60 s
1.
0
0.5 tMin = 0.15s
H
Hz
z/
/s
s
0.7
2.0
5 Hz
Hz/
/s TIME
49.7
s
(s)
0.00 0.15 0.30 0.45 0.60
START
TRIP
Settings groups
Characteristics
Reset ratio 1
Inaccuracy:
- Operate time(overshoot ≥ 0.2 Hz/s) ±35 ms, when area is 0.2 – 1.0 Hz/s
72) This
is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in Easergy Pro to accept the zero operate time setting for the DT function.
NOTE: ROCOF stage is using the same low voltage blocking limit as the
frequency stages.
P3U10 x x
P3U20 x x
P3U30 x x
Description
The lockout feature, also called latching, can be programmed for outputs in the
Output matrix setting view. Any protection stage start or trip, digital input, logic
output, alarm and GOOSE signal connected to the following outputs can be
latched when required:
Figure 129 - The lockout programmed for LED A and I>> trip signals
In Figure 129, the latched signal is identified with a dot and circle in the matrix
signal line crossing.
The lockout can be released through the display or via the Easergy Pro. See
Chapter 4 Control functions.
In the General > Release latches setting view, select the Store latch state
setting to configure latched states of relay outputs, virtual outputs, binary outputs
(BO) and high-speed outputs (HSO) to be stored. If some of these outputs are
latched and in “on” state, and the device is restarted, their status is set back to
“on” after restart.
P3U10 x x
P3U20 x x
P3U30 x x
Description
For special applications, you can build your own protection stages by selecting
the supervised signal and the comparison mode.
f Frequency
P Active power
Q Reactive power
S Apparent power
Setting groups
6 Supporting functions
Table 99 - Example of Pgr1 stage trip on event and its visibility in local panel and
communication protocols
Events are the major data for a SCADA system. SCADA systems are reading
events using any of the available communication protocols. The Event log can
also be scanned using the front panel or Easergy Pro. With Easergy Pro, the
events can be stored to a file especially if the relay is not connected to any
SCADA system.
Only the latest event can be read when using communication protocols or
Easergy Pro. Every reading increments the internal read pointer to the event
buffer. (In case of communication interruptions, the latest event can be reread any
number of times using another parameter.) On the local panel, scanning the event
buffer back and forth is possible.
Event enabling/masking
You can make this modification in the Local panel conf setting view.
An indication screen (popup screen) can also be enabled in the same menu in
Easergy Pro. The oldest event is overwritten when a new event occurs. The
shown resolution of a time stamp is one millisecond, but the actual resolution
depends on the particular function creating the event. For example, most
The normal procedure is to poll events from the relay all the time. If this is not
done, the event buffer could reach its limits. In that case, the oldest event is
deleted and the newest displayed with OVF (overflow) code on the front panel.
Clear
yyyy-mm-dd Date
hh:mm:ss.nnn Time
The available recording channels depend on the voltage measurement mode, too.
If a channel is added for recording and the added signal is not available because
of the used settings, the signal is automatically rejected from the recording
channel list.
The recording can be triggered by any start or trip signal from any protection
stage, by a digital input, logic output or GOOSE signals. The triggering signal is
selected in the output matrix (vertical signal DR). The recording can also be
triggered manually. All recordings are time-stamped.
Reading recordings
The recordings can be uploaded with Easergy Pro program. The recording is in
COMTRADE format. This also means that other programs can be used to view
and analyse the recordings made by the relay.
Number of channels
Parameters
32/cycle Waveform
16/cycle Waveform
8/cycle Waveform
1/200ms Average
1/1s Average
1/5s Average
1/10s Average
1/15s Average
1/30s Average
1/1min Average
- Not active
Trig Recording
f Frequency X
CosPhi cosφ X
TanPhi tanφ X
NOTE: The selection of signals depends on the relay type, the used voltage
connection and the scaling mode.
Characteristics
Sample rate: -
1, 5, 10, 15, 30 s
1 min
Recording time (one record) 0.1 s–12 000 min (According recorder
setting)
The recording time and the number of records depend on the time setting and the
number of selected channels.
1. To select the channels and sample rate for the disturbance recorder:
a. In Easergy Pro, go to General > Disturbance recorder.
c. Click the Sample rate drop-down list, and select the desired rate.
3. To write the setting to the device, on the Easergy Pro toolbar, select Write
settings > Write all settings.
NOTE: To save the relay's configuration information for later use, also
save the Easergy Pro setting file on the PC. Use WaweWin or another
customer preferred tool to analyze disturbance recorder file.
a. On the Easergy Pro toolbar, click the Save icon. The Save a file window
opens.
b. Browse to the folder where you want to save the file. Type a descriptive
file name, and click Save.
NOTE: By default, the setting file *.epz is saved in the Easergy Pro
folder.
A situation is regarded as cold load when all the three phase currents have been
below a given idle value and then at least one of the currents exceeds a given
start level within 80 ms. In such a case, the cold load detection signal is activated
for the time set as Maximum time or until the measured signal returns below the
value set as Pickup current. This signal is available for the output matrix and
blocking matrix. Using virtual outputs of the output matrix setting group control is
possible.
Right after closing a circuit breaker, a given amount of overload can be allowed
for a given limited time to take care of concurrent thermostat-controlled loads. The
cold load start function does this, for example, by selecting a more coarse setting
group for overcurrent stages. It is also possible to use the cold load detection
signal to block any set of protection stages for a given time.
Magnetizing inrush detection is quite similar to the cold load detection but it also
includes a condition for second harmonic content of the currents. When all phase
currents have been below a given idle value and then at least one of them
exceeds a given start level within 80 ms and the second harmonic ratio to
fundamental frequency, If2/If1, of at least one phase exceeds the given setting, the
inrush detection signal is activated. This signal is available for the output matrix
and blocking matrix. Using virtual outputs of the output matrix setting group
control is possible.
By setting the second harmonic start parameter for If2/If1 to zero, the inrush signal
will behave equally with the cold load start signal.
The inrush current of transformers usually exceeds the start setting of sensitive
overcurrent stages and contains a lot of even harmonics. Right after closing a
circuit breaker, the start and tripping of sensitive overcurrent stages can be
avoided by selecting a more coarse setting group for the appropriate overcurrent
stage with an inrush detect signal. It is also possible to use the detection signal to
block any set of protection stages for a given time.
A C D
Pick-up
Idle
Cold load
A. No activation because the current has not been under the set IDLE current.
B. Current dropped under the IDLE current level but now it stays between the IDLE current and the
start current for over 80 ms.
C. No activation because the phase two lasted longer than 80 ms.
D. Now we have a cold load activation which lasts as long as the operate time was set or as long
as the current stays above the start setting.
Characteristics
Inrush settings:
The system clock should be externally synchronised to get comparable event time
stamps for all the relays in the system.
The synchronizing is based on the difference of the internal time and the
synchronizing message or pulse. This deviation is filtered and the internal time is
corrected softly towards a zero deviation.
Time zone offset (or bias) can be provided to adjust the relay's local time. The
offset can be set as a Positive (+) or Negative (-) value within a range of -15.00 to
+15.00 hours and a resolution of 0.01/h. Basically, resolution by a quarter of an
hour is enough.
Daylight time standards vary widely throughout the world. Traditional daylight/
summer time is configured as one (1) hour positive bias. The new US/Canada
DST standard, adopted in the spring of 2007 is one (1) hour positive bias, starting
at 2:00am on the second Sunday in March, and ending at 2:00am on the first
Sunday in November. In the European Union, daylight change times are defined
relative to the UTC time of day instead of local time of day (as in U.S.) European
customers, carefully check the local country rules for DST.
The daylight saving rules are by default UTC +2:00 (24-hour clock):
• Daylight saving time start: Last Sunday of March at 03.00
• Daylight saving time end: Last Sunday of October at 04.00
During tens of hours of synchronizing, the relay learns its average deviation and
starts to make small corrections by itself. The target is that when the next
synchronizing message is received, the deviation is already near zero.
Parameters "AAIntv" and "AvDrft" show the adapted correction time interval of this
±1 ms auto-adjust function.
If any external synchronizing source is not available and the system clock has a
known steady drift, it is possible to roughly correct the clock deviation by editing
the parameters "AAIntv" and "AvDrft". The following equation can be used if the
previous "AAIntv" value has been zero.
604.8
AAIntv =
DriftInOneWeek
If the auto-adjust interval "AAIntv" has not been zero, but further trimming is still
needed, the following equation can be used to calculate a new auto-adjust
interval.
1
AAIntvNEW =
1 DriftInOneWeek
+
AAIntvPREVIOUS 604.8
The term DriftInOneWeek/604.8 may be replaced with the relative drift multiplied
by 1000 if some other period than one week has been used. For example, if the
drift has been 37 seconds in 14 days, the relative drift is 37*1000/(14*24*3600) =
0.0306 ms/s.
Example 1
If there has been no external sync and the relay's clock is leading sixty-one
seconds a week and the parameter AAIntv has been zero, the parameters are set
as
AvDrft = Lead
604.8
AAIntv = = 9.9 s
61
With these parameter values, the system clock corrects itself with –1 ms every
9.9 seconds which equals –61.091 s/week.
Example 2
If there is no external sync and the relay's clock has been lagging five seconds in
nine days and the AAIntv has been 9.9 s, leading, then the parameters are set as
1
AAIntv NEW = = 10.6
1 5000
−
9.9 9 ⋅ 24 ⋅ 3600
AvDrft = Lead
When the internal time is roughly correct – the deviation is less than four seconds
– no synchronizing or auto-adjust turns the clock backwards. Instead, if the clock
is leading, it is softly slowed down to maintain causality.
y-d-m Year-Month-Day
d.m.y Day.Month.Year
m/d/y Month/Day/Year
77)
SyncDI Possible values The digital input
depends on the used for clock
types of I/O synchronization.
cards
Minute pulse
DI1 – DI6
input
Note: This is a
decimal number.
For example for
state of Nepal
the time zone
5:45 is given as
5.75
SySrc Clock
synchronization
source
Internal No sync
recognized
since 200s
DI Digital input
IRIG timecode
B00379)
Synchronization with DI
The clock can be synchronized by reading minute pulses from digital inputs,
virtual inputs or virtual outputs. The sync source is selected with the SyncDI
setting. When a rising edge is detected from the selected input, the system clock
is adjusted to the nearest minute. The length of the digital input pulse should be at
least 50 ms. The delay of the selected digital input should be set to zero.
Synchronization correction
If the sync source has a known offset delay, it can be compensated with the
SyOS setting. This is useful for compensating hardware delays or transfer delays
Sync source
When the relay receives new sync message, the sync source display is updated.
If no new sync messages are received within the next 1.5 minutes, the relay
switches over to internal sync mode.
IRIG standard time formats B003 and B004 are supported with a dedicated
communication option (See 12.2 Accessories).
IRIG-B input clock signal voltage level is TLL. The input clock signal originated in
the GPS receiver must be taken to multiple relays trough an IRIG-B distribution
module. This module acts as a centralized unit for a point-to-multiple point
connection.
NOTE: Daisy chain connection of IRIG-B signal inputs in multiple relays must
be avoided.
B
C
P3U P3x3x
The recommended cable must be shielded and either of coaxial or twisted pair
type. Its length must not exceed 10 meters.
Deviation
The time deviation means how much the system clock time differs from the sync
source time. The time deviation is calculated after receiving a new sync message.
The filtered deviation means how much the system clock was really adjusted.
Filtering takes care of small deviation in sync messages.
Auto-lag/lead
The relay synchronizes to the sync source, meaning that it starts automatically
leading or lagging to stay in perfect sync with the master. The learning process
takes a few days.
Easergy P3U10, P3U20 and P3U30 provides separate monitoring logs for sags
and swells. The voltage log is triggered if any voltage input either goes under the
sag limit (U<) or exceeds the swell limit (U>). There are four registers for both
sags and swells in the fault log. Each register contains start time, phase
information, duration and the minimum, average and maximum voltage values of
each sag and swell event. Furthermore, it contains the total number of sags and
swells counters as well as the total number of timers for sags and swells.
The voltage power quality functions are located under the submenu “U”.
Count - Cumulative
swell counter
Total - Cumulative
swell time
counter
Min1 % UN Minimum
voltage value
during the sag/
swell in the
input 1
Min2 % UN Minimum
voltage value
during the sag/
swell in the
input 2
Min3 % UN Minimum
voltage value
during the sag/
swell in the
input 3
Max1 % UN Maximum
voltage value
during the sag/
swell in the
input 1
Max2 % UN Maximum
voltage value
during the sag/
swell in the
input 2
Max3 % UN Maximum
voltage value
during the sag/
swell in the
input 3
Characteristics
Reset ration:
- Sag 1.03
- Swell 0.97
Inaccuracy:
If one of the line-to-line voltages is below sag limit and above block limit but
another line-to-line voltage drops below block limit, blocking is disabled.
The relay includes a simple function to detect voltage interruptions. The function
calculates the number of voltage interruptions and the total time of the voltage-off
time within a given calendar period. The period is based on the relay's real-time
clock. The available periods are:
• 8 hours, 00:00–08:00, 08:00–16:00, 16:00–24:00
• one day, 00:00–24:00
• one week, Monday 00:00 – Sunday 24:00
• one month, the first day 00:00 – the last day 24:00
• one year, 1st January 00:00 – 31st December 24:00
After each period, the number of interruptions and the total interruption time are
stored as previous values. The interruption counter and the total time are cleared
for a new period. Previous values are overwritten.
Voltage interruption is based on the value of the positive sequence voltage U1 and
a limit value you can define. Whenever the measured U1 goes below the limit, the
interruption counter is increased, and the total time counter starts increasing.
If the voltage has been significantly over the limit U1< and then there is a small
and short under-swing, it is not recognized (Figure 137).
U 1<
10 20 30 40 50 60 70 80 90 B
On the other hand, if the limit U1< is high and the voltage has been near this limit,
and then there is a short but very deep dip, it is not recognized (Figure 138).
A
U 1<
10 20 30 40 50 60 70 80 90
B
Month
Date - - Date
Time - - Time
Table 110 - Measured and recorded values of voltage sag measurement function
U1 % Measured
positive
sequence
voltage
Prev - Number of
voltage sags
during the
previous
observation
period
Characteristics
Inaccuracy:
P3U10 x x
P3U20 x x
P3U30 x x
Description
The relay supervises the current transformers (CTs) and the external wiring
between the relay terminals and the CTs. This is a safety function as well, since
an open secondary of a CT causes dangerous voltages.
The CT supervision function measures phase currents. If one of the three phase
currents drops below the IMIN< setting while another phase current exceeds the
IMAX> setting, the function issues an alarm after the operation delay has elapsed.
ILmin A Minimum of
phase currents
Time - Time of CT
supervision
alarm
Characteristics
Inaccuracy: -
P3U10
P3U20
P3U30 x x
Description
The relay supervises the voltage transformers (VTs) and VT wiring between the
relay terminals and the VTs. If there is a fuse in the voltage transformer circuitry,
the blown fuse prevents or distorts the voltage measurement. Therefore, an alarm
should be issued. Furthermore, in some applications, protection functions using
voltage signals should be blocked to avoid false tripping.
I2 %IN Measured
negative
sequence
current
Time - Time of VT
supervision
alarm
U2 %UN Recorded
negative
sequence
voltage
I2 %IN Recorded
negative
sequence
current
Characteristics
Inaccuracy: -
Circuit breaker (CB) wear is a function that monitors CB wear by calculating how
much wear the CB can sustain. It raises an alarm about the need for CB
maintenance before the condition of the CB becomes critical.
This function records the peak symmetrical current81) from each phase82), and
uses that magnitude as the breaking current for that phase to estimate the
amount of wear on the CB. The function then calculates the estimated number of
cycles or trips remaining before the CB needs to be replaced or serviced.
100000
10000
A 1000
100
50
20
10
100 200 500 1000 10000 100000
Up to eight points can be selected from the diagram and entered to the device.
Each point specifies a breaking current and the associated maximum number of
permitted operations. The device assumes there is a straight line between each
two consecutive points in the log-log diagram (that is, uses logarithmic
interpolation between the points), and thus forms an approximation of the
permissible cycle diagram. It should be possible to accurately describe most
permissible cycle diagrams in this way.
81) The used peak current is the magnitude of the fundamental frequency component. This
magnitude does not include a possible DC component.
82) The current is sampled every 10 milliseconds, starting from the moment the monitored trip relay
is asserted and ending when the current of every phase has decreased below one quarter of
the phase’s breaking current or after 500 milliseconds have elapsed, whichever happens first.
4 100 1
5 100 1
6 100 1
7 100 1
8 100 1
Alarm points
Two alarm points can be configured to notify about the approaching need for CB
maintenance.
The table in the Operations left setting view shows the number of operation
cycles left before the alarm points are reached. The number of remaining cycles
is tracked for each phase separately, and the alarm is raised when any phase
runs out of cycles.
83) Each cycle causes mechanical wear on the CB. In addition, large enough currents create arcs
inside the CB, which causes erosion of the electrical contacts for each phase. The larger the
current, the greater the erosion, and thus the greater the wear on the CB. A worn CB has fewer
cycles left at any breaking current.
The first alarm point can be set, for example, to the CB’s nominal current and the
second alarm point to a typical fault current.
When an alarm is raised, a signal is asserted in the output matrix. Also, an event
is created depending on the settings given in the Event enabling setting view.
Logarithmic interpolation
The permitted number of operations for the currents between the defined points is
logarithmically interpolated:
Equation 30
a
C=
In
C = permitted operations
I = interrupted current
Equation 31
a = C k I k2
Equation 32
Ck
ln
C k +1
n=
I
ln k +1
Ik
The current 6 kA lies between points 2 and 3 in the table. That gives value for the
index k. Using
k=2
Ck = 10000
Ck+1 = 80
Ik+1 = 31 kA
Ik = 1.25 kA
Equation 33
10000
ln
n= 80 = 1.5038
31000
ln
1250
Equation 34
Using Equation 30, the device gets the number of permitted operations for current
6 kA.
Equation 35
454 ⋅ 10 6
C= = 945
60001.5038
Alarm 2 is set to 6 kA. The CB failure protection supervises trip relay T1, and a
trip signal of an overcurrent stage detecting a two-phase fault is connected to this
trip relay T1. The interrupted phase currents are 12.5 kA, 12.5 kA and 1.5 kA. By
what number are Alarm2 counters decremented?
Using Equation 30 and values n and a from the previous example, the device gets
the number of permitted operations at 10 kA.
Equation 36
454 ⋅ 10 6
C10 kA = = 313
125001.5038
Equation 37
C AlarmMax
∆=
C
945
∆A = ∆B = =3
313
Thus, Alarm2 counters for phases L1 and L2 are decremented by 3. In phase L1,
the current is less than the alarm limit current 6 kA. For such currents, the
decrement is 1.
Δ L3 = 1
CBWEAR STATUS
Operations left
for
Al1L1
- Alarm 1, phase
Al1L2
L1
Al1L3
- Alarm 1, phase
Al2L1 L2
Al2L2 - Alarm 1, phase
Al2L3 L3
- Alarm 2, phase
L1
- Alarm 2, phase
L2
- Alarm 2, phase
L3
Latest trip
Broken current
of phase L3
CBWEAR SET
Alarm1
Alarm2
CBWEAR SET2
Circuit breaker (CB) condition monitoring monitors the CB wear with the help of
the cumulative breaking current. It raises an alarm about the need for CB
maintenance before the CB’s condition becomes critical. This function has two
stages.
The approach to calculating the CB condition is different from the approach used
by the CB wear function described in 6.9 Circuit breaker wear. CB condition
monitoring also provides some additional features for integrating the device with
other Schneider Electric products. These functions are based on data analytics
for integration into EcoStruxure Asset Advisor cloud-based offers.
cycles diagram describes how much more wear the CB can sustain, and this
approach describes how much wear the CB has accumulated.
Each bin also has three counters (one for each phase). Each counter tracks the
number of times the CB has opened and something was added to the
corresponding sum on that bin (see Figure 141).
If all cumulative breaking currents for the bins are zero when the value of the CT
primary parameter is changed in the Scaling setting view, the breaking current
ranges for the bins are automatically set to their default values relative to the new
CT primary value. The lower limit for the first bin is set to zero and the upper limit
to two times the CT primary value. There is no upper limit for the fifth bin.
The cumulative breaking currents are tracked with greater precision than what is
visible on the setting tool, that is, there are hidden decimals stored for each sum.
A non-zero sum that is too small to be visible in the setting tool may prevent the
bin ranges from getting their default values when the CT primary value is
changed.
The cumulative breaking currents can be read over the Modbus protocol as
floating-point values (IEEE 754, binary32). These values are represented in two
consecutive holding registers, so that the register in the lower address contains
the MSB 16 bits. To change the sum by writing a floating-point value, the MSB 16
bits must be written first.
The cumulative breaking currents can be cleared by writing value zero to them.
This function includes a counter that tracks the number of times the monitored CB
is opened, and a second counter that tracks how many of those operations were
caused by a protection stage trip. This requires that one of the controllable
objects (see 4.6 Controllable objects) has been configured to represent the CB
and this object has been selected in the Monitored object parameter.
Internally, each object has its own open counter and the counter for the monitored
object is shown under Opening counts, Trip counts and Rack-out counter (see
Figure 142). These open counters are incremented even when this function has
been disabled. In contrast, the trip counter is incremented when the monitored
object is opened by a protection stage trip and this function is enabled. Thus, if
you change the monitored object, the open counter value switches to the counter
of the new object, but the trip counter continues from its current value. Both
counters' values can be changed.
The number of times the monitored CB is racked out from the bay is tracked by its
own counter. This requires that a digital input is set up to indicate when the CB is
racked out85). This digital input is selected under Rack-out counter. Each digital
input has its own counter. The same counter is also found in the Digital inputs
setting view.
This function records the completion times for the eight previous open, close, and
charge operations of the monitored CB. Each operate time is recorded with a
timestamp indicating when the operation was completed. This function also keeps
a cumulative moving average of 20 previous operate times for each of the three
categories.
The completion times are recorded even if this function has been disabled,
provided that the monitored object has been selected.
All three logs of completion times can be cleared by the Clear logs command.
85) When the CB r is in the bay, this digital input has logical value false, and when the CB is racked
out, this input has logical value true.
The charging times are recorded in seconds whereas the opening and closing
times are recorded in milliseconds.
The operate times can be read over the Modbus protocol as floating-point values
(IEEE 754, binary32), so that a range of holding registers is used to represent all
operate times of a given category, from the newest to oldest. Each operate time is
represented in two consecutive holding registers, so that the register in the lower
address contains the MSB 16 bits.
If an opening time or a closing time is greater than 300 milliseconds, this value is
given as NaN (not-a-number) when it is read as a floating-point value. Similarly,
charging times greater than 60 seconds are given as NaN.
The relay can be configured to send a pulse whenever a certain amount of energy
has been imported or exported. The principle is presented in Figure 144. Each
time the energy level reaches the pulse size, a digital output is activated and the
relay is active as long as defined by a pulse duration setting.
Configurable:
100 ms − 5 000 ms
Configurable:
10 – 10 000 kWh
kvarh
The relay has four energy pulse outputs. The output channels are:
Each channel can be connected to any combination of the digital outputs using
the output matrix. The parameters for the energy pulses can be found in the
ENERGY menu "E" under the submenus E-PULSE SIZES and E-PULSE
DURATION.
Scaling examples
This is not a practical scaling example unless a digital output lifetime of about
six years is accepted.
Figure 145 - Application example of wiring the energy pulse outputs to a PLC
having common plus and using an external wetting voltage
+
Easergy P3 PLC
Figure 146 - Application example of wiring the energy pulse outputs to a PLC
having common minus and using an external wetting voltage
Easergy P3 +
PLC
Active exported
energy pulses +E
Pulse counter input 1
Reactive exported
energy pulses +Eq
Pulse counter input 2
Active imported
energy pulses -E
Pulse counter input 3
Reactive imported
energy pulses -Eq
Pulse counter input 4
Figure 147 - Application example of wiring the energy pulse outputs to a PLC
having common minus and an internal wetting voltage.
Easergy P3 PLC
Reactive exported
energy pulses +Eq Pulse counter input 2
Active imported
Pulse counter input 3
energy pulses -E
Reactive imported
energy pulses -Eq Pulse counter input 4
The running hour counter is typically used to monitor the service time of the motor
or appropriate feeder. This function calculates the total active time of the selected
digital input, virtual I/O function button, GOOSE signal, POC signal or output
matrix output signal. The resolution is ten seconds and the data is stored in the
non-volatile memory.
Parameters
Output matrix
out signal LF
Output matrix
out signal LG
Output matrix
out signal DR
Virtual outputs
6.13 Timers
Description
The Easergy P3 protection platform includes four settable timers that can be used
together with the user's programmable logic or to control setting groups and other
applications that require actions based on calendar time. Each timer has its own
settings. The selected on-time and off-time is set, after which the activation of the
timer can be set to be as daily or according to the day of the week (See the
setting parameters for details). The timer outputs are available for logic functions
and for the block and output matrix.
(not in use)
Daily
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
MTWTF
MTWTFS
SatSun
You can force any timer, which is in use, on or off. The forcing is done by writing a
new status value. No forcing flag is needed as in forcing for example the digital
outputs.
The forced time is valid until the next forcing or until the next reversing timed act
from the timer itself.
The status of each timer is stored in the non-volatile memory when the auxiliary
power is switched off. At startup, the status of each timer is recovered.
- Not in use
0 Output is inactive
1 Output is active
This function collects faults, fault types and registered fault currents of all enabled
overcurrent stages and shows them in the event log.
LINE ALARM
1 = Start is on
OCs Combined
overcurrent start
0
status.
1
AlrL1 = AlrL2 =
AlrL3 = 0
AlrL1 = 1 or
AlrL2 = 1 or
AlrL3 = 1
Events are
enabled /
Events are
disabled
Events are
enabled /
Events are
disabled
Events are
enabled /
Events are
disabled
Events are
enabled /
Events are
disabled
Several events
are enabled89)
Several events
of an increasing
fault is
disabled 90)
LINE FAULT
1 = Fault is on
OCt - Combined
overcurrent trip
0
status.
1
FltL1 = FltL2 =
FltL3 = 0
FltL1 = 1 or
FltL2 = 1 or
FltL3 = 1
Events are
enabled /
Events are
disabled
Events are
enabled /
Events are
disabled
Events are
enabled /
Events are
disabled
Events are
enabled /
Events are
disabled
Several events
are enabled89)
Several events
of an increasing
fault is
disabled90)
corresponding on-event.
The relay includes a stand-alone fault locator algorithm. The algorithm can locate
a short circuit in radially operated networks if the relay located in the incoming
feeder is connected CT & VT polarity-wise for forward (positive) power direction. If
the incoming feeder's power flow direction is configured negative, the short-circuit
fault locator function does not work.
The fault location is given as in reactance (ohms) and kilometres or miles. The
fault value can then be exported, for example, with an event to a Distribution
Management System (DMS). The system can then localize the fault. If a DMS is
not available, the distance to the fault is displayed as kilometres, and as a
reactance value. However, the distance value is valid only if the line reactance is
set correctly. Furthermore, the line should be homogenous, that is, the wire type
of the line should be the same for the whole length. If there are several wire types
on the same line, an average line reactance value can be used to get an
approximate distance value to the fault. Names and reactance values for widely
used overhead wires are:
The fault locator is normally used in the incoming bay of the substation.
Therefore, the fault location is obtained for the whole network with just one relay.
3. Phase currents and voltages are registered in three stages: before the fault,
during the fault and after the faulty feeder circuit breaker was opened.
Table 125 - Measured and recorded values of the incomer short circuit fault
locator
recorded values
Xfault ohm Fault reactance
Post A Post-fault
current
Voltages
dI
Currents
Figure 150 - Application example with fault location algorithm at the feeder side
Voltages
dI
Currents
P3U10
P3U20
P3U30 x x
Description
The device includes a stand-alone fault locator algorithm. The algorithm can
locate a short-circuit fault and an earth fault in radially-operated networks.
The fault location is given in reactance (ohms) and kilometers or miles. The fault
value can then be exported, for example, with an event to a distribution
management system (DMS). The system can then localize the fault. If a DMS is
not available, the distance to the fault is displayed as kilometers and as a
reactance value. However, the distance value is valid only if the line reactance is
set correctly.
Four segments with different reactance values can be configured for a line.
Names and reactance values for widely used overhead wires are:
This fault locator cannot be used in incomer because the locator has no ability to
compensate effect of healthy feeders away.
When the feeder fault locator is calculating short-circuit impedance, the following
formula is used:
When the feeder fault locator is calculating ground fault impedance, the following
formula is used:
K0 = (Z0L-Z1L) / (3 x Z1L)
Triggering of the fault reactance calculation happens when the start value is
exceeded or both “Start setting” and “Triggering digital input” terms are fulfilled.
When used, “Triggering digital input” can be either digital or virtual input.
Advanced settings
NOTE: In the fault log, the Pre-fault current and Current after fault columns
are only used for the incomer fault locator.
Trip circuit supervision is used to ensure that the wiring from the protective relay
to a circuit breaker (CB) is in order. Even though the trip circuit is unused most of
the time, keeping it in order is important so that the CB can be tripped whenever
the relay detects a fault in the network.
Also the closing circuit can be supervised using the same principle.
NOTE: Apply trip circuit supervision using a digital input and its programmable
time delay.
The benefits of this scheme are that only one digital inputs is needed and no extra
wiring from the relay to the circuit breaker (CB) is needed. Also, supervising a 24
Vdc trip circuit is possible.
The drawback is that an external resistor is needed to supervise the trip circuit on
both CB positions. If supervising during the closed position only is enough, the
resistor is not needed.
• The digital input is connected parallel to the trip contacts (see Figure 152).
• The digital input is configured as normal closed (NC).
• The digital input delay is configured to be longer than the maximum fault time
to inhibit any superfluous trip circuit fault alarm when the trip contact is closed.
• The digital input is connected to a relay in the output matrix giving out any trip
circuit alarm.
• The trip relay must be configured as non-latched. Otherwise, a superfluous
trip circuit fault alarm follows after the trip contact operates, and the relay
remains closed because of latching.
• By utilizing an auxiliary contact of the CB for the external resistor, also the
auxiliary contact in the trip circuit can be supervised.
Figure 152 - Trip circuit supervision using a single digital input and an external
resistor R
A
comm
C
D
0.5 s
G F
52b 52a
-VAUX
H
CB
R
-VAUX
NOTE: The need for the external resistor R depends on the application and
circuit breaker manufacturer's specifications.
Figure 153 - Alternative connection without using circuit breaker 52b auxiliary
contacts
A
comm
C
D
0.5 s
G F
52a
-VAUX
R
H
CB
-VAUX
Trip circuit supervision using a single digital input and an external resistor R. The
circuit breaker is in the closed position. The supervised circuitry in this CB
position is double-lined. The digital input is in active state when the trip circuit is
complete.
Alternative connection without using circuit breaker 52b auxiliary contacts. This is
applicable for any digital inputs.
Figure 154 - Trip circuit supervision using a single digital input when the circuit
breaker is in open position
C
D
0.5 s
G F
52b 52a
-VAUX
H
CB
R
-VAUX
Figure 155 - Alternative connection without using circuit breaker 52b auxiliary
contacts. Trip circuit supervision using a single digital input, when the circuit
breaker is in open position
C
D
0.5 s
G F
52a
-VAUX
R
H
CB
-VAUX
Figure 156 - Example of digital input DI7 configuration for trip circuit supervision
with one digital input
Figure 157 - Example of output matrix configuration for trip circuit supervision with
one digital input
IDI = 3 mA, Typical current needed to activate the digital input including a 1 mA
safety margin.
PCOIL = 50 W, Rated power of the open coil of the circuit breaker. If this value is
not known, 0 Ω can be used for the RCOIL.
UMIN = UAUX - 20 % = 88 V
Equation 38
U MIN − U DI − I DI ⋅ RCoil
R=
I DI
The power rating for the external resistor is estimated using Equation 39 and
Equation 40.
The Equation 39 is for the CB open situation including a 100 % safety margin to
limit the maximum temperature of the resistor:
Equation 39
P = 2 ⋅ I DI
2
⋅R
When the trip contacts are still closed and the CB is already open, the resistor
has to withstand much higher power (Equation 40) for this short time:
Equation 40
2
U MAX
P=
R
A 0.5 W resistor is enough for this short time peak power, too. However, if the trip
relay is closed for longer than a few seconds, a 1 W resistor should be used.
The drawbacks are that two digital inputs (DIs) from two separate groups and two
extra wires from the relay to the CB compartment are needed. Additionally, the
minimum allowed auxiliary voltage is 48 V dc which is more than twice the
threshold voltage of the dry digital input because when the CB is in open position,
the two digital inputs are in series.
When two DIs are connected in a series, the switching threshold value used with
one DI is too high. Therefore, a lower value must be selected: 24 V if the nominal
operation voltage for DI inputs is 110 V or 110 V if the nominal operation voltage
is 220 V.
• The first digital input is connected parallel to the auxiliary contact of the circuit
breaker's open coil.
• Another auxiliary contact is connected in series with the circuitry of the first
digital input. This makes it possible to supervise also the auxiliary contact in
the trip circuit.
• The second digital input is connected in parallel with the trip contacts.
• Both inputs are configured as normal closed (NC).
• The user’s programmable logic is used to combine the digital input signals
with an AND port. The delay is configured to be longer than the maximum
fault time to inhibit any superfluous trip circuit fault alarm when the trip contact
is closed.
• The output from the logic is connected to a relay in the output matrix giving
out any trip circuit alarm.
• Both digital inputs must have their own common potential.
Using the other digital inputs in the same group as the upper DI in Figure 158
is not possible in most applications. Using the other digital inputs in the same
group as the lower DI in Figure 158 is limited because the whole group is tied
to the auxiliary voltage VAUX.
Figure 158 - Trip circuit supervision with two digital inputs and closed CB
A
comm
C
D
& 0.5 s
G F
52b 52a
-VAUX
H
CB
-VAUX
Figure 159 - Trip circuit supervision with two digital inputs and CB in open position
A
comm
C
D
& 0.5 s
G F
52b 52a
-VAUX
H
CB
-VAUX
Figure 160 - An example of digital input configuration for trip circuit supervision
with two dry digital inputs DI1 and DI2
Figure 161 - An example of logic configuration for trip circuit supervision with two
digital inputs DI1 and DI2.
Figure 162 - An example of output matrix configuration for trip circuit supervision
with two digital inputs
7.1 Cybersecurity
According to a classic model of information security, the three security goals are:
• confidentiality (prevention of unauthorized disclosure of information)
• integrity (prevention of unauthorized modification of information)
• availability (ensuring that information is always available to authorized users)
These goals may be used as a starting point in designing security solutions for
electric power distribution.
We recommend that:
• Computer systems used to design or operate electric power distribution
systems are designed with the principle of least privilege, in other words, that
users only have those access rights that they needs to perform their duties.
• All workstations and servers have an effective antimalware solution, such as a
virus scanner.
• Computer systems are protected with adequate physical security measures to
prevent physical tampering of the devices or networks.
NOTICE
CYBERSECURITY HAZARD
To improve cybersecurity:
• Change all passwords from their default values when taking the protection
device into use.
• Change all passwords regularly.
• Ensure a minimum level of password complexity according to common
password guidelines.
Related topics
2.4 Access to device configuration
At the back, the relay may optionally have the following connections, depending
on the type of the communication option:
NOTE: By default and when the device comes from the factory, Ethernet
Protocol 1 is enabled and the default protocol is IEC-61850. Also Ethernet
Protocol 2 is enabled and the default protocol is Modbus TCPs.
Remote and extension ports are used for serial protocols like Modbus or IEC
60870-5-103. The physical interface is described in 9.5 Connections.
The parameters for the port can be set via the relay's front panel or using Easergy
Pro. The number of available serial ports depends on the type of the
communication option ordered.
The Ethernet port is used for Ethernet protocols like IEC61850 and Modbus TCP.
The parameters for the port can be set via the device's front panel or using
Easergy Pro. Two different protocols can be used simultaneously – both protocols
use the same IP address and MAC address (but different port number).
NOTICE
CYBERSECURITY HAZARD
This disables all the Ethernet-based protocols (FTP, HTTP, Telnet, and
Ethernet protocols).
The storm protection limit defines how big percentage of the broadcast messages
are forwarded to the CPU.
Storm protection level 0.01% means 15 packets per second in a 100 Mbps
network. Broadcast traffic forwarded to CPU can be limited down to 15% for 100
Mbps. This is based on a theoretical maximum of 100 packets per second that the
CPU can receive and process.
Storm protection can be enabled in the Advanced Ethernet options setting view
with the Storm protection on Port1 and Storm protection on Port2
parameters.
PRP properties:
For additional information, see application note Parallel Redundancy Protocol for
Easergy P3Ux and Easergy P3x3x relays with dual-port 100 Mbps Ethernet
interface (P3/EN ANCOM/A004).
• events
• status information
• measurements
• control commands
• clock synchronization
• some settings through SPA bus, IEC-103, Modbus and IEC-61850 protocols
• disturbance recordings through IEC-103, Modbus and IEC-61850 protocols
Modbus RTU and Modbus TCP protocols are often used in power plants and
industrial applications. The difference between these two protocols is the media.
Modbus TCP uses Ethernet and Modbus RTU uses RS-485, optic fibre, or
RS-232.
Modbus TCP supports using two masters and IEC 61850 at the same time.
Easergy Pro shows a list of all available data items for Modbus. They are also
available as a zip file ("Communication parameter protocol mappings.zip").
The information available via Modbus RTU and Modbus TCP includes:
• status values
• control commands
• measurement values
• events
• protection settings
• disturbance recordings
The Modbus communication is activated via a menu selection with the parameter
"Protocol".
7.5.2 Profibus DP
The Profibus DP protocol is widely used in the industry. An external VPA 3CG
option module and VX084 cable are required.
Using the request mode, it is possible to read all the available data from the
Easergy P3 relay and still use only a very short buffer for Profibus data transfer.
The drawback is the slower overall speed of the data transfer and the need of
increased data processing at the Profibus master as every data item must be
separately requested by the master.
NOTE: In the request mode, it is not possible to read continuously only one
single data item. At least two different data items must be read in turn to get
updated data from the relay.
There is a separate manual for VPA 3CG for the continuous mode and request
mode. The manual is available for downloading on our website.
Available data
Easergy Pro shows the list of all available data items for both modes. A separate
document "Communication parameter protocol mappings.zip" is also available.
7.5.3 SPA-bus
The relay has full support for the SPA-bus protocol including reading and writing
the setting values. Also, reading multiple consecutive status data bits,
measurement values or setting values with one message is supported.
Several simultaneous instances of this protocol, using different physical ports, are
possible, but the events can be read by one single instance only.
The IEC standard 60870-5-103 "Companion standard for the informative interface
of protection equipment" provides a standardized communication interface to a
primary system (master system).
The unbalanced transmission mode of the protocol is used, and the relay
functions as a secondary station (slave) in the communication. Data is transferred
to the primary system using the "data acquisition by polling" principle.
It is also possible to transfer parameter data and disturbance recordings via the
IEC 103 protocol interface.
The following application service data unit (ASDU) types can be used:
• ASDU 1: Time-tagged message
• ASDU 3: Measurands I
• ASDU 5: Identification message
• ASDU 6: Time synchronization
• ASDU 8: Termination of general interrogation
• ASDU 10: Generic data
These are fixed for data items in the compatible range of the protocol, for
example, the trip of I> function is identified by:
• type identification = 1
• function type = 160
• information number = 90
"Private range" function types are used for such data items that are not defined by
the standard (for example, the status of the digital inputs and the control of the
objects).
The function type and information number used in private range messages is
configurable. This enables flexible interfacing to different master systems.
For more information on IEC 60870-5-103 in Easergy P3 relays, see the "IEC 103
Interoperability List.pdf" and "Communication parameter protocol mappings.zip"
documents.
The relay supports communication using the DNP 3.0 protocol. The following
DNP 3.0 data types are supported:
• binary input
• binary input change
• double-bit input
• binary output
• analog input
• counters
For more information, see the “DNP 3.0 Device Profile Document.pdf" and
“"Communication parameter protocol mappings.zip"”. DNP 3.0 communication is
activated via menu selection.
The IEC 60870-5-101 standard is derived from the IEC 60870-5 protocol standard
definition. In Easergy P3 relays, the IEC 60870-5-101 communication protocol is
available via menu selection. The relay works as a controlled outstation (slave)
unit in unbalanced mode.
The IEC 61850 protocol is available with the optional communication module. It
can be used to read or write static data from the relay or to receive events and to
receive or send GOOSE messages from or to other relays.
• 32 data points can be published with GOOSE (two goose control blocks with
maximum 16 data points).
• 64 binary data points and five analog data points can be subscribed in
GOOSE (maximum five different MAC addresses).
• The maximum number of clients is eight (the maximum number of BRCBs is
eight and the maximum number or URCBs is eight).
• Both Ed1 and Ed2 are supported and can be selected with a parameter.
7.5.8 Ethernet/IP
The relay supports communication using the Ethernet/IP protocol which is a part
of the Common Industrial Protocol (CIP) family. The Ethernet/IP protocol is
available with the optional in-built Ethernet port. The protocol can be used to read
or write data from or to the relay using request / response communication or via
cyclic messages transporting data assigned to assemblies (sets of data).
For more detailed information and parameter lists for Ethernet/IP, refer to a
separate application note “EtherNet/IP configuration instructions.pdf”.
For the complete data model of Ethernet/IP, see the document “DeviceNet and
EtherNetIP data model.pdf” and "Communication parameter protocol
mappings.zip".
The Webset HTTPS configuration interface provides the option to configure the
relay with a standard web browser such as Internet Explorer, Mozilla Firefox, or
Google Chrome. The feature is available when the communication option C, D, E
or F is in use.
A subset of the relays's features is available in the Webset interface. The group
list and group view from the relay are provided, and most groups, except the
LOGIC and the MIMIC groups are configurable.
7.6 IP filter
Easergy P3 devices contain a simple IP filter (IP firewall), which can be used to
filter incoming TCP/IP connections. This filtering applies only to Modbus TCP,
DNP3, and Ethernet/IP, and can be configured via Easergy Pro.
The IP filter works based on configured rules. Incoming IP packets are compared
against the rules, and when a matching rule is found, the packet is handled using
the action specified for the rule. If none of the rules matches the packet, the
default action is taken on the packet. The IP filter records how many times a
packet has matched a rule. The number is shown in the Counter column.
On TCP connections, the rules are mostly applied only when a connection is
opened.
You can configure up to 10 rules for the IP filter via Easergy Pro and enable each
rule individually.
IP address Description
Action Description
The IP filter also can also detect unexpected packets. For example, if a client
attempts to close a connection that does not exist, this is considered an
unexpected packet.
Parameter Description
7.6.3 Alarms
Active cybersecurity (CS) alarms can be viewed in the Alarms view. When an
alarm signal has been asserted, it remains active until it is cleared with the Clear
alarms command.
The relays provide a circuit breaker control function. Additional primary switching
relays (earthing switches and disconnector switches) can also be controlled from
the front panel or the control or SCADA/automation system. A programmable
logic function is also implemented in the relay for various applications, for
example interlockings schemes.
Figure 173 - Easergy P3U10, P3U20 and P3U30 used in substation feeder
protection
Figure 174 - Easergy P3U10, P3U20 and P3U30 used in substation feeder
protection in compensated network
In this application, the network grounding information, taken from Petersen coil, is
obtained for the directional earth fault overcurrent stage through relay's digital
input. The grounding status controls dynamically the operation characteristics of
the directional earth fault overcurrent stage. For a grounded network, Res mode
and for an isolated network, Cap mode is applied.
Figure 175 - Easergy P3U10, P3U20 and P3U30 used in cable protection of an
industry plant network.
The relay supports directional earth fault protection and three-phase overcurrent
protection that is required in a cable feeder. Furthermore, the thermal stage can
be used to protect the cable against overloading. All necessary motor protection
functions are supported when using the motor application mode.
8.3 Using CSH120 and CSH200 with 0.2 A core balance CT input
General
The CSH120 and CSH200 core balance CTs are for direct earth fault overcurrent
measurement. The only difference between them is the diameter. Because of their
low-voltage insulation, they can only be used on cables.
These core balance CTs can be connected to the Easergy P3 protection device
range when 0.2 A I0 input is used. This needs to be determined when ordering the
protection device (select 0.2 A for the earth fault current input in the order code).
The device also allows selecting ten times lower scaling values. Set the values to:
• I0X CT primary: 47 A
• I0X CT secondary: 0.1 A
• Nominal I0X input: 0.2 A
The minimum setting for the primary current is then 0.005 x 47 A = 0,235 A.
Measuring specifications
The CSH120 and CSH200 core balance CTs are dedicated accessories for
Schneider Electric’s specially designed devices. They are used for direct earth
fault overcurrent measurement. The only difference between them is the diameter.
Because of their low-voltage insulation, they can only be used on cables.
In the Easergy P3 Standard device, the CSH input can only be configured for I01.
In this case, two primary windings are used to select the nominal input range: 2 A
or 20 A.
Measuring specifications
Two primary windings are used to select the nominal input range 2 A or 20 A. Set
the device parameter I01 CSH primary to 20 A or 2 A.
If I01 CSH primary = 2 A, the minimum setting for primary current is then 0.05 x 2
A = 0.10 A.
If I01 CSH primary = 20 A, the minimum setting for primary current is then 0.05 x
20 A = 1.00 A.
Figure 180 - Earth fault overcurrent setting view when I01 CSH primary = 2 A
9 Installation
To identify an Easergy P3 protection relay, see the labels on the package and on
the side of the relay.
Type: P3U30-5AAA1BCAA 7
REL52003 11
S/N: EB173050011 8 VID: P3U30-016985 12
1. Rated voltage Un
2. Rated frequency fn
7. Order code
8. Serial number
9. Manufacturing date
REL52010 A x1
Protection relay
Relais de protection
B Made in Finland
EB172720007
A REL52010
135716
Easergy - P3 C
D P3U30-5AAA2BDA
E
3 606481 3571 68
SCHNEIDER ELECTRIC
CS30323
F-92506 RUEIL MALMAISON CEDEX
9.3 Storage
Store the relay in its original packaging in a closed, sheltered location with the
following ambient conditions:
9.4 Mounting
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Wear your personal protective equipment (PPE) and comply with the safe
electrical work practices. For clothing refer applicable local standards.
• Only qualified personnel should install this equipment. Such work should
be performed only after reading this entire set of instructions and checking
the technical characteristics of the device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing relay to ensure that all power
is off.
• Do not open the secondary circuit of a live current transformer.
• Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
A B
P3Uxx-5 214mm / 8.4″ 192mm / 7.6″
P3Uxx-6 226mm / 8.9″ 204mm / 8.0″
mm
128
171
in 5.04 A 2.5 124.5
6.72
155 0.1 4.90
Easergy 6.10
OK
176 137 B
F1 F2 6.94 5.39
O
I
13.25
0.52 144.5 6
5.69 12 6
A B 4.9
9.25 5.0 mm
0.36 0.2 in
28.5
1.12
Ea se rg
y 2 Ea se rg
y
9.5
0.37
120
139 4.72
OK
5.47
OK
F2
F2
F1
9.5 F1
O 0.37 O
I
1. I
0.040-10
- 0.3
9
X1 (P3Uxx-6) X1 (P3Uxx-5) X2, X3, X4, X5
T max. 1.40Nm T max. 1.40Nm T max. 0.6Nm
12lb.in 12lb.in 5.3lb.in
0.8 x 4.0
5/32in x 0.03in
T max. 0.80Nm
7lb.in
> 20
min. 2.5mm2
C 0.79
Ø 4-6mm
y
Ea se rg
y
Ea se rg
Nut M4
7mm 1.5Nm OK
OK
9/32in 13.3Ib in F2
F2
F1
F1
OK
OK
F2
F2 O
O
F1
F1
I
I
OO
II
2.5
0.1
A B C
y
Ea se rg Ea se rg
y
rgyy
serg
Ease
Ea
OK
OK
F2
F2
F1 OK
OK
F1
F2
F2
F1
F1
O
O
I
I
OO
II
X1 (P3Uxx-6) 13.25
0.52
T max. 1.40Nm
D 144.5 6
12lb.in 5.69 12 6
4.9 mm
9.25 5.0 in
0.8 x 4.0 0.36 0.2
5/32in x 0.03in
28.5
1.12
X1 (P3Uxx-5) 2 Ea se rg y y
Ea se rg
T max. 1.40Nm 9.5
12lb.in 0.37
0.8 x 4.0 120
5/32in x 0.03in 139 4.72
T max. 0.80Nm
5.47
OK
7lb.in OK
F2
0.4 x 2.5 F2
0.37 O
X2, X3, X4, X5 O
1. I
0.040-12
T max. 0.6Nm I
5.3lb.in - 0.4
7
0.4 x 2.5
> 20
3/32in x 0.015in E 0.79
min. 2.5mm2
y
Ø 4-6mm Ea se rg
y
Ea se rg
OK
OK
Nut M4 F2
F2
7mm 1.5Nm F1
F1
9/32in 13.3Ib in OK
F2
O
O
F1
I
I
CAUTION
HAZARD OF CUTS
Trim the edges of the cut-out plates to remove any jagged edges.
Use protective gloves when moving and mounting the device.
See "P3 Standard Series facial label instruction" document for more information.
Protective film
NOTICE
RISK OF DESTRUCTION OF THE RELAY
The protective film on the relay's display is plastic and can melt if exposed to
high temperatures intensive sunlight. Remove the protective film after mounting
the relay.
Failure to follow these instructions can result in equipment damage.
9.5 Connections
NOTE: The figures show the relay outputs with the auxiliary power on and the
protection functions on standby mode.
NOTE: Digital inputs are polarity-free, which means that you can freely
choose "-" and "+" terminals for each digital input.
Terminal X1 connections
The Easergy P3U10, P3U20 and P3U30 relays have two alternative pluggable
current input terminals containing automatic short circuiting if the terminal is
removed from its relay socket. Order option 5 has screw clamp terminals and
option 6 ring lug screw terminals.
- Phase current connection 5 and 7 = Pluggable clamp / 6 and 8 = Pluggable ring lug
pins / input polarity / nominal
secondary current
2 IL1 (S2)
3 IL2 (S1)
4 IL2 (S2)
5 IL3 (S1)
6 IL3 (S2)
7 I0 (S1) 5A 1A 20 A
8 I0 (S2)
9 I0 (S1) 1A 0.2 A 2A
10 I0 (S2)
92) Nominal secondary phase current can be scaled to 1-10A
NOTE: Connect the earth fault overcurrent I0 either to terminal pins 7–8 or 9–
10 as the relay has only one I0 input channel.
Figure 188 - Option 5: Pluggable clamp Figure 189 - Option 6: Pluggable ring
connector lug connector
1 I0 (S1) 5A 1A 20 A
2 I0 (S2)
3 I0 (S1) 1A 0.2 A 2A
4 I0 (S2)
Terminal X2 connections
No Symbol Description
1 U4 Uo/ULN/ULL
(da/a/a)
2 U4
Uo/ULN/ULL
3 +/~
(dn/n/b)
4 -/~
Auxiliary voltage
Auxiliary voltage
Terminal X3 connections
- No Symbol Description
20 SF NC Self-diagnostic relay,
normal close when
19 SF NO
power ON
18 SF COM
Self-diagnostic relay,
17 T1 normal open when
16 T1 power ON
15 T2 Self-diagnostic relay,
common terminal
14 T2
Trip relay 1
13 T3
Trip relay 1
12 T3
Trip relay 2
11 T4
Trip relay 2
10 T4
Trip relay 3
9 A1 NC
Trip relay 3
8 A1 NO
Trip relay 4
7 A1 COM
Trip relay 4
6 DI2
Alarm relay 1,
5 DI2
normal closed
4 DI1 terminal
2 - normal open
1 - Alarm relay 1,
common
Digital input 2
Digital input 2
Digital input 1
Digital input 1
No connection
No connection
CAUTION
RISK OF DESTRUCTION OF THE RELAY
No Symbol Description
RS-485 interface
termination resistor
for “+“ connection
RS-485 interface
ground terminal
RS-485 interface
cable shield
connection
CAUTION
RISK OF DESTRUCTION OF THE RELAY
No Symbol Description
Digital input 3
CAUTION
RISK OF DESTRUCTION OF THE RELAY
No Symbol Description
Digital input 3
CAUTION
RISK OF DESTRUCTION OF THE RELAY
No Symbol Description
Digital input 3
CAUTION
RISK OF DESTRUCTION OF THE RELAY
Cable VX082, VX083 or VX084 is needed for connecting external option modules to the
RS-232 connector of the Easergy P3U10, P3U20 and P3U30.
No Symbol Description
Digital input 3
CAUTION
RISK OF DESTRUCTION OF THE RELAY
No Symbol Description
RS-485 interface
termination resistor
for “+“ connection
RS-485 interface
ground terminal
RS-485 interface
cable shield
connection
CAUTION
RISK OF DESTRUCTION OF THE RELAY
No Symbol Description
Trip relay 7
CAUTION
RISK OF DESTRUCTION OF THE RELAY
No Symbol Description
6 T5 Trip relay 5
5 T5 Trip relay 5
4 T6 Trip relay 6
3 T6 Trip relay 6
2 T7 Trip relay 7
1 T7 Trip relay 7
CAUTION
RISK OF DESTRUCTION OF THE RELAY
20 U1 ULN/ULL (a/a)
19 U1 ULN/ULL (n/b)
18 U2 ULN/ULL (a/a)
17 U2 ULN/ULL (n/b)
16 U3 Uo/ULN/ULL (da/a/a)
15 U3 Uo/ULN/ULL (dn/n/b)
14 T5 Trip relay 5
13 T5 Trip relay 5
12 T6 Trip relay 6
11 T6 Trip relay 6
10 T7 Trip relay 7
9 T7 Trip relay 7
8 DI 16 Digital input 16
7 DI 15 Digital input 15
6 DI 14 Digital input 14
4 DI 13 Digital input 13
3 DI 12 Digital input 12
2 DI 11 Digital input 11
20 U1 ULN/ULL (a/a)
19 U1 ULN/ULL (n/b)
18 U2 ULN/ULL (a/a)
17 U2 ULN/ULL (n/b)
16 U3 Uo/ULN/ULL (da/a/a)
15 U3 Uo/ULN/ULL (dn/n/b)
14 T8 Trip relay 8
13 T8 Trip relay 8
12 T9 Trip relay 9
11 T9 Trip relay 9
8 DI 14 Digital input 14
7 DI 13 Digital input 13
6 DI 12 Digital input 12
4 DI 11 Digital input 11
3 DI 10 Digital input 10
2 DI 9 Digital input 9
CAUTION
RISK OF DESTRUCTION OF THE RELAY
Terminal X5 C = 6DI+3DO
14 T5 Trip relay 5
13 T5 Trip relay 5
12 T6 Trip relay 6
11 T6 Trip relay 6
10 T7 Trip relay 7
9 T7 Trip relay 7
8 DI 16 Digital input 16
7 DI 15 Digital input 15
6 DI 14 Digital input 14
4 DI 13 Digital input 13
3 DI 12 Digital input 12
2 DI 11 Digital input 11
CAUTION
RISK OF DESTRUCTION OF THE RELAY
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Before connecting the devices, disconnect the supply voltage to the unit.
The external auxiliary voltage UAUX for the relay is connected to the pins X2: 3–4.
NOTE: The 24-48 (+/-20%) V dc power supply has been taken into use as
follows:
NOTE: Check the available power supply range from the device's serial
number label.
NOTICE
LOSS OF PROTECTION OR RISK OF NUISANCE TRIPPING
The front panel USB type B port is always using the command line protocol for
Easergy Pro.
The speed of the interface is defined in the CONF/DEVICE SETUP menu via the
front panel. The default settings for the relay are 38400/8N1.
Connecting a cable between the PC and the relay creates a virtual com-port. The
default settings for the relay are 38400/8N1. The communication parameter
display on the local display shows the active parameter values for the local port.
It is possible to change the front USB port's bit rate. This setting is visible only on
the relay's local display. The bit rate can be set between 1200 and 187500. This
changes the bit rate of the relay, and the Easergy Pro bit rate has to be set
separately. If the bit rate in the setting tool is incorrect, it takes a longer time to
establish the communication.
NOTE: Use the same bit rate in the relay and the Easergy Pro setting tool.
24–48 V dc (±20%)
Note! Polarity
Continuously: 19.2–57.6 V
dc
Power consumption
Model: P3U30-xxxxxBxx: 16
Model: P3U20-xxxxxAxx: 10
Model: P3U20-xxxxxG/H/Ixx: 8
Nominal operation voltage DI1 – DI16 (as 1: 24–230 V ac/dc (max. 255 V ac/dc)
per the order code digits)
2: 110–230 V ac/dc (max. 255 V ac/dc)
3: 155 V dc
Cycle time 10 ms
NOTE: Set the dc/ac mode according to the used voltage in Easergy Pro.
Model: P3U20-xxxxxAxx: 4
Model: P3U20-xxxxxxG/H/Ixx: 7
Continuous carry 5A
at 48 V dc: 1.15 A
Number of contacts: 1
Continuous carry 5A
at 48 V dc: 1A
Terminal X1 X2 X3 X4 X5
characteris
tics
Terminal X1 X2 X3 X4 X5
characteris
tics
Maximum 2.5
wire cross
(14)
section if
directly
mounted
under screw,
mm2 (AWG)
Maximum 1.5 Nm
wiring screw
(13)
tightening
torgue Nm
(Ib-in)
Maximum 1.4
connector
(12)
retention
screw
tightening
torque Nm
(Ib-in)
RS-485 (option)
Spabus, slave
IEC 60870-5-103
IEC 61870-5-101
Profibus DP
DNP 3.0
IRIG-B
Modbus TCP
DNP 3.0
Ethernet/IP
IEC 61870-5-101
Modbus TCP
DNP 3.0
Ethernet/IP
IEC 61870-5-101
- Burden 0.075 VA
I0 input (5 A)
- Burden 0.075 VA
I0 input (1 A)
- Burden 0.02 VA
I0 input (0.2 A)
- Burden 0.02 VA
Voltage inputs
Frequency
Thermal withstand 60 V
Thermal withstand 25 V
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• VSE001PP (Plastic-plastic)
• VSE001GG (Glass-glass)
• None
• IEC-103
• Modbus slave
• SpaBus
The power for the module is taken from RS-232 connector of the Easergy P3U10,
P3U20 and P3U30 or from an external power supply interface. The module is
connected to the RS-232 serial port with a VX082 or VX083 cable.
A
C
VX082 REM
A. VSE-001 C. VX082
B. Communication bus
The physical interface of the VSE-001 is a 9-pin D-connector. The signal level is
RS-232.
NOTE: The product manual for VSE-001 can be found on our website.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• None
• IEC-103
• ModbusSlv
• SpaBus
The power for the module is taken from RS-232 connector of the protection
device or from an external power supply interface. The module is connected to
the RS-232 serial port with VX082 or VX083 cable.
A
C
VX082 REM
A. VSE-002 C. VX082
B. Communication bus
The physical interface of the VSE-002 is a 9-pin D-connector. The signal level is
RS-232 and therefore, the interface type for the module has to be selected as
RS-232.
Termination
ON OFF
73 mm
Interface type
TLL RS-232
20 mm
1 - -
7 GND GND
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• None
• ProfibusDP
The power for the module is taken from an external power supply interface.
A
C
VX084
VPA3CG
+ -
+ -
+ -
D
B
A. VPA-3CG C. VX084
B. Communication bus D. +12 Vdc power supply
The maximum cable length depends on the transmission speed and cable type.
The specified cable length can be increased by the use of repeaters. The use of
more than 3 repeaters in a series is not recommended.
VIO 12A I/O modules can be connected to Easergy P3U20 and P3U30 using
RS-485 connection in interface modules. Alternatively VIO 12A I/O modules can
be connected to Easergy P3U20 and P3U30 using RS-232 connection. If RS-232
connection is used a separate VX082 or VX083 connection cable and VSE001 or
VSE002 option module are needed.
The status of the output contacts is shown when the relay is energized but none
of the protection, controlling or self-supervision elements are activated.
A
X2:1
U4 X2
X2:2
X2:3 ~
P3U10- 5 AA A2 AAA
X2:4 = X3 T1
X3:17
X3:16
X1:1
IL1
X1 T2 X3:15
6
X1:2
X3:14
X1:3
IL2 T3 X3:13
X1:4
X3:12
X1:5
IL3 T4 X3:11
3
1
X1:6
X3:10
X1:7
I0 5A A1 X3:7
X1:8 X3:9
X1:9 X3:8
I0 1A
X1:10 SF X3:20
X3:19
X3:18
X3:3 DI1 DI X3
X3:4 DI1
X3:5 DI2
X3:6 DI2
A. Front
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
A
X2:1
U4 X2
X2:2 B
P3U20- 5 AA A2 ABAA
X2:3 ~
X2:4 = X4 X4:1 1)
X4:2 RS - 485 GND
X4:3 2)
X1:1
IL1
X1
X4:4 RS - 485 +
6
X1:2
X4:5 RS - 485 -
X1:3 X4:6 3)
IL2
X1:4
X1:5
3
1
IL3
X1:6 X3 T1
X3:17
X1:7
I0 5A X3:16
X1:8 T2 X3:15
X1:9
I0 1A X3:14
T3 X3:13
X1:10
X3:12
T4 X3:11
X3:3 DI1 DI X3
X3:10
X3:4 DI1
A1 X3:7
X3:5 DI2
X3:9
X3:6 DI2 X3:8
SF X3:20
X4:7 DI3 DI X4 X3:19
X4:8 DI3 X3:18
X4:9 DI4
X4:10 DI4
X4:11 DI5
X4:12 DI5
X4:13 DI6
X4:14 DI6
X4:15 COM DI
X4:16 DI7
X4:17 DI8
X4:18 COM DI
X4:19 DI9
X4:20 DI10
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
A
X2:1
U4 X2
X2:2
~
P3U20- 5 AA A2 ACAA
X2:3
X2:4 = X4
Eth1
X1:1
IL1
X1
6
X1:2 Eth2
X1:3
IL2
X1:4
X1:5
3
1
IL3
X1:6 X3 T1
X3:17
X1:7
I0 5A X3:16
X1:8 T2 X3:15
X1:9
I0 1A X3:14
T3 X3:13
X1:10
X3:12
T4 X3:11
X3:3 DI1 DI X3
X3:10
X3:4 DI1
A1 X3:7
X3:5 DI2
X3:9
X3:6 DI2 X3:8
SF X3:20
X4:1 DI3 DI X4 X3:19
X4:2 DI3 X3:18
X4:3 DI4
X4:4 DI4
X4:5 DI5
X4:6 DI5
X4:7 DI6
X4:8 DI6
X4:9 COM DI
X4:10 DI7
X4:11 DI8
X4:12 COM DI
X4:13 DI9
X4:14 DI10
A. Front
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
A
X2:1
U4 X2
X2:2
~
P3U20- 5 AA A2 AH AA
X2:3
X2:4 = X4
Eth1
X1:1
IL1
X1
6
X1:2 Eth2
X1:3
IL2
X1:4
X1:5
3 I
1
IL3
X1:6 X3 T1
X3:17
X1:7
I0 5A X3:16
X1:8 T2 X3:15
X1:9
I0 1A X3:14
T3 X3:13
X1:10
X3:12
T4 X3:11
X3:3 DI1 DI X3
X3:10
X3:4 DI1
A1 X3:7
X3:5 DI2
X3:9
X3:6 DI2 X3:8
SF X3:20
X4:20 DI8 DI X4 X3:19
X4:19 DI7 X3:18
X4:18 DI6
X4:17 COM
X4 T5 X4:12
X4:16 DI5
X4:15 DI4 X4:11
T6 X4:10
X4:14 DI3
X4:13 COM X4:9
T7 X4:8
X4:7
A. Front
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
A
X2:1
U4 X2
X2:2
~
P3U20- 5 AA A2 AGAA
X2:3
X2:4 = X4
RS-485
X1:1
IL1
X1
6
X1:2
X1:3
IL2
X1:4
X1:5
IL3
3
1
X1:6 X3 T1
X3:17
X1:7
I0 5A X3:16
X1:8 T2 X3:15
X1:9
I0 1A X3:14
T3 X3:13
X1:10
X3:12
T4 X3:11
X3:3 DI1 DI X3
X3:10
X3:4 DI1
A1 X3:7
X3:5 DI2
X3:9
X3:6 DI2 X3:8
SF X3:20
X4:14 DI8 DI X4 X3:19
X4:13 DI7 X3:18
X4:12 DI6
X4:11 COM
X4 T5 X4:6
X4:10 DI5
X4:9 DI4 X4:5
T6 X4:4
X4:8 DI3
X4:7 COM X4:3
T7 X4:2
X4:1
A. Front
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
A
X2:1
U4 X2
X2:2 B
P3U30- 5 AA A2 BBA
X2:3 ~
X2:4 = X4 X4:1 1)
X4:2 RS-485 GND
X4:3 2)
X1:1 X1
6
IL1 X4:4 RS-485 +
X1:2
X4:5 RS-485 -
X1:3 X4:6 3)
IL2
X1:4
X1:5
3
1
IL3
X1:6 X3 T1 X3:17
X1:7
Io 5A X3:16
X1:8 T2 X3:15
X1:9
Io 1A X3:14
T3 X3:13
X1:10
X3:12
T4 X3:11
X5:20 X5
U1
X5:19 X3:10
A1 X3:7
X5:18
U2 X3:9
X5:17 X3:8
X5:16
U3
X5:15 SF X3:20
X3:19
X3:18
X3:3 DI1 DI X3
X3:4 DI1
X3:5 DI2
X3:6 DI2 X5
T5 X5:14
X5:13
X4:7 DI3 DI X4
X4:8 DI3
T6 X5:12
X4:9 DI4
X5:11
X4:10 DI4
X4:11 DI5 T7 X5:10
X4:12 DI5
X5:9
X4:13 DI6
X4:14 DI6
X4:15 COM DI
X4:16 DI7
X4:17 DI8
X4:18 COM DI
X4:19 DI9
X4:20 DI10
X5:1 COM DI X5
X5:2 DI11
X5:3 DI12
X5:4 DI13
X5:5 COM DI
X5:6 DI14
X5:7 DI15
X5:8 DI16
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
A
X2:1 ~
P3U30-7AA A2 BBA
X2:2 =
X2
B
X4 X4:1 1)
LPCT
IL1 RJ45
X4:2 RS-485 GND
X4:3 2)
IL2 RJ45
X4:4 RS-485 +
IL3 RJ45
X4:5 RS-485 -
LPVT X4:6 3)
3
1
HUB1 U1, U2, U3
HUB2 U4, U5
X3 T1
X3:17
X1:1 X1
Io 5A X3:16
X1:2 T2 X3:15
X1:3
Io 1A X3:14
T3 X3:13
X1:4
X3:12
T4 X3:11
X3:10
A1 X3:7
X3:9
X3:8
SF X3:20
X3:19
X3:18
X3:3 DI1 DI X3
X3:4 DI1
X3:5 DI2
X3:6 DI2 X5
T5 X5:14
X5:13
X4:7 DI3 DI X4
X4:8 DI3
T6 X5:12
X4:9 DI4
X5:11
X4:10 DI4
X4:11 DI5 T7 X5:10
X4:12 DI5
X5:9
X4:13 DI6
X4:14 DI6
X4:15 COM DI
X4:16 DI7
X4:17 DI8
X4:18 COM DI
X4:19 DI9
X4:20 DI10
X5:1 COM DI X5
X5:2 DI11
X5:3 DI12
X5:4 DI13
X5:5 COM DI
X5:6 DI14
X5:7 DI15
X5:8 DI16
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
A
X2:1
U4 X2
P3U30- 5 AA A2 BCA
X2:2
X2:3 ~
X2:4 = X4
Eth1
6
X1:1
IL1
X1
X1:2 Eth2
X1:3
IL2
X1:4
3
1
X1:5
IL3
X1:6 X3 T1
X3:17
X1:7
I0 5A X3:16
X1:8 T2 X3:15
X1:9
I0 1A X3:14
T3 X3:13
X1:10
X3:12
T4 X3:11
X5:20 X5
U1
X5:19 X3:10
A1 X3:7
X5:18
U2 X3:9
X5:17 X3:8
X5:16
U3
X5:15 SF X3:20
X3:19
X3:18
X3:3 DI1 DI X3
X3:4 DI1
X3:5 DI2
X3:6 DI2 X5
T5 X5:14
X5:13
X4:1 DI3 DI X4
X4:2 DI3
T6 X5:12
X4:3 DI4
X5:11
X4:4 DI4
X4:5 DI5 T7 X5:10
X4:6 DI5 X5:9
X4:7 DI6
X4:8 DI6
X4:9 COM DI
X4:10 DI7
X4:11 DI8
X4:12 COM DI
X4:13 DI9
X4:14 DI10
X5:1 COM DI X5
X5:2 DI11
X5:3 DI12
X5:4 DI13
X5:5 COM DI
X5:6 DI14
X5:7 DI15
X5:8 DI16
A. Front
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
A
X2:1
U4 X2
X2:2
P3U30-5 AA A2 BHA
X2:3 ~
X2:4 = X4
Eth1
X1:1 X1
6
IL1
X1:2 Eth2
X1:3
IL2
X1:4
X1:5
IL3
X3
3
1
X1:6 T1 X3:17
X1:7
Io 5A X3:16
X1:8 T2 X3:15
X1:9
Io 1A X3:14
T3 X3:13
X1:10
X3:12
T4 X3:11
X5:20 X5
U1 X3:10
X5:19
A1 X3:7
X5:18
U2 X3:9
X5:17 X3:8
X5:16
U3
X5:15 SF X3:20
X3:19
X3:18
X3:3 DI1 DI X3
X3:4 DI1
X3:5 DI2
X3:6 DI2 X4
T5 X4:6
X4:5
A. Front
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
P3 S _2ph current
L1 L2 L3
X1:1
IL1
X1
X1:2
X1:3 IL2
X1:4
X1:5
IL3
1) X1:6
X1:7
Io 5A
X1:8
X1:9
2) Io 1A
X1:10
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
P3 S OC with 3ph CT
L1 L2 L3
X1:1
IL1
X1
X1:2
X1:3 IL2
X1:4
X1:5
IL3
1) X1:6
X1:7
Io 5A
X1:8
X1:9
2) Io 1A
X1:10
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
X1:1
IL1
X1
X1:2
X1:3 IL2
X1:4
X1:5
IL3
1) X1:6
X1:7
Io 5A
X1:8
X1:9
2) Io 1A
X1:10
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
P3 S OC with 3ph CT
L1 L2 L3
X1:1
IL1
X1
X1:2
X1:3 IL2
X1:4
X1:5
IL3
1) X1:6
X1:7
Io 5A
X1:8
X1:9
2) Io 1A
X1:10
2) Not in use
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
P3 S EF CORE BALANCE
L1 L2 L3
X1:1
IL1
X1
X1:2
X1:3 IL2
X1:4
X1:5
IL3
1) X1:6
X1:7
Io 5A
X1:8
X1:9
2) Io 1A
X1:10
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
P3 S EF TR STAR
X1:1
IL1
X1
X1:2
X1:3 IL2
X1:4
X1:5
IL3
X1:6
X1:7
Io 5A
X1:8
X1:9
1) Io 1A
L1 L2 L3 N X1:10
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
P3 S Io LV sum
X1:1
IL1
X1
X1:2
X1:3 IL2
X1:4
X1:5
IL3
X1:6
X1:7
Io 5A
X1:8
X1:9
Io 1A
L1 L2 L3 N PEN X1:10
• used in TN network
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
P3 S Io LV core balance
X1:1
IL1
X1
X1:2
X1:3 IL2
X1:4
X1:5
IL3
X1:6
X1:7
Io 5A
X1:8
X1:9
1) Io 1A
L1 L2 L2 N PEN X1:10
• used in TT network
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
L1
P3U30_3LN_A
L2
L3
X5:20 X5
U1
X5:19
X5:18
U2
X5:17
X5:16
U3
X5:15
Easergy P3 Standard
X2:1 X2
U4
X2:2
X1:1
IL1
X1
X1:2
X1:3
IL2
X1:4
1) X1:5
IL3
X1:6
X1:7
I0 5A
X1:8
X1:9
2) I0 1A
X1:10
1) Positive CT current flow, positive energy direction (imported), negative energy direction
(exported)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
L1
P3U30_3LN+Uo_A
L2
L3
X2:1
U4 X2
X2:2
X5:20 X5
U1
X5:19
X5:18
U2
X5:17
Easergy P3 Standard
X5:16
U3
X5:15
X1:1
IL1
X1
X1:2
X1:3
IL2
X1:4
X1:5
1) IL3
X1:6
X1:7
I0 5A
X1:8
X1:9
2) I0 1A
X1:10
1) Positive CT current flow, positive energy direction (imported), negative energy direction
(exported)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
L1 L2 L3
LPCT
IL1 RJ45
IL2 RJ45
IL3 RJ45
1)
X1:1
X1
Io 5A
X1:2
X1:3
2) Io 1A
X1:4
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
NOTE: If one or two LPVTs are connected to the LPVT hub connector, a
termination accessory delivered with the protection device needs to be
plugged on the second and third input.
L1
L2
L3
LPVT L1
LPVT L2
A
LPVT L3
B
LPVT
HUB1 (U1, U2, U3)
B. Cable < 10 m
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
L1
L2
L3
LPVT L1
LPVT L2
A
LPVT L3
B
C
LPVT
HUB1 (U1, U2, U3)
A LPVT
HUB2 (U4)
B. Cable < 10 m
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
Protection devices need current and voltage data from the equipment to be
protected. For technical, economic and safety reasons, this data cannot be
obtained directly from the equipment’s medium-voltage (MV) power supply. For
this purpose, low-power instrument transformers (LPITs) can be used. LPITs:
• reduce the size of value to be measured
• provide galvanic separation
• supply the power needed to process the data or even for the protection device
to work
Using LPITs has many benefits compared to using tranditional CTs or VTs:
• improved personal safety during testing and operation
• one LPCT replaces the dedicated measurement CTs and protection CTs
• the LPCT primary rating is no longer to be as close as possible to the nominal
current
• time and money savings during project planning and execution
• reduced environmental impact because of reduced instrument transformer
size
LPITs compliant with the standards IEC 60044 and IEC 61869 can be connected
to the LPIT inputs of Easergy P3 devices.
NOTE: If the LPCT sensor is disconnected, the current becomes zero, and an
alarm is raised in diagnosis log.
1 Io (S1) 5A 1A 5A 1A
2 Io (S2)
4 Io (S2)
Connections
NOTICE
INCORRECT VOLTAGE MEASUREMENT
• The earth of the connection diagrams below must be the same of the whole
Easergy P3 protection device. The 0 V of the Easergy P3 power supply input
must be connected to this earth.
• The AC voltage adapter’s earth connection point must be connected to the
VT sensor’s (LV transformer) isolated ground. For other wiring cases,
consult Schneider Electric.
A
B
C
A B C
E
D
P533H9B
A
B
C
A B C
E
D
P533HAB
A
B
C
A C
B
P533HBB
A
B
C
A C
B
P533HCB
A
B
C
A C
B
P533HDB
The Ethernet RJ45 cable is connected to the Easergy P3 protection device. The
cable length is maximum 4 m (13.12 ft).
NOTE: The voltage adapter is delivered with black, brown, grey and light blue
cables. The light blue cable in the voltage transformer adapter input is not
used.
Dimensions
B C
E
P533HEA
Click!
2
1 3
P533HFA
Mount the adapter using two fastening collars (width: 4 mm/0.16 in).
A
P533HHA
A. Screw
Mount the adapter on Telequick grid using two screws (4 mm/0.16 in).
You can lock the voltage transformer adapter’s RJ45 input in open or closed
position by placing a seal in the hole marked with a lock symbol. This allows to
lock the RJ45 connector of the Ethernet cable in its slot or helps to prevent its
connection.
A
P533HGB
P533RVA
Impulse voltage distance IEC 60255-27 1.2 μs, 50 μs, 5 kV, 0.5J
Figure 231 shows the connection diagram that includes the Easergy P3 protection
relay and a low-frequency generator as described in 9.6.1 Testing tools and
equipment.
1
2
3
4
IL1 RJ45 1
2
IL2 RJ45 1
LPCTs
IL3 RJ45
2 C
1
2
A B
4
5 VL1, VL2, VL3 RJ45
4
LPVTs
5
4 RJ45
5
This test verifies that the accuracy of the low-power current transformer (LPCT)
measurement is within acceptable tolerances.
4. Check its magnitude using a multimeter or reading from the test equipment.
5. Check the current magnitude displayed on the local panel of the Easergy P3
device.
This test verifies that the accuracy of the low-power voltage transformer (LPVT)
measurement is within acceptable tolerances.
2. Use a generator with low voltage output (10 V max) and connect it directly to
the LPVT hub as described in 9.6.1 Testing tools and equipment.
NOTE: If you have only one cable connected to the LPVT hub, you must
use the provided termination accessory in the empty channels to enable
measurement.
4. Check its magnitude using a multimeter or reading from the test equipment.
5. Check the voltage magnitude on the local panel of the Easergy P3 device.
Terminal X5 X2
20 19 18 17 16 15 1 2
Voltage channel U1 U2 U3 U4
3LN+U0 U0
3LN+LNy LNy
2LL LLy U0
+U0+LLy
2LL LNy
+U0+LNy
LL U12y U12z
+U0+LLy
+LLz
P3U10 U0 U0
P3U20
ULN UL1
ULL UL1-2
P3U30_3LN
UL2
UL3
X5:20
U1
X5
X5:19
X5:18
U2
X5:17
X5:16
U3
X5:15
3LN
• Voltages measured by VTs: : UL1, UL2, UL3
• Values calculated: UL12, UL23, UL31, U0, U1, U2, U2/U1, f
• Measurements available: All
• Protection functions not available: ANSI 67NI, ANSI 25
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
UL1
UL2
UL3
X2:1 X2
U4
X2:2
X5:20
U1
X5
X5:19
X5:18
U2
X5:17
X5:16
U3
X5:15
3LN+U0
This connection is typically used for feeder and motor protection schemes.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
UL1
UL2
UL3
X2:1 X2
U4
X2:2
X5:20
U1
X5
X5:19
X5:18
U2
X5:17
X5:16
U3
X5:15
3LN+LLy
• Voltages measured by VTs: UL1, UL2, UL3, UL12y
• Values calculated: UL12, UL23, UL31, U0, U1, U2, U2/U1, f
• Measurements available: All
• Protection functions not available: ANSI 67NI
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
UL1
UL2
UL3
X2:1 X2
U4
X2:2
X5:20
U1
X5
X5:19
X5:18
U2
X5:17
X5:16
U3
X5:15
3LN+LNy
This connection is typically used for feeder protection scheme where line-to-
neutral voltage is required for synchrocheck application.
• Voltages measured by VTs: UL1, UL2, UL3, UL1y
• Values calculated: UL12, UL23, UL31, U0, U1, U2, U2/U1, f
• Measurements available: All
• Protection functions not available: ANSI 67NI
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
UL1
P3U30_2LL + Uo
UL2
UL3
X5:20
U1
X5
X5:19
X5:18
U2
X5:17
X5:16
U3
X5:15
2LL+U0
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
UL1
UL2
UL3
X2:1 X2
U4
X2:2
X5:20
U1
X5
X5:19
X5:18
U2
X5:17
X5:16
U3
X5:15
2LL+U0+LLy
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
UL1
UL2
UL3
X2:1 X2
U4
X2:2
X5:20
U1
X5
X5:19
X5:18
U2
X5:17
X5:16
U3
X5:15
2LL+U0+LNy
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
UL1
UL2
UL3
X2:1 X2
U4
X2:2
X5:20
U1
X5
X5:19
X5:18
U2
X5:17
X5:16
U3
X5:15
LL+U0+LLy+LLz
This scheme has two CBs to be synchronized. The left side of the bus bar has
line-to-line and right side line-to-line connection for synchrocheck's reference
voltages. In the middle system, voltages are measured by phase-to-neutral and
broken delta connection.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
X2:1 X2
U4
X2:2
X5:20
U1
X5
X5:19
X5:18
U2
X5:17
X5:16
U3
X5:15
LN+U0+LNy+LNz
This scheme has two CBs to be synchronized. The left and right sides of the bus
bar have line-to-neutral connections for synchrocheck's reference voltages. In the
middle system, voltages are measured by phase-to-neutral and broken delta
connection.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and / or the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
Table 154 - Voltage measurement modes for P3U30 using LPVT or VT with voltage adapter
Voltage channel U1 U2 U3 U4
3LN+U0 U0
3LN+LNy LNy
3LN
UL1
P3x3x 3LN
UL2
UL3
8/E/2 : 1...8
8/F/2 : 1...8
1
U1
2
3
U2
4
5
U3
6
7
U4
8
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
3LN+U0
This connection is typically used for feeder and motor protection schemes.
3LN+LNy
This connection is typically used for feeder protection scheme where line-to-
neutral voltage is required for synchrocheck application.
LN+U0+LNy+LNz
This scheme has two CBs to be synchronized. The left and right sides of the bus
bar have line-to-neutral connections for synchrocheck's reference voltages. In the
UL1
P3x3x LN + Uo + LNy + LNz UL2
UL3
8/E/2 : 1...8
8/F/2 : 1...8
1 U1
2
3 U2
4
5 U3
6
7 U4
8
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
The specifically designed CSH120 and CSH200 core balance CTs are for direct
earth fault overcurrent measurement. The difference between CSH120 and
CSH200 is the inner diameter.
Characteristics
CSH120 CSH200
(-13°F to +158°F)
Maximum permissible 20 kA - 1 s
current
Dimensions
A B
C
G H J D
I K
F E
Dime C. D. E. F. G. H. I. J. K.
nsion
s
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
• Only qualified personnel should install this equipment. Such work should
be performed only after reading this entire set of instructions and checking
the technical characteristics of the device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing device to confirm that all
power is off.
• Only CSH120 and CSH200 core balance CTs can be used for direct earth
fault overcurrent measurement.
• Install the core balance CTs on insulated cables.
• Cables with a rated voltage of more than 1000 V must also have an
earthed shielding.
Assembly
Group the MV cable (or cables) in the middle of the core balance CT.
CAUTION
HAZARD OF NON-OPERATION
Connect the secondary circuit and the cable shielding of the CSH core
balance CTs to earth in the shortest possible manner according to the
connection diagram presented in this document.
Connection
Recommended cable
The maximum resistance of the Easergy P3U10, P3U20 and P3U30 connection
wiring must not exceed 4 Ω (i.e. 20 m maximum for 100 mΩ/m or 66 ft maximum
for 30.5 mΩ/ft).
±15 kV air
Fast transients (EFT) IEC/EN 61000-4-4 Level 4 ±4 kV, 5/50 ns, 5 kHz
IEEE C37.90.1
Impulse voltage withstand IEC/EN 60255-27, Class III 5 kV, 1.2/50 μs, 0.5 J
0.5 kV, 50 Hz
Communication
Device in operation
Device de-energized
Device in operation
93% RH
5 cycles
Device in storage
Condition Value
10.6 Casing
Table 160 - Casing
Parameter Value
Degree of protection (IEC 60529) IP54 Front panel, IP20 rear side
11 Maintenance
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Wear your personal protective equipment (PPE) and comply with the safe
electrical work practices. For clothing, see applicable local standards.
• Only qualified personnel should install this equipment. Such work should
be performed only after reading this entire set of instructions and checking
the technical characteristics of the device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing device to ensure that all
power is off.
• Do not open the secondary circuit of a live current transformer.
• Always connect the polarity of the current transformer (CT) and the voltage
transformer (VT) and their secondary ground wiring according to the
connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
The Easergy P3 protection relays and arc flash detection products together with
their extension units, communication accessories, arc flash detection sensors and
cabling, later called “device”, require maintenance in work according to their
specification. Keep a record of the maintenance actions. The maintenance can
include, but is not limited to:
• preventive maintenance
• periodic testing
• hardware cleaning
• system status messages
• spare parts
• self-supervision
• dirty components
• loose wire connections
• damaged wiring
• indicator lights
• other mechanical connections
Related topics
2.5.6 Testing the LEDs and LCD screen
Conduct the testing with a secondary injection principle for the protection stages
used in the device and its extension units.
In corrosive or offshore environments, carry out functional testing every three (3)
years. For the testing procedures, see separate testing manuals.
11.6 Self-supervision
NOTICE
LOSS OF PROTECTION OR RISK OF NUISANCE TRIPPING
Description
The electronic parts and the associated circuitry as well as the program execution
are supervised by means of a separate watchdog circuit. Besides supervising the
device, the watchdog circuit attempts to restart the microcontroller in an
inoperable situation. If the microcontroller does not restart, the watchdog issues a
self-supervision signal indicating a permanent internal condition.
When the watchdog circuit detects a permanent fault, it always blocks any control
of other digital outputs (except for the self-supervision digital output). In addition,
the internal supply voltages are supervised. Should the auxiliary supply of the
device disappear, an indication is automatically given because the device status
inoperative (SF) digital output functions on a working current principle. This
means that the SF relay is energized, the X3:18–20 contact closed, when the
auxiliary supply is on. The service LED and SF contact are assigned to work
together. The manufacturer recommends that the SF output is hardwired into the
substation's automation system for alarm purposes.
11.6.1 Diagnostics
The device runs self-diagnostic tests for hardware and software in boot sequence
and also performs runtime checking.
Diagnostic registers
There are four 16-bit diagnostic registers which are readable through remote
protocols.
1 (Reserved) (Reserved)
2 T1 Detected digital
output fault
3 T2
4 T3
5 T4
6 T5
7 T6
8 T7
10 A1
The code is displayed in self-diagnostic events and on the diagnostic menu on the
local panel and Easergy Pro.
NOTE: All signals are not necessarily available in every Easergy P3 product.
X1 X1 X2 X5 X4
Application
U10 = Feeder & Motor, 4xI, 1xU. 2DI, 5DO
Future option
A = None
3 = 220 Vdc/ac
Product version
A = Version 2.1, newest FW
Region
A = English, IEC
B = English, ANSI
1) Always check the power supply range from the device's serial number label.
Application
U20 = Feeder & Motor, 4xI, 1xU. 2DI, 5DO
Product version
A = Version 2.1, newest FW
B = FW30.108
A
Region
B = English, IEC
= English, ANSI X1=6
1) Always check the power supply range from the device's serial number label.
Application
U30 = Feeder & Motor, 4xI, 4xU. 2DI, 5DO
Future option
A = None
B = Ecofit
Product version
A = Version 2.1, newest FW
B = FW30.108
Region
A = English, IEC
B = English, ANSI Slot X1 = 6
C = Chinese
R = Russian
1) Always check the power supply range from the device's serial number label.
12.2 Accessories
Table 162 - Accessories for Easergy P3 Standard
VW3A8306RC LPVT hub termination, use this if all LPVT are VW3A8306R X
not present C
13 Firmware revision
Table 163 - Firmware revisions
FW revision Changes
Version: 30.205 • Support for the new CSH sensor I0 input (applies to P3Ux, P3F30, P3G30,
P3L30, and P3M30)
Release date: October 2021
• Added residual voltage calculation for intermittent earth fault (67NI)
• Frequency stage improvement
• Global trip line to output matrix
• Local panel control no longer requires activation of the Operator access level
when it is disabled in the Objects setting view
• HMI password enhancement with letters and characters
• Communication:
◦ IEC61850 new LN (LTIM) added for time management
◦ IEC61850 new LN (ZMOT) added for running hours
◦ Modbus update to access arc sensor status
◦ New timeout mechanism added for Telnet/Serial/Http connections
Version: 30.204 • Phase rotation configuration ABC to ACB for voltage and currents
• Communications:
Release date: January 2021
◦ IEC61850 and Modbus: Alarm setting and operations left parameters for
circuit breaker monitoring
◦ Ethernet/IP communication protocol restored back to use
Version: 30.203 • I>>> stage latch function upgrade during the power on-off-on state
• RSTP network reconstruction optimization
Release date: July 2020
• Adjusted time stamps for disturbance recorder and events logs
• Backlight off default timeout changed to 10 min
• Added Modbus registers for alarm setting of CB wear (read) and Operation left
data (read)
• DNP3 updates:
◦ Added function 24 record current time
◦ Added VO and LED status to BI data list
◦ Added the possibility to configure time reference to UTC
FW revision Changes
Version: 30.111 • Improved menu titles for COM ports and Ethernet ports in the Protocol
Configuration menu
Release date: October 2019
• IEC-61850 speed optimizations
• Modbus:
◦ registers to include protection function status
◦ added LED status information
Version: 30.109 • Negative sequence voltage U2>, U2>> and U2>>>(ANSI 47) stages added.
• Maximum number of disturbance records increased from 12 to 24.
Release date: March 2019
Version: 30.106 • The setting "Inv. time coefficient k" in stages I>, Iφ>, Iφ>>, Io>, Ioφ>, Ioφ>>,
Ioφ>>> has three decimals instead of two and the minimum value for the earth
Release date: 16.5.2018
fault overcurrent was changed from 0.05 to 0.025.
• Communication protocol updates