p3T32 2024 Version
p3T32 2024 Version
p3T32 2024 Version
P3T/EN/M/30-208A
www.schneider-electric.com
Table of Contents Transformer protection relay
Table of Contents
1 About this manual........................................................................ 12
1.1 Purpose...........................................................................................................12
1.2 Related documents......................................................................................... 12
1.3 Abbreviations and terms................................................................................. 13
1.4 Easergy to PowerLogic renaming................................................................... 18
1.5 Description of the document versions.............................................................19
2 Product introduction..................................................................... 20
2.1 Warranty..........................................................................................................20
2.2 Product overview............................................................................................ 20
2.3 Product selection guide...................................................................................21
2.4 Access to device configuration....................................................................... 29
2.4.1 User accounts.......................................................................................30
2.4.2 Logging on via the front panel.............................................................. 30
2.4.3 HTTP and FTP logon details................................................................ 31
2.4.4 Password management........................................................................ 31
2.4.5 Password restoring............................................................................... 32
2.5 Front panel......................................................................................................32
2.5.1 Push-buttons.........................................................................................33
2.5.2 LED indicators...................................................................................... 33
2.5.3 Configuring the LED names via eSetup Easergy Pro...........................34
2.5.4 Controlling the alarm screen.................................................................35
2.5.5 Accessing operating levels................................................................... 35
2.5.6 Adjusting the LCD contrast................................................................... 35
2.5.7 Testing the LEDs and LCD screen........................................................36
2.5.8 Controlling an object with selective control...........................................36
2.5.9 Controlling an object with direct control................................................ 36
2.5.10 Menus................................................................................................. 36
2.5.10.1 Moving in the menus ............................................................ 39
2.5.10.2 Local panel messages...........................................................39
2.6 eSetup Easergy Pro setting and configuration tool.........................................40
3 Mechanical structure.................................................................... 41
3.1 Modularity....................................................................................................... 41
3.2 Slot info and order code..................................................................................42
4 Measurement functions................................................................44
4.1 Primary, secondary and per unit scaling......................................................... 48
4.1.1 Frequency adaptation mode................................................................. 51
4.1.2 Current scaling......................................................................................52
4.1.3 Voltage scaling for analog module E, F................................................ 54
4.1.4 Residual value scaling.......................................................................... 56
4.2 Measurements for protection functions...........................................................58
4.3 Measurements for arc flash detection function............................................... 59
P3T/EN/M/30-208A 3
Transformer protection relay Table of Contents
5 Control functions.......................................................................... 70
5.1 Digital outputs................................................................................................. 70
5.2 Digital inputs................................................................................................... 74
5.3 Virtual inputs and outputs................................................................................80
5.4 Matrix.............................................................................................................. 87
5.4.1 Output matrix........................................................................................ 87
5.4.2 Blocking matrix..................................................................................... 88
5.4.3 LED matrix............................................................................................ 90
5.4.4 Object block matrix............................................................................... 92
5.5 Releasing latches............................................................................................92
5.5.1 Releasing latches using eSetup Easergy Pro.......................................92
5.5.2 Releasing latches using buttons and local panel display......................93
5.5.3 Releasing latches using F1 or F2 buttons............................................ 93
5.6 Controllable objects........................................................................................ 94
5.6.1 Object control with digital inputs........................................................... 96
5.6.2 Local or remote selection......................................................................96
5.6.3 Object control with I and O buttons.......................................................97
5.6.4 Object control with F1 and F2...............................................................97
5.6.5 Adjustable time delay mechanism for the object’s closing operation....99
5.7 Logic functions.............................................................................................. 100
5.8 Local panel....................................................................................................108
5.8.1 Mimic view.......................................................................................... 109
5.8.2 Local panel configuration.................................................................... 112
4 P3T/EN/M/30-208A
Table of Contents Transformer protection relay
6.6.2 Free parameterization using IEC, IEEE and IEEE2 curves................ 155
6.6.3 Programmable dependent time curves...............................................156
6.7 Volts/hertz overexcitation protection Uf> (ANSI 24)...................................... 160
6.8 Synchrocheck (ANSI 25)...............................................................................162
6.9 Undervoltage (ANSI 27)................................................................................166
6.10 Positive sequence undervoltage (ANSI 27P)..............................................169
6.11 Negative sequence overcurrent (ANSI 46) .................................................172
6.12 Negative sequence overvoltage protection (ANSI 47)................................ 174
6.13 Thermal overload (ANSI 49 RMS).............................................................. 175
6.14 Breaker failure (ANSI 50BF)....................................................................... 179
6.15 Breaker failure 1 and 2 (ANSI 50BF).......................................................... 181
6.16 Switch-on-to-fault (ANSI 50HS) ................................................................. 187
6.17 Phase overcurrent (ANSI 50/51).................................................................189
6.18 Earth fault overcurrent (ANSI 50N/51N) .................................................... 194
6.18.1 Earth fault faulty phase detection algorithm......................................197
6.19 Capacitor bank unbalance (ANSI 51C) ......................................................198
6.19.1 Taking unbalance protection into use............................................... 201
6.20 Overvoltage (ANSI 59)................................................................................205
6.21 Neutral voltage displacement (ANSI 59N).................................................. 209
6.22 Restricted high-impedance earth fault (ANSI 64REF, 64BEF)....................212
6.23 Restricted earth fault (ANSI 64REF) ..........................................................213
6.24 Directional phase overcurrent (ANSI 67) ................................................... 218
6.25 Directional earth fault overcurrent (ANSI 67N)........................................... 226
6.25.1 Earth fault faulty phase detection algorithm......................................231
6.26 Magnetizing inrush detection (ANSI 68F2)................................................. 233
6.27 Fifth harmonic detection (ANSI 68H5)........................................................ 235
6.28 Overfrequency and underfrequency (ANSI 81) ..........................................236
6.29 Rate of change of frequency (ANSI 81R)................................................... 239
6.30 Lockout (ANSI 86).......................................................................................243
6.31 Differential overcurrent protection (ANSI 87T) ........................................... 245
6.32 Arc flash detection (AFD)............................................................................253
6.32.1 Arc flash detection, general principle................................................253
6.32.2 Arc flash detection menus................................................................ 253
6.32.3 Binary inputs and outputs................................................................. 257
6.32.4 Binary input and binary output self-supervision................................ 258
6.32.5 Configuration example of arc flash detection....................................259
6.32.6 Arc flash detection characteristics.................................................... 263
6.33 Programmable stages (ANSI 99)................................................................ 265
P3T/EN/M/30-208A 5
Transformer protection relay Table of Contents
10 Installation................................................................................ 352
10.1 Safety in installation.................................................................................... 352
10.2 Checking the consignment..........................................................................354
10.3 Product identification...................................................................................354
10.4 Storage....................................................................................................... 355
10.5 Mounting..................................................................................................... 355
6 P3T/EN/M/30-208A
Table of Contents Transformer protection relay
P3T/EN/M/30-208A 7
Transformer protection relay Table of Contents
12 Maintenance.............................................................................432
12.1 Preventive maintenance............................................................................. 432
12.2 Periodic testing........................................................................................... 433
12.3 Hardware cleaning...................................................................................... 433
12.4 System status messages............................................................................ 433
12.5 Spare parts................................................................................................. 433
12.6 Self-supervision.......................................................................................... 433
12.6.1 Diagnostics....................................................................................... 435
12.7 Arc flash detection system maintenance.................................................... 437
12.7.1 Visual inspection...............................................................................438
12.7.2 Hardware cleaning............................................................................438
12.7.3 Sensor condition and positioning check........................................... 439
14 Firmware revision.....................................................................444
8 P3T/EN/M/30-208A
Legal information Transformer protection relay
Legal information
The Schneider Electric brand and any registered trademarks of Schneider Electric
Industries SAS referred to in this guide are the sole property of Schneider Electric
SA and its subsidiaries. They may not be used for any purpose without the
owner's permission, given in writing. This guide and its content are protected,
within the meaning of the French intellectual property code (Code de la propriété
intellectuelle français, referred to hereafter as "the Code"), under the laws of
copyright covering texts, drawings and models, as well as by trademark law. You
agree not to reproduce, other than for your own personal, noncommercial use as
defined in the Code, all or part of this guide on any medium whatsoever without
Schneider Electric's permission, given in writing. You also agree not to establish
any hypertext links to this guide or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the guide or its
content, except for a non-exclusive license to consult it on an "as is" basis, at your
own risk. All other rights are reserved.
As standards, specifications and designs change from time to time, please ask for
confirmation of the information given in this publication.
P3T/EN/M/30-208A 9
Transformer protection relay Safety information
Safety information
Important information
Read these instructions carefully and look at the equipment to become familiar
with the device before trying to install, operate, service or maintain it.
The following special messages may appear throughout this publication or on the
equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result
in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could
result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Please note
Protective grounding
The user is responsible for compliance with all the existing international and
national electrical codes concerning protective grounding of any device.
10 P3T/EN/M/30-208A
EU directive and UKCA regulations compliance Transformer protection relay
P3T/EN/M/30-208A 11
Transformer protection relay 1 About this manual
1.1 Purpose
This document contains instructions on the installation, commissioning and
operation of PowerLogic P3T32.
This document is intended for persons who are experts on electrical power
engineering, and it covers the relay models as described by the order code in
13.1 Order codes.
Document Identification1)
12 P3T/EN/M/30-208A
1 About this manual Transformer protection relay
A standardization organization
CB Circuit breaker
CM Common mode
CT Current transformer
DC Direct current
DI Digital input
DM Differential mode
P3T/EN/M/30-208A 13
Transformer protection relay 1 About this manual
DO Digital output
DT Definite time
Eth packets per second limit Use this to set the maximum transmitted
packet limit in each second by the
PowerLogic P3 device. The recommended
setting is 75.
14 P3T/EN/M/30-208A
1 About this manual Transformer protection relay
IN Nominal current
An international standardization
organisation
P3T/EN/M/30-208A 15
Transformer protection relay 1 About this manual
P Active power
Unit = [W]
PF Power factor
pu Per unit
Q Reactive power
Unit = [var]
RH Relative humidity
16 P3T/EN/M/30-208A
1 About this manual Transformer protection relay
S Apparent power
Unit = [VA]
P3T/EN/M/30-208A 17
Transformer protection relay 1 About this manual
UN Nominal voltage
VI Virtual input
VO Virtual output
VT Voltage transformer
This brand optimization initiative affects Protection & Control portfolio including
Easergy P3 protection and control relays. The Easergy P3 has been renamed to
PowerLogic P3. It is essential to emphasize that this renaming exclusively affects
the brand name of the products and will have absolutely no consequence on the
current performance, specifications, characteristics, and/or quality of the product,
which remain totally unaffected by this brand name migration. During the brand
transition project, it may happen that the application of this change to different
parts of the offer becomes effective with different time schedules. There is
absolutely no difference between Easergy and PowerLogic branded P3 products
and accessories. Easergy accessories can be used with PowerLogic P3 product
as long as the commercial reference is matching. The commercial references
18 P3T/EN/M/30-208A
1 About this manual Transformer protection relay
have not changed along with the renaming of the offer. eSetup Easergy Pro and
CET850 remain the software to configure PowerLogic P3 protection and control
relays.
• Product type
◦ P3U stands for PowerLogic P3 Standard; P3X stands for PowerLogic P3
Advanced;
◦ P3F stands for PowerLogic P3 Feeder;
◦ P3G stands for PowerLogic P3 Generator;
◦ P3L stands for PowerLogic P3 Line differential;
◦ P3M stands for PowerLogic P3 Motor;
◦ P3T stands for PowerLogic P3 Transformer.
• Language and standard definition
◦ EN, FR, IT, ES, PT, RU, CN, ANSI, and so on.
◦ By default, the IEC standard applies. ANSI version is always published in
the English language.
• Document type
◦ M stands for User Manual, QS stands for Quick Start Manual, C stands for
Communication Manual.
• Major version of the firmware
• Release version of the firmware
• Document version, which loops from A to Z for a dedicated release version.
P3T/EN/M/30-208A 19
Transformer protection relay 2 Product introduction
2 Product introduction
2.1 Warranty
This product has a standard warranty of 2 years.
Ask your local Schneider Electric representative about our optional 10-year
warranty. Local conditions and availability apply.
Protection functions
20 P3T/EN/M/30-208A
2 Product introduction Transformer protection relay
Virtual injection
Robust hardware
P3T/EN/M/30-208A 21
Transformer protection relay 2 Product introduction
Table 3 - Applications
Voltage – –
Feeder P3F30
w. directional
–
P3L30
P3U30 w. line diff.
with directional
Transformer o/c P3T32
–
P3U20 with voltage with differential
protection
Motor P3M32
P3M30
with differential
Generator P3G32
P3G30
with differential
Measuring inputs Phase current 1/5A CT (x3) 1/5A CT (x3) or 1/5A CT (x3) or 1/5A CT (x6)
LPCT (x3) LPCT (x3)2)
Output 0 or 4 3) 0 or 4 3)
Nominal power supply 24 Vdc or 24...48 Vdc (20...57 Vdc) or 24...48 Vdc (20...57 Vdc) or 110...240
48...240 Vdc/ac (39...265 V dc/ac)4) Vdc/ac (88...265 V dc/ac)
22 P3T/EN/M/30-208A
2 Product introduction Transformer protection relay
Communication
IRIG/B ■ ■ ■
Ethernet ■ ■ ■
IEC 60870-5-101 ■ ■ ■
IEC 60870-5-103 ■ ■ ■
IEC 60870-5-104 ■ ■ ■
Modbus serial ■ ■ ■
Modbus TCP/IP ■ ■ ■
Ethernet/IP ■ ■ ■
Profibus DP ■ ■ ■
SPAbus ■ ■ ■
Redundancy RSTP ■ ■ ■
protocols
PRP ■ ■ ■
Others
Logic Matrix ■ ■
Logic equations ■ ■
Remote UMI – ■
NOTE: The numbers in the following tables represent the amount of stages
available for each PowerLogic P3 type.
P3T/EN/M/30-208A 23
Transformer protection relay 2 Product introduction
Protection functions ANSI Feeder P3U20 Feeder P3U30 Motor P3U20 Motor P3U30
code
Synchronization check5) 25 – 2 – 2
Undervoltage 27 – 3 – 3
Phase undercurrent 37 1 1 1 1
Negative sequence 46 – – 2 2
overcurrent (motor,
generator)
Negative sequence 47 – 3 – 3
overvoltage protection
Thermal overload 49 1 1 1 1
SOTF 50HS 1 1 1 1
Voltage-dependent 51V – 1 – 1
overcurrent
Overvoltage 59 – 3 – 3
CT supervision 60 1 1 1 1
VT supervision 60FL – 1 – 1
24 P3T/EN/M/30-208A
2 Product introduction Transformer protection relay
Protection functions ANSI Feeder P3U20 Feeder P3U30 Motor P3U20 Motor P3U30
code
Directional phase 67 – 4 – 4
overcurrent
Auto-Recloser 79 5 5 – –
Lockout 86 1 1 1 1
Programmable stages 99 8 8 8 8
Programmable curves – 3 3 3 3
Setting groups 8) – 4 4 4 4
5) The availability depends on the selected voltage measurement mode (in the Scaling setting view in eSetup Easergy Pro)
6) Using external RTD module
7) Capacitor bank unbalance protection is connected to the earth fault overcurrent input and shares two stages with the earth fault
overcurrent protection.
8) Not all protection functions have 4 setting groups. See details in the manual.
Protection functions ANSI P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
code
Under-impedance 21G – – – – 2 2 –
Overfluxing 24 – – – – 1 1 1
Synchronization check9) 25 2 2 2 2 2 2 2
Undervoltage 27 3 3 3 3 3 3 3
Phase undercurrent 37 – – 1 1 – – –
P3T/EN/M/30-208A 25
Transformer protection relay 2 Product introduction
Protection functions ANSI P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
code
Loss of field 40 – – – – 1 1 –
Under-reactance 21/40 – – – – 2 2 –
Negative sequence 46 – – 2 2 2 2 2
overcurrent (motor,
generator)
Negative sequence 47 3 3 3 3 3 3 3
overvoltage protection
Thermal overload 49 1 1 1 1 1 1 1
SOTF 50HS 1 1 1 1 1 1 1
Voltage-dependent 51V 1 1 – – 1 1 –
overcurrent
Overvoltage 59 3 3 3 3 3 3 3
CT supervision 60 1 1 1 1 1 2 2
VT supervision 60FL 1 1 1 1 1 1 1
Directional phase 67 4 4 4 4 4 4 4
overcurrent
26 P3T/EN/M/30-208A
2 Product introduction Transformer protection relay
Protection functions ANSI P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
code
Auto-Recloser 79 5 5 – – – – –
Over or under frequency 81 2/2 2/2 2/2 2/2 2/2 2/2 2/2
Lockout 86 1 1 1 1 1 1 1
Programmable stages 99 8 8 8 8 8 8 8
Programmable curves – 3 3 3 3 3 3 3
overcurrent protection.
12) Not all protection functions have 4 setting groups. See details in the manual.
Control functions P3U20 P3U30 P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
Switchgear monitoring – – 2 2 2 2 2 2 2
only
Programmable switchgear ■ ■ ■ ■ ■ ■ ■ ■ ■
interlocking
P3T/EN/M/30-208A 27
Transformer protection relay 2 Product introduction
Control functions P3U20 P3U30 P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
Local/remote function ■ ■ ■ ■ ■ ■ ■ ■ ■
Function keys 2 2 2 2 2 2 2 2 2
Table 8 - Measurements
Measurement P3U20 P3U30 P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
Frequency ■ ■ ■ ■ ■ ■ ■ ■ ■
Fundamental frequency – ■ ■ ■ ■ ■ ■ ■ ■
voltage values
Fundamental frequency – ■ ■ ■ ■ ■ ■ ■ ■
active, reactive and
apparent power values
Power factor – ■ ■ ■ ■ ■ ■ ■ ■
28 P3T/EN/M/30-208A
2 Product introduction Transformer protection relay
Measurement P3U20 P3U30 P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
Harmonic values of – ■ ■ ■ ■ ■ ■ ■ ■
voltage and THD
Logs and Records P3U20 P3U30 P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
Disturbance record ■ ■ ■ ■ ■ ■ ■ ■ ■
Monitoring functions P3U20 P3U30 P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
Relay monitoring ■ ■ ■ ■ ■ ■ ■ ■ ■
P3T/EN/M/30-208A 29
Transformer protection relay 2 Product introduction
NOTE: To log on via the front panel, you need a password that consists of
letters, digits, or other characters in the scope of ASCII 0x21~0x7E.
1. Press and on the front panel. The Enter password view opens.
Select a digit value using , and if the password is longer than one digit,
move to the next digit position using .
30 P3T/EN/M/30-208A
2 Product introduction Transformer protection relay
NOTE: There are 16 digit positions in the Enter password view. Enter the
password starting from the first digit position.
For example, if the password is 2, you can enter 2***, **2*, ***2, or 0002
to log on.
Related topics
2.4.4 Password management
You can log on to the HTTP server and FTP using these user names and
passwords.
HTTP conf 2
FTP conf 2
NOTICE
CYBERSECURITY HAZARD
• Change all passwords from their default values when taking the protection
device into use.
• Change all passwords regularly.
• Ensure a minimum level of password complexity according to common
password guidelines.
You can change the password for the operator or configurator user accounts in
the DEVICE/TEST > System info setting view in eSetup Easergy Pro.
The password can contain letters, digits or other characters in the scope of ASCII
0x21~0x7E. However, the new password cannot be any of the default passwords
(digits 0–4 or 9999).
Follow these guidelines to improve the password complexity and thus device
security:
• Use a password of minimum 8 characters.
• Use alphabetic (uppercase and lowercase) and numeric characters in addition
to symbols.
• Avoid character repetition, number or letter sequences and keyboard patterns.
• Do not use any personal information, such as birthday, name, etc.
• Do not use the same password for different user accounts.
• Do not reuse old passwords.
P3T/EN/M/30-208A 31
Transformer protection relay 2 Product introduction
Also, all users must be aware of the best practices concerning passwords
including:
• not sharing personal passwords
• not displaying passwords during password entry
• not transmitting passwords in email or by other means
• not saving the passwords on PCs or other devices
• no written passwords on any supports
• regularly reminding users about the best practices concerning passwords
Related topics
2.4.2 Logging on via the front panel
If you have lost or forgotten all passwords, contact Schneider Electric to restore
the default passwords.
A B D E F
ON Service
A B
C D
E F
G H
I J
K L
M N
F1 F2
I J G C G J H
32 P3T/EN/M/30-208A
2 Product introduction Transformer protection relay
2.5.1 Push-buttons
Symbol Function
14) The default names of the function buttons are Function button 1 and 2. You can change the names
of the buttons in the Control > Names for function buttons setting view.
When the relay is powered, the power LED is green. During normal use, the
service LED is not active, it activates only when an error occurs or the relay is not
operating correctly. Should this happen, contact your local representative for
further guidance. The service LED and watchdog contact are assigned to work
together. Hardwire the status output into the substation's automation system for
alarm purposes.
The user-configurable LEDs may be red or green. You can configure them via
eSetup Easergy Pro.
P3T/EN/M/30-208A 33
Transformer protection relay 2 Product introduction
To customize the LED texts on the front panel for the user-configurable LEDs, the
text may be created using a template and then printed. The printed text may be
placed in the pockets beside the LEDs.
You can also customize the LED texts that are shown on the screen for active
LEDs via eSetup Easergy Pro.
2. To change a LED name, click the LED Description text and type a new
name. To save the new name, press Enter.
34 P3T/EN/M/30-208A
2 Product introduction Transformer protection relay
Figure 3 - LED NAMES menu in eSetup Easergy Pro for LED configuration
You can enable or disable the alarm screen either via the relay's local display or
using eSetup Easergy Pro:
NOTE: By nature, the LCD display changes its contrast depending on the
ambient temperature. The display may become dark or unreadable at low
temperatures. However, this condition does not affect the proper operation of
the protection or other functions.
P3T/EN/M/30-208A 35
Transformer protection relay 2 Product introduction
You can start the test sequence in any main menu window.
1. Press .
2. Press .
The relay tests the LCD screen and the functionality of all LEDs.
Prerequisite: You have logged in with the correct password and enabled selective
control in the Objects setting view.
– Press to cancel.
• Press to open an object.
– Press to cancel.
Prerequisite: You have logged in with the correct password and enabled direct
control in the Objects setting view.
When direct control is enabled, the control operation is done without confirmation.
• Press to close an object.
• Press to open an object.
2.5.10 Menus
This section gives an overview of the menus that you can access via the device's
front panel.
Press the right arrow to access more measurements in the main menu.
36 P3T/EN/M/30-208A
2 Product introduction Transformer protection relay
P3T/EN/M/30-208A 37
Transformer protection relay 2 Product introduction
38 P3T/EN/M/30-208A
2 Product introduction Transformer protection relay
OK
ISTART setting
OK OK
NOTE: To enter the parameter edit mode, enter the password. When the
value is in edit mode, its background is dark.
P3T/EN/M/30-208A 39
Transformer protection relay 2 Product introduction
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC
FLASH
• General
• Measurements
• Inputs/outputs
• Protection
• Matrix
• Logs
• Communication
The contents of the tabs depend on the relay type and the selected application
mode.
eSetup Easergy Pro stores the relay configuration in a setting file. The
configuration of one physical relay is saved in one setting file. The configurations
can be printed out and saved for later use.
For more information, see the eSetup Easergy Pro user manual.
NOTICE
HAZARD OF EQUIPMENT DAMAGE
40 P3T/EN/M/30-208A
3 Mechanical structure Transformer protection relay
3 Mechanical structure
3.1 Modularity
The relay has a modular structure. The relay is built from hardware modules that
are installed into 10 different slots at the back of the relay. The location of the
slots is shown in Figure 5.
Figure 5 - Slot numbering and card options in the PowerLogic P3T32 rear panel
and an example of defining the pin address 1/C/1:1
A
B 1 2 3 4 5 6 7 8
9 10
C
7, 8, 10 Analog
measurement card
(I, U)
For complete availability information on the different option cards, see 13.2
Accessories.
P3T/EN/M/30-208A 41
Transformer protection relay 3 Mechanical structure
Example
42 P3T/EN/M/30-208A
3 Mechanical structure Transformer protection relay
NOTE: See 13.1 Order codes for the relay ordering options.
P3T/EN/M/30-208A 43
Transformer protection relay 4 Measurement functions
4 Measurement functions
PowerLogic P3 has various amounts of analog inputs depending on the model in
use. Also see 2.3 Product selection guide.
±3 % for range
0.1–0.3xPN
±3 % for range
0.1–0.3xQN
±3 % for range
0.1–0.3xSN
44 P3T/EN/M/30-208A
4 Measurement functions Transformer protection relay
I > 1.5 x IN ±3 % of
value
P3T/EN/M/30-208A 45
Transformer protection relay 4 Measurement functions
±3 % for range
0.1–0.3xPN
±3 % for range
0.1-0.3xQN
±3 % for range
0.1–0.3xSN
46 P3T/EN/M/30-208A
4 Measurement functions Transformer protection relay
I > 1.5 x IN ±3 % of
value
Refer to the following table for the right Modbus address to retrieve measurement
values under voltage measurement modes.
P3T/EN/M/30-208A 47
Transformer protection relay 4 Measurement functions
Mod RMS UL1 UL2 UL3 U12 U23 Uo Uo UL1y U12y UL1 U12 UL1z U12z
bus volta RMS RMS RMS RMS RMS RMS RMS RMS RMS y(LN y(LL RMS RMS
regis ge +Uo/ +Uo/
ter mea 6250 6251 6252 6253 6254 6255 6256 6257 6258 y/z) y/z) 6261 6262
n RMS RMS
Meas
urem
ent
mode
2LL ■ — — — ■ ■ — ■ — — — — — —
+Uo
3LN ■ ■ ■ ■ — — — — — — — — — —
3LN/L ■ ■ ■ ■ — — — — ■ — — — — —
Ny
3LN/L ■ ■ ■ ■ — — — — — ■ — — — —
Ly
2LL ■ — — — ■ ■ — ■ ■ — — — — —
+Uo/L
Ny
2LL ■ — — — ■ ■ — ■ — ■ — — — —
+Uo/L
Ly
3LN ■ ■ ■ ■ — — ■ — — — — — — —
+Uo
LL — — — — ■ — — ■ — — — ■ — ■
+Uo/y
/z
LN — ■ — — — — — ■ — — ■ — ■ —
+Uo/y
/z
The scaling is done using the rated values of VTs and CTs depending on the
selected model order option.
48 P3T/EN/M/30-208A
4 Measurement functions Transformer protection relay
Scaling settings
Parameter Description
CT' primary Primary current value of the CT at the I’L (low-voltage) side (only
P3x32 devices).
CT' secondary Secondary current value of the CT at the I’L (low-voltage) side
(only P3x32 devices).
Nominal input (IL Rated value of the phase current input. The given thermal
side) withstand, burden and impedance are based on this value.
Nominal input (I'L Rated value of the phase current input at I' side. The given
side) thermal withstand, burden and impedance are based on this
value (only P3x32 devices). See Table 166 for details.
I01 CT primary Primary current value of the earth fault I01 overcurrent transformer
I01 CT secondary Secondary current value of the earth fault I01 overcurrent
transformer
Nominal I01 input Selectable nominal input rating for the earth fault overcurrent
input. Select either 5A or 1A depending on which Io input is used.
The given thermal withstand, burden and impedance are based
on this value.
I02 CT primary Primary current value of the earth fault I02 overcurrent transformer
Nominal I02 input Selectable nominal input rating for the earth fault overcurrent
input. Select either 1A or 0.2A depending on which Io input is
used. The given thermal withstand, burden and impedance are
based on this value. See Table 166 for details.
I03 CT primary Primary current value of the earth fault I03 overcurrent transformer
P3T/EN/M/30-208A 49
Transformer protection relay 4 Measurement functions
Parameter Description
I03 CT secondary Secondary current value of the earth fault I03 overcurrent
transformer
Nominal I03 input Selectable nominal input rating for the earth fault overcurrent
input. Select either 1A or 0.2A depending on which Io input is
used. The given thermal withstand, burden and impedance are
based on this value. See Table 166 for details.
Frequency adaptation Parameter used to set the system frequency. There are three
mode modes available: manual, auto and fixed. For more information,
see 4.1.1 Frequency adaptation mode.
Adapted frequency When the frequency adaption mode is set to manual, you can set
the frequency in the Adapted frequency field, and it is not be
updated even if the measured frequency is different.
Angle memory Time setting for the directional overcurrent stage to keep the
duration phase angle fixed if the system voltage collapses
I' 180 deg. angle turn A setting to turn I' currents 180 degrees (only P3x32 devices)
50 P3T/EN/M/30-208A
4 Measurement functions Transformer protection relay
Parameter Description
Residual value Choose to show primary or per unit value of residual currents and
scaling voltages.
The scaling equations presented in 4.1.2 Current scaling and 4.1.3 Voltage
scaling for analog module E, F are useful when doing secondary testing.
You can set the system frequency in General > Scaling in eSetup Easergy Pro.
• Manual: When the adaption mode is set to manual, you can set the frequency
in the Adapted frequency field, and it will not be updated even if the
measured frequency is different. However, the relay monitors the system
frequency internally and adapts to the new frequency even if the frequency
has been set manually.
• Auto: The network frequency is automatically updated when the relay has
measured the voltage for approximately 45 seconds. The Adapted frequency
field is updated even if it has been set previously. The frequency is measured
from the voltage signals.
LN+U0/y/z UL1 U1
LL+U0/y/z U12 U1
• Fixed: The frequency is not updated based on the measured voltage and only
the set value is used. This mode is recommended to be used for the line-
differential function.
P3T/EN/M/30-208A 51
Transformer protection relay 4 Measurement functions
NOTE: The rated value of the relay's current input, for example 5 A or 1 A,
does not have any effect on the scaling equations, but it defines the
measurement range and the maximum allowed continuous current. See Table
166 for details.
Current (CT)
primary → secondary
CTSEC
I SEC = I PRI ⋅
CTPRI
For earth fault overcurrent to input I0, use the corresponding CTPRI and CTSEC
values. For earth fault stages using I0 Calc signals, use the phase current CT
values for CTPRI and CTSEC.
Examples
1. Secondary to primary
CT = 500 / 5
Current to the relay's input is 4 A.
=> Primary current is IPRI = 4 x 500 / 5 = 400 A
2. Primary to secondary
CT = 500 / 5
The relay displays IPRI = 400 A
=> Injected current is ISEC = 400 x 5 / 500 = 4 A
The rated current for high-voltage side (HV) and low-voltages side (LV) are
calculated by the relay itself using Equation 1.
Equation 1
SN
IN =
3 ⋅U N
52 P3T/EN/M/30-208A
4 Measurement functions Transformer protection relay
Examples
CT = 750/5
IN = 525 A
Current injected to the relay's inputs is 7 A.
Per unit current is IPU = 7 x 750 / (5 x 525) = 2.00 pu = 2.00 x IN = 200%
Per unit current is IPU = 7 x 750 / (5 x 525) = 2.00 pu = 2.00 x ITN= 200%
CT = 750 / 5
The relay setting is 2 pu = 200%.
Secondary current is ISEC = 2 x 5 = 10 A
CT = 750 / 5
IN = 525 A
The relay setting is 2 x IN = 2 pu = 200%.
The relay setting is 2 x ITN = 2 pu = 200%.
Secondary current is ISEC = 2 x 5 x 525 / 750 = 7 A
Input is I01.
CT0 = 50 / 1
Current injected to the relay's input is 30 mA.
Per unit current is IPU = 0.03 / 1 = 0.03 pu = 3%
P3T/EN/M/30-208A 53
Transformer protection relay 4 Measurement functions
Input is I01.
CT0 = 50 / 1
The relay setting is 0.03 pu = 3%.
Secondary current is ISEC = 0.03 x 1 = 30 mA
Input is I0 Calc.
CT = 750 / 5
Currents injected to the relay's IL1 input is 0.5 A.
IL2 = IL3 = 0.
Per unit current is IPU = 0.5 / 5 = 0.1 pu = 10%
Input is I0 Calc.
CT = 750 / 5
The relay setting is 0.1 pu = 10%.
If IL2 = IL3 = 0, then secondary current to IL1 is ISEC = 0.1 x 5 = 0.5 A
Examples
VT = 12000/110
Voltage connected to the relay's input UA or UB is 100 V.
=> Primary voltage is UPRI = 100x12000/110 = 10909 V.
VT = 12000/110
Three phase symmetric voltages connected to the relay's inputs UA, UB
and UC are 57.7 V.
=> Primary voltage is UPRI = √3 x58x12000/110 = 10902 V
54 P3T/EN/M/30-208A
4 Measurement functions Transformer protection relay
VT = 12000/110
The relay displays UPRI = 10910 V.
=> Secondary voltage is USEC = 10910x110/12000 = 100 V
VT = 12000/110
The relay displays U12 = U23 = U31 = 10910 V.
=> Symmetric secondary voltages at UA, UB and UC are USEC = 10910/√3
x110/12000 = 57.7 V.
Examples
VT = 12000/110
Voltage connected to the relay's input UA or UB is 110 V.
=> Per unit voltage is UPU = 110/110 = 1.00 pu = 1.00 x UN = 100%
VT = 12000/110
Three symmetric phase-to-neutral voltages connected to the relay's inputs
UA, UB and UC are 63.5 V
=> Per unit voltage is UPU = √3 x63.5/110x12000/11000 = 1.00 pu = 1.00 x
UN = 100%
VT = 12000/110
The relay displays 1.00 pu = 100%.
=> Secondary voltage is USEC = 1.00 x 110 x 11000/12000 = 100.8 V
VT = 12000/110
UN = 11000 V
P3T/EN/M/30-208A 55
Transformer protection relay 4 Measurement functions
U 0 SEC VTSEC 3
Examples
VT = 12000/110
Voltage connected to the relay's input UA is 38.1 V, while UB = UC = 0.
=> Per unit voltage is UPU = (38.1+0+0)/(√3 x110) = 0.20 pu = 20%
VT = 12000/110
The relay displays U0 = 20%.
=> If UB = UC = 0, then secondary voltages at UA is USEC = √3 x0.2x110 =
38.1 V
“Residual value scaling” setting allows users to choose to show primary or per
unit value of residual currents and voltages. The conversion is based on primary
and secondary nominal value of CT and PT.
56 P3T/EN/M/30-208A
4 Measurement functions Transformer protection relay
The user can see the changes through “measurements -> current and voltage”
and residual value relevant protection page, such as 50N/51N, 67N,67NI,59N and
50BF.
Table 23 - Scaling equations between residual pu voltage and primary voltage
• •
PRI
VT SEC
Examples
VT = 10000 / 100
U0SEC = 57.75 V
VT = 10000 / 100
U0SEC = 57.75 V
The U0 injected to the relay is 0.01 pu.
The primary value is UPRI = 0.01 * 57.75 * 10000 / 100 = 57.75 V.
VT = 10000 / 100
VT = 10000 / 100
P3T/EN/M/30-208A 57
Transformer protection relay 4 Measurement functions
Examples
The IMODE = 50 A.
Input is I0.
U0SEC = 57.75 V
The relay displays Ipu = 1 pu.
The IMODE = 50 A.
Primary current is IPRI = 1 * 50 = 400 A.
Input is I0Calc
CT = 750 / 5.
Current IL1 is 75 A.
IL2 = IL3 = 0
Input is I0Calc .
CT = 750 / 5
58 P3T/EN/M/30-208A
4 Measurement functions Transformer protection relay
Load = 0%
100
-5
IL2
-10
All the direct measurements are based on fundamental frequency values. The
exceptions are frequency and instantaneous current for arc protection. Most
protection functions are also based on the fundamental frequency values.
Signals “I>” or “I0>” are connected to an FPGA chip which implements the arc
flash detection function. The start settings are named “I> int” and “I01> int” in the
local LCD panel or eSetup Easergy Pro views, these settings are used to set the
THRESHOLD levels for the electronics.
P3T/EN/M/30-208A 59
Transformer protection relay 4 Measurement functions
3xI
B
Io
A Io>> I>>
FPGA
The relay calculates the RMS value of each phase current. The minimum and
maximum RMS values are recorded and stored (see 4.7 Minimum and maximum
values).
I RMS = I f 1 + I f 2 + ... + I f 15
2 2 2
RMS voltages
The relay calculates the RMS value of each voltage input. The minimum and the
maximum of RMS values are recorded and stored (see 4.7 Minimum and
maximum values).
U RMS = U f 1 + U f 2 + ... + U f 15
2 2 2
60 P3T/EN/M/30-208A
4 Measurement functions Transformer protection relay
relay calculates the harmonics from the 2nd to the 15th of phase currents and
voltages. (The 17th harmonic component is also shown partly in the value of the
15th harmonic component. This is due to the nature of digital sampling.)
Equation 2
15
∑f
i =2
i
2
THD =
h1
f1 = Fundamental value
f2– 15 = Harmonics
Example
f1 = 100 A, f3 = 10 A, f7 = 3 A, f11 = 8 A
10 2 + 3 2 + 8 2
THD = = 13.2%
100
For reference, the RMS value is:
P3T/EN/M/30-208A 61
Transformer protection relay 4 Measurement functions
RMS values
62 P3T/EN/M/30-208A
4 Measurement functions Transformer protection relay
IL1 RMS, IL2 RMS, IL3 RMS Phase current, RMS value
f Frequency
P3T/EN/M/30-208A 63
Transformer protection relay 4 Measurement functions
Table 27 - Parameters
NOTE: The saving process starts every 30 minutes and it takes a while. If the
relay's auxiliary supply power is switched off before all values have been
saved, the old values remain for the unsaved ones.
Corresponding time stamps are stored for the last 31 days. The registered values
are listed in Table 28.
64 P3T/EN/M/30-208A
4 Measurement functions Transformer protection relay
S X Apparent X X
power
P X X Active power X X
Q X X Reactive X X
power
The timebase can be a value from one cycle to one minute. Also a demand value
can be used as the timebase and its value can be set between 10 and 60
minutes. The demand value menu is located under the Measurements view.
Table 29 - Parameters of the day and month registers
P3T/EN/M/30-208A 65
Transformer protection relay 4 Measurement functions
Frequency x
66 P3T/EN/M/30-208A
4 Measurement functions Transformer protection relay
Power factor x
Active energy x
Reactive energy x
P3T/EN/M/30-208A 67
Transformer protection relay 4 Measurement functions
Events x
Disturbance record x
+90°
II I
ind +cap
cos = cos = +
PF = + PF =
V REF 0°
III I IV
cap +ind
cos = cos = +
PF = PF = +
Q
+90°
II cap +ind I
cos = cos = +
PF = PF = +
S
P 0°
III IV
ind +cap
cos = cos = +
PF = + PF =
68 P3T/EN/M/30-208A
4 Measurement functions Transformer protection relay
• Positive sequence 1
• Negative sequence 2
• Zero sequence 0
S 0 1 1 1 S A
S = 1 1 a a S B
2
1 3
S 2 1 a 2 a S C
1 3
a = 1∠120° = − + j
2 2
, a phase rotating constant
P3T/EN/M/30-208A 69
Transformer protection relay 5 Control functions
5 Control functions
The digital outputs can be set to normal or reverse position with eSetup Easergy
Pro and Web HMI by selecting "NO" or "NC" in the Relays Polarity view of
Device/Test menu. As the relay polarity parameter is set to “NC”, the relay
position will be set reverse.
Any internal signal can be connected to the digital outputs in the Matrix > Arc
matrix - output setting views.
The Output matrix and Relays setting views represent the state (de-energized /
energized) of the digital output's coil. For example, a bright green vertical line in
the Output matrix and a logical "1" in the Relays view represent the energized
state of the coil. The same principle applies for both NO and NC type digital
outputs. The actual position (open / closed) of the digital outputs' contacts in coil's
de-energized and energized state depends on the type (NO / NC) of the digital
outputs. De-energized state of the coil corresponds to the normal state of the
contacts. A digital output can be configured as latched or non-latched. 5.5
Releasing latches describes releasing latches procedure.
The difference between trip contacts and signal contacts is the DC breaking
capacity. The contacts are single pole single throw (SPST) normal open (NO)
type, except signal relay A1 which has a changeover contact single pole double
throw (SPDT).
In addition to this, the relay has so called heavy duty outputs available in the
power supply modules C and D. For more details, see Table 166.
Programming matrix
70 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
NOTE: Logic outputs are assigned automatically in the output matrix as well
when logic is built.
Trip contact status can be viewed and forced to operate in the Relays setting
view. Logical "0" means that the output is not energized and logical "1" states that
the output is set active.
P3T/EN/M/30-208A 71
Transformer protection relay 5 Control functions
Enable NO / NC outputs in the Polarity setting view for the signals shown.
Default numbering of DI / DO
Every option card and slot has default numbering. Below is an example of model
P3x30 CGGII-AAEAA-BA showing the default numbering of digital outputs.
You can see the default digital output numbering and change the numbering of
the following option cards in the Inputs/Outputs > Relay config setting view: slot
2, 3, 4, 5: G, I.
72 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
Power supply card outputs are not visible in the Relay config setting view.
P3T/EN/M/30-208A 73
Transformer protection relay 5 Control functions
Names for output relays (editable with eSetup Easergy Pro only)
The polarity normal open (NO) / normal closed (NC) and a delay can be
configured according to the application by using the front panel or eSetup
Easergy Pro.
Digital inputs can be used in many operations. The status of the input can be
checked in the Output matrix and Digital inputs setting views. The digital inputs
make it possible to change group, block/enable/disable functions, to program
logics, indicate object status, etc.
The digital inputs require an external control voltage (ac or dc). The digital inputs
are activated after the activation voltage is exceeded. Deactivation follows when
the voltage drops below threshold limit. The activation voltage level of digital
inputs can be selected in the order code when such option cards are equipped.
74 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
Digital inputs can be viewed, named and changed between NO/NC in the Digital
inputs and Names for digital inputs setting views.
P3T/EN/M/30-208A 75
Transformer protection relay 5 Control functions
76 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
All essential information on digital inputs can be found in the same location in the
Digital inputs setting view. DI on/off events and alarm display (pop-up) can be
enabled and disabled in Digital inputs setting view. Individual operation counters
are located in the same view as well.
Label and description texts can be edited with eSetup Easergy Pro according to
the demand. Labels are the short parameter names used on the local panel and
descriptions are the longer names used by eSetup Easergy Pro.
Digital input delay determines the activation and de-activation delay for the input.
Figure 25shows how the digital input behaves when the delay is set to 1 second.
1
VOLTAGE
0
1
DIGITAL INPUT
0
For normal
closed contacts
(NC)
Active edge is 1
>0
P3T/EN/M/30-208A 77
Transformer protection relay 5 Control functions
NAMES for DIGITAL INPUTS (editable with eSetup Easergy Pro only)
Default is "DI1 –
DIx". x is the
maximum
number of the
digital input.
x is the
maximum
number of the
digital input.
24) Set = An editable parameter (password needed).
Every option card and slot has default numbering. After making any changes to
the numbering, read the settings from the relay after the relay has rebooted.
78 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
You can see the default digital input numbering and change the numbering of the
following option cards in the Inputs/Outputs > Digital inputs setting view: slot 2,
3, 4, 5: G, I.
C: -
G: DI1–6
G: DI7–12
I: DI13–22
I: DI23–32
P3T/EN/M/30-208A 79
Transformer protection relay 5 Control functions
Virtual inputs can be used in many operations. The status of the input can be
checked in the Matrix > Output matrix and Control > Virtual inputs setting
views. The status is also visible on local mimic display, if so selected. Virtual
inputs can be selected to be operated with the function buttons F1 and F2, the
local mimic or simply by using the virtual input menu. Virtual inputs have similar
functions as digital inputs: they enable changing groups, block/enable/disable
functions, to program logics and other similar to digital inputs.
Number of outputs 20
Virtual inputs and outputs can be used for many purposes in the Output matrix
setting view.
80 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
Virtual inputs
The virtual inputs can be viewed, named and controlled in the Control > Virtual
inputs setting view.
P3T/EN/M/30-208A 81
Transformer protection relay 5 Control functions
82 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
Off
Names for virtual inputs (editable with eSetup Easergy Pro only)
Default is "VIn",
n = 1–20
P3T/EN/M/30-208A 83
Transformer protection relay 5 Control functions
VI1 to VI10 are configurable virtual inputs. They can operate on pulse mode,
which is achieved by a settable VI pulse length. When the VI pulse length is set to
"0 = infinite", it keeps actual operation; and with any setting >0 s, the VI state gets
automatically reset to 0 (low/ inactive), once the pulse timer expires.
NOTE: The configurable VIs state is cleared once the power supply is lost
when the timer is still counting down.
Configurable VI number 10
Virtual outputs
In eSetup Easergy Pro, the Virtual outputs setting view is located under Control.
84 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
P3T/EN/M/30-208A 85
Transformer protection relay 5 Control functions
Off
NAMES for VIRTUAL OUTPUTS (editable with eSetup Easergy Pro only)
86 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
5.4 Matrix
The relay has several matrices that are used for configuring the relay:
• Output matrix used to link protection stage signals, digital inputs, virtual
inputs, function buttons, object control, logic output, relay's internal alarms,
GOOSE signals and release latch signals to outputs, disturbance recorder trig
input and virtual outputs
• Block matrix used to block protection stages
• LED matrix used to control LEDs on the front panel
• Object block matrix used to inhibit object control
• Auto-recloser matrix used to control auto-recloser
• Arc matrix used to control current and light signals to arc stages and arc
stages to the high-speed outputs
Virtual
inputs
Digital n
inputs
n Output relays Virtual
optional
DI delay and indicators outputs
n
and
inversion n
Output contacts
NOTE: Blocking matrix can not be used to block the arc flash detection
stages.
With the output matrix, the output signals of the various protection stages, digital
inputs, logic outputs and other internal signals can be connected to the digital
outputs, virtual outputs and so on.
NOTE: For configuring the high-speed operations of the arc flash detection,
use the Arc matrix – output view. The configuration also becomes visible in
the output matrix. The output matrix shows the status of the FPGA-driven
outputs whereas the other electro-mechnical outputs can also be configured
in the output matrix.
There are general-purpose LED indicators – "A", "B", "C" to ”N” – available for
customer-specific indications on the front panel. Their usage is to define in a
separate LED matrix.
P3T/EN/M/30-208A 87
Transformer protection relay 5 Control functions
There are two LED indicators specified for keys F1 and F2. The triggering of the
disturbance recorder (DR) and virtual outputs are configurable in the output
matrix.
There is a common "release all latches" signal to release all the latched relays.
This release signal resets all the latched digital outputs and indicators. The reset
signal can be given via a digital input, via front panel or remotely through
communication. For instructions on how to release latches, see 5.5 Releasing
latches.
Trip and alarm relays together with virtual outputs can be assigned in the output
matrix. Also automatic triggering of disturbance recorder is done in the output
matrix.
By means of a blocking matrix, the operation of any protection stage (except the
arc flash detection stages) can be blocked. The blocking signal can originate from
the digital inputs or it can be a start or trip signal from a protection stage or an
output signal from the user's programmable logic. In Figure 37, an active blocking
is indicated with a black dot (●) in the crossing point of a blocking signal and the
signal to be blocked.
All protection stages (except Arc stages) can be blocked in the block matrix
88 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
The Blocked status becomes visible only when the stage is about to activate.
Figure 39 - Result for the I> stage when the DI is active and the stage exceeds its
current start value
P3T/EN/M/30-208A 89
Transformer protection relay 5 Control functions
NOTICE
RISK OF NUISANCE TRIPPING
Activate the protection stages first, then store the settings in a relay. After that,
refresh the blocking matrix before configuring it.
The LED matrix is used to link digital inputs, virtual inputs, function buttons,
protection stage outputs, object statuses, logic outputs, alarm signals and
GOOSE signals to various LEDs located on the front panel.
In the LED configuration setting view, each LED has three checkboxes with
which the behavior of the LED is configured.
LEDs are assigned to control signals in the LED matrix setting view. It is not
possible to control LEDs directly with logics.
90 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
Normal setting
With no checkboxes selected, the assigned LED is active when the control signal
is active. After deactivation, the LED turns off. LED activation and deactivation
delay when controlled is approximately 10 ms.
Latch setting
A latched LED activates when the control signal activates but remains active
when the control signal deactivates. Latched LEDs are released using the
procedure described in 5.5 Releasing latches.
Blink setting
When the Blink setting is selected, the LED blinks when it is active.
Store setting
In the LED configuration setting view, you can configure the latched states of
LEDs to be stored after a restart. In Figure 40, storing has been configured for
LED A (green).
Inputs for LEDs can be assigned in the LED matrix. All 14 LEDs can be assigned
as green or red. The connection can be normal, latched or blink-latched. In
addition to protection stages, there are lots of functions that can be assigned to
output LEDs. See Table 38.
Protection, Arc and LED A–N Normal/ Latched/ Different type of Set
program-mable stages BlinkLatch protection stages can
green or red
be assigned to LEDs
Digital/Virtual inputs LED A–N Normal/ Latched/ All different type of Set
and function buttons BlinkLatch inputs can be assigned
green or red
to LEDs
Local control enabled LED A–N Normal/ Latched/ While remote/local Set
BlinkLatch state is selected as
green or red
local the “local control
enabled” is active
Logic output 1–20 LED A–N Normal/ Latched/ All logic outputs can be Set
BlinkLatch assigned to LEDs at
green or red
the LED matrix
P3T/EN/M/30-208A 91
Transformer protection relay 5 Control functions
Manual control LED A–N Normal/ Latched/ When the user has Set
indication BlinkLatch controlled the
green or red
objectives
COM 1–5 comm. LED A–N Normal/ Latched/ When the Set
BlinkLatch communication port 1 -
green or red
5 is active
Setting error, seldiag LED A–N Normal/ Latched/ Self diagnostic signal Set
alarm, pwd open and BlinkLatch
green or red
setting change
GOOSE NI1–64 LED A–N Normal/ Latched/ IEC 61850 goose Set
BlinkLatch communication signal
green or red
The object block matrix is used to link digital inputs, virtual inputs, function
buttons, protection stage outputs, logic outputs, alarm signals and GOOSE
signals to inhibit the control of objects, that is, circuit breakers, isolators and
earthing switches.
Typical signals to inhibit controlling of the objects like circuit breaker are:
These and other signals are linked to objects in the object block matrix.
There are also event-type signals that do not block objects as they are on only for
a short time, for example "Object1" open and "Object1 close" signals.
2. From the eSetup Easergy Pro toolbar, select Device > Release all latches.
92 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
Alternatively, go to Control > Release latches, and click the Release button.
1. Press .
2. Press .
You can use the function buttons F1 or F2 to release all latches after configuring
this function in eSetup Easergy Pro. You can make the configuration either under
Control > Release Latches or under Control > Function buttons.
P3T/EN/M/30-208A 93
Transformer protection relay 5 Control functions
After this, pressing the F1 button on the relay’s front panel releases all
latches.
• To configure F1 to release latches under Control >Function buttons:
a. Under Function buttons, for F1, select PrgFncs from the Selected
control drop down menu.
c. Under Programmable functions for F1, select “On” from the Release all
latches drop-down menu.
After this, pressing the F1 button on the relay's front panel releases all
latches.
NOTE: The latch release signal can be activated only if the latched
output is active.
94 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
Object states
Open
Close
Undefined (11)
Max ctrl pulse length 0.02–600 s Pulse length for open and
close commands. Control
pulse stops once object
changes its state
If changing the states takes longer than the time defined by the “Max ctrl pulse
length” setting, the object is inoperative and the “Object failure” matrix signal is
set. Also, an undefined event is generated. “Completion timeout” is only used for
the ready indication. If “DI for ‘obj ready’” is not set, the completion timeout has no
meaning.
P3T/EN/M/30-208A 95
Transformer protection relay 5 Control functions
These signals send control pulse when an object is controlled by digital input,
remote bus, auto-reclose etc.
Objects can be controlled with digital inputs, virtual inputs or virtual outputs. There
are four settings for each object:
Setting Active
If the relay is in local control state, the remote control inputs are ignored and vice
versa. An object is controlled when a rising edge is detected from the selected
input. The length of digital input pulse should be at least 60 ms.
In local mode, digital outputs can be controlled via the front panel but they cannot
be controlled via a remote serial communication interface.
In remote mode, digital outputs cannot be controlled via a front panel but they can
be controlled via a remote serial communication interface.
The local or remote mode can be selected by using the front panel or via one
selectable digital input. The digital input is normally used to change a whole
station to local or remote mode. You can select the L/R digital input in the Control
> Objects setting view in eSetup Easergy Pro.
96 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
The relay also has dedicated control buttons for objects. (I) stands for object
closing and (O) controls object open command internally. Control buttons are
configured in the Control > Objects setting view.
Button
opens selected
object if
password is
enabled
Control
operation is
done without
confirmation
P3T/EN/M/30-208A 97
Transformer protection relay 5 Control functions
You can configure the button funtions in the Control > Function buttons setting
view in eSetup Easergy Pro.
If ObjCtrl has been selected under Selected control, the selected object is
shown under Selected object. Otherwise, this column is empty.
When selecting ObjCtrl, link the function button to the appropriate object in the
Control > Objects setting view.
98 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
5.6.5 Adjustable time delay mechanism for the object’s closing operation
For the safety of the operating personnel, the PowerLogic P3 offers an adjustable
time delay mechanism to ensure the operating personnel has enough time to
evacuate safely. To adjust the local close delay time for the object’s closing
operation, navigate to the CONTROL > Objects setting view in eSetup Easergy
Pro. By enabling the Local close delay setting, you can set the desired close
delay time for the object within a range of 0 to 60 seconds.
Note that the close delay time for the object is only available in Local mode. The
closing operation of the object occurs asynchronously which can ensure smooth
and uninterrupted system performance.
P3T/EN/M/30-208A 99
Transformer protection relay 5 Control functions
Taking the figure below as an example, if you set 15 seconds close delay for
Object1, the assigned LED E on the device’s front panel is active for the duration
of the delay. After the elapsed 15 seconds, the state of the Object1 will change to
“Close”.
Logic functions No. of gates Max. no. of input Max. no. of logic
reserved gates outputs
AND 1
OR 1
32
XOR 1
(An input gate can 20
AND+OR 2 include any number
of inputs.)
CT (Count+Reset) 2
INVAND 2
100 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
Logic functions No. of gates Max. no. of input Max. no. of logic
reserved gates outputs
INVOR 2
OR+AND 2
RS (Reset+Set) 2
R_OR 1
F_OR 1
E_OR 1
The logic is operational as long the memory consumption of the inputs, gates or
outputs remains individually below or equal to 100%.
P3T/EN/M/30-208A 101
Transformer protection relay 5 Control functions
Truth tables
AND In Out
A Y
0 0
1 1
In Out
A Y
0 1
1 0
In Out
A B Y
0 1 0
1 0 0
1 1 1
0 0 0
In Out
A B Y
0 1 1
1 0 1
1 1 0
0 0 1
AND+OR In Out
A B Y
0 0 0
1 1 1
1 0 1
0 1 1
102 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
CT (Count+Reset) In Out
A B Y Y
1 3 0
1 3 0
1 3 1
1 3 0
INVAND In Out
A B Y
0 0 0
1 0 1
1 1 0
0 1 0
INVOR In Out
A B Y
0 0 1
1 1 1
1 0 1
0 1 0
P3T/EN/M/30-208A 103
Transformer protection relay 5 Control functions
OR In Out
A B Y
0 0 0
1 1 1
1 0 1
0 1 1
In Out
A B Y
0 0 1
1 1 0
1 0 0
0 1 0
In Out
A B C Y
0 0 0 1
1 1 0 1
1 0 0 1
0 1 0 1
1 1 1 1
In Out
A B C Y
0 0 0 1
1 0 0 0
1 1 0 0
0 1 0 0
1 1 1 0
104 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
OR+AND In Out
A B Y
0 0 0
1 1 1
1 0 0
0 1 0
RS (Reset+Set) In Out
A B Y
Set Reset Y
1 0 1
0 0 129)
0 0 030)
X 1 031)
29) Output = 1 (latched), if
previous state was 1, 0, 1.
30) Output = 0, if previous state
was X, 1, 0.
31) Output = 0, if RESET = 1
RS_D (Set+D+Load+Reset) A B C D Y
0 0 0 0 032)
1 X X 0 1
1 X X 1 0
0 1 0 0 0
0 1 1 0 1
0 1 1 1 033)
32) Initial
state
33) Thestate remains 1 until
Reset is set active
X = Any state
P3T/EN/M/30-208A 105
Transformer protection relay 5 Control functions
XOR In Out
A B C Y
0 0 0 0
0 0 1 1
0 1 0 1
0 1 1 0
1 0 0 1
1 0 1 0
1 1 0 0
1 1 1 1
106 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
After you have selected the required logic gate in eSetup Easergy Pro, you can
change the function of the gate in the Element properties window by clicking the
gate.
Table 44 - Settings available for the logical gates depending on the selected
element
Property Description
Element properties
P3T/EN/M/30-208A 107
Transformer protection relay 5 Control functions
Property Description
OFF delay Time delay for how long the gate remain
active even the logical condition is reset
Inputs
All the main menus are located on the left side of the display. To get to a
submenu, move up and down the main menus.
108 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
The mimic view is set as the local panel's main view as default. You can modify
the mimic according to the application or disable it, if it is not needed, via the
eSetup Easergy Pro setting tool.
You can modify the mimic in the General > Mimic setting view in eSetup Easergy
Pro and disable the mimic view in the General > Local panel conf setting view.
NOTE: The mimic itself or the local mimic settings cannot be modified via the
local panel.
C A B F I G H F J
D
E
I
A. To clear an object or drawing, first point an F. The remote/local selection defines whether
empty square (A) with the mouse. Then point the certain actions are granted or not. In remote
object item with the mouse. The color of the object state, it is not possible to locally enable or
item turns red. To clear the whole mimic, click on disable auto-reclosing or to control objects. The
the empty area. remote/local state can be changed in Control >
Objects.
B. Text tool G. Creates auto-reclosing on/off selection to
mimic.
P3T/EN/M/30-208A 109
Transformer protection relay 5 Control functions
C. To move an existing drawing or object, point it H. Creates virtual input activation on the local
with the mouse. The color turns green. Hold down mimic view.
the left mouse button and move the object.
D. Different type of configurable objects. The I. Describes the relay's location. Text comes
object's number corresponds to the number in from the relay info menu.
Control > Objects.
E. Some predefined drawings. J. Up to six configurable measurements.
110 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
Set = Settable.
P3T/EN/M/30-208A 111
Transformer protection relay 5 Control functions
You can modify the local panel configuration in the General > Local panel conf
setting view in eSetup Easergy Pro.
112 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
f, P, Q, S, P.F.
CosPhi
ARStart,
ARFaill,
ARShot1–5
IFLT
Starts, Trips
I0 Calc
IL
IL1–3da
IL1–3 max
IL1–3 min
IL1–3daMax
Pda, Qda,
Sda
T
fSYNC,
USYNC
I’L1–3
dIL1–3
VAI1–5
ExtAI1–636)
SetGrp
P3T/EN/M/30-208A 113
Transformer protection relay 5 Control functions
114 P3T/EN/M/30-208A
5 Control functions Transformer protection relay
P3T/EN/M/30-208A 115
Transformer protection relay 5 Control functions
When selected,
the mimic is the
local panel's
default main
view. When
unselected, the
measurement
view is the
default main
view.
116 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
6 Protection functions
Each protection stage can independently be enabled or disabled according to the
requirements of the intended application.
The condition to be fulfilled by the CT saturation current (Isat) depends on the type
of overcurrent protection operate time.
IDMT Isat > 1.5 x the curve value which is the smallest of these two values:
• Isc max., maximum installation short-circuit current
• 20 x Is (IDMT curve dynamic range)
A B
t t
I I
Is Isat Is Isat
C D
The method for calculating the saturation current depends on the CT accuracy
class.
P3T/EN/M/30-208A 117
Transformer protection relay 6 Protection functions
Table 48 - CT requirements
For 5 A: Vk > 150 x (Rct + Rw); for example: 150 x 0.53 = 79.5 V
If the resistance Rct is known, it is possible to calculate the actual CT ALF which
takes account of the actual CT load. The saturation current equals the actual ALF
x Inp.
Equation 3
118 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
To have an ALF of at least 20, that is, a saturation current of 20 x Inp = 2 kA, the
load resistance Rw of the CT must be less than Equation 4.
Equation 4
VAct 2.5
Rw, max = 2 = = 0.1Ω
Ins 52
This represents 12 m (39 ft) of wire with cross-section 2.5 mm² (AWG 14) for a
resistance per unit length of approximately 8 Ω/km (2.4 mΩ/ft). For an installation
with 50 m (164 ft) of wiring with section 2.5 mm² (AWG 14), Rw = 0.4 Ω.
Equation 5
Equation 6
Vk Inp
Isat = ×
Rct + Rw Ins
P3T/EN/M/30-208A 119
Transformer protection relay 6 Protection functions
CT Vk Rct Rw Saturation
Transformati current
on ratio
Two REF schemes are possible: the Low impedance REF and the High
impedance REF.
The Low impedance REF protection should be used with power networks X/R
only up to 15.
‘K’ depends on X/R and the maximum through-fault current (three-phase fault
current) as defined in Table 50.
Table 50 - K factor
X/R <= 10 45 60 70
X/R <= 15 55 70 80
For power system with an X/R ratio above 15, or when the above CT
requirements cannot be met, the high impedance REF protection shall be used
instead.
The CT requirements for high impedance REF are given in the Application Note
"P3APS17016EN_(HiZ-REF_87N)".
NOTE: The high impedance REF must use a different winding of the primary
CT than the Transformer Differential.
120 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Table 51 - CT settings
Parameter Value
Slope1 50%
Slope2 150%
For maximum sub-synchronous through fault above 7 In and below 9 In, K = 25.
The minimum rated burden is SVA > ((K / Kalf) x (RCT + Rba) – RCT) x Isr2
where kalf is the CT accuracy limit factor (i.e. 20 for 5P20, i.e. 10 for 5P10)
P3T/EN/M/30-208A 121
Transformer protection relay 6 Protection functions
B
C
E F
G D
H IEC 1263/2000
A. Current F. Ip
B. Top envelope G. A
C. d.c. component Id.c. of the short-circuit current H. Bottom envelope
D. 2√2 I’k I. Time
E. 2√2 Ik
For accuracy, class PX or class 5P CTs are recommended but TPY or 5PR can
also be used.
The CT requirements are based on the following settings based on the rated
current of the transformer “In”:
Table 52 - CT settings
Parameter Value
Slope1 50%
Slope2 150%
The maximum through fault measured by the protection device must be limited to
15 In. Thus, choose the CT ratio carefully to meet this requirement. With a
through fault flowing from both sides, choose the highest one.
For power network X/R up to 10 and for all the above-listed CT classes, K = 30.
122 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
7 15
X/R up to 10 TPX - PX - 5P 30
TPY - 5PR
X/R up to 60 TPX - PX - 5P 55
TPY - 5PR 30 40
5 7 15
X/R up to 10 TPX - PX - 5P 30 33
TPY - 5PR
X/R up to 60 TPX - PX - 5P 55 70
TPY - 5PR 30 40
P3T/EN/M/30-208A 123
Transformer protection relay 6 Protection functions
The minimum rated burden is SVA > ((K / Kalf) x (RCT + Rba) – RCT) x Isr2
where Kalf is the CT accuracy limit factor (20 for 5P20, 10 for 5P10)
The individual protection stage and total load status can be found in the
Protection > Protection stage status setting view in the eSetup Easergy Pro
setting tool.
Setting groups are controlled by using digital inputs, function keys or virtual
inputs, via the front panel or custom logic. When none of the assigned inputs are
active, the setting group is defined by the parameter ‘SetGrp no control state’.
When controlled input activates, the corresponding setting group is activated as
well. If the control signal of the setting group is lost, the setting “Keep last” forces
the last active group into use. If multiple inputs are active at the same time, the
active setting group is defined by ‘SetGrp priority’. By using virtual I/O, the active
setting group can be controlled using the local panel display, any communication
protocol or the built-in programmable logic functions. All protection stages have
four setting groups.
124 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Example
Any digital input can be used to control setting groups but in this example, DI1,
DI2, DI3 and DI4 are chosen to control setting groups 1 to 4. This setting is done
with the parameter “Set group x DI control” where x refers to the desired setting
group.
Use the 'SetGrp common change' parameter to force all protection stages to
group 1, 2, 3 or 4. The control becomes active if there is no local control in the
protection stage. You can activate this parameter using eSetup Easergy Pro.
P3T/EN/M/30-208A 125
Transformer protection relay 6 Protection functions
Assuming that DI2 and DI3 are active at the same time and SetGrp priority is set
to “1 to 4”, setting group 2 becomes active. If SetGrp priority is reversed, that is,
set to “4 to 1”, the setting group 3 becomes active.
User can set the delay time to 0 by enabling this selection. For normal operation,
the user can only set the delay time to the minimum value of the setting range.
• Ok = ‘-‘
The stage is idle and is measuring the analog quantity for the protection. No
power system fault detected.
• Blocked
The blocking reason may be an active signal via the block matrix from other
stages, the programmable logic or any digital input. Some stages also have built-
in blocking logic. For more details about the block matrix, see 5.4.2 Blocking
matrix.
Each protection stage has start and trip counters that are incremented when the
stage starts or trips. The start and trip counters are reset on relay reboot.
The user can also view and reset the start and trip counters through eSetup
Easergy Pro on Protection > Protection stage status 2, and clear fault logs as
well.
126 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
The firmware records and shows the last fault current and earth fault current
values. The user can view this through eSetup Easergy Pro on Protection >
Protection stage status 2.
The user can supervise line alarm and fault through the above page; once
overcurrent stage starts, overcurrent alarm (L1,L2,L3) is issued. Earth fault alarm
works for the same mechanism. When the overcurrent stage trips, overcurrent
fault is issued and the corresponding fault is issued at the same time. The user
can also set the reset time for alarms and faults, and as the set time has elapsed,
the alarms and faults are set to zero.
Firmware provides fault current recording. After one stage trips and releases, it
will record L1~L3 current and residual currents. It also provides a clearing delay
for the fault value, and after the delay has elapsed, it can record new fault values,
otherwise, if new fault current happens during the countdown, the value will not
be recorded.
There is a "Forcing flag" parameter which, when activated, allows forcing the
status of any protection stage to be "start" or "trip" for half a second. By using this
forcing feature, current or voltage injection is not necessary to check the output
matrix configuration, to check the wiring from the digital outputs to the circuit
breaker and also to check that communication protocols are correctly transferring
event information to a SCADA system.
After testing, the forcing flag is automatically reset five minutes after the last local
panel push button activity.
The force flag also enables forcing the digital outputs and the optional mA
outputs.
The force flag can be found in the Device/Test > Relays setting view.
P3T/EN/M/30-208A 127
Transformer protection relay 6 Protection functions
Every protection stage has two internal binary output signals: start and trip. The
start signal is issued when a fault has been detected. The trip signal is issued
after the configured operation delay unless the fault disappears before the end of
the delay time.
Start level
> Start
Output matrix
Using the output matrix, you can connect the internal start and trip signals to the
digital outputs and indicators. For more details, see 5.4.1 Output matrix.
Blocking
Any protection function, except for arc flash detection, can be blocked with
internal and external signals using the block matrix (5.4.2 Blocking matrix).
Internal signals are for example logic outputs and start and trip signals from other
stages and external signals are for example digital and virtual inputs.
Some protection stages have also built-in blocking functions. For example under-
frequency protection has built-in under-voltage blocking to avoid tripping when the
voltage is off.
The operate time in the dependent time mode is dependent on the magnitude of
the injected signal. The bigger the signal, the faster the stage issues a trip signal
and vice versa. The tripping time calculation resets if the injected quantity drops
below the start level.
128 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
IDMT DT
t (s)
If (A)
The operate time in the definite time mode is fixed by the Operation delay
setting. The timer starts when the protection stage activates and counts until the
set time has elapsed. After that, the stage issues a trip command. Should the
protection stage reset before the definite time operation has elapsed, then the
stage resets.
By default, the definite time delay cannot be set to zero because the value
contains processing time of the function and operate time of the output contact.
This means that the time indicated in the Definite time setting view is the actual
operate time of the function. Use the Accept zero delay setting in the protection
stage setting view to accept the zero setting for definite time function. In this case,
the minimum operate time of the function must be tested separately.
Overshoot time
Overshoot time is the time the protection device needs to notice that a fault has
been cleared during the operate time delay. This parameter is important when
grading the operate time delay settings between devices.
tFAULT
tRET < 50 ms
TRIP CONTACTS
If the delay setting would be slightly shorter, an unselective trip might occur (the
dash line pulse).
P3T/EN/M/30-208A 129
Transformer protection relay 6 Protection functions
For example, when there is a big fault in an outgoing feeder, it might start both the
incoming and outgoing feeder relay. However, the fault must be cleared by the
outgoing feeder relay and the incoming feeder relay must not trip. Although the
operating delay setting of the incoming feeder is more than at the outgoing feeder,
the incoming feeder might still trip if the operate time difference is not big enough.
The difference must be more than the overshoot time of the incoming feeder relay
plus the operate time of the outgoing feeder circuit breaker.
Figure 63 shows an overcurrent fault seen by the incoming feeder when the
outgoing feeder clears the fault. If the operation delay setting would be slightly
shorter or if the fault duration would be slightly longer than in the figure, an
unselective trip might happen (the dashed 40 ms pulse in the figure). In
PowerLogic P3 devices, the overshoot time is less than 50 ms.
Reset time
Figure 64 shows an example of reset time, that is, release delay when the relay is
clearing an overcurrent fault. When the relay’s trip contacts are closed, the circuit
breaker (CB) starts to open. After the CB contacts are open, the fault current still
flows through an arc between the opened contacts. The current is finally cut off
when the arc extinguishes at the next zero crossing of the current. This is the start
moment of the reset delay. After the reset delay the trip contacts and start contact
are opened unless latching is configured. The precise reset time depends on the
fault size; after a big fault, the reset time is longer. The reset time also depends
on the specific protection stage.
The maximum reset time for each stage is specified under the characteristics of
every protection function. For most stages, it is less than 95 ms.
tSET
tCB
tRESET
TRIP CONTACTS
Reset time is the time it takes the trip or start relay contacts to open after the fault
has been cleared.
130 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
hysteresis
Start level
> Start
Start level
< Start
Time grading
When a fault occurs, the protection scheme only needs to trip circuit breakers
whose operation is required to isolate the fault. This selective tripping is also
called discrimination or protection coordination and is typically achived by time
grading. Protection systems in successive zones are arranged to operate in times
that are graded through the sequence of equipment so that upon the occurrence
of a fault, although a number of protections devices respond, only those relevant
to the faulty zone complete the tripping function.
δt TC m Tm δt
time
Δt
There is detailed information available on the last eight faults for each protection
stage. The recorded values are specific for the protection stages and can contain
P3T/EN/M/30-208A 131
Transformer protection relay 6 Protection functions
information like time stamp, fault value, elapsed delay, fault current, fault voltage,
phase angle and setting group.
NOTE: The recorded values are lost if the relay power is switched off.
Squelch limit
Current inputs have a squelch limit (noise filter) at 0.005 x IN. When the
measured signal goes below this threshold level, the signal is forced to zero.
NOTE: If ICALC is used to measure the residual current, the squelch limit for
the ICALC signal is same as for the phase currents. The I0 setting range begins
at the level of phase currents' squelch limit. This can cause instability if the
minimum setting is used with the I0 CALC mode.
Dependent delay means that the operate time depends on the measured real
time process values during a fault. For example, with an overcurrent stage using
dependent delay, a bigger a fault current gives faster operation. The alternative to
dependent delay is definite delay. With definite delay, a preset time is used and
the operate time does not depend on the size of a fault.
Some protection functions have their own specific type of dependent delay.
Details of these dedicated dependent delays are described with the appropriate
protection function.
Operation modes
There are three operation modes to use the dependent time characteristics:
• Standard delays
selecting a curve family (IEC, IEEE, IEEE2) and defining one's own
parameters for the selected delay formula. This mode is activated by setting
delay type to ‘Parameters’, and then editing the delay function parameters A –
E. See 6.6.2 Free parameterization using IEC, IEEE and IEEE2 curves.
• Fully programmable dependent delay characteristics
132 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
1
T ( I/I ) =
Start f ( I/ I Start )
where
f ( I/ I Start )
CAUTION
UNINTENDED EQUIPMENT OPERATION
The relay shows a graph of the currently used dependent delay on the local panel
display. The up and down keys can be used for zooming. Also the delays at 20 x
ISET, 4 x ISET and 2 x ISET are shown.
If there are any errors in the dependent delay configuration, the appropriate
protection stage uses the definite time delay.
There is a signal ‘Setting Error’ available in the output matrix that indicates
different situations:
1. Settings are currently changed with eSetup Easergy Pro or local panel.
P3T/EN/M/30-208A 133
Transformer protection relay 6 Protection functions
3. There are errors in formula parameters A – E, and the relay is not able to
build the delay curve.
4. There are errors in the programmable curve configuration, and the relay is not
able to interpolate values between the given points.
Limitations
Table 55 - Maximum measured secondary currents and settings for phase and
earth fault overcurrent inputs
I01 = 5 A 50 A 2.5 A
I01 = 1 A 10 A 0.5 A
Example of limitation
CT = 750 / 5
For overcurrent stage I>, Table 55 gives 12.5 A. Thus, the maximum setting the
for I> stage giving full dependent delay range is 12.5 A / 5 A = 2.5 xIN = 1875
APrimary.
For earth fault stage I0>, Table 55 gives 0.5 A. Thus, the maximum setting for the
I0> stage giving full dependent delay range is 0.5 A / 1 A = 0.5 xI0N = 50 APrimary.
1. Example of limitation
6.6.1 Standard dependent delays using IEC, IEEE, IEEE2 and RI curves
The available standard dependent delays are divided in four categories called
dependent curve families: IEC, IEEE, IEEE2 and RI. Each category contains a set
of different delay types according to Table 56.
134 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
The dependent time setting error signal activates if the delay category is changed
and the old delay type does not exist in the new category. See 6.6 Dependent
operate time for more details.
Limitations
The minimum definite time delay starts when the measured value is twenty times
the setting, at the latest. However, there are limitations at high setting values due
to the measurement range. See 6.6 Dependent operate time for more details.
Table 56 - Available standard delay families and the available delay types within
each family
DT Definite X
time
NI Normal X X
inverse
VI Very X X X
inverse
EI Extremely X X X
inverse
MI Moderately X X
inverse
RI Old ASEA X
type
P3T/EN/M/30-208A 135
Transformer protection relay 6 Protection functions
The operate time depends on the measured value and other parameters
according to Equation 7. Actually this equation can only be used to draw graphs
or when the measured value I is constant during the fault. A modified version is
implemented in the relay for real time usage.
Equation 7
kA
t= B
I
− 1
I START
I = Measured value
There are three different dependent delay types according to IEC 60255-3,
Normal inverse (NI), Extremely inverse (EI), Very inverse (VI) and a VI extension.
In addition, there is a de facto standard Long time inverse (LTI).
Parameter
Delay type
A B
EI Extremely inverse 80 2
k = 0.50
I = 4 pu (constant current)
IPICKUP = 2 pu
A = 0.14
B = 0.02
136 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Equation 8
0.50 ⋅ 0.14
t= 0.02
= 5.0
4
−1
2
The operate time in this example is five seconds. The same result can be read
from Figure 68.
IEC NI
B inverseDelayIEC_NI
P3T/EN/M/30-208A 137
Transformer protection relay 6 Protection functions
IEC EI
0.1
0.08
0.04
B inverseDelayIEC_EI
138 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
IEC VI
B inverseDelayIEC_VI
P3T/EN/M/30-208A 139
Transformer protection relay 6 Protection functions
IEC LTI
B inverseDelayIEC_LTI
There are three different delay types according to IEEE Std C37.112-1996 (MI, VI,
EI) and many de facto versions according to Table 58. The IEEE standard defines
dependent delay for both trip and release operations. However, in the PowerLogic
P3 relay only the trip time is dependent according to the standard but the reset
time is constant.
The operate delay depends on the measured value and other parameters
according to Equation 9. Actually, this equation can only be used to draw graphs
or when the measured value I is constant during the fault. A modified version is
implemented in the relay for real-time usage.
Equation 9
A
t=k C
+ B
I − 1
I START
k = User’s multiplier
140 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
I = Measured value
A B C
k = 0.50
I = 4 pu
IPICKUP = 2 pu
A = 0.0515
B = 0.114
C = 0.02
Equation 10
t = 0.50 ⋅ 0.0515
+ 0.1140 = 1.9
4 0.02
−1
2
P3T/EN/M/30-208A 141
Transformer protection relay 6 Protection functions
The operate time in this example is 1.9 seconds. The same result can be read
from Figure 75.
IEEE LTI
B inverseDelayIEEE1_LTI
142 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
IEEE LTVI
B inverseDelayIEEE1_LTVI
P3T/EN/M/30-208A 143
Transformer protection relay 6 Protection functions
IEEE LTEI
B inverseDelayIEEE1_LTEI
144 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
IEEE MI
B inverseDelayIEEE1_MI
P3T/EN/M/30-208A 145
Transformer protection relay 6 Protection functions
IEEE STI
B inverseDelayIEEE1 STI
146 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
IEEE STEI
B inverseDelayIEEE1 STEI
Before the year 1996 and ANSI standard C37.112 microprocessor relays were
using equations approximating the behavior of various induction disc type relays.
A quite popular approximation is Equation 11 which in PowerLogic P3 relays is
called IEEE2. Another name could be IAC because the old General Electric IAC
relays have been modeled using the same equation.
There are four different delay types according to Table 59. The old
electromechanical induction disc relays have dependent delay for both trip and
release operations. However, in PowerLogic P3 relays, only the trip time is
dependent and the reset time is constant.
The operate delay depends on the measured value and other parameters
according to Equation 11. Actually, this equation can only be used to draw graphs
or when the measured value I is constant during the fault. A modified version is
implemented in the relay for real-time usage.
P3T/EN/M/30-208A 147
Transformer protection relay 6 Protection functions
Equation 11
B D E
t = k A + + + 3
I 2
− C I − C I − C
I START I START
I
START
k = User’s multiplier
I = Measured value
Parameter
Delay type
A B C D E
k = 0.50
I = 4 pu
ISTART = 2 pu
A = 0.1735
B = 0.6791
C = 0.8
D = -0.08
E = 0.127
148 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Equation 12
0.6791 − 0.08 0.127
t = 0.5 ⋅ 0.1735 + + + = 0.38
4 4
2
4
3
− 0.8 − 0.8 − 0.8
2 2 2
The operate time in this example is 0.38 seconds. The same result can be read
from Figure 78.
IEEE2 MI
B inverseDelayIEEE2_MI
P3T/EN/M/30-208A 149
Transformer protection relay 6 Protection functions
IEEE2 NI
B inverseDelayIEEE2_NI
150 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
IEEE2 VI
B inverseDelayIEEE2_VI
P3T/EN/M/30-208A 151
Transformer protection relay 6 Protection functions
IEEE2 EI
B inverseDelayIEEE2_EI
These two dependent delay types have their origin in old ASEA (nowadays ABB)
earth fault relays.
The operate delay of types RI and RXIDG depends on the measured value and
other parameters according to Equation 13 and Equation 14. Actually, these
equations can only be used to draw graphs or when the measured value I is
constant during the fault. Modified versions are implemented in the relay for real-
time usage.
Equation 13 Equation 14
k I
t RI = t RXIDG = 5.8 − 1.35 ln
0.236 k I START
0.339 −
I
I START
k = User’s multiplier
I = Measured value
152 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
k = 0.50
I = 4 pu
ISTART = 2 pu
Equation 15
0.5
t RI = = 2.3
0.236
0.339 −
4
2
The operate time in this example is 2.3 seconds. The same result can be read
from Figure 82.
k = 0.50
I = 4 pu
ISTART = 2 pu
Equation 16
4
t RXIDG = 5.8 − 1.35 ln = 3.9
0.5 ⋅ 2
The operate time in this example is 3.9 seconds. The same result can be read
from Figure 83.
P3T/EN/M/30-208A 153
Transformer protection relay 6 Protection functions
RI
B inverseDelayRI
154 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
This mode is activated by the setting delay type to ‘Parameters’, and then editing
the delay function constants, that is, the parameters A – E. The idea is to use the
standard equations with one’s own constants instead of the standardized
constants as in the previous chapter.
k = 0.50
I = 4 pu
ISTART = 2 pu
A = 0.2078
B = 0.8630
C = 0.8000
D = - 0.4180
E = 0.1947
P3T/EN/M/30-208A 155
Transformer protection relay 6 Protection functions
Equation 17
0.8630 − 0.4180 0.1947
t = 0.5 ⋅ 0.2078 + + + = 0.37
4 4
2
4
3
− 0.8 − 0.8 − 0.8
2 2 2
The resulting time/current characteristic of this example matches quite well the
characteristic of the old electromechanical IAC51 induction disc relay.
The dependent time setting error signal actives if interpolation with the given
parameters is not possible. See 6.6 Dependent operate time for more details.
Limitations
The minimum definite time delay starts at the latest when the measured value is
twenty times the setting. However, there are limitations at high setting values due
to the measurement range. See 6.6 Dependent operate time for more details.
Programming dependent time curves requires eSetup Easergy Pro setting tool
and rebooting the unit.
The [current, time] curve points are programmed using eSetup Easergy Pro PC
program.
The user gives the desired current-time point in the form of a table. The listed
points are used to interpolate all possible current-time values that fall between the
given points.
Interpolation is septically designed to fit curves with inverse time nature. Figure 84
depicts an example of the inverse time curve. Interpolation of non-inverse time
curves is possible, but curve fitting is not as good as with inverse curves.
156 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
I/Iset I/Iset
Inverse type Non-nverse type
of a curve of a curve
1 1.00 10.00 s
2 2.00 6.50 s
3 5.00 4.00 s
4 10.00 3.00 s
5 20.00 2.00 s
6 40.00 1.00 s
7 1.00 0.00 s
8 1.00 0.00 s
9 1.00 0.00 s
10 1.00 0.00 s
11 1.00 0.00 s
12 1.00 0.00 s
13 1.00 0.00 s
14 1.00 0.00 s
15 1.00 0.00 s
16 1.00 0.00 s
The dependent time setting error signal activates if interpolation with the given
points fails. See 6.6 Dependent operate time for more details.
P3T/EN/M/30-208A 157
Transformer protection relay 6 Protection functions
Limitations
The minimum definite time delay starts at the latest when the measured value is
twenty times the setting. However, there are limitations at high setting values due
to the measurement range. See 6.6 Dependent operate time for more details.
Curve 1 for the first three points, point 1, point 2 and point 3, is like this.
4 * ( I I1
(
x=
I3
y = ax bx 2 y1
Using the first three points, we can then get the coefficients a, b.
158 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
4 a * I 3 * I 31 y31 * I 32
b=
16 * I 312
y21 = y2 - y1
etc.
Thus, we get the formula for curve 1 among the first three points.
All the I/ISTART values between point 1 and point 3 can use this formula to get the
operate time.
In the same way, using point 3, point 4 and point 5, we can get another formula
for curve2 among these three points. In the formula, I3 takes the place of I1, I5
takes the place of I3, etc.
Using point 5, point 6 and point 7, we can get another formula for curve 3 among
these three points.
Like in the table, at last if there is only one point left, to get the curve between
point 7 and point 8, we must use point 6, point 7 and point 8 to get the formula.
But if the user only gives two points, like in the following table, then we get
another point this way.
1. If you define N points in your curve, and when N is even, the curve for the test
point between N-2 and N-1 is defined by N-2, N-1, N, and not by N-3, N-2,
N-1.
2. If the test point current is lower than the first point, the operate time will be
equal to the first point. If the test point current is higher than the last point, the
operate time will be equal to the last point.
P3T/EN/M/30-208A 159
Transformer protection relay 6 Protection functions
The used net frequency is automatically adopted according to the local network
frequency.
Overexcitation protection is needed for generators that are excitated even during
startup and shutdown. If such a generator is connected to a unit transformer, also
the unit transformer needs volts/hertz overexcitation protection. Another
application is sensitive overvoltage protection of modern transformers with no flux
density margin in networks with unstable frequency.
This figure shows the difference between volts/hertz and normal overvoltage
protection. The volts/hertz characteristics on the left depend on the frequency,
while the standard overvoltage function on the right is insensitive to frequency.
The network frequency, 50 Hz or 60 Hz, is automatically adopted by the relay.
2.0
E 2.0
E 18
0
%
1.8 1.8
1.6 C 1.6 14
0%
140 %
1.4 1.4
1.2 1.2
C 0%
10
A 1.0
100 % A 1.0
0.8 0.8
0.6 0.6
0.4
D 0.4
0.2 0.2
D
30 35 40 45 50 55 60 65 30 35 40 45 50 55 60 65
30 36 42 48 54 60 66 72 30 36 42 48 54 60 66 72
OverVoltFreqChar VoltPerHerz
B B
Setting groups
Characteristics
160 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Inaccuracy:
f < 0.05 Hz
P3T/EN/M/30-208A 161
Transformer protection relay 6 Protection functions
The relay includes a function that checks the synchronism before giving or
enabling the circuit breaker close command. The function monitors the voltage
amplitude, frequency and phase angle difference between two voltages. Since
there are two stages available, it is possible to monitor three voltages. The
voltages can be busbar and line or busbar and busbar (bus coupler).
Close
Request
cmd
Side 2 f1 = f2
φ1 = φ2 & & CB close
Register
U1 event
U2 & ≥1 Sync OK
The synchrocheck stage includes two separate synchronism criteria that can be
used separately or combined:
• voltage only
• voltage, frequency, and phase
The voltage check simply compares voltage conditions of the supervised objects.
The supervised object is considered dead (not energized) when the measured
voltage is below the Udead setting limit. Similarly, the supervised object is
considered live (energized) when the measured voltage is above the Ulive setting
limit. Based on the measured voltage conditions and the selected voltage check
criteria, synchronism is declared.
When the network sections to be connected are part of the same network, the
frequency and phase are the same. Therefore, the voltage check criteria is safe to
use without frequency and phase check.
The frequency and phase check compares the voltages, frequency and phase of
the supervised objects. Synchronism is declared if the voltages are above the
Ulive limit and all three difference criteria are within the given limits. This
synchronism check is dynamic by nature, and the object close command is given
at a certain moment of time, depending on the selected mode of operation.
When two networks are running at slightly different frequencies, there is also a
phase difference between these two networks. Because of the different frequency,
the phase angle tends to rotate. The time for one cycle depends on the frequency
difference. The stress for electrical components is lowest when two networks are
connected at zero phase difference.
In the “Sync” mode, the circuit breaker closing is aimed at the moment of zero
phase difference. Therefore, the close command is advanced by the time defined
by the CB close time setting. In the “Async” mode, the circuit breaker closing is
162 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
aimed at the moment when the synchronism conditions are met, that is, when the
phase difference is within the given phase difference limit.
When two network sections to be connected are from different sources or
generators, the voltage criteria alone is not safe, so also frequency and phase
check must be used.
When two networks with different frequencies are to be connected, the request
timeout setting must be long enough to allow the synchronism criteria to be met.
For example, if the frequency difference is 0.1 Hz, the synchronism criteria is met
only once in ten seconds.
The synchrocheck stage starts from an object close command that generates a
request to close the selected circuit breaker (as per CONTROL SETTINGS view)
when the synchronism conditions are met. The synchrocheck stage provides a
"request" signal that is active from the stage start until the synchronism conditions
are met or the request timeout has elapsed. When the synchronism conditions
are not met within the request timeout, a “fail” pulse is generated. The fail pulse
has a fixed length of 200 ms. When the synchronism conditions are met in a
timely manner, the object close command is initiated for the selected object. This
signal is purely internal and not available outside the synchrocheck stage. When
the synchronism conditions are met, the “OK” signal is always active. The
activation of the bypass input bybasses the synchronism check and declares
synchronism at all times.
The request, OK, and fail signals are available in the output matrix.
The synchronized circuit breaker close execution order is shown in Figure 87.
1 2 3
A B C
4 5
A. Synchrocheck stage
B. Object
C. Circuit breaker (physical) as selected in the CB Object 1 or CB Object 2 setting in the
CONTROL SETTINGS view of the synchro-check stage.
2. Synchronism declared
4. Sync fail signal if request timeout elapsed before synchronism conditions met
P3T/EN/M/30-208A 163
Transformer protection relay 6 Protection functions
A B
1
C D
1. Sync request
2. Sync OK
A. The object close command given (mimic or bus) actually only makes a sync request.
B. The sync request ends when the synchronism conditions are met and CB command is given or
if the request timeout elapsed.
C. If the request timeout elapsed before synchronism conditions are met, sync fail pulse is
generated.
D. Normal object close operation
3LN+LLy 1
3LN+LNy 1
2LL+U0+LLy 1
2LL+U0+LNy 1
LL+U0+LLy+LLz 2
LN+U0+LNy+LNz 2
The voltage used for synchrochecking is always line-to-line voltage U12 even
when UL1 is measured. The sychrocheck stage 1 always compares U12 with U12y.
The compared voltages for the stage 2 can be selected (U12/U12y, U12/U12z,
U12y/U12z). See 10.8 Voltage measurement modes.
164 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Characteristics
Input signal UA – UN
Voltage check mode (UMODE) DD; DL; LD; DD/DL; DD/LD; DL/LD;
DD/DL/LD 42) 43) 44) 45)
Inaccuracy:
- voltage ±3% UN
limit setting).
44) L means that the side must be “live” when closing (live = The voltage is higher than the live voltage
limit setting).
45) Example: DL mode for stage 1: The U12 side must be “dead” and the U12y side must be “live”.
P3T/EN/M/30-208A 165
Transformer protection relay 6 Protection functions
As all the protection stages, the undervoltage function can be blocked with any
internal or external signal using the block matrix. For example if the secondary
voltage of one of the measuring transformers disappears because of a fuse failure
(See the voltage transformer supervision function in 7.8 Voltage transformer
supervision (ANSI 60FL)). The blocking signal can also be a signal from the
custom logic (see 5.7 Logic functions).
The stages can be blocked with a separate low-limit setting. With this setting, the
particular stage is blocked when the biggest of the three line-to-line voltages
drops below the given limit. The idea is to avoid unwanted tripping when the
voltage is switched off. If the operate time is less than 0.08 s, the blocking level
setting should not be less than 15% for the blocking action to be fast enough. The
self blocking can be disabled by setting the low-voltage block limit equal to zero.
A
K K K
I
B
C
J J
H J
D
G
L L F
166 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
There are three separately adjustable stages: U<, U<< and U<<<. All these
stages can be configured for the definite time (DT) operation characteristic.
Setting groups
Characteristics
Inaccuracy:
P3T/EN/M/30-208A 167
Transformer protection relay 6 Protection functions
Inaccuracy:
Inaccuracy:
168 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Whenever the positive sequence voltage U1 drops below the start setting of a
particular stage, this stage activates and a start signal is issued. If the fault
situation remains on longer than the time defined in the operate time delay
setting, a trip signal is issued.
Like all the protection stages, the undervoltage function can be blocked with any
internal or external signal using the block matrix, for example, if the secondary
voltage of one of the measuring transformers disappears because of a fuse failure
(See VT supervision function in 7.8 Voltage transformer supervision (ANSI
60FL)). The blocking signal can also be a signal from the user's logic (see 5.7
Logic functions).
The stages are blocked when the voltage is below a separate low-voltage
blocking setting. With this setting, LVBlk, both stages are blocked when the
voltage U1 drops below the given limit. The idea is to avoid purposeless alarms
when the generator is not running. The LVBlk setting is common for both stages.
The selfblocking can not be disabled.
Further the start can be delayed by using the setting I<Blk. When the maximum of
the three measured phase currents is less than 1% of the rated generator current,
this delay is enabled. The idea is to avoid purposeless alarms, when the
generator circuit breaker is open and the excitation is switched off. By setting the
delay equal to zero, this feature is disabled.
Initial selfblocking
When the voltage U1 has been below the block limit, the stages are blocked until
the start setting has been reached.
P3T/EN/M/30-208A 169
Transformer protection relay 6 Protection functions
A
K K K
I
B
C
J H
H J
D
G
L L F
A. ULLmax = max (U12, U23, G. The positive sequence voltage U1 is below the block limit. This is
U31) not regarded as an undervoltage situation.
B. Deadband H. The positive sequence voltage U1 is above the block limit but below
the start level. However, this is not regarded as an undervoltage
situation because the voltage has never been above the start level
since being below the block limit.
C. U< setting I. The voltage is OK because it is above the start limit.
D. Block limit J. This is an undervoltage situation.
E. U< undervoltage state K. The voltage is OK.
F. Time L. The voltage is below the block limit and this is not regarded as an
undervoltage situation.
There are two separately adjustable stages: U1< and U1<< . Both stages can be
configured for definite time (DT) operate characteristic.
Setting groups
Characteristic
- Blocking time, when I< 1% x IGN 2–100% x UGN (common for both stages)
170 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Inaccuracy:
- Starting 1% unit
P3T/EN/M/30-208A 171
Transformer protection relay 6 Protection functions
Equation 18
K1
T= 2
I 2 − K 22
I
TN
T = Operate time
K1 = Delay multiplier
Example
K1 = 15 s
K2 = 5 % = 0.05 x ITN
15
t= 2
= 300.4
0.229
− 0.05
2
1
The operate time in this example is five minutes.
If more than one definite time delay stages are needed for negative sequence
overcurrent protection, the freely programmable stages can be used (6.33
Programmable stages (ANSI 99)).
172 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
500 K2 = 2 % K 2 = 40 % K 2 = 70 %
200
100 K1 = 50 s
A 50
K2 = 2 % K 2 = 40 % K 2 = 70 %
20
10
5
K1 = 1 s
2
1
0 20 40 60 80 100
B
Setting groups
Characteristics
Inaccuracy:
NOTE: The stage is operational when all secondary currents are above 250
mA.
P3T/EN/M/30-208A 173
Transformer protection relay 6 Protection functions
This protection stage can be used to detect voltage unbalance and phase
reversal situations. It calculates the fundamental frequency value of the negative
sequence component U2 based on the measured voltages (for calculation of U2,
see 4.11 Symmetrical components).
Whenever the negative sequence voltage U2 raises above the user's start setting
of a particular stage, this stage starts, and a start signal is issued. If the fault
situation remains on longer than the user's operate time delay setting, a trip signal
is issued.
Like all the protection stages, the negative sequence overvoltage can be blocked
with any internal or external signal using the block matrix, for example, if the
secondary voltage of one of the measuring transformers disappears because of a
fuse failure (See VT supervision function in 7.8 Voltage transformer supervision
(ANSI 60FL)).
The blocking signal can also be a signal from the user's logic (see 5.7 Logic
functions).
There are three separately adjustable stages: U2>, U2>>, and U2>>>. Both stages
can be configured for the definite time (DT) operation characteristic.
Setting groups
There are four settings groups available for all stages. Switching between setting
groups can be controlled by digital inputs, virtual inputs (mimic display,
communication, logic) and manually.
Characteristics
Inaccuracy:
174 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Thermal model
The temperature is calculated using RMS values of phase currents and a thermal
model according IEC60255-149. The RMS values are calculated using harmonic
components up to the 15th.
Trip time:
I2 − I
2
t = τ ⋅ ln 2 P2
I −a
Alarm (alarm 60% = 0.6):
a = k ⋅ kΘ ⋅ I TN ⋅ alarm
Trip:
a = k ⋅ kΘ ⋅ I TN
Reset time:
2
IP
t = τ ⋅ Cτ ⋅ ln
a − I2
2
Trip release:
a = 0.95 × k × I TN
a = 0.95 × k × I TN × alarm
T = Operate time
I =Measured RMS phase current (the max. value of three phase currents)
P3T/EN/M/30-208A 175
Transformer protection relay 6 Protection functions
If the transformer's fan is stopped, the cooling will be slower than with an active
fan. Therefore there is a coefficient Cτ for thermal constant available to be used
as cooling time constant, when current is less than 0.3 x ITN.
The trip level is determined by the maximum allowed continuous current IMAX
corresponding to the 100% temperature rise ΘTRIP for example the heat
capacitance of the transformer. IMAX depends of the given service factor k and
ambient temperature ΘAMB and settings IMAX40 and IMAX70 according the following
equation.
I MAX = k ⋅ k Θ ⋅ I TN
k
1.2
IMAX40
1.0
0.8 IMAX70
0.6
10 20 30 40 50 60 70 80 (°C)
AMB
176 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
When the relay is switched on, an initial temperature rise of 70% is used.
Depending on the actual current, the calculated temperature rise then starts to
approach the final value.
Alarm function
The thermal overload stage is provided with a separately settable alarm function.
When the alarm limit is reached, the stage activates its start signal.
Θoverload
Θmax
Θalarm
Reset ratio=95%
Θp
Settings:
τ = 30 minutes
k = 1.06
Θalarm = 90%
Alarm
Trip
45 min
IP = 0.85*IN
Time
100 min 200 min 300 min 400 min 500 min
Setting groups
Characteristics
P3T/EN/M/30-208A 177
Transformer protection relay 6 Protection functions
178 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
The circuit breaker failure protection stage (CBFP) can be used to operate any
upstream circuit breaker (CB) if the programmed output matrix signals, selected
to control the main breaker, have not disappeared within a given time after the
initial command. The supervised output contact is defined by the “Monitored Trip
Relay” setting. An alternative output contact of the relay must be used for this
backup control selected in the Output matrix setting view.
The CBFP operation is based on the supervision of the signal to the selected
output contact and the time. The following output matrix signals, when
programmed into use, start the CBFP function:
• protection functions
• control functions
• supporting functions
• GOOSE signals (through communication)
If the signal is longer than the CBFP stage’s operate time, the stage activates
another output contact defined in the Output matrix setting view. The output
contact remains activated until the signal resets. The CBFP stage supervises all
the signals assigned to the same selected output contact.
In Figure 94, both the trip and CBFP start signals activate simultaneously (left
picture). If T> trip fails to control the CB through T1, the CBFP activates T3 after
the breaker failure operate time.
Figure 94 - Trip and CBFP start signals in the Output matrix view
NOTE: For the CBFP, always select the ”Connected” crossing symbol in the
Output matrix setting view.
P3T/EN/M/30-208A 179
Transformer protection relay 6 Protection functions
Characteristics
Inaccuracy:
180 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Description
Power system protection should always have some sort of backup protection
available. Backup protection is intended to operate when a power system fault is
not cleared or an abnormal condition is not detected in the required time because
of a failure or the inability of the primary protection to operate or failure of the
appropriate circuit breakers to trip. Backup protection may be local or remote.
Circuit breaker failure protection (CBFP) is part of the local backup protection.
CBFP provides a backup trip signal to an upstream circuit breaker (CB) when the
CB nearest to fault fails to clear fault current. The CB may fail to operate for
several reasons, for example burnt open coil or a flashover in the CB.
Two separate stages are provided to enable re-trip and CBFP trip commands.
The first stage can be used to give re-trip command (for example to control
second/backup open coil of the main CB) while the second stage can give
dedicated CBFP trip command to an upstream circuit breaker. Select the required
outputs for re-trip and CBFP trip through the output matrix.
P3T/EN/M/30-208A 181
Transformer protection relay 6 Protection functions
Block diagram
A I
IL1
IL2 Imax > &
& J
IL3
I0 > & ≥ t K
B
C & & J
D
&
E
F G H
CBFP operation
The CBFP function can be enabled and disabled with the Enable for BF2
selection. The CBFP function activates when any of the selected start signals
becomes and stays active.
The CBFP operation can be temporarily blocked by the stage block signal from
the block matrix. When the stage is blocked by the block signal, the stage timer
stops but it does not reset. The stage timer continues its operation when the block
signal is disabled. When the block signal is active, the stage output signals are
disabled.
Condition selectors
The CBFP function has four condition selectors that can be used separately or all
together to activate and reset the CBFP function.
The four condition selectors are almost identical. The only difference is that
condition selectors 1 and 2 are for all protection functions that benefit from zero-
current detection for resetting the CBFP as described in section Zero-current
detector, and selectors 3 and 4 are for all the protection functions that do not
benefit from zero-current detection for CBFP.
182 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
For monitoring condition 1~3, user can set 6 protection stages at most for each
monitoring condition. Once the stages monitored trips, 50BF-1/2 starts
immediately to check the CB and current status.
For monitoring condition 4, user can set 3 monitoring outputs and inputs for
monitoring needs. 50BF-1/2 can also be reset by these signals.
The user can reset the 50BF-1/2 by CB status if the CB parameter is set for all
conditions. 50BF-1/2 can also be reset by monitored stage for condition 1~3. Zero
current criteria can be used to reset condition 1 while zero EF current criteria can
be used to reset condition 2.
Figure 97 - Start signal and reset condition setting view for Condition 1
Separate zero-current detection with dedicated start settings exists for phase
overcurrent and earth fault overcurrent signals. Zero-current detection is
independent of the protection stages.
The condition criteria, available signals and reset conditions are listed in Table 71.
NOTE: The start signal can be selected for each condition in advance from
the pull-down menu even if the concerned stage is not enabled. For the CBFP
activation, the concerned stage must be enabled from the protection stage
menu and the stage has to start to activate the CBFP start signal.
P3T/EN/M/30-208A 183
Transformer protection relay 6 Protection functions
Condition 1 I>, I>>, I>>>, Iv>, I2>, dI>, Reset by CB status: DI1 –
dI>>, Iφ>, Iφ>>, Iφ>>>, DIx (1, F1, F2, VI1-20,
Iφ>>>>, T>, If2>, X<, X<<, VO1–20, GOOSE_NI1–64,
I’>, I’>>, If5, SOTF POC1–16, Obj1-8Op
In addition to the selection of the start signal, the CBFP reset condition needs to
be selected.
If no reset conditions are selected, the stage uses Reset by monitored stage as
the reset condition. This prevents a situation where the stage never releases.
The reset condition Reset by CB status is useful if the current is already zero
when the CB is opened (for example unloaded CB).
When more than one selection criteria are selected, AND condition is used, for
example “zero current detection” AND “object open”. See Figure 96 for details.
Stage timer
The operate delay timer is started by a signal activated by the monitored stages
(condition selectors). The operate time delay is a settable parameter. When the
given time delay has elapsed, the stage provides a trip signal through the output
matrix and the event codes.
Zero-current detector
184 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
can be performed only when the fault current really is zero or near zero instead of
relying on the protection stage reset.
The setting range of the zero-current detector is always associated with the CT
nominal value, even in case of motor and transformer protection. The setting
range minimum depends on the relay accuracy. Instead of zero, a small minimum
value can be accepted. See Table 72.
CBFP coordination
The CBFP delay setting has to be coordinated according to the CB operation time
and the reset time of protection stages monitored by the CBFP function as
described in Figure 99.
B
C E F
D G
A
H I
P3T/EN/M/30-208A 185
Transformer protection relay 6 Protection functions
Characteristics
Zero-current detection:
Inaccuracy:
186 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
The switch-on-to-fault (SOTF) protection function offers fast protection when the
circuit breaker (CB) is closed manually against a faulty line. Overcurrent-based
protection does not clear the fault until the intended time delay has elapsed.
SOTF gives a trip signal without additional time delay if the CB is closed and a
fault is detected after closing the CB.
Figure 100 - Switch-on-to-fault function operates when the CB has detected open
and the fault current reaches start setting value
E
A
G
B
C
F
D
A. Start setting
B. Maximum of IL1, IL2, IL3
C. Low limit 0.02 x IN
D. SOTF trip
E. Switch-on-to-fault does not activate if the CB has not been in open position before the fault.
Open CB detection is noticed from the highest phase current value which has to be under a fixed
low-limit threshold (0.02 x IN). Opening of the CB can be detected also with digital inputs (Dead
line detection input = DI1 – DIx, VI1 – VIx). The default detection input is based on the current
threshold, so the dead line detection input parameter has value “–“.
F. Dead line detection delay defines how long the CB has to be open so that the SOTF function is
active. If the set time delay is not fulfilled and the highest phase current value (maximum of IL1, IL2,
IL3) rises over the start setting, the SOTF does not operate.
G.If the highest phase current value of IL1, IL2, IL3 goes successfully under the low limit and rises to
a value between the low limit and the start value, then if the highest phase current value rises over
the start setting value before the set SOTF active after CB closure time delay has elapsed, the
SOTF trips. If this time delay is exceeded, the SOTF does not trip even if the start setting value is
exceeded.
Setting groups
Characteristics
P3T/EN/M/30-208A 187
Transformer protection relay 6 Protection functions
188 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
For the fastest operation delay (30 ms), the sample based operating quantity is
used for stage start instead of fundamental frequency component. Sample based
value allows faster stage start, resulting faster trip time. The sample based
operating quantity is more sensitive for the transient DC component that the
fundamental frequency component.
Block diagram
3vlsblock
Im1
Im2 MAX > ts tr
& H
Im3
& I
A t
>1 J
& I
B C D E F G
A. Block F. Multiplier
B. Setting I>s G. Enable events
C. Delay H. Start
D. Definite / dependent time I. Register event
E. Dependent time characteristics J. Trip
P3T/EN/M/30-208A 189
Transformer protection relay 6 Protection functions
Figure 102 - Block diagram of the three-phase overcurrent stage I>> and I>>>
3vIssblock
Im1
Im2 MAX > & E
Im3 ts tr
& F
A
t
G
& F
B C D
A. Block E. Start
B. Setting I>>s F. Register event
C. Delay G. Trip
D. Enable events
There are three separately adjustable overcurrent stages: I>, I>> and I>>>. The
first stage I> can be configured for definite time (DT) or dependent operate time
(IDMT) characteristic. The stages I>> and I>>> have definite time operation
characteristic. By using the definite delay type and setting the delay to its
minimum, an instantaneous (ANSI 50) operation is obtained.
Figure 101 shows a functional block diagram of the I> overcurrent stage with
definite time and dependent time operate time. Figure 102 shows a functional
block diagram of the I>> and I>>> overcurrent stages with definite time operation
delay.
Dependent operate time means that the operate time depends on the amount the
measured current exceeds the start setting. The bigger the fault current is, the
faster is the operation. The dependent time delay types are described in 6.6
Dependent operate time. The relay shows the currently used dependent operate
time curve graph on the local panel display.
The maximum measured secondary current is 50 x IN. This limits the scope of
dependent curves with high start settings. See 6.6 Dependent operate time for
more information.
The I> and I>> (50/51) overcurrent protection stages have a setting parameter to
include harmonics. When this setting is activated, the overcurrent stage
190 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
calculates the sum of the base frequency and all measured harmonics. This
feature is used to determine the signal's true root mean square value to detect the
signal's real heating factor. The operate time is 5 ms more when harmonics are
included in the measurement. Activate the "Include harmonics" setting if the
overcurrent protection is used for thermal protection and the content of the
harmonics is known to exist in the power system.
Setting groups
Characteristics
IDMT function:
- RI curve 0.025–20.0
0.025–20.0
Inaccuracy:
Moderately Inverse
52) In equals to rated primary current of the current transformer or rated primary current of LPCT
sensor.
P3T/EN/M/30-208A 191
Transformer protection relay 6 Protection functions
Inaccuracy:
±3% of the set value or 0.005 In54)
- Starting
±1% or ±25 ms
- operate time
53) This is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in eSetup Easergy Pro to accept the zero operate time setting for the DT function.
54) In equals to rated primary current of the current transformer or rated primary current of LPCT
sensor.
192 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Inaccuracy:
sensor.
P3T/EN/M/30-208A 193
Transformer protection relay 6 Protection functions
Block diagram
Figure 103 - Block diagram of the earth fault stage overcurrent I0>
i0s1
A > & I
ts tr
& J
B t
>1 K
& J
C D E F G H
A. I0 G. Multiplier
B. Block H. Enable events
C. Setting I0>s I. Start
D. Delay J. Register event
E. Definite / inverse time K. Trip
F. Inverse time characteristics
194 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Figure 104 - Block diagram of the earth fault stages overcurrent I0>>, I0>>>,
I0>>>>
I0ssblock
A > ts tr
& F
& G
B
t
H
& G
C D E
A. I0 E. Enable events
B. Block F. Start
C. Setting I0>>s G. Register event
D. Delay H. Trip
Each stage can be connected to supervise any of the following inputs and signals:
• Input I01 for all networks other than solidly earthed.
• Input I02 for all networks other than solidly earthed.
• Calculated signal I0 Calc for solidly and low-impedance earthed networks.. I0
Calc = IL1 + IL2 + IL3.
There are four separately adjustable earth fault overcurrent stages: I0>, I0>>,
I0>>>, and I0>>>>. The first stage I0> can be configured for definite time (DT) or
dependent time operation characteristic (IDMT). The other stages have definite
time operation characteristic. By using the definite delay type and setting the
delay to its minimum, an instantaneous (ANSI 50N) operation is obtained.
Using the directional earth fault overcurrent stages (6.25 Directional earth fault
overcurrent (ANSI 67N)) in nondirectional mode, three more stages with
dependent operate time delay are available for nondirectional earth fault
overcurrent protection.
The maximum measured secondary earth fault overcurrent is 10 x I0N and the
maximum measured phase current is 50 x IN. This limits the scope of dependent
curves with high start settings.
Setting groups
P3T/EN/M/30-208A 195
Transformer protection relay 6 Protection functions
Characteristics
IDMT function:
0.025–20.0, except
Inaccuracy:
- Starting (Peak mode) ±5% of the set value or ±2% of the rated
value (Sine wave <65 Hz)
57) This is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in eSetup Easergy Pro to accept the zero operate time setting for the DT function.
58) EI = Extremely Inverse, NI = Normal Inverse, VI = Very Inverse, LTI = Long Time Inverse, MI=
Moderately Inverse
59) In equals to rated primary current of the current transformer or rated primary current of LPCT
sensor.
196 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Inaccuracy:
- Starting (Peak mode) ±5% of the set value or ±2% of the rated
value (Sine wave <65 Hz)
60) This is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in eSetup Easergy Pro to accept the zero operate time setting for the DT function.
61) In equals to rated primary current of the current transformer or rated primary current of LPCT
sensor.
The earth fault overcurrent stage (ANSI 50N/51N) and directional earth fault
overcurrent stage (ANSI 67N) have an inbuilt detection algorithm to detect a faulty
phase. This algorithm is meant to be used in radial-operated distribution
networks. The faulty phase detection can be used in solidly-earthed, impedance-
earthed or resonant-earthed networks.
Operation
The faulty phase detection starts from the earth fault stage trip. At the moment of
stage start, the phase currents measured prior to start are registered and stored
as prior-to-fault currents. At the moment of trip, phase currents are registered
again. Finally, faulty phase detection algorithm is performed by comparing prior-
to-fault currents to fault currents. The algorithm also uses positive sequence
current and negative sequence current to detect faulty phase.
The detected faulty phase is registered in the protection stage fault log (and also
in the event list and alarm screen). Faulty phase is also indicated by a line alarm
and line fault signals in the output matrix.
Possible detections of faulty phases are L1-N, L2-N, L3-N, L1-L2-N, L1-L3-N, L2-
L3-N, L1-L2-L3-N, and REV. If the relay protection coordination is incorrect, REV
indication is given in case of a relay sympathetic trip to a reverse fault.
P3T/EN/M/30-208A 197
Transformer protection relay 6 Protection functions
Description
The relay enables capacitor, filter and reactor bank protection with its five current
measurement inputs. The fifth input is typically useful for unbalance current
measurement of a double-wye connected unearthed bank.
The relay enables capacitor, filter and reactor bank protection with its five current
measurement inputs. The fifth input is typically useful for unbalance current
measurement of a double-wye connected ungrounded bank.
As the capacitor elements are not identical and have acceptable tolerances, there
is a natural unbalance current between the starpoints of the capacitor banks. This
natural unbalance current can be compensated to tune the protection sensitive
against real faults inside the capacitor banks.
8/E/1:1
IL1 5A
8/E/1:2
8/E/1:3
IL2 5A
8/E/1:4
8/E/1:5
IL3 5A
8/E/1:6
8/E/1:7 I01 5A
8/E/1:8
I01 1A
8/E/1:9
8/E/1:10 I02 1A
8/E/1:11
I02 0,2A
8/E/1:12
255
Compensation method
198 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
This feature is implemented to the stage I0>>>>, while the other stage I0>>> can
still function as normal unbalance protection stage with the compensation
method. Normally, the I0>>>> could be set as an alarming stage while stage I0>>>
trips the circuit breaker.
The stage I 0>>>> should be set based on the calculated unbalance current
change of one faulty element. You can calculate this using the following formula:
Equation 19
U L− N U L− N
−
(2 ⋅ π ⋅ f ⋅ C1 ) −1
(2 ⋅ π ⋅ f ⋅ C2 ) −1
3I 0 =
3
P3T/EN/M/30-208A 199
Transformer protection relay 6 Protection functions
90
3I0
A
180 0
B
270
If there is an element failure in the bank, the algorithm checks the phase angle of
the unbalance current related to the phase angle of the phase current IL1. Based
on this angle, the algorithm can increase the corresponding faulty elements
counter (there are six counters).
Figure 107 - How a failure in different branches of the bank affects the I0
measurement
Easergy P3 H I
G C
A B
F D
E
You can set for the stage I0>>>> the allowed number of faulty elements. For
example, if set to three elements, the fourth fault element will issue the trip signal.
The fault location is used with internal fused capacitor and filter banks. There is
no need to use it with fuseless or external fused capacitor and filter banks, nor
with the reactor banks.
200 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Application example
Figure 108 - 131.43 μF Y-Y connected capacitor bank with internal fuses
12kV A
I B
I0
Characteristics
Inaccuracy:
P3T/EN/M/30-208A 201
Transformer protection relay 6 Protection functions
– via the PowerLogic P3 device's front panel: go to the I0>>>> menu, scroll
right to 1 SET 50N/51N, and select Location for CMode.
– via the device's front panel: go to the I0>>>> menu, scroll right to SET2
50N/51N, and select Get for SaveBal.
Equation 20
U L− N U L− N
−
(2 ⋅ π ⋅ f ⋅ C1 ) −1
(2 ⋅ π ⋅ f ⋅ C 2 ) −1
3I 0 =
3
6928 6928
−
(2 ⋅ π ⋅ 50 ⋅ 43.81 ⋅ 10 −6 ) −1 (2 ⋅ π ⋅ 50 ⋅ 43.81 ⋅ 10 −6 ) −1
3I 0 =
3
3I 0 = 1.37 A
Failure of one element inside the bank on the left branch causes
approximately 1.37 ampere unbalance current at the star point. On the right
branch, there are two capacitor units in parallel, and therefore, a failure of one
202 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
element causes only 0.69 ampere unbalance. A different start value for each
branch is necessary. Set the start value to 80% of the calculated value.
4. Test the operation of the unbalance protection.
0.80
0.60
0.40
0.20
0.00
Conduct testing by injecting current to channels IL1 and I01 of the device. In
the example above, 0.69 A primary current is injected to the I01 channel. I01 is
leading the phase current IL1 by 60 degrees. This means the fault has to be
on the right branch and in phase 2. Compensation happens automatically
after the set operate time until the allowed total amount of failed units is
exceeded (Max. allowed faults). In this application, the fourth failed element
would cause the stage to trip.
P3T/EN/M/30-208A 203
Transformer protection relay 6 Protection functions
204 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Overvoltage protection is used to detect too high system voltages or to check that
there is sufficient voltage to authorize a source transfer.
In solidly earthed, four-wire networks with loads between phase and neutral
voltages, overvoltage protection may be needed for line-to-neutral voltages, too.
In such applications, the programmable stages can be used. 6.33 Programmable
stages (ANSI 99).
There are three separately adjustable stages: U>, U>> and U>>>. All the stages
can be configured for the definite time (DT) operation characteristic.
The U> stage has a settable reset delay that enables detecting intermittent faults.
This means that the time counter of the protection function does not reset
immediately after the fault is cleared, but resets after the release delay has
elapsed. If the fault appears again before the release delay time has elapsed, the
delay counter continues from the previous value. This means that the function
eventually trips if faults are occurring often enough.
Configurable hysteresis
The dead band is 3% by default. This means that an overvoltage fault is regarded
as a fault until the voltage drops below 97% of the start setting. In a sensitive
alarm application, a smaller hysteresis is needed. For example, if the start setting
is about only 2% above the normal voltage level, the hysteresis must be less than
2%. Otherwise, the stage does not release after fault.
P3T/EN/M/30-208A 205
Transformer protection relay 6 Protection functions
Block diagram
Figure 113 - Block diagram of the three-phase overvoltage stages U>, U>> and
U>>>
3vus
Um1
Um2 MAX > & G
Um3 ts tr
& H
A
t
I
& H
B C D E F
Setting groups
Characteristics
206 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Inaccuracy:
Inaccuracy:
63) This
is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in eSetup Easergy Pro to accept the zero operate time setting for the DT function.
P3T/EN/M/30-208A 207
Transformer protection relay 6 Protection functions
Inaccuracy:
208 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Whenever the measured value exceeds the start setting of a particular stage, this
stage starts and a start signal is issued. If the fault situation remains on longer
than the operate time delay setting, a trip signal is issued.
There are two separately adjustable stages: U0> and U0>>. Both stages can be
configured for the definite time (DT) operation characteristic.
P3T/EN/M/30-208A 209
Transformer protection relay 6 Protection functions
Block diagram
Figure 114 - Block diagram of the neutral voltage displacement stages U0>, U0>>
U0sblock
A > ts tr
& G
& H
B
t
I
& H
C D E F
A. U0 F. Enable events
B. Blocking G. Start
C. Setting U0>s H. Register event
D. Release delay I. Trip
E. Delay
Setting groups
Characteristics
Input signal U0
Inaccuracy:
210 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Input signal U0
Inaccuracy:
P3T/EN/M/30-208A 211
Transformer protection relay 6 Protection functions
212 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
The restricted earth fault (REF) protection function is used to detect earth faults in
solidly-earthed or impedance-earthed power transformers, earthing transformers
and shunt reactors. REF protection can also be used to protect rotating machines
if the machine’s neutral point is earthed.
Figure 115 to Figure 118 describe the basic low-impedance REF protection
schemes.
L1 L1
L2 L2
L3 L3
Figure 116 - Restricted earth fault protection of a transformer and neutral point
reactor
L1 L1
L2 L2
L3 L3
L1 L1
L2 L2
L3 L3
P3T/EN/M/30-208A 213
Transformer protection relay 6 Protection functions
L1
L2
L3
The REF protection principle has several advantages. It is very selective because
the protection zone is limited between the current transformers that are used for
the REF protection. Because of its selectivity, the REF protection requires no
additional time delay for protection coordination. Therefore, REF protection is
especially suitable for the protection of transformers and rotating machines
against internal earth faults. Because of the differential protection principle, it is
also very sensitive which makes it suitable for detecting faults located near the
neutral point of transformers and rotating machines.
The REF protection function is based on the differential protection principle and is
sensitive to the fundamental frequency component of the measured currents.
Figure 119 depicts the differential protection principle applied to REF protection.
A
C C
I B I
64REF
I0Meas I0Calc = IL1 + IL2 + IL3
The function is based on the difference of the current measured at the neutral
point (I0 Meas) and the calculated residual current (I0 Calc). The function calculates
the differential current ID according to Equation 21. So the function is based on
the absolute value of ID that is a sum of the current vectors I0 Meas and I0 Calc.
NOTE: Nominal current of the I0 Meas and I0 Calc are current transformer
ratings.
Equation 21
ID = |I0Meas + I0Calc|
214 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
During healthy conditions, the neutral point current (I0 Meas) is near or equal to
zero and the same is true for the residual current or the calculated sum of the
phase currents I0 Calc = 3I0 =IL1+IL2 +IL3. During healthy conditions, the differential
current ID is also close to zero and the REF protection stage does not start.
Figure 120 depicts through-fault conditions and a fault in the protected zone.
During a through-fault condition, an earth fault current flowing from the faulty
phase to earth returns to the system’s neutral point. Because of the convention of
current directions, the resulting neutral point current (I0 Meas) and calculated
residual current (I0 Calc) are flowing in opposite directions resulting in zero or very
small differential current ID according to Equation 21.
When a fault occurs inside the protection zone, the neutral point current flowing
into the protection zone has a positive current direction according to the current
direction convention. Depending on the network conditions, an additional fault
current may or may not flow into the zone along the line. This additional fault
current manifests itself as a residual current. Additional fault currents flowing into
the protection zone have a positive current direction, too. In other words, the
neutral point current and residual current are in a phase which results in a high
differential current ID according to Equation 21.
Figure 120 - Through-fault condition (left) and earth fault in protected zone (right)
L1 L1 L1 L1
L2 L2 L2 L2
L3 L3 L3 L3
I0Calc = IL1 + IL2 + IL3 I0Calc = IL1 + IL2 + IL3
I0Meas I0Meas
Id ≈ 0 Id > 0
During a through-fault or short-circuit fault outside the protection zone, the current
transformers may be exposed to very high currents. These high fault currents
may lead to different saturation of the phase current transformers resulting in an
erroneous residual current. To ensure correct operation of the protection stage, a
stabilization method is provided. Protection stage stabilisation is based on the
calculated bias current IB and programmable operating characteristics. The bias
current is calculated according to Equation 22.
Equation 22
|IL1|+|IL2|+|IL3|
IB =
3
This bias current stabilization method is used in the dI0> stage. The dI0>> stage
does not consider the stabilization current IB and is purely based on the
differential current ID. Both the differential current ID and stabilization current IB
are current transformer ratings.
P3T/EN/M/30-208A 215
Transformer protection relay 6 Protection functions
N
I K
L
D
J
M
E H
F G
A. ID/ IN H. IB / IN
B. 2 x IN I. Single-end-feed limit
C. IN J. ISTART
D. 50% IN K. Maximum setting
E. 5% IN L. Slope 1
F. IN M. Minimum setting
G. 3 x IN N. Slope 2
A
B
C I & J
D
>
& K
E F G H
216 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Characteristics
dIo> dIo>>
Input signals - -
Start value - -
Slope 1 5–100 % -
Slope 2 100–200 % -
Inaccuracy of starting ±3% of set value or 0.02 x In ±3 % of the set value or ±0.5
when currents are < 200 mA % of the rated value
P3T/EN/M/30-208A 217
Transformer protection relay 6 Protection functions
The directional phase overcurrent protection can be used for directional short-
circuit protection. Typical applications are:
NOTE: For networks where the maximum possible earth-fault current is lower
than the overcurrent setting value, use the directional earth-fault (67N) stages.
For line-to-line and three-phase faults, the fault direction is determined with
positive-sequence polarization using the angles between the positive sequences
of currents and voltages.
For details on power direction, see 4.10 Power and current direction.
Voltage memory
218 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Block diagrams
Figure 123 - Block diagram of directional phase overcurrent stage Iϕ > and Iϕ >>
3vlsblock_Idir>_Idir>>
K
U1 U1
I1 I1
Im1
Im2 MAX > ts tr
& H
Im3
& I
A t
>1 J
& I
B C D E F G
Figure 124 - Block diagram of directional phase overcurrent stage Iϕ >>> and Iϕ
>>>>
3vlsblock_Idir>>>_Idir>>>>
K
U1 U1
I1 I1
Im1
Im2 MAX > & H
Im3 ts tr
& I
A
t
J
& I
B C G
A. Block H. Start
B. Setting I>>>s I. Register event
C. Delay J. Trip
G. Enable events K. Directional discrimination by U1/I1 angle
P3T/EN/M/30-208A 219
Transformer protection relay 6 Protection functions
Operation
The function has two conditions as shown in the block diagram. One is the current
threshold and the other is the fault direction or fault angle. If both conditions are
true, the stage starts and trips after the set trip delay. Whenever the highest three-
phase current exceeds the set value, there is an overcurrent condition.
For faults that do not involve earth, the fault direction or fault angle is determined
as an angle between the positive sequences of current and voltage. The angle
reference for the positive-sequence current is the positive-sequence voltage that
is rotated by the base-angle setting (also called relay characteristics angle). The
actual trip area is ± 88° from the base-angle setting. If the positive-sequence
current vector falls into the trip area, there is a directional condition.
If the current threshold and directional conditions are true, the stage starts and
trips after the set trip delay.
For faults that involve earth, the fault direction or fault angle is determined as an
angle between the healthy line-to-line voltage and the faulted phase current. The
angle reference for the faulted phase current is opposite to the healthy line-to-line
voltage that is rotated by the base-angle setting plus 90° to the positive direction.
The actual trip area is ± 88° from the base angle setting plus 90°. If the fault
current vector falls into the trip area, there is a directional condition. If both
conditions are true, the stage starts and trips after the set trip delay. If the current
threshold and directional conditions are true, the stage starts and trips after the
set trip delay.
A typical characteristic for the directional phase overcurrent protection for line-to-
line faults is shown in Figure 125. The base angle setting is -30°. The stage starts
if the maximum of the three-phase currents exceeds the current threshold and if
the tip of the positive-sequence current phasor gets into the grey area.
220 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Figure 125 - Example of the directional phase overcurrent protection area for line-
to-line fault
+90°
Reverse Forward
+88°
0°
U1
-88°
-90° ldir_angle1
A typical characteristic for the directional phase overcurrent protection for line-to-
earth faults is shown in Figure 126. The base angle setting is -30°. The stage
starts if the maximum of the three-phase currents exceeds the current threshold
and if the tip of the fault current phasor gets into the grey area.
Figure 126 - Example of the directional phase overcurrent protection area for line-
to-earth fault , RCA internally rotated +90o CCW during earth fault
+90°
+60°
Forward
+88°
-88°
0°
U1
Reverse
-90° ldir_angle2
In the non-directional mode, the stage acts like an ordinary overcurrent 50/51
stage.
The directional + backup mode works like the directional mode, but it has non-
directional backup protection that is used if a close-up fault forces all voltages to
about zero. After the angle memory hold time, the direction would be lost.
P3T/EN/M/30-208A 221
Transformer protection relay 6 Protection functions
The directional + backup mode is required when the operate time is set longer
than the voltage memory setting or no other non-directional backup protection is
used.
+90° +90°
-ind. +cap. -ind. +cap.
2°
DIRECTIONAL NON-DIRECTIONAL
SET SET
VALUE 0° VALUE 0°
-res. +res. -res. +res.
BASE ANGLE= 0°
-90° -90°
Figure 128 - Bidirectional application with two stages Iφ> and Iφ>>
+90°
-ind. +cap.
4°
Iφ>> TRIP AREA
SET SET
VALUE VALUE 0°
-res. +res.
BASE ANGLE= 0°
-cap. +ind.
When any of the three-phase currents exceeds the setting value and, in
directional mode, the phase angle including the base angle is within the active
±88° wide sector, the stage starts and issues a start signal. If this fault remains on
longer than the time defined by the delay setting, a trip signal is issued.
There are four separately adjustable stages available: Iφ>, Iφ>>, Iφ>>> and
Iφ>>>>.
222 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Stages Iφ> and Iφ>> can be configured for definite time (DT) or dependent time
characteristic. See 6.6 Dependent operate time for details on the available
dependent delays.
Stages Iφ>>> and Iφ>>>> have definite time operation delay. The relay shows a
scaleable graph of the configured delay on the local panel display.
The maximum measured secondary current is 50 x IN. This limits the scope of
dependent curves with high start settings. See 6.6 Dependent operate time for
more information.
Setting groups
Characteristics
Characteristic Value
UL1 – UL3
Mode Directional/Directional+BackUp
IDMT function:
0.025...20.0, except
P3T/EN/M/30-208A 223
Transformer protection relay 6 Protection functions
Characteristic Value
Inaccuracy:
- Starting (rated value IN= 1...5 A) ±3% of the set value or ±0.5% of the rated
value
- Angle
±2° U>5 V
±30° U = 0.1...5.0 V
- Operate time at DT function ±1% or ±25 ms
- Operate time at IDMT function ±5% or at least ±30 ms65)
65) This is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in eSetup Easergy Pro to accept the zero operate time setting for the DT function.
66) EI = Extremely Inverse, NI = Normal Inverse, VI = Very Inverse, LTI = Long Time Inverse, MI=
Moderately Inverse
Characteristic Value
UL1 – UL3
Mode Directional/Directional+BackUp
224 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Characteristic Value
Inaccuracy:
- Starting (rated value IN= 1...5 A) ±3% of the set value or ±0.5% of the rated
value
- Angle
±2° U>5 V
±30° U = 0.1...5.0 V
- Operate time at DT function ±1% or ±25 ms
67) This
is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in eSetup Easergy Pro to accept the zero operate time setting for the DT function.
P3T/EN/M/30-208A 225
Transformer protection relay 6 Protection functions
The earth fault protection is adapted for various network earth systems.
Polarization
• 3LN/LLY, 3LN/LNY and 3LN/U0: the zero sequence voltage is calculated from
the line-to-line voltages and therefore any separate zero sequence voltage
transformers are not needed. The setting values are relative to the configured
voltage transformer (VT) voltage/√3.
• 3LN+U0, 2LL+U0, 2LL+U0+LLy, 2LL+U0+LNy, LL+U0+LLy+LLz, and LN
+U0+LNy+LNz: the neutral voltage displacement voltage is measured with
voltage transformer(s) for example using a broken delta connection. The
setting values are relative to the VT0 secondary voltage defined in the
configuration.
• 3LN: the zero sequence voltage is calculated from the line-to-line voltages
and therefore any separate zero sequence voltage transformers are not
needed. The setting values are relative to the configured voltage transformer
(VT) voltage/√3.
• 3LN+U0 and 2LL+U0: the zero sequence voltage is measured with voltage
transformer(s) for example using a broken delta connection. The setting
values are relative to the VT0 secondary voltage defined in configuration.
This mode consists of two sub modes, Res and Cap. A digital signal can be
used to dynamically switch between these two submodes. When the digital
input is active (DI = 1), Cap mode is in use and when the digital input is
inactive (DI = 0), Res mode is in use. This feature can be used with
compensated networks when the Petersen coil is temporarily switched off.
◦ Res
226 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
This mode is used with networks earthed with a small resistance. In this
context, "small" means that a fault current may be more than the rated phase
currents. The trip area has a shape of a sector as drawn in Figure 132. The
base angle is usually set to zero degrees or slightly on the lagging inductive
side (negative angle).
• Undir
This mode makes the stage equal to the undirectional stage I0>. The phase
angle and U0 amplitude setting are discarded. Only the amplitude of the
selected I0 input is supervised.
Each stage can be connected to supervise any of the following inputs and signals:
Short earth faults make the protection start but does not cause a trip. A short fault
means one cycle or more. For shorter than 1 ms transient type of intermittent
earth faults in compensated networks, there is a dedicated stage I0INT> 67NI.
When starting happens often enough, such intermittent faults can be cleared
using the intermittent time setting.
When a new start happens within the set intermittent time, the operation delay
counter is not cleared between adjacent faults and finally the stage trips.
There are five separately adjustable stages: I0φ>, I0φ>>, I0φ>>>, I0φ>>>>, and
I0φ>>>>>.All the stages can be configured for definite time delay (DT) or
dependent time delay operate time.
Accomplished dependent delays are available for all stages I0φ>, I0φ>>, I0φ>>>,
I0φ>>>>, and I0φ>>>>>.
P3T/EN/M/30-208A 227
Transformer protection relay 6 Protection functions
The relay shows a scalable graph of the configured delay on the local panel
display.
The maximum measured secondary earth fault overcurrent is 10 x I0N and the
maximum measured phase current is 50 x IN. This limits the scope of dependent
curves with high start settings.
Block diagram
Figure 130 - Block diagram of the directional earth fault overcurrent stages I0φ>,
I0φ>>, I0φ>>>, I0φ>>>>, and I0φ>>>>>
I0fiisblock
A I0sinφ
I0cosφ
> & I
& J
B
C K
> t
& J
D E F G H
A. I0 G. Delay
B. Block H. Enable events
C. U0 I. Start
D. Choose I0cosφ (Res) / I0sinφ (Cap) J. Register event
E. Setting Iφ > s K. Trip
F. Setting I0 > s
+90º
CAP
Iosin φ
I0φ>
I0
RES
φ
0º
Iocos φ -U0
I0φ>
Res mode can be used with compensated networks. Cap mode is used with unearthed networks.
228 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
I0
TRIP AREA +152º +32º
I0φ> 120º
70º 0º 0º
-U0 120º -U0
70º I0φ>
-15º
I0
TRIP AREA
-85º -88º
IoDir_SectorAdj
The drawn I0 phasor is inside the trip area. The angle offset and half sector size are user’s
parameters.
Setting groups
Characteristics
Start value I0φ>> 0.01–20.00 x I0N (up to 8.00 for inputs other
than I0 Calc)
Mode Non-directional/Sector/ResCap
IDMT function:
0.025–20.0, except
P3T/EN/M/30-208A 229
Transformer protection relay 6 Protection functions
Inaccuracy:
- Starting U0 & I0 (rated value In= 1–5A) ±3% of the set value or ±0.3% of the rated
value
- Starting U0 & I0 (Peak Mode when, rated ±5% of the set value or ±2% of the rated
value I0n= 1–10A) value (Sine wave <65 Hz)
- Starting U0 & I0 (I0 Calc) ±3% of the set value or ±0.5% of the rated
value
else ±20°
Moderately Inverse
Mode Non-directional/Sector/ResCap
230 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
IDMT function:
0.05–20.0, except
Inaccuracy:
- Starting U0 & I0 (rated value In= 1 – 5A) ±3% of the set value or ±0.3% of the rated
value
- Starting U0 & I0 (Peak Mode when, rated ±5% of the set value or ±2% of the rated
value I0n= 1 – 10A) value (Sine wave <65 Hz)
- Starting U0 & I0 (I0 Calc) ±3% of the set value or ±0.5% of the rated
value
else ±20°
Moderately Inverse
The earth fault overcurrent stage (ANSI 50N/51N) and directional earth fault
overcurrent stage (ANSI 67N) have an inbuilt detection algorithm to detect a faulty
phase. This algorithm is meant to be used in radial-operated distribution
networks. The faulty phase detection can be used in solidly-earthed, impedance-
earthed or resonant-earthed networks.
Operation
The faulty phase detection starts from the earth fault stage trip. At the moment of
stage start, the phase currents measured prior to start are registered and stored
P3T/EN/M/30-208A 231
Transformer protection relay 6 Protection functions
The detected faulty phase is registered in the protection stage fault log (and also
in the event list and alarm screen). Faulty phase is also indicated by a line alarm
and line fault signals in the output matrix.
Possible detections of faulty phases are L1-N, L2-N, L3-N, L1-L2-N, L1-L3-N, L2-
L3-N, L1-L2-L3-N, and REV. If the relay protection coordination is incorrect, REV
indication is given in case of a relay sympathetic trip to a reverse fault.
232 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
This stage can be used to block other stages and to indicate possible primary
faults in the power distribution network. The ratio between the second harmonic
component and the fundamental frequency component is measured on all the
phase currents. When the ratio in any phase exceeds the setting value, the stage
gives a start signal. After a settable delay, the stage gives a trip signal.
The start and trip signals can be used for blocking the other stages.
The trip delay is irrelevant if only the start signal is used for blocking.
The trip delay of the stages to be blocked must be more than 60 ms to ensure a
proper blocking.
Block diagram
2ndHarm
Im1
Im2 MAX > & E
Im3 ts tr
& F
A
t
G
& F
B C D
A. Block E. Start
B. Setting 2nd harmonics F. Register event
C. Delay G. Trip
D. Enable events
Characteristics
Settings:
Inaccuracy:
P3T/EN/M/30-208A 233
Transformer protection relay 6 Protection functions
234 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
The ratio between the fifth harmonic component and the fundamental frequency
component is measured on all the phase currents. When the ratio in any phase
exceeds the setting value, the stage activates a start signal. After a settable delay,
the stage operates and activates a trip signal.
The trip delay of the stages to be blocked must be more than 60 ms to ensure a
proper blocking.
Characteristics
Settings:
Inaccuracy:
P3T/EN/M/30-208A 235
Transformer protection relay 6 Protection functions
Frequency protection is used for load sharing, loss of power system detection and
as a backup protection for overspeeding.
The frequency function measures the frequency from the two first voltage inputs.
At least one of these two inputs must have a voltage connected to be able to
measure the frequency. Whenever the frequency crosses the start setting of a
particular stage, this stage starts, and a start signal is issued. If the fault remains
on longer than the operating delay setting, a trip signal is issued. For situations
where no voltage is present, an adapted frequency is used.
The underfrequency stages are blocked when the biggest of the three line-to-line
voltages is below the low-voltage block limit setting. With this common setting,
LVBlk, all stages in underfrequency mode are blocked when the voltage drops
below the given limit. The idea is to avoid purposeless alarms when the voltage is
off.
When the biggest of the three line-to-line voltages has been below the block limit,
the underfrequency stages are blocked until the start setting has been reached.
There are five separately adjustable frequency stages: f><, f>><<, f<, f<<, f<<<.
The two first stages can be configured for either overfrequency or underfrequency
usage. So totally five underfrequency stages can be in use simultaneously. Using
the programmable stages even more can be implemented (chapter 6.33
Programmable stages (ANSI 99)). All the stages have definite operate time delay
(DT).
Setting groups
Characteristics
236 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Inaccuracy:
NOTE: If the relay restarts for some reason, there is no trip even if the
frequency is below the set limit during the start-up (Start and trip is blocked).
To cancel this block, frequency has to rise above the set limit.
Table 93 - Underfrequency f<, f<<, f<<< (81L)
P3T/EN/M/30-208A 237
Transformer protection relay 6 Protection functions
Inaccuracy:
238 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
The rate of change of frequency (ROCOF or df/dt) function is used for fast load
shedding, to speed up operate time in overfrequency and underfrequency
situations. For example, a centralized dedicated load shedding relay can be
omitted and replaced with distributed load shedding, if all outgoing feeders are
equipped with PowerLogic P3 relays.
Load switching and fault situations may generate change in frequency. A load
drop may increase the frequency and increasing load may decrease the
frequency, at least for a while. The frequency may also oscillate after the initial
change. After a while, the control system of any local generator may drive the
frequency back to the original value. However, in case of a heavy short-circuit
fault or if the new load exceeds the generating capacity, the average frequency
keeps on decreasing.
Figure 134 - An example of definite time df/dt operate time. At 0.6 s, which is the
delay setting, the average slope exceeds the setting 0.5 Hz/s and a trip signal is
generated.
FREQUENCY ROCOF1_v3
(Hz)
Settings:
df/dt = 0.5 Hz/s
1. t = 0.60 s
0
Hz 0.5
/s Hz tMin = 0.60 s
/s
0.7
2.0
5 Hz
H
/s TIME
z/s
(s)
START
TRIP
ROCOF implementation
The ROCOF function is sensitive to the absolute average value of the time
derivate of the measured frequency |df/dt|. Whenever the measured frequency
slope |df/dt| exceeds the setting value for 80 ms time, the ROCOF stage starts
and issues a start signal after an additional 60 ms delay. If the average |df/dt|,
since the start moment, still exceeds the setting, when the operation delay has
elapsed, a trip signal is issued. In this definite time mode the second delay
parameter "minimum delay, tMIN" must be equal to the operation delay parameter
"t".
If the frequency is stable for about 80 ms and the time t has already elapsed
without a trip, the stage resets.
One difference between the overfrequency and underfrequency and the df/dt
function is the speed. Often a df/dt function can predict an overfrequency or
P3T/EN/M/30-208A 239
Transformer protection relay 6 Protection functions
Figure 134 shows an example where the df/dt start value is 0.5 Hz/s and the
delay settings are t = 0.60 s and tMIN = 0.60 s. Equal times t = tMIN gives a definite
time delay characteristic. Although the frequency slope fluctuates, the stage does
not release but continues to calculate the average slope since the initial start. At
the defined operate time, t = 0.6 s, the average slope is 0.75 Hz/s. This exceeds
the setting, and the stage trips.
At slope settings less than 0.7 Hz/s, the fastest possible operate time is limited
according to the Figure 135.
Figure 135 - At very sensitive slope settings the fastest possible operate time is
limited.
ROCOF5_v3
Fastest possible operation time setting (s)
By setting the second delay parameter tMIN smaller than the operate time delay t,
a dependent type of operate time characteristic is achieved.
Figure 137 shows one example, where the frequency behavior is the same as in
the first figure, but the tMIN setting is 0.15 s instead of being equal to t. The
operate time depends on the measured average slope according to the following
equation:
Equation 23
s SET ⋅ t SET
t TRIP =
s
240 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
The minimum operate time is always limited by the setting parameter tMIN. In the
example, the fastest operate time, 0.15 s, is achieved when the slope is 2 Hz/s or
more. The leftmost curve in Figure 136 shows the dependent characteristics with
the same settings as in Figure 137.
ROCOF6_v3
Operation time (s)
Figure 137 - An example of dependent df/dt operate time. The time to trip will be
0.3 s, although the setting is 0.6 s, because the average slope 1 Hz/s is steeper
than the setting value 0.5 Hz/s.
FREQUENCY ROCOF3_v3
(Hz)
50.0 Settings:
df/dt = 0.5 Hz/s
t = 0.60 s
1.
0
Hz
z/
/s
s
0.7
2.0
5 Hz
Hz/
/s TIME
49.7
s
(s)
0.00 0.15 0.30 0.45 0.60
START
TRIP
Settings groups
P3T/EN/M/30-208A 241
Transformer protection relay 6 Protection functions
Characteristics
Reset ratio 1
Inaccuracy:
- Operate time(overshoot ≥ 0.2 Hz/s) ±35 ms, when area is 0.2 – 1.0 Hz/s
74) This
is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in eSetup Easergy Pro to accept the zero operate time setting for the DT function.
NOTE: ROCOF stage is using the same low voltage blocking limit as the
frequency stages.
242 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
The lockout feature, also called latching, can be programmed for outputs in the
Output matrix setting view. Any protection stage start or trip, digital input, logic
output, alarm and GOOSE signal connected to the following outputs can be
latched when required:
Figure 138 - The lockout programmed for LED A and I>> trip signals
In Figure 138, the latched signal is identified with a dot and circle in the matrix
signal line crossing.
The lockout can be released through the display or via the eSetup Easergy Pro.
See Chapter 4 Control functions.
In the General > Release latches setting view, select the Store latch state
setting to configure latched states of relay outputs, virtual outputs, binary outputs
(BO) and high-speed outputs (HSO) to be stored. If some of these outputs are
latched and in “on” state, and the device is restarted, their status is set back to
“on” after restart.
P3T/EN/M/30-208A 243
Transformer protection relay 6 Protection functions
In the LED configuration setting view, you can configure the latched states of
LEDs to be stored after a restart. In this example, storing has been configured for
LED A (green).
244 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
A D
B E
C F
G H I J K L
In the second example, if the transformer IL side is connected to open delta for
example Dy11, then the winding currents are calculated on the delta side (IL
side), see Figure 142.
A D
B E
C F
G H I J K L
P3T/EN/M/30-208A 245
Transformer protection relay 6 Protection functions
(
IL1W = IL1 − IL 2 )
3
(
IL 2W = IL 2 − IL 3 )
3
(
IL 3W = IL 3 − IL1 )
3
IW + I ' W
Ib =
2
I d = IW + I ' W
Bias current calculation is only used in protection stage ΔI>. Bias current
describes the average current flow in the transformer. Bias and differential
currents are calculated individually for each phase.
If the transformer is earthed, for example having the connection group Dyn11,
then zero current must be compensated before differential and bias current
calculation. Zero current compensation can be selected individually for the IL and
I’L side.
Table 95 describes the connection group and zero current compensation for
different connection groups. If the protection area is only generator, then the
connection group setting is always Yy0, see Table 95. Also the settings of Un and
U’n are set to be the same, for example generator nominal voltage.
246 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
YNyn0 Yy0 ON ON
YNyn6 Yy6 ON ON
P3T/EN/M/30-208A 247
Transformer protection relay 6 Protection functions
difflslohko
IL1
IL2 H I M >1 & N
IL3
I'L1
I'L2 H J M
I'L3
& O
K M
L >
>
A B C D E F G
The stage ΔI> can be configured to operate as shown in Figure 144. This dual
slope characteristic allows more differential current at higher currents before
tripping.
248 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
A
M
B
N
K
J L
0.5
C 0.1
H
D E F G
A. ID/ITN H. IBIAS
B. Minimum trip area I. Maximum setting
C. ISTART J. Slope 1
D. 0.5 x IN / IBIAS1 K. Slope 2
E. IN L. Minimum setting
F. IBIAS2 M. Default setting
G. 3 x IN N. Setting area
Table 97 - Settings
Inrush blocking
The dI> stage includes the 2nd harmonic detection for inrush blocking. The dI>>
stage does not include the inrush blocking.
The 2nd harmonic current is calculated from the differential current. The harmonic
ratio of If2/If1 is used. As the harmonic ratio exceeds the set value, the differential
stage is blocked from tripping.
The harmonic ratio is calculated separately for all three phases. The inrush
blocking uses the cross blocking principle.
When the harmonic ratio in any phase exceeds the set threshold, all phase
elements are blocked at once.
P3T/EN/M/30-208A 249
Transformer protection relay 6 Protection functions
Overflux blocking
When overfluxing occurs, the transformer core becomes partially saturated and
the resultant magnetizing current waveforms increase in magnitude and become
harmonically distorted. Such waveforms have a significant fifth harmonic content
which is used as a means of identifying the abnormal operating condition.
This blocking can be set to be either phase selective or cross blocking operation.
In the latter, all three phase differential elements are blocked, if an overflux
condition is determined in at least one phase.
The differential CTS method uses the ratio between positive and negative
sequence currents at both sides of the protected transformer to determine a CT
failure. This algorithm is inbuilt in the dI> stage. When this ratio is small (zero),
one of the following four conditions is present:
When the ratio is non-zero, one of the following two conditions is present:
The I2 to I1 ratio is calculated at both sides of the protected transformer. With this
information, we can assume that:
• If the ratio is non-zero at both sides, there is a real fault in the network and the
CTS should not operate.
• If the ratio is non-zero only at one side, there is a change of CT failure and the
CTS should operate.
250 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Another criterion for CTS is to check whether the differential system is loaded or
not. For this purpose, the positive sequence current I1 is checked at both sides of
the protected transformer.
If load current is detected only at one side, it is assumed that there is an internal
fault condition and CTS is prevented from operating, but if load current is detected
at both line ends, CTS operation is permitted.
Another criterion for CTS is to check whether the differential system is loaded or
not. For this purpose, the positive sequence current I1 is checked at both ends. If
load current is detected only at one end, it is assumed that there is an internal
fault condition and CTS is prevented from operating, but if load current is detected
at both line ends, CTS operation is permitted.
The differential CTS block mode is not recommended for two reasons:
• If there is a real fault during a CT failure, the differential protection would not
protect the line at all.
• Blocking the protection could slow down the operate time of the differential
protection because of transients in the beginning of the fault on the protected
line.
87-1 inrush enable setting analyzes the 2nd harmonics from the differential
currents. The pickup value for 2nd harmonic is 10% by default, which should be
adjusted by actual case.
Setting groups
Characteristics
Slope 1 5–100 %
Slope 2 100–200 %
P3T/EN/M/30-208A 251
Transformer protection relay 6 Protection functions
Inaccuracy:
Inaccuracy:
252 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The arc flash detection contains 8 arc stages that can be used to trip for example
the circuit breakers. Arc stages are activated with overcurrent and light signals (or
light signals alone). The allocation of different current and light signals to arc
stages is defined in arc flash detection matrices: current, light and output matrix.
The matrices are programmed via the arc flash detection menus. Available matrix
signals depend on the order code (see 13.1 Order codes).
The available signal inputs and outputs for arc flash detection depend on the
relay's hardware configuration.
The arc flash detection menus are located in the main menu under ARC. The
ARC menu can be viewed either on the front panel or by using eSetup Easergy
Pro.
Arc protection
P3T/EN/M/30-208A 253
Transformer protection relay 6 Protection functions
(Overshoot time
<35ms)
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not use the arc stage delay for primary trip. The delay and arc stage are
designed for the circuit breaker's backup system only.
Failure to follow these instructions can result in death, serious injury,
or equipment damage.
In the Arc matrix – current setting view, the available current signals (left
column) are linked to the appropriate arc stages (1–8).
254 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
In the Arc matrix – light setting view, the available arc light signals (left column)
are linked to the appropriate arc stages (1–8).
P3T/EN/M/30-208A 255
Transformer protection relay 6 Protection functions
NOTE: The arc output matrix must be configured in the Arc matrix - output
setting view instead of the Output matrix view.
In the Arc matrix – output setting view, the used Arc stages (1–8) are connected
to the required outputs. A possible latched function per output is also determined
in this view. The available outputs depend on the order code.
The matrix connection done in the Arc matrix – output view also becomes
visible in the output matrix.
When determining the activating conditions for a certain arc stage, a logical AND
operator is made between the outputs from the arc light matrix and arc current
matrix.
If an arc stage has selections in only one of the matrixes, the stage operates on a
light-only or on current-only principle.
256 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Figure 149 - Matrix correlation principle with the logical AND operator
A
& C
B
Information from the arc protection function can be transmitted and/or received
through binary inputs (BI) and outputs (BO). The rated voltage of these signals is
30 V dc when active. The input signal has to be 18–250 V dc to be activated.
P3T/EN/M/30-208A 257
Transformer protection relay 6 Protection functions
Binary inputs
The binary inputs (BI) can be used to get the light indication from another IED to
build selective arc protection systems. BI is a dry input for a 18–250 V dc signal.
The connection of BI signals is configured in the matrices of the arc flash
protection function.
Binary output
The binary outputs (BO) can be used to give the light indication signal or any
other signal or signals to another IED’s binary input to build selective arc
protection systems. BO is an internally driven (wetted) 30 Vdc signal. The
connection of BO signals is configured in the matrices of the arc flash protection
function.
Binary signal lines connected between the PowerLogic P3 Advanced devices are
supervised for short circuit or broken connection. Binary output sends a short
pulse to the line and binary input receives this pulse but filters it away. Therefore,
this test pulse is not seen as activation of binary input. If the pulse disappears, the
relay will issue an alarm of lost binary signal connection.
Binary input and output self-supervision is supported for optical BIO (C-card on
slot number 2) and for copper BIO (B-card on slot number 2).
The binary output test pulses can be enabled and disabled in the BINARY
OUTPUT menu view.
258 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
2. Under Settings, click the Install arc sensors drop-down list and select
Install.
3. Wait until the Installation state shows Ready. The communication between
the system components is created.
4. The installed sensors and units can be viewed at the bottom of the Arc
protection group view.
P3T/EN/M/30-208A 259
Transformer protection relay 6 Protection functions
7. Click the DI block value, set it to for example '-' and press Enter.
The General > Scaling setting view contains the primary and secondary values
of the CT. However, the Arc protection menu calculates the primary value only
after the I start setting value is given.
For example:
2. Click the CT primary value, set it to for example 1200 A, and press Enter.
3. Click the CT secondary value, set it to for example 5 A, and press Enter.
4. On the eSetup Easergy Pro group list, select Protection > Arc protection.
Define the current signals that are received in the arc flash detection system’s
relay. Connect currents to Arc stages in the matrix.
260 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
For example:
The arc flash fault current is measured from the incoming feeder, and the current
signal is linked to Arc stage 1 in the current matrix.
2. In the matrix, select the connection point of Arc stage 1 and I>int.
Define what light sensor signals are received in the detection system. Connect
the light signals to the arc stages in the matrix.
For example:
P3T/EN/M/30-208A 261
Transformer protection relay 6 Protection functions
Define the trip relays that the current and light signals affect.
For example:
2. In the matrix, select the connection point of Arc stage 1 and T1.
Arc output matrix includes only outputs which are directly controlled by FPGA.
Define which arc events are written to the event list in this application.
262 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
For example:
The operation of the arc detection depends on the setting value of the I> int and
I01> int current limits.
The arc current limits cannot be set, unless the relay is provided with the optional
arc protection card.
P3T/EN/M/30-208A 263
Transformer protection relay 6 Protection functions
Start current:
Operate time
- Light only ≤9 ms
- Light only ≤7 ms
- Light only ≤2 ms
Inaccuracy:
264 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
For special applications, you can build your own protection stages by selecting
the supervised signal and the comparison mode.
f Frequency
P Active power
P3T/EN/M/30-208A 265
Transformer protection relay 6 Protection functions
Q Reactive power
S Apparent power
266 P3T/EN/M/30-208A
6 Protection functions Transformer protection relay
Setting groups
P3T/EN/M/30-208A 267
Transformer protection relay 7 Supporting functions
7 Supporting functions
Table 107 - Example of Pgr1 stage trip on event and its visibility in local panel and
communication protocols
Events are the major data for a SCADA system. SCADA systems are reading
events using any of the available communication protocols. The Event log can
also be scanned using the front panel or eSetup Easergy Pro. With eSetup
Easergy Pro, the events can be stored to a file especially if the relay is not
connected to any SCADA system.
Only the latest event can be read when using communication protocols or eSetup
Easergy Pro. Every reading increments the internal read pointer to the event
buffer. (In case of communication interruptions, the latest event can be reread any
number of times using another parameter.) On the local panel, scanning the event
buffer back and forth is possible.
Event enabling/masking
You can make this modification in the Local panel conf setting view.
An indication screen (popup screen) can also be enabled in the same menu in
eSetup Easergy Pro. The oldest event is overwritten when a new event occurs.
The shown resolution of a time stamp is one millisecond, but the actual resolution
depends on the particular function creating the event. For example, most
protection stages create events with 5 ms, 10 ms or 20 ms resolution. The
268 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
absolute accuracy of all time stamps depends on the relay's time synchronization.
See 7.4 System clock and synchronization for system clock synchronizing.
The normal procedure is to poll events from the relay all the time. If this is not
done, the event buffer could reach its limits. In that case, the oldest event is
deleted and the newest displayed with OVF (overflow) code on the front panel.
Clear
P3T/EN/M/30-208A 269
Transformer protection relay 7 Supporting functions
yyyy-mm-dd Date
hh:mm:ss.nnn Time
The available recording channels depend on the voltage measurement mode, too.
If a channel is added for recording and the added signal is not available because
of the used settings, the signal is automatically rejected from the recording
channel list.
The recording can be triggered by any start or trip signal from any protection
stage, by a digital input, logic output or GOOSE signals. The triggering signal is
selected in the output matrix (vertical signal DR). The recording can also be
triggered manually. All recordings are time-stamped.
Reading recordings
The recordings can be uploaded with eSetup Easergy Pro program. The
recording is in COMTRADE format. This also means that other programs can be
used to view and analyse the recordings made by the relay.
Number of channels
270 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Parameters
32/cycle Waveform
16/cycle Waveform
8/cycle Waveform
1/200ms Average
1/1s Average
1/5s Average
1/10s Average
1/15s Average
1/30s Average
P3T/EN/M/30-208A 271
Transformer protection relay 7 Supporting functions
1/1min Average
- Not active
Trig Recording
272 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
f Frequency X X
CosPhi cosφ X
TanPhi tanφ X
P3T/EN/M/30-208A 273
Transformer protection relay 7 Supporting functions
NOTE: The selection of signals depends on the relay type, the used voltage
connection and the scaling mode.
NOTE: For waveform, IoCalc (Primary or Pu) can be added only if IL1, IL2
and IL3 are already on the DR channel list. Uo (Primary or Pu) can be added
only if UL1, UL2 and UL3 are already on the DR channel list or Uo is
measured directly from samples (the voltage measurement mode contains
Uo).
Characteristics
Sample rate: -
1, 5, 10, 15, 30 s
1 min
Recording time (one record) 0.1 s–12 000 min (According recorder
setting)
The recording time and the number of records depend on the time setting and the
number of selected channels.
274 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
1. To select the channels and sample rate for the disturbance recorder:
c. Click the Sample rate drop-down list, and select the desired rate.
3. To write the setting to the device, on the eSetup Easergy Pro toolbar, select
Write settings > Write all settings.
NOTE: To save the relay's configuration information for later use, also
save the eSetup Easergy Pro setting file on the PC. Use WaweWin or
another customer preferred tool to analyze disturbance recorder file.
a. On the eSetup Easergy Pro toolbar, click the Save icon. The Save a file
window opens.
b. Browse to the folder where you want to save the file. Type a descriptive
file name, and click Save.
P3T/EN/M/30-208A 275
Transformer protection relay 7 Supporting functions
A situation is regarded as cold load when all the three phase currents have been
below a given idle value and then at least one of the currents exceeds a given
start level within 80 ms. In such a case, the cold load detection signal is activated
for the time set as Maximum time or until the measured signal returns below the
value set as Pickup current. This signal is available for the output matrix and
blocking matrix. Using virtual outputs of the output matrix setting group control is
possible.
Right after closing a circuit breaker, a given amount of overload can be allowed
for a given limited time to take care of concurrent thermostat-controlled loads. The
cold load start function does this, for example, by selecting a more coarse setting
group for overcurrent stages. It is also possible to use the cold load detection
signal to block any set of protection stages for a given time.
Magnetizing inrush detection is quite similar to the cold load detection but it also
includes a condition for second harmonic content of the currents. When all phase
currents have been below a given idle value and then at least one of them
exceeds a given start level within 80 ms and the second harmonic ratio to
fundamental frequency, If2/If1, of at least one phase exceeds the given setting, the
inrush detection signal is activated. This signal is available for the output matrix
and blocking matrix. Using virtual outputs of the output matrix setting group
control is possible.
By setting the second harmonic start parameter for If2/If1 to zero, the inrush signal
will behave equally with the cold load start signal.
The inrush current of transformers usually exceeds the start setting of sensitive
overcurrent stages and contains a lot of even harmonics. Right after closing a
circuit breaker, the start and tripping of sensitive overcurrent stages can be
avoided by selecting a more coarse setting group for the appropriate overcurrent
stage with an inrush detect signal. It is also possible to use the detection signal to
block any set of protection stages for a given time.
276 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
A C D
Pick-up
Idle
Cold load
A. No activation because the current has not been under the set IDLE current.
B. Current dropped under the IDLE current level but now it stays between the IDLE current and the
start current for over 80 ms.
C. No activation because the phase two lasted longer than 80 ms.
D. The cold load activation will last until maximum time setting has elapsed or current drops below
the cold load pickup setting level, which ever takes place first.
Characteristics
Inrush settings:
P3T/EN/M/30-208A 277
Transformer protection relay 7 Supporting functions
The system clock should be externally synchronised to get comparable event time
stamps for all the relays in the system.
The synchronizing is based on the difference of the internal time and the
synchronizing message or pulse. This deviation is filtered and the internal time is
corrected softly towards a zero deviation.
Time zone offset (or bias) can be provided to adjust the relay's local time. The
offset can be set as a Positive (+) or Negative (-) value within a range of -15.00 to
+15.00 hours and a resolution of 0.01/h. Basically, resolution by a quarter of an
hour is enough.
Daylight time standards vary widely throughout the world. Traditional daylight/
summer time is configured as one (1) hour positive bias. The new US/Canada
DST standard, adopted in the spring of 2007 is one (1) hour positive bias, starting
at 2:00am on the second Sunday in March, and ending at 2:00am on the first
Sunday in November. In the European Union, daylight change times are defined
relative to the UTC time of day instead of local time of day (as in U.S.) European
customers, carefully check the local country rules for DST.
The daylight saving rules are by default UTC +2:00 (24-hour clock):
278 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
During tens of hours of synchronizing, the relay learns its average deviation and
starts to make small corrections by itself. The target is that when the next
synchronizing message is received, the deviation is already near zero.
Parameters "AAIntv" and "AvDrft" show the adapted correction time interval of this
±1 ms auto-adjust function.
If any external synchronizing source is not available and the system clock has a
known steady drift, it is possible to roughly correct the clock deviation by editing
the parameters "AAIntv" and "AvDrft". The following equation can be used if the
previous "AAIntv" value has been zero.
604.8
AAIntv =
DriftInOneWeek
If the auto-adjust interval "AAIntv" has not been zero, but further trimming is still
needed, the following equation can be used to calculate a new auto-adjust
interval.
1
AAIntvNEW =
1 DriftInOneWeek
+
AAIntvPREVIOUS 604.8
The term DriftInOneWeek/604.8 may be replaced with the relative drift multiplied
by 1000 if some other period than one week has been used. For example, if the
drift has been 37 seconds in 14 days, the relative drift is 37*1000/(14*24*3600) =
0.0306 ms/s.
P3T/EN/M/30-208A 279
Transformer protection relay 7 Supporting functions
Example 1
If there has been no external sync and the relay's clock is leading sixty-one
seconds a week and the parameter AAIntv has been zero, the parameters are set
as
AvDrft = Lead
604.8
AAIntv = = 9.9 s
61
With these parameter values, the system clock corrects itself with –1 ms every
9.9 seconds which equals –61.091 s/week.
Example 2
If there is no external sync and the relay's clock has been lagging five seconds in
nine days and the AAIntv has been 9.9 s, leading, then the parameters are set as
1
AAIntv NEW = = 10.6
1 5000
−
9.9 9 ⋅ 24 ⋅ 3600
AvDrft = Lead
When the internal time is roughly correct – the deviation is less than four seconds
– no synchronizing or auto-adjust turns the clock backwards. Instead, if the clock
is leading, it is softly slowed down to maintain causality.
Table 113 - System clock parameters
y-d-m Year-Month-Day
d.m.y Day.Month.Year
m/d/y Month/Day/Year
80)
SyncDI Possible values The digital input
depends on the used for clock
types of I/O synchronization.
cards
Minute pulse
input
280 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Note: This is a
decimal number.
For example for
state of Nepal
the time zone
5:45 is given as
5.75
SySrc Clock
synchronization
source
Internal No sync
recognized
since 200s
DI Digital input
P3T/EN/M/30-208A 281
Transformer protection relay 7 Supporting functions
Synchronization with DI
The clock can be synchronized by reading minute pulses from digital inputs,
virtual inputs or virtual outputs. The sync source is selected with the SyncDI
setting. When a rising edge is detected from the selected input, the system clock
is adjusted to the nearest minute. The length of the digital input pulse should be at
least 50 ms. The delay of the selected digital input should be set to zero.
Synchronization correction
If the sync source has a known offset delay, it can be compensated with the
SyOS setting. This is useful for compensating hardware delays or transfer delays
of communication protocols. A positive value compensates a lagging external
sync and communication delays. A negative value compensates any leading
offset of the external synch source.
282 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Sync source
When the relay receives new sync message, the sync source display is updated.
If no new sync messages are received within the next 1.5 minutes, the relay
switches over to internal sync mode.
IRIG standard time formats B003 and B004 are supported with a dedicated
communication option (See 13.2 Accessories).
IRIG-B input clock signal voltage level is TLL. The input clock signal originated in
the GPS receiver must be taken to multiple relays trough an IRIG-B distribution
module. This module acts as a centralized unit for a point-to-multiple point
connection.
NOTE: Daisy chain connection of IRIG-B signal inputs in multiple relays must
be avoided.
B
C
P3U P3x3x
The recommended cable must be shielded and either of coaxial or twisted pair
type. Its length must not exceed 10 meters.
Deviation
The time deviation means how much the system clock time differs from the sync
source time. The time deviation is calculated after receiving a new sync message.
The filtered deviation means how much the system clock was really adjusted.
Filtering takes care of small deviation in sync messages.
P3T/EN/M/30-208A 283
Transformer protection relay 7 Supporting functions
Auto-lag/lead
The relay synchronizes to the sync source, meaning that it starts automatically
leading or lagging to stay in perfect sync with the master. The learning process
takes a few days.
PowerLogic P3T32 provides separate monitoring logs for sags and swells. The
voltage log is triggered if any voltage input either goes under the sag limit (U<) or
exceeds the swell limit (U>). There are four registers for both sags and swells in
the fault log. Each register contains start time, phase information, duration and
the minimum, average and maximum voltage values of each sag and swell event.
Furthermore, it contains the total number of sags and swells counters as well as
the total number of timers for sags and swells.
The voltage power quality functions are located under the submenu “U”.
284 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Count - Cumulative
swell counter
Total - Cumulative
swell time
counter
Min1 % UN Minimum
voltage value
during the sag/
swell in the
input 1
Min2 % UN Minimum
voltage value
during the sag/
swell in the
input 2
Min3 % UN Minimum
voltage value
during the sag/
swell in the
input 3
P3T/EN/M/30-208A 285
Transformer protection relay 7 Supporting functions
Max1 % UN Maximum
voltage value
during the sag/
swell in the
input 1
Max2 % UN Maximum
voltage value
during the sag/
swell in the
input 2
Max3 % UN Maximum
voltage value
during the sag/
swell in the
input 3
Characteristics
Reset ration:
- Sag 1.03
- Swell 0.97
286 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Inaccuracy:
If one of the line-to-line voltages is below sag limit and above block limit but
another line-to-line voltage drops below block limit, blocking is disabled.
The relay includes a simple function to detect voltage interruptions. The function
calculates the number of voltage interruptions and the total time of the voltage-off
time within a given calendar period. The period is based on the relay's real-time
clock. The available periods are:
• 8 hours, 00:00–08:00, 08:00–16:00, 16:00–24:00
• one day, 00:00–24:00
• one week, Monday 00:00 – Sunday 24:00
• one month, the first day 00:00 – the last day 24:00
• one year, 1st January 00:00 – 31st December 24:00
After each period, the number of interruptions and the total interruption time are
stored as previous values. The interruption counter and the total time are cleared
for a new period. Previous values are overwritten.
Voltage interruption is based on the value of the positive sequence voltage U1 and
a limit value you can define. Whenever the measured U1 goes below the limit, the
interruption counter is increased, and the total time counter starts increasing.
If the voltage has been significantly over the limit U1< and then there is a small
and short under-swing, it is not recognized (Figure 166).
U 1<
10 20 30 40 50 60 70 80 90 B
On the other hand, if the limit U1< is high and the voltage has been near this limit,
and then there is a short but very deep dip, it is not recognized (Figure 167).
P3T/EN/M/30-208A 287
Transformer protection relay 7 Supporting functions
A
U 1<
10 20 30 40 50 60 70 80 90
B
Month
Date - - Date
Time - - Time
Table 118 - Measured and recorded values of voltage sag measurement function
U1 % Measured
positive
sequence
voltage
288 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Prev - Number of
voltage sags
during the
previous
observation
period
Characteristics
Inaccuracy:
The relay supervises the current transformers (CTs) and the external wiring
between the relay terminals and the CTs. This is a safety function as well, since
an open secondary of a CT causes dangerous voltages.
P3T/EN/M/30-208A 289
Transformer protection relay 7 Supporting functions
The CT supervision function measures phase currents. If one of the three phase
currents drops below the IMIN< setting while another phase current exceeds the
IMAX> setting, the function issues an alarm after the operation delay has elapsed.
ILmin A Minimum of
phase currents
290 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Time - Time of CT
supervision
alarm
Characteristics
Inaccuracy: -
The relay supervises the voltage transformers (VTs) and VT wiring between the
relay terminals and the VTs. If there is a fuse in the voltage transformer circuitry,
the blown fuse prevents or distorts the voltage measurement. Therefore, an alarm
should be issued. Furthermore, in some applications, protection functions using
voltage signals should be blocked to avoid false tripping.
P3T/EN/M/30-208A 291
Transformer protection relay 7 Supporting functions
When the CB position is selected, the supervision process monitors U1 and I1 and
CB position. If CB is closed and I1 exceed setting value and U1 is lower than 1%
of nominal voltage, VT fuse fail alarm is issued after operational delay has
elapsed. When the CB position is not selected, the supervision process monitors
only U1 and I1 value. If U1 is lower than 1% of nominal voltage and I1 exceeds
setting value, VT fuse fail is issued after operational delay has elapsed.
I2 %IN Measured
negative
sequence
current
U1 %Un Measured
positive
sequence
voltage
I1 %In Measured
positive
sequence
current
292 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Time - Time of VT
supervision
alarm
U2 %UN Recorded
negative
sequence
voltage
I2 %IN Recorded
negative
sequence
current
U1 %Un Recorded
positive
sequence
voltage
I1 %In Recorded
positive
sequence
current
Characteristics
Inaccuracy: -
P3T/EN/M/30-208A 293
Transformer protection relay 7 Supporting functions
U2> l2<
U2 >
AND
l2 < >1 VT fuse fail
U1 <
l1 > AND
CB Closed
U1 < l1 >
Circuit breaker (CB) wear is a function that monitors CB wear by calculating how
much wear the CB can sustain. It raises an alarm about the need for CB
maintenance before the condition of the CB becomes critical.
This function records the peak symmetrical current84) from each phase85), and
uses that magnitude as the breaking current for that phase to estimate the
amount of wear on the CB. The function then calculates the estimated number of
cycles or trips remaining before the CB needs to be replaced or serviced.
84) The used peak current is the magnitude of the fundamental frequency component. This
magnitude does not include a possible DC component.
85) The current is sampled every 10 milliseconds, starting from the moment the monitored trip relay
is asserted and ending when the current of every phase has decreased below one quarter of
the phase’s breaking current or after 500 milliseconds have elapsed, whichever happens first.
294 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
100000
10000
A 1000
100
50
20
10
100 200 500 1000 10000 100000
Up to eight points can be selected from the diagram and entered to the device.
Each point specifies a breaking current and the associated maximum number of
permitted operations. The device assumes there is a straight line between each
two consecutive points in the log-log diagram (that is, uses logarithmic
interpolation between the points), and thus forms an approximation of the
permissible cycle diagram. It should be possible to accurately describe most
permissible cycle diagrams in this way.
The values in the example match the diagram in Figure 169.
4 100 1
5 100 1
6 100 1
7 100 1
8 100 1
Alarm points
Two alarm points can be configured to notify about the approaching need for CB
maintenance.
P3T/EN/M/30-208A 295
Transformer protection relay 7 Supporting functions
The table in the Operations left setting view shows the number of operation
cycles left before the alarm points are reached. The number of remaining cycles
is tracked for each phase separately, and the alarm is raised when any phase
runs out of cycles.
The first alarm point can be set, for example, to the CB’s nominal current and the
second alarm point to a typical fault current.
When an alarm is raised, a signal is asserted in the output matrix. Also, an event
is created depending on the settings given in the Event enabling setting view.
Logarithmic interpolation
The permitted number of operations for the currents between the defined points is
logarithmically interpolated:
Equation 28
a
C=
In
C = permitted operations
I = interrupted current
Equation 29
a = C k I k2
86) Each cycle causes mechanical wear on the CB. In addition, large enough currents create arcs
inside the CB, which causes erosion of the electrical contacts for each phase. The larger the
current, the greater the erosion, and thus the greater the wear on the CB. A worn CB has fewer
cycles left at any breaking current.
296 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Equation 30
Ck
ln
C k +1
n=
I
ln k +1
Ik
k=2
Ck = 10000
Ck+1 = 80
Ik+1 = 31 kA
Ik = 1.25 kA
Equation 31
10000
ln
n= 80 = 1.5038
31000
ln
1250
Equation 32
Using Equation 28, the device gets the number of permitted operations for current
6 kA.
P3T/EN/M/30-208A 297
Transformer protection relay 7 Supporting functions
Equation 33
454 ⋅ 10 6
C= = 945
60001.5038
Alarm 2 is set to 6 kA. The CB failure protection supervises trip relay T1, and a
trip signal of an overcurrent stage detecting a two-phase fault is connected to this
trip relay T1. The interrupted phase currents are 12.5 kA, 12.5 kA and 1.5 kA. By
what number are Alarm2 counters decremented?
Using Equation 28 and values n and a from the previous example, the device gets
the number of permitted operations at 10 kA.
Equation 34
454 ⋅ 10 6
C10 kA = = 313
125001.5038
Equation 35
C AlarmMax
∆=
C
945
∆A = ∆B = =3
313
Thus, Alarm2 counters for phases L1 and L2 are decremented by 3. In phase L1,
the current is less than the alarm limit current 6 kA. For such currents, the
decrement is 1.
Δ L3 = 1
298 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
CBWEAR STATUS
Operations left
for
Al1L1
- Alarm 1, phase
Al1L2
L1
Al1L3
- Alarm 1, phase
Al2L1 L2
Al2L2 - Alarm 1, phase
Al2L3 L3
- Alarm 2, phase
L1
- Alarm 2, phase
L2
- Alarm 2, phase
L3
Latest trip
Broken current
of phase L3
CBWEAR SET
Alarm1
Alarm2
CBWEAR SET2
P3T/EN/M/30-208A 299
Transformer protection relay 7 Supporting functions
Circuit breaker (CB) condition monitoring monitors the CB wear with the help of
the cumulative breaking current. It raises an alarm about the need for CB
maintenance before the CB’s condition becomes critical. This function has two
stages.
The approach to calculating the CB condition is different from the approach used
by the CB wear function described in 7.9 Circuit breaker wear. CB condition
monitoring also provides some additional features for integrating the device with
other Schneider Electric products. These functions are based on data analytics
for integration into EcoStruxure Asset Advisor cloud-based offers.
Each bin also has three counters (one for each phase). Each counter tracks the
number of times the CB has opened and something was added to the
corresponding sum on that bin (see Figure 171).
300 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
If all cumulative breaking currents for the bins are zero when the value of the CT
primary parameter is changed in the Scaling setting view, the breaking current
ranges for the bins are automatically set to their default values relative to the new
CT primary value. The lower limit for the first bin is set to zero and the upper limit
to two times the CT primary value. There is no upper limit for the fifth bin.
The cumulative breaking currents are tracked with greater precision than what is
visible on the setting tool, that is, there are hidden decimals stored for each sum.
A non-zero sum that is too small to be visible in the setting tool may prevent the
bin ranges from getting their default values when the CT primary value is
changed.
The cumulative breaking currents can be read over the Modbus protocol as
floating-point values (IEEE 754, binary32). These values are represented in two
consecutive holding registers, so that the register in the lower address contains
the MSB 16 bits. To change the sum by writing a floating-point value, the MSB 16
bits must be written first.
The cumulative breaking currents can be cleared by writing value zero to them.
This function includes a counter that tracks the number of times the monitored CB
is opened, and a second counter that tracks how many of those operations were
caused by a protection stage trip. This requires that one of the controllable
objects (see 5.6 Controllable objects) has been configured to represent the CB
and this object has been selected in the Monitored object parameter.
Internally, each object has its own open counter and the counter for the monitored
object is shown under Opening counts, Trip counts and Rack-out counter (see
Figure 172). These open counters are incremented even when this function has
been disabled. In contrast, the trip counter is incremented when the monitored
object is opened by a protection stage trip and this function is enabled. Thus, if
you change the monitored object, the open counter value switches to the counter
of the new object, but the trip counter continues from its current value. Both
counters' values can be changed.
P3T/EN/M/30-208A 301
Transformer protection relay 7 Supporting functions
The number of times the monitored CB is racked out from the bay is tracked by its
own counter. This requires that a digital input is set up to indicate when the CB is
racked out88). This digital input is selected under Rack-out counter. Each digital
input has its own counter. The same counter is also found in the Digital inputs
setting view.
This function records the completion times for the eight previous open, close, and
charge operations of the monitored CB. Each operate time is recorded with a
timestamp indicating when the operation was completed. This function also keeps
a cumulative moving average of 20 previous operate times for each of the three
categories.
There are two methods to monitor the CB open/close time. The default selection
is CB DI chg which calculates the delta time of close and open statuses from the
auxiliary contacts and measures the time it takes the main contacts to open/close.
The alternative method, CMD to DO, measures the time from the request to
operate to the auxiliary contact feedback. This method measures the complete
time it takes from a stationary breaker to the auxiliary contacts changing state.
You should select which relay is used to monitor the CB open and which relay is
used to monitor the CB close. The calculation starts from the output control to DI
status change. Normally, the operating time should be within the max time. If it
exceeds the max time, it will reset automatically, and no new item will be updated
in the log.
88) When the CB r is in the bay, this digital input has logical value false, and when the CB is racked
out, this input has logical value true.
302 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
The completion times are recorded even if this function has been disabled,
provided that the monitored object has been selected.
All three logs of completion times can be cleared by the Clear logs command.
The charging times are recorded in seconds whereas the opening and closing
times are recorded in milliseconds.
The operate times can be read over the Modbus protocol as floating-point values
(IEEE 754, binary32), so that a range of holding registers is used to represent all
operate times of a given category, from the newest to oldest. Each operate time is
represented in two consecutive holding registers, so that the register in the lower
address contains the MSB 16 bits.
If an opening time or a closing time is greater than 300 milliseconds, this value is
given as NaN (not-a-number) when it is read as a floating-point value. Similarly,
charging times greater than 60 seconds are given as NaN.
The relay can be configured to send a pulse whenever a certain amount of energy
has been imported or exported. The principle is presented in Figure 176. Each
time the energy level reaches the pulse size, a digital output is activated and the
relay is active as long as defined by a pulse duration setting.
P3T/EN/M/30-208A 303
Transformer protection relay 7 Supporting functions
Configurable:
100 ms − 5 000 ms
Configurable:
10 – 10 000 kWh
kvarh
The relay has four energy pulse outputs. The output channels are:
Each channel can be connected to any combination of the digital outputs using
the output matrix. The parameters for the energy pulses can be found in the
ENERGY menu "E" under the submenus E-PULSE SIZES and E-PULSE
DURATION.
304 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Scaling examples
This is not a practical scaling example unless a digital output lifetime of about
six years is accepted.
P3T/EN/M/30-208A 305
Transformer protection relay 7 Supporting functions
Figure 177 - Application example of wiring the energy pulse outputs to a PLC
having common plus and using an external wetting voltage
+
Easergy P3 PLC
Figure 178 - Application example of wiring the energy pulse outputs to a PLC
having common minus and using an external wetting voltage
Easergy P3 +
PLC
Active exported
energy pulses +E
Pulse counter input 1
Reactive exported
energy pulses +Eq
Pulse counter input 2
Active imported
energy pulses -E
Pulse counter input 3
Reactive imported
energy pulses -Eq
Pulse counter input 4
306 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Figure 179 - Application example of wiring the energy pulse outputs to a PLC
having common minus and an internal wetting voltage.
Easergy P3 PLC
Reactive exported
energy pulses +Eq Pulse counter input 2
Active imported
Pulse counter input 3
energy pulses -E
Reactive imported
energy pulses -Eq Pulse counter input 4
Independently of the power direction setting, the energy counter has an additional
setting for sign conversion. Use the Energy sign convention setting to define
positive and negative direction for export and import energy.
• The selection “Export – Positive power” results in positive power to
accumulate the export energy counter, while negative power accumulates the
import energy counter. Similarly, positive reactive power accumulates the
exported reactive energy counter, while negative reactive accumulates the
imported reactive power counter.
• The selection “Export – Negative power” results in negative power to
accumulate the export energy counter, while positive power accumulates the
import energy counter. Similarly, negative power accumulates the exported
reactive power counter, while positive reactive power accumulates the
imported reactive power counter.
Changing the energy sign conversion must reset the energy counter.
When the apparent energy counter reaches 1 TVAh, the active and reactive
energy counters reset to zero. To monitor the energy consumption on a feeder, a
P3T/EN/M/30-208A 307
Transformer protection relay 7 Supporting functions
dedicated energy counter can be set up over a defined time window of between
10 minutes and 24 hours.
Parameter Description
The running hour counter is typically used to monitor the service time of the motor
or appropriate feeder. This function calculates the total active time of the selected
digital input, virtual I/O function button, GOOSE signal, POC signal or output
matrix output signal. The resolution is ten seconds and the data is stored in the
non-volatile memory.
Parameters
308 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
7.14 Timers
Description
The PowerLogic P3 protection platform includes four settable timers that can be
used together with the user's programmable logic or to control setting groups and
other applications that require actions based on calendar time. Each timer has its
own settings. The selected on-time and off-time is set, after which the activation of
the timer can be set to be as daily or according to the day of the week (See the
setting parameters for details). The timer outputs are available for logic functions
and for the block and output matrix.
(not in use)
Daily
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
MTWTF
MTWTFS
SatSun
You can force any timer, which is in use, on or off. The forcing is done by writing a
new status value. No forcing flag is needed as in forcing for example the digital
outputs.
The forced time is valid until the next forcing or until the next reversing timed act
from the timer itself.
The status of each timer is stored in the non-volatile memory when the auxiliary
power is switched off. At startup, the status of each timer is recovered.
P3T/EN/M/30-208A 309
Transformer protection relay 7 Supporting functions
- Not in use
0 Output is inactive
1 Output is active
310 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
This function collects faults, fault types and registered fault currents of all enabled
overcurrent stages and shows them in the event log.
LINE ALARM
1 = Start is on
OCs - Combined
overcurrent start
0
status.
1
AlrL1 = AlrL2 =
AlrL3 = 0
AlrL1 = 1 or
AlrL2 = 1 or
AlrL3 = 1
P3T/EN/M/30-208A 311
Transformer protection relay 7 Supporting functions
Events are
disabled
Events are
disabled
Events are
enabled
Events are
disabled
Events are
enabled
Events are
disabled
312 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Several events
are enabled 90)
Several events
of an increasing
fault is
disabled 91)
corresponding on-event.
LINE FAULT
1 = Fault is on
OCt - Combined
overcurrent trip
0
status.
1
FltL1 = FltL2 =
FltL3 = 0
FltL1 = 1 or
FltL2 = 1 or
FltL3 = 1
P3T/EN/M/30-208A 313
Transformer protection relay 7 Supporting functions
Events are
disabled
Events are
disabled
Events are
enabled
Events are
disabled
Events are
enabled
Events are
disabled
314 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Several events
are enabled 92)
Several events
of an increasing
fault is
disabled 93)
corresponding on-event.
The fault that can be seen in the Figure 181 was 3.18 times to nominal and it
increased in to a two phase short circuit L1-L2. All signals those are stated as “1”
are also activated in the output matrix. After the fault disappears, the activated
signals release.
The combined overcurrent status can be found from eSetup Easergy Pro through
Protection > Protection stage status 2.
P3T/EN/M/30-208A 315
Transformer protection relay 7 Supporting functions
Trip circuit supervision is used to ensure that the wiring from the protective relay
to a circuit breaker (CB) is in order. Even though the trip circuit is unused most of
the time, keeping it in order is important so that the CB can be tripped whenever
the relay detects a fault in the network.
The digital inputs of the relay can be used for trip circuit monitoring.
Also the closing circuit can be supervised using the same principle.
NOTE: Apply trip circuit supervision using a digital input and its programmable
time delay.
NOTE: Change the Digital inputs’ Mode to AC in case trip circuit supervision
is applied to the ac control voltage.
The benefits of this scheme are that only one digital inputs is needed and no extra
wiring from the relay to the circuit breaker (CB) is needed. Also, supervising a 24
Vdc trip circuit is possible.
The drawback is that an external resistor is needed to supervise the trip circuit on
both CB positions. If supervising during the closed position only is enough, the
resistor is not needed.
• The digital input is connected parallel to the trip contacts (see Figure 182).
• The digital input is configured as normal closed (NC).
• The digital input delay is configured to be longer than the maximum fault time
to inhibit any superfluous trip circuit fault alarm when the trip contact is closed.
• The digital input is connected to a relay in the output matrix giving out any trip
circuit alarm.
• The trip relay must be configured as non-latched. Otherwise, a superfluous
trip circuit fault alarm follows after the trip contact operates, and the relay
remains closed because of latching.
• By utilizing an auxiliary contact of the CB for the external resistor, also the
auxiliary contact in the trip circuit can be supervised.
316 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Figure 182 - Trip circuit supervision using a single digital input and an external
resistor R
A
comm
C
D
0.5 s
G F
52b 52a
-VAUX
H
CB
R
-VAUX
NOTE: The need for the external resistor R depends on the application and
circuit breaker manufacturer's specifications.
P3T/EN/M/30-208A 317
Transformer protection relay 7 Supporting functions
Figure 183 - Alternative connection without using circuit breaker 52b auxiliary
contacts
A
comm
C
D
0.5 s
G F
52a
-VAUX
R
H
CB
-VAUX
Trip circuit supervision using a single digital input and an external resistor R. The
circuit breaker is in the closed position. The supervised circuitry in this CB
position is double-lined. The digital input is in active state when the trip circuit is
complete.
Alternative connection without using circuit breaker 52b auxiliary contacts. This is
applicable for any digital inputs.
318 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Figure 184 - Trip circuit supervision using a single digital input when the circuit
breaker is in open position
C
D
0.5 s
G F
52b 52a
-VAUX
H
CB
R
-VAUX
P3T/EN/M/30-208A 319
Transformer protection relay 7 Supporting functions
Figure 185 - Alternative connection without using circuit breaker 52b auxiliary
contacts. Trip circuit supervision using a single digital input, when the circuit
breaker is in open position
C
D
0.5 s
G F
52a
-VAUX
R
H
CB
-VAUX
Figure 186 - Example of digital input DI7 configuration for trip circuit supervision
with one digital input
320 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Figure 187 - Example of output matrix configuration for trip circuit supervision with
one digital input
IDI = 3 mA, Typical current needed to activate the digital input including a 1 mA
safety margin.
PCOIL = 50 W, Rated power of the open coil of the circuit breaker. If this value is
not known, 0 Ω can be used for the RCOIL.
UMIN = UAUX - 20 % = 88 V
Equation 36
U MIN − U DI − I DI ⋅ RCoil
R=
I DI
The power rating for the external resistor is estimated using Equation 37 and
Equation 38.
The Equation 37 is for the CB open situation including a 100 % safety margin to
limit the maximum temperature of the resistor:
Equation 37
P = 2 ⋅ I DI
2
⋅R
P3T/EN/M/30-208A 321
Transformer protection relay 7 Supporting functions
When the trip contacts are still closed and the CB is already open, the resistor
has to withstand much higher power (Equation 38) for this short time:
Equation 38
2
U MAX
P=
R
A 0.5 W resistor is enough for this short time peak power, too. However, if the trip
relay is closed for longer than a few seconds, a 1 W resistor should be used.
The drawbacks are that two digital inputs (DIs) and two extra wires from the relay
to the CB compartment are needed. Additionally, the minimum allowed auxiliary
voltage is 48 V dc which is more than twice the threshold voltage of the digital
input because when the CB is in open position, the two digital inputs are in series.
When two DIs are connected in a series, the switching threshold value used with
one DI is too high. Therefore, a lower value must be selected: 24 V if the nominal
operation voltage for DI inputs is 110 V or 110 V if the nominal operation voltage
is 220 V.
• The first digital input is connected parallel to the auxiliary contact of the circuit
breaker's open coil.
• Another auxiliary contact is connected in series with the circuitry of the first
digital input. This makes it possible to supervise also the auxiliary contact in
the trip circuit.
• The second digital input is connected in parallel with the trip contacts.
• Both inputs are configured as normal closed (NC).
• The user’s programmable logic is used to combine the digital input signals
with an AND port. The delay is configured to be longer than the maximum
fault time to inhibit any superfluous trip circuit fault alarm when the trip contact
is closed.
• The output from the logic is connected to a relay in the output matrix giving
out any trip circuit alarm.
322 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Figure 188 - Trip circuit supervision with two digital inputs and closed CB
A
comm
C
D
& 0.5 s
G F
52b 52a
-VAUX
H
CB
-VAUX
P3T/EN/M/30-208A 323
Transformer protection relay 7 Supporting functions
Figure 189 - Trip circuit supervision with two digital inputs and CB in open position
A
comm
C
D
& 0.5 s
G F
52b 52a
-VAUX
H
CB
-VAUX
Figure 190 - An example of digital input configuration for trip circuit supervision
with two digital inputs DI1 and DI2
324 P3T/EN/M/30-208A
7 Supporting functions Transformer protection relay
Figure 191 - An example of logic configuration for trip circuit supervision with two
digital inputs DI1 and DI2.
Figure 192 - An example of output matrix configuration for trip circuit supervision
with two digital inputs
The trip circuit supervision scheme with two digital inputs 52a and 52b can be
implemented as illustrated in Figure 193. No external resistors are needed for this
scheme to function.
wire 1
Trip
relay(s) CB open DI1 CB closed DI2 Easergy P3
wire 2a
wire 2b
Circuit breaker
Trip
coil
wire 3
When the trip circuit is OK under normal conditions, the status of inputs is
opposite (0,1) or (1,0). When the trip circuit is not OK (coil, wires, auxiliary contact
state or auxiliary voltage failure), both the logic inputs are in the same state, and
an alarm is issued after a delay. This delay is needed to prevent false signaling
during breaker opening events. The timing is set based on breaker operating time
and trip pulse length.
P3T/EN/M/30-208A 325
Transformer protection relay 7 Supporting functions
Table 133 - TCS alarm output depending on the CB and its auxiliary contact
positions, and the possible wiring failure conditions
CB open DI1
T 0
=1 TCS alarm
CB closed DI2
T=2s
P533RKB
326 P3T/EN/M/30-208A
8 Communication and protocols Transformer protection relay
8.1 Cybersecurity
According to a classic model of information security, the three security goals are:
• confidentiality (prevention of unauthorized disclosure of information)
• integrity (prevention of unauthorized modification of information)
• availability (ensuring that information is always available to authorized users)
These goals may be used as a starting point in designing security solutions for
electric power distribution.
We recommend that:
• Computer systems used to design or operate electric power distribution
systems are designed with the principle of least privilege, in other words, that
users only have those access rights that they need to perform their duties.
• All workstations and servers have an effective antimalware solution, such as a
virus scanner.
• Computer systems are protected with adequate physical security measures to
help to prevent physical tampering of the devices or networks.
NOTICE
CYBERSECURITY HAZARD
• Change all passwords from their default values when taking the protection
device into use.
• Change all passwords regularly.
• Ensure a minimum level of password complexity according to common
password guidelines.
Related topics
2.4 Access to device configuration
Optionally, the relay may have up to to two serial ports, COM 3 and COM 4, for
serial protocols (for example IEC 103) and one Ethernet port for Ethernet-based
communication protocols (for example IEC 61850).
The number of available serial ports depends on the type of the communication
option cards.
P3T/EN/M/30-208A 327
Transformer protection relay 8 Communication and protocols
NOTE: By default and when the device comes from the factory, Ethernet
Protocol 1 is enabled and the default protocol is IEC-61850. Also Ethernet
Protocol 2 is enabled and the default protocol is Modbus TCPs.
328 P3T/EN/M/30-208A
8 Communication and protocols Transformer protection relay
The Protocol configuration setting view contains selection for the protocol, port
settings and message/error/timeout counters. Only serial communication
protocols are valid with RS-232 interface.
P3T/EN/M/30-208A 329
Transformer protection relay 8 Communication and protocols
None -
ProfibusDP Interface to
Profibus DB
module VPA
3CG (slave)
IEC-103 IEC-60870-5-10
3 (slave)
330 P3T/EN/M/30-208A
8 Communication and protocols Transformer protection relay
GetSet Communicationi
protocola for
eSetup Easergy
Pro interface
Display of 1.
speed/DPS
current
communication
parameters.
speed = bit/s
D = number of
data bits
P = parity: none,
even, odd
S = number of
stop bits
1. The communication parameters are set in the protocol specific menus. For the local
port command line interface the parameters are set in configuration menu.
The Ethernet port is used for Ethernet protocols like IEC61850 and Modbus TCP.
P3T/EN/M/30-208A 331
Transformer protection relay 8 Communication and protocols
The parameters for the port can be set via the device's front panel or using
eSetup Easergy Pro. Two different protocols can be used simultaneously – both
protocols use the same IP address and MAC address (but different port number).
NOTICE
CYBERSECURITY HAZARD
332 P3T/EN/M/30-208A
8 Communication and protocols Transformer protection relay
This disables all the Ethernet-based protocols (FTP, HTTP, Telnet, and
Ethernet protocols).
b. Unselect the Enable... checkbox for the servers or protocols you want to
disable.
P3T/EN/M/30-208A 333
Transformer protection relay 8 Communication and protocols
334 P3T/EN/M/30-208A
8 Communication and protocols Transformer protection relay
Here we use the F1 key as an example to show you how to lock the remote
configuration.
2. Select the Enable HTTP Server checkbox and Enable Telnet checkbox.
4. Click Write.
Operation principle:
P3T/EN/M/30-208A 335
Transformer protection relay 8 Communication and protocols
The storm protection limit defines how big percentage of the broadcast messages
are forwarded to the CPU.
Storm protection level 0.01% means 15 packets per second in a 100 Mbps
network. Broadcast traffic forwarded to CPU can be limited down to 15% for 100
Mbps. This is based on a theoretical maximum of 100 packets per second that the
CPU can receive and process.
Storm protection can be enabled in the Advanced Ethernet options setting view
with the Storm protection on Port1 and Storm protection on Port2
parameters.
PRP properties:
336 P3T/EN/M/30-208A
8 Communication and protocols Transformer protection relay
For additional information, see application note Parallel Redundancy Protocol for
Easergy P3Ux and Easergy P3x3x relays with dual-port 100 Mbps Ethernet
interface (P3/EN ANCOM/A004).
• events
• status information
• measurements
• control commands
P3T/EN/M/30-208A 337
Transformer protection relay 8 Communication and protocols
• clock synchronization
• some settings through SPA bus, IEC-103, Modbus and IEC-61850 protocols
• disturbance recordings through IEC-103, Modbus and IEC-61850 protocols
Modbus RTU and Modbus TCP protocols are often used in power plants and
industrial applications. The difference between these two protocols is the media.
Modbus TCP uses Ethernet and Modbus RTU uses RS-485, optic fibre, or
RS-232.
eSetup Easergy Pro shows a list of all available data items for Modbus. They are
also available as a zip file ("Communication parameter protocol mappings.zip").
The information available via Modbus RTU and Modbus TCP includes:
• status values
• control commands
• measurement values
• events
• protection settings
• disturbance recordings
The Modbus communication is activated via a menu selection with the parameter
"Protocol". See 8.2 Communication ports.
8.5.2 Profibus DP
The Profibus DP protocol is widely used in the industry. An external VPA 3CG and
VX072 cables are required.
Using the request mode, it is possible to read all the available data from the
PowerLogic P3 relay and still use only a very short buffer for Profibus data
transfer. The drawback is the slower overall speed of the data transfer and the
need of increased data processing at the Profibus master as every data item must
be separately requested by the master.
338 P3T/EN/M/30-208A
8 Communication and protocols Transformer protection relay
NOTE: In the request mode, it is not possible to read continuously only one
single data item. At least two different data items must be read in turn to get
updated data from the relay.
There is a separate manual for VPA 3CG for the continuous mode and request
mode. The manual is available for downloading on our website.
Available data
eSetup Easergy Pro shows the list of all available data items for both modes. A
separate document "Communication parameter protocol mappings.zip" is also
available.
The Profibus DP communication is activated usually for remote port via a menu
selection with parameter "Protocol". See 8.2 Communication ports.
8.5.3 SPA-bus
The relay has full support for the SPA-bus protocol including reading and writing
the setting values. Also, reading multiple consecutive status data bits,
measurement values or setting values with one message is supported.
Several simultaneous instances of this protocol, using different physical ports, are
possible, but the events can be read by one single instance only.
The IEC standard 60870-5-103 "Companion standard for the informative interface
of protection equipment" provides a standardized communication interface to a
primary system (master system).
The unbalanced transmission mode of the protocol is used, and the relay
functions as a secondary station (slave) in the communication. Data is transferred
to the primary system using the "data acquisition by polling" principle.
It is also possible to transfer parameter data and disturbance recordings via the
IEC 103 protocol interface.
The following application service data unit (ASDU) types can be used:
• ASDU 1: Time-tagged message
• ASDU 3: Measurands I
• ASDU 5: Identification message
• ASDU 6: Time synchronization
• ASDU 8: Termination of general interrogation
• ASDU 10: Generic data
P3T/EN/M/30-208A 339
Transformer protection relay 8 Communication and protocols
These are fixed for data items in the compatible range of the protocol, for
example, the trip of I> function is identified by:
• type identification = 1
• function type = 160
• information number = 90
"Private range" function types are used for such data items that are not defined by
the standard (for example, the status of the digital inputs and the control of the
objects).
The function type and information number used in private range messages is
configurable. This enables flexible interfacing to different master systems.
For more information on IEC 60870-5-103 in PowerLogic P3 relays, see the "IEC
103 Interoperability List.pdf" and "Communication parameter protocol
mappings.zip" documents.
The relay supports communication using the DNP 3.0 protocol. The following
DNP 3.0 data types are supported:
• binary input
• binary input change
• double-bit input
• binary output
• analog input
• counters
For more information, see the “DNP 3.0 Device Profile Document" and
"Communication parameter protocol mappings.zip". DNP 3.0 communication is
activated via menu selection. RS-485 interface is often used but also RS-232 and
fibre optic interfaces are possible.
The IEC 60870-5-101 standard is derived from the IEC 60870-5 protocol standard
definition. In PowerLogic P3 relays, the IEC 60870-5-101 communication protocol
is available via menu selection. The relay works as a controlled outstation (slave)
unit in unbalanced mode.
340 P3T/EN/M/30-208A
8 Communication and protocols Transformer protection relay
The IEC 61850 protocol is available with the optional communication module. It
can be used to read or write static data from the relay or to receive events and to
receive or send GOOSE messages from or to other relays.
P3T/EN/M/30-208A 341
Transformer protection relay 8 Communication and protocols
8.5.8 Ethernet/IP
The relay supports communication using the Ethernet/IP protocol which is a part
of the Common Industrial Protocol (CIP) family. The Ethernet/IP protocol is
available with the optional in-built Ethernet port. The protocol can be used to read
or write data from or to the relay using request / response communication or via
cyclic messages transporting data assigned to assemblies (sets of data).
For more detailed information and parameter lists for Ethernet/IP, refer to a
separate application note “EtherNet/IP configuration instructions.pdf”.
For the complete data model of Ethernet/IP, see the document “DeviceNet and
EtherNetIP data model.pdf” and "Communication parameter protocol
mappings.zip".
The Webset HTTPS configuration interface provides the option to configure the
relay with a standard web browser such as Internet Explorer, Mozilla Firefox, or
Google Chrome. The feature is available when the communication option C, D, N
or R is in use.
A subset of the relays's features is available in the Webset interface. The group
list and group view from the relay are provided, and most groups, except the
LOGIC and the MIMIC groups are configurable.
The IEC 60870-5-104 standard is derived from the IEC 60870-5 protocol standard
definition. It is a combination of the application layer of IEC 60870-5-101 and the
transport functions provided by a TCP/IP protocol stack.
342 P3T/EN/M/30-208A
8 Communication and protocols Transformer protection relay
8.6 IP filter
PowerLogic P3 devices contain a simple IP filter (IP firewall), which can be used
to filter incoming TCP/IP connections. This filtering applies to all protocols
assigned as Ethernet Protocol 1 and Ethernet Protocol 2, and can be configured
via eSetup Easergy Pro.
The IP filter works based on configured rules. Incoming IP packets are compared
against the rules, and when a matching rule is found, the packet is handled using
the action specified for the rule. If none of the rules matches the packet, the
default action is taken on the packet. The IP filter records how many times a
packet has matched a rule. The number is shown in the Counter column.
On TCP connections, the rules are mostly applied only when a connection is
opened.
You can configure up to 10 rules for the IP filter via eSetup Easergy Pro and
enable each rule individually.
P3T/EN/M/30-208A 343
Transformer protection relay 8 Communication and protocols
IP address Description
344 P3T/EN/M/30-208A
8 Communication and protocols Transformer protection relay
Action Description
The IP filter also can also detect unexpected packets. For example, if a client
attempts to close a connection that does not exist, this is considered an
unexpected packet.
P3T/EN/M/30-208A 345
Transformer protection relay 8 Communication and protocols
Parameter Description
8.6.3 Alarms
Active cybersecurity (CS) alarms can be viewed in the Alarms view. When an
alarm signal has been asserted, it remains active until it is cleared with the Clear
alarms command.
346 P3T/EN/M/30-208A
9 Applications and configuration examples Transformer protection relay
The relays provide a circuit breaker control function. Additional primary switching
relays (earthing switches and disconnector switches) can also be controlled from
the front panel or the control or SCADA/automation system. A programmable
logic function is also implemented in the relay for various applications, for
example interlockings schemes.
Figure 210 - Typical arc flash detection scheme with integrated arc flash option
card
T1
7
S1
G
A 6
T1
B S2
C S1 S3 S1 S1 S1 S1
T1 T1 T1 T1
D T1
S2 S2 S2 S2 S2
E
S3
1 S3
2 S3
3 S3
4 S3
5
In this application example, the arc flash sensor for zone E is connected to device
1. If the sensor detects a fault and simultaneously, device 1 detects an
overcurrent signal, zone E is isolated by the outgoing feeder breaker.
The arc flash sensor for the second feeder zone E is connected to device 2, and it
operates the same way. The arc flash sensors for zones C and D are connected
to device 1, 2, 3, 4, or 5. If a sensor detects a fault in zone C or D, the light-only
signal is transferred to device 6 which also detects the overcurrent and then trips
the main circuit breaker.
P3T/EN/M/30-208A 347
Transformer protection relay 9 Applications and configuration examples
An arc flash fault in zone A or B does not necessarily activate the current
detection in device 6. However, arc flash detection can be achieved by using the
light-only principle. If an arc flash occurs in the cable termination or incomer
circuit breaker in zone A or B, the fault is cleared by an overcurrent signal.
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not route the Binary Input and Output (BIO) line close to the primary
power circuits.
T1
7
S1
E
A 6
T1
B
T1 T1 T1 T1
C T1
D
S1 S1 S1 S1 S1
1 2 3 4 5
The fiber-loop arc flash sensor for zone D is connected to device 1. If the sensor
detects a fault and simultaneously, device 1 detects an overcurrent signal, zone D
is isolated by the outgoing feeder breaker.
For the other feeders, the fiber-loop arc flash sensors monitoring zone D are
connected to the appropriate feeder relays and they operate the same way as
feeder 1.
The fiber loop arc flash sensors for zones C, B and A are connected to device 6.
If a sensor detects a fault in zone C, B or A and simultaneously, device 6 detects
an overcurrent signal, the fault is cleared by the incoming breaker operation.
Device 7 measures the overcurrent and receives light detection signals from
zones A, B, and C. It trips the substation if device 6 is unable to measure the
overcurrent.
348 P3T/EN/M/30-208A
9 Applications and configuration examples Transformer protection relay
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not route the Binary Input and Output (BIO) line close to the primary
power circuits.
A A
B B C
P3T/EN/M/30-208A 349
Transformer protection relay 9 Applications and configuration examples
9.2 Using CSH120 and CSH200 with I02 0.2 A / 1 A core balance
CT input
General
The CSH120 and CSH200 core balance CTs are for direct earth fault overcurrent
measurement. The only difference between them is the diameter. Because of their
low-voltage insulation, they can only be used on cables.
The device also allows selecting ten times lower scaling values. Set the values to:
• I02 CT primary: 47 A
• I02 CT secondary: 0.1 A
• Nominal I02 input: 0.2 A
The minimum setting for the primary current is then 0.005 x 47 A = 0,235 A.
350 P3T/EN/M/30-208A
9 Applications and configuration examples Transformer protection relay
Measuring specifications
P3T/EN/M/30-208A 351
Transformer protection relay 10 Installation
10 Installation
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH BEFORE
PERFORMING ANY INTERVENTION:
• Turn off all power supplying the protection device and the equipment in
which it is installed before working on it.
• Always use a properly rated voltage sensing device to confirm that power
is off.
• Replace all devices, doors, and covers before turning on power to this
equipment.
• Apply appropriate personal protective equipment and follow safe electrical
work practices. See local regulation.
• Do not install this product in ATEX class 0, 1 and 2 areas.
DANGER
HAZARD OF FIRE
352 P3T/EN/M/30-208A
10 Installation Transformer protection relay
WARNING
HAZARD OF UNEXPECTED OPERATION
Do not energize the primary circuit before this protection relay is properly
configured.
CAUTION
HAZARD OF FIRE, DAMAGE TO ELECTRONICS OR MALFUNCTION
The protective conductor (ground) connection must not be removed since the
protection against electric shock provided by the equipment would be lost.
When the protective (ground) conductor terminal (PCT) is also used to terminate
cable screens, etc., it is essential that the integrity of the protective (ground)
conductor is checked after the addition or removal of such functional ground
connections. For M4 stud PCTs the integrity of the protective (ground)
connections should be ensured by use of a locknut or similar.
The recommended minimum protective conductor (ground) wire size is 2.5 mm²
(AWG 14) (3.3 mm² (AWG 12) for North America) unless otherwise stated in the
technical data section of the equipment documentation, or otherwise required by
local or country wiring regulations.
P3T/EN/M/30-208A 353
Transformer protection relay 10 Installation
To identify a PowerLogic P3 protection relay, see the labels on the package and
on the side of the relay.
1. Rated voltage Un
2. Rated frequency fn
354 P3T/EN/M/30-208A
10 Installation Transformer protection relay
P3F30 A x1
B
Protection relay
Relais de protection
Made in Country
EB20253L0100022
C REL52101
135732
PowerLogic - P3
D P3F30-CGGII-KAENA-BAAAA F
P3F30-009096
E
606481 3571 6 8 3
SCHNEIDER ELECTRIC
CS30323
F-92506 RUEIL MALMAISON CEDEX
10.4 Storage
Store the relay in its original packaging in a closed, sheltered location with the
following ambient conditions:
10.5 Mounting
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Wear your personal protective equipment (PPE) and comply with the safe
electrical work practices. For clothing refer applicable local standards.
• Only qualified personnel should install this equipment. Such work should
be performed only after reading this entire set of instructions and checking
the technical characteristics of the device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing relay to ensure that all power
is off.
• Do not open the secondary circuit of a live current transformer.
• Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
P3T/EN/M/30-208A 355
Transformer protection relay 10 Installation
CAUTION
HAZARD OF CUTS
• Trim the edges of the cut-out plates to remove any jagged edges.
• Use protective gloves when moving and mounting the device.
Panel mounting
mm
225
1 8.86
in 2
erg y c
Pow erL ogi
Eas
c
Pow erL ogi
152
5.98
1.0
0.0-60
4-2
.3 6
T max. 1.2 Nm
3b 3c 10.6 lb-in T max. 0.3 Nm
2.7 lb-in
T max. 0.6 Nm
2.5 Nm 3 Nm
22 lb-in 27 lb-in 5.3 lb-in
3 4
3a
3a
erg yerL ogi c
EasPow
min. 2.5mm2
Ø 5-8mm
CLICK !
Nut M5
1.5Nm, 13.3 Ib in
mm 208 253.40
in 264 9.97 24.60
8.18 0.97
10.37 223.33
183 9.17
PowerLogic 7.20
153
6.02
177 150
6.97 5.91 183
7.20
The conventional mounting technique has always been installing the relay on the
secondary compartment's door. A limitation of this approach could be that the
door construction is not strong enough for the relay's weight and wiring a large
amount of secondary and communication cabling could be challenging.
356 P3T/EN/M/30-208A
10 Installation Transformer protection relay
mm 247
in 9.72
180 199
7.09 7.81
Pow erLo
gic
199
7.83 150
180 5.91
7.09
29 264
1.12 10.37
1 210
PowerLogic
8.27
Ø5 177
0.2 6.97
M4x20
mm Torx T-20
in 1.5Nm
100
3.94
2
18
0.71
11.5
0.45
20 34
0.79 1.34 Pow erL ogi
c
T max. 1.2Nm
10.6 lb.in T max. 0.3Nm
2.7 lb.in
T max. 0.6Nm
5.3 lb-in
180
3 7.09
Ø7
0.28
min. 2.5mm2
Ø 5-8mm
180
7.09
Nut M5
1.5 Nm, 13.3 Ib in
This mounting technique allows the door to be lighter as the relay's frame is
installed on the back of the secondary compartment. Normally, the relay is
mounted by the terminal blocks, hence the secondary wiring is short.
Communication cabling is easier, too, as the door movement does not need to be
considered. In this case, only the communication between relay base and display
have to be wired.
P3T/EN/M/30-208A 357
Transformer protection relay 10 Installation
Projection mounting
225
mm
1 2 8.86
in
c
Pow erL ogi
erLyogi c
Powerg
Eas
152
5.98
1.0
0.0 -60
4-2
.36
3 4
3a y ogi c
ergerL
EasPow
Vamp 300
3a min. 2.5mm2
Ø 5-8mm ON
OK
F2
F1
I O
Nut M5
1.5Nm, 13.3 Ib in
CLICK !
mm 269
in 264 208 10.59
10.37 8.18 45
224
183 1.77
8.82
PowerLogic 7.20
Vamp 300
ON
152
5.98
177 150 177
6.97 5.91
OK 7.0
F1 F2
I O
If the depth dimension behind the compartment door is limited, the relay can be
equipped with a frame around the collar. This arrangement reduces the depth
inside the compartment by 45 mm. For more details, see 11.5 Environmental
conditions.
358 P3T/EN/M/30-208A
10 Installation Transformer protection relay
A B
C D
E F
1
G H
I J
K L
M N
F1 F2
A B
C D
E F
G H
I J
K L
M N
F1 F2
A B
C D
3 E
G
I
K
M
F
H
J
L
N
F1 F2
See "P3 Advanced Series facial label instruction" document for more information.
Protective film
NOTICE
PERMANENT RELAY DAMAGE
NOTE: The display of the protective relay is plastic and can melt if exposed to
high temperatures or intensive sunlight.
10.6 Connections
The PowerLogic P3T32 has a fixed combination of analog interface, power
supply, digital input and output, communication and arc flash detection cards as
per the chosen order code. Do not remove cards from the relay's card slots in any
circumstances.
9 10 OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE
DEVICES VY197B
P3T/EN/M/30-208A 359
Transformer protection relay 10 Installation
Auxiliary voltage
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Before connecting the devices, disconnect the supply voltage to the unit.
The external auxiliary voltage UAUX (110–240 V ac/dc, or optionally 24–48 V dc)
of the relay is connected to the pins 1/C/1:1–2 or 1/D/1:1–2.
The rated frequency (ac) is 50/60 Hz and the AC frequency operating range is the
following:
• 50 Hz, ±10%
• 60 Hz, ±10%
NOTICE
LOSS OF PROTECTION OR RISK OF NUISANCE TRIPPING
Check that the operating mode and SF relay wiring are compatible with the
installation.
360 P3T/EN/M/30-208A
10 Installation Transformer protection relay
Table 138 - Supply voltage card Power C 110-240 & Power D 24-48
P3T/EN/M/30-208A 361
Transformer protection relay 10 Installation
4 No connection
3 No connection
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
This card contains connections for current transformers for measuring of the
phase currents L1–L3 and two earth fault overcurrents I0, and four voltage
transformers for measuring the U0, ULL or ULN.
The relay is able to measure three phase currents, and two earth fault
overcurrents. It also measures up to four voltage signals: line-to-line, line-to-
neutral, neutral displacement voltage and voltage from another side
(synchrocheck). See the voltage modes selection below:
362 P3T/EN/M/30-208A
10 Installation Transformer protection relay
P3T/EN/M/30-208A 363
Transformer protection relay 10 Installation
Totally, the relay is able to measure six phase currents, three earth fault
overcurrents and additionally four voltages.
364 P3T/EN/M/30-208A
10 Installation Transformer protection relay
Figure 226 - Analog measurement card "1 = 3xI (5/1A) ring lug + Io (5/1A)”
1 2
3 4
5 6
7 8
9 10
11 12
P3T/EN/M/30-208A 365
Transformer protection relay 10 Installation
This card contains connections to two arc light sensors (for example, VA 1 DA),
three binary inputs and three binary outputs.
The option card also has three normal open trip contacts that can be controlled
either with the relay’s normal trip functions or using the fast arc matrix.
For more information on BIO, see 6.32.3 Binary inputs and outputs.
366 P3T/EN/M/30-208A
10 Installation Transformer protection relay
This card contains connections to one arc fiber sensor, two fiber binary inputs,
two fiber binary outputs and three fast trip relays.
Arc loop sensor input is used with Arc-SLm sensor. The sensor’s sensitivity can
be set in the Arc protection setting view in eSetup Easergy Pro. If the sensitivity
needs to be reduced, increase the setting value from the default value. As an
example, it could be set up to 900. Test that the switching object no longer
initiates an unwanted sensor activation. Validate also with a strong external light
source that the arc loop channel remains operational. The default adjusted value
is 737. The setting range is from 100 to 900.
NOTE: Some applications have strong Arc flash sources, for example
switching devices such as a CB or a contactor, which could illuminate the loop
sensor during a normal switching operation.
P3T/EN/M/30-208A 367
Transformer protection relay 10 Installation
NOTE: The setting value is a relative value for sensitivity, and it does not
anticipate any light intensity (lux) value.
Binary inputs and outputs are designed to be used with 50/125 μm, 62.5/125 μm,
100/140 μm, and 200 μm fiber sizes (Connector type: ST).
The option card also has three normal open trip contacts that can be controlled
either with the relay’s normal trip functions or using the fast arc matrix.
Table 143 - Fiber 2 x BI/BO, 1 x Arc loop sensor, T2, T3, T4 I/O card pins (slot 2)
368 P3T/EN/M/30-208A
10 Installation Transformer protection relay
19–20 NC No connection
1797) 5/D/1:16
5/D/1:15
1597)
8–14 NC No connection
P3T/EN/M/30-208A 369
Transformer protection relay 10 Installation
1–3 NC No connection
97) Terminals18-17 and 16-15 are interconnected, so it is sufficient to connect the wiring to terminals
15 and 17 or 16 and 18 only.
This card contains four arc point connections to four arc light sensors (for
example. VA 1 DA). The card provides sensors 3 to 6.
This card provides six digital inputs and four relay outputs. The threshold level is
selectable in the order code.
370 P3T/EN/M/30-208A
10 Installation Transformer protection relay
The card is equipped with six dry digital inputs with hardware-selectable
activation/threshold voltage and four trip contacts. Input and output contacts are
normally open.
Table 146 - Channel numbering for "C" or "D" power module and four “G” cards in
slots 2–5/G-G-G-G
Card type C or D G G G G
19, 20 12 16 20 24 28
17, 18 11 15 19 23 27
15, 16 10 14 18 22 26
13, 14 9 13 17 21 25
11, 12 1
DI channel numbering
11, 12 6 12 18 24
9, 10 5 11 17 23
7, 8 4 10 16 22
5, 6 3 9 15 21
3, 4 2 8 14 20
1, 2 1 7 13 19
P3T/EN/M/30-208A 371
Transformer protection relay 10 Installation
NOTE: Digital inputs are polarity-free, which means that you can freely
choose "-" and "+" terminals for each digital input.
Table 147 - Channel numbering for “C” or “D” power module, "B" or "C" arc sensor
interface card and three “G” cards in slots 3–5/G-G-G
Card type C or D B C G G G
19, 20 12 4
17, 18 11 3
15, 16 10 2
13, 14 9
11, 12 1
5, 6 4
3, 4 3
1, 2 2
19, 20 16 20 24
17, 18 15 19 23
15, 16 14 18 22
13, 14 13 17 21
DI channel numbering
11, 12 6 12 18
9, 10 5 11 17
7, 8 4 10 16
5, 6 3 9 15
3, 4 2 8 14
1, 2 1 7 13
NOTE: Digital inputs are polarity-free, which means that you can freely
choose "-" and "+" terminals for each digital input.
This card provides six digital inputs and four relays outputs that are normally
closed (NC). The threshold level is selectable in the order code.
372 P3T/EN/M/30-208A
10 Installation Transformer protection relay
The 6xDI+4xDO option card is equipped with six dry digital inputs with hardware-
selectable activation/threshold voltage and four normally closed (NC) trip
contacts.
20 Tx Trip relay
19
18 Tx Trip relay
17
16 Tx Trip relay
15
14 Tx Trip relay
13
11
P3T/EN/M/30-208A 373
Transformer protection relay 10 Installation
This card provides 10 digital inputs. The threshold level is selectable in the order
code.
Table 149 - Channel numbering for slots 2–5/G-I-I-I/1:1–20 when one "G" and
three "I" cards are used
Card type G I I I
19, 20 16 26 36
17, 18 15 25 35
15, 16 14 24 34
374 P3T/EN/M/30-208A
10 Installation Transformer protection relay
13, 14 13 23 33
11, 12 6 12 22 32
9, 10 5 11 21 31
7, 8 4 10 20 30
5, 6 3 9 19 29
3, 4 2 8 18 28
1, 2 1 7 17 27
NOTE: Digital inputs are polarity-free, which means that you can freely
choose "-" and "+" terminals for each digital input.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Clean the arc sensor periodically as instructed in this user manual and after
an arc flash fault.
mm 22.2
in 0.83 20
14 0.79
0.55
10
0.39
25
1.83
46.4
0.98
8
0.31
4.2
0.17
P3T/EN/M/30-208A 375
Transformer protection relay 10 Installation
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Install arc flash sensors inside the switchgear. There are two options for mounting
the sensors:
376 P3T/EN/M/30-208A
10 Installation Transformer protection relay
mm 50 51
in 1.97 25 2.0
15
0.59 0.98
59
2.32 2.5
42 0.1
1.65
10
0.39
15
7 50 0.59
0.28 1.97
mm
in 10
0.39
15 59 15
0.59 2.32 0.59
3
0.12
30
1.18
30
1.18
P3T/EN/M/30-208A 377
Transformer protection relay 10 Installation
1. Press the active part of the sensor through the 10 mm hole in the panel
surface.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
1. Route the wire to the nearest device using the shortest route possible.
Cut the wire to a suitable length.
Take into account the wiring methods inside the equipment. This should be
compliant with local regulations.
378 P3T/EN/M/30-208A
10 Installation Transformer protection relay
3. If using a shielded cable, connect the cable shield to ground at the sensor
end.
Related topics
10.6.3.1 I/O card “B = 3BIO+2Arc”
10.6.3.2 I/O card “C = F2BIO+1Arc”
10.6.3.4 I/O option card “D=4Arc”
(slot 6) 2 = TX COM 1
3 = RX COM 1
4 = IRIG-B
5 = IRIG-B GND
7 = GND
8 = RX COM 2
9 = +12V
P3T/EN/M/30-208A 379
Transformer protection relay 10 Installation
(slot 9) 2 = TX COM 3
3 = RX COM 3
4 = IRIG-B
5 = IRIG-B GND
6=
7 = GND
8 = RX COM 4
9 = +12V
(slot 9) 2 = TX COM 3
3 = RX COM 3
4 = IRIG-B
5 = IRIG-B GND
6=
7 = GND
8 = RX COM 4
9 = +12V
3 = Receive +
4=
5=
6 = Receive -
7=
8=
380 P3T/EN/M/30-208A
10 Installation Transformer protection relay
(slot 9) 2 = TX COM 3
3 = RX COM 3
4 = IRIG-B
5 = IRIG-B GND
6=
7 = GND
8 = RX COM 4
9 = +12V
P3T/EN/M/30-208A 381
Transformer protection relay 10 Installation
7 = RS-485 interface 2
“-“ connection
6 = RS-485 interface 2
“+“ connection
5 = RS-485 interface 2
ground terminal
4 = RS-485 interface 1
“-“ connection
3 = RS-485 interface 1
“+“ connection
2 = RS-485 interface 1
ground terminal
1 = RS-485 interface 1
cable shield
connection
* RS-485 interfaces 1
and 2 galvanically
isolated from each
other
382 P3T/EN/M/30-208A
10 Installation Transformer protection relay
3 =Receive+
4=
5=
6 = Receive-
7=
8=
4 = RS-485 interface 1
“-“ connection
3 = RS-485 interface 1
“+“ connection
2 = RS-485 interface 1
ground terminal
1 = RS-485 interface 1
cable shield
connection
P3T/EN/M/30-208A 383
Transformer protection relay 10 Installation
4 = RS-485 interface 1
“-“ connection
3 = RS-485 interface 1
“+“ connection
2 = RS-485 interface 1
ground terminal
1= RS-485 interface 1
cable shield
connection
4=
5=
6=Receive-
7=
8=
-Port 1 Rx
-Port 1 Tx
384 P3T/EN/M/30-208A
10 Installation Transformer protection relay
RS-485 connections
Figure 238 - All shields connected through and grounded at one end
DIP switches
1 Right Echo on
The COM 1 port is for serial communication protocols. The type of the physical
interface on this port depends on the type of the selected communication option
P3T/EN/M/30-208A 385
Transformer protection relay 10 Installation
module. The use of some protocols may require a certain type of option module.
The parameters for this port are set via the front panel or with eSetup Easergy
Pro in the COM 1 setting view.
Profibus DP
COM 3 and COM 4 are ports for serial communication protocols. The type of the
physical interface on these ports depends on the type of the selected
communication option module. The use of some protocols may require a certain
type of option module. The parameters for these ports are set via the front panel
or with eSetup Easergy Pro in the COM 3 PORT – COM 4 PORT setting views.
386 P3T/EN/M/30-208A
10 Installation Transformer protection relay
or - IEC-101
232+Eth RJ - IRIG-B
or - GetSet
232+Eth LC
VIO12-AB VIO 12 AB None - None
(Slot 9)
and - - ExternalIO
VSE-002 VSE002
and - - ExternalIO
VSE-002 VSE002
and - - ExternalIO
VSE-002 VSE002
- IEC-103
- ModbusSlv
- SpaBus
- IEC-103
- ModbusSlv
- SpaBus
- DNP3
- ProfibusDP
or - IEC-101
232+Eth RJ - IRIG-B
or - GetSet
P3T/EN/M/30-208A 387
Transformer protection relay 10 Installation
232+Eth LC
and - - ExternalIO
VSE-002 VSE002
and - - ExternalIO
VSE-002 VSE002
- IEC-103
- ModbusSlv
- SpaBus
- IEC-103
- ModbusSlv
- SpaBus
- DNP3
To be able to use COM 3 and COM 4 ports, the RS-232 communication interface
(option B, C or D) has to be split in two by using a VX067 cable.
1 2 3 4 5 6 8
A
9
VX067
VX067
388 P3T/EN/M/30-208A
10 Installation Transformer protection relay
Use a VX086 cable to interface simultaneously with two protocols and IRIG-B.
None -
ProfibusDP Interface to
Profibus DB
module VPA
3CG (slave)
IEC-103 IEC-60870-5-10
3 (slave)
P3T/EN/M/30-208A 389
Transformer protection relay 10 Installation
GetSet Communicationi
protocola for
interface
Display of 1.
speed/DPS
current
communication
parameters.
speed = bit/s
D = number of
data bits
P = parity: none,
even, odd
S = number of
stop bits
1. The communication parameters are set in the protocol-specific menus. For the local
port command line interface, the parameters are set in the configuration menu.
390 P3T/EN/M/30-208A
10 Installation Transformer protection relay
The front panel USB type B port is always using the command line protocol for
eSetup Easergy Pro.
The speed of the interface is defined in the CONF/DEVICE SETUP menu via the
front panel. The default settings for the relay are 187500.
110/120/220/240 V ac
110/125/220 V dc
or
24–48 ±20% V dc
24/48 V dc
Power consumption
(as per the order code letters) A: 24–230 V ac/dc (max. 255 V ac/dc)
Nominal operation voltage for DI inputs B: 110–230 V ac/dc (max. 255 V ac/dc)
P3T/EN/M/30-208A 391
Transformer protection relay 10 Installation
C: 155 V dc
Cycle time 10 ms
NOTE: Set the dc/ac mode according to the used voltage in eSetup Easergy
Pro.
Continuous carry 5A
at 48 V dc: 5A
at 110 V dc: 3A
at 220 V dc 1A
392 P3T/EN/M/30-208A
10 Installation Transformer protection relay
Continuous carry 5A
at 48 V dc: 1.15 A
Number of contacts: 1
Continuous carry 5A
P3T/EN/M/30-208A 393
Transformer protection relay 10 Installation
at 48 V dc: 1A
Protocols GetSet
RS-485 (option)
Spabus, slave
IEC 60870-5-103
IEC 61870-5-101
Profibus DP
DNP 3.0
IRIG-B
394 P3T/EN/M/30-208A
10 Installation Transformer protection relay
LC 100Mbps (option)
Modbus TCP
DNP 3.0
Ethernet/IP
IEC 61870-5-101
Modbus TCP
DNP 3.0
Ethernet/IP
IEC 61870-5-101
T = 3 x I (5/1A) + I0 (5/1A)
P3T/EN/M/30-208A 395
Transformer protection relay 10 Installation
E = 3L(5/1A) + 2I0(5/1A+1/0.2A) + 4 U
1A: 0.02–50 A
I0 input (5 A) Slot 8:
E = 3L(5/1A) + 2I0(5/1A+1/0.2A) + 4 U
- Burden 0.075 VA
396 P3T/EN/M/30-208A
10 Installation Transformer protection relay
I0 input (1 A) Slot 8:
E = 3L(5/1A) + 2I0(5/1A+1/0.2A) + 4 U
- Burden 0.02 VA
E = 3L(5/1A) + 2I0(5/1A+1/0.2A) + 4 U
Rated earth fault overcurrent 0.2 A (configurable for CT secondaries 0.1 – 10.0 A)
- Burden 0.02 VA
Voltage inputs
600 V (10 s)
Frequency
< 44Hz / > 66Hz (other protection is not steady except frequency protection)
P3T/EN/M/30-208A 397
Transformer protection relay 10 Installation
Terminal characteristics
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• VSE001PP (Plastic-plastic)
• VSE001GG (Glass-glass)
398 P3T/EN/M/30-208A
10 Installation Transformer protection relay
• None
• IEC-103
• Modbus slave
• SpaBus
The power for the module is taken from pin 9 of the D-connector or from an
external power supply interface.
The physical interface of the VSE-001 is a 9-pin D-connector. The signal level is
RS-232.
NOTE: The product manual for VSE-001 can be found on our website.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• None
• IEC-103
• ModbusSlv
• SpaBus
P3T/EN/M/30-208A 399
Transformer protection relay 10 Installation
The power for the module is taken from pin 9 of the D-connector or from an
external power supply interface.
The physical interface of the VSE-002 is a 9-pin D-connector. The signal level is
RS-232 and therefore, the interface type for the module has to be selected as
RS-232.
Termination
ON OFF
73 mm
Interface type
TLL RS-232
20 mm
1 - -
7 GND GND
400 P3T/EN/M/30-208A
10 Installation Transformer protection relay
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• None
• ProfibusDP
The power for the module is taken from an external power supply interface.
P3T/EN/M/30-208A 401
Transformer protection relay 10 Installation
The maximum cable length depends on the transmission speed and cable type.
The specified cable length can be increased by the use of repeaters. The use of
more than 3 repeaters in a series is not recommended.
VIO 12A I/O modules can be connected to PowerLogic P3T32 using VSE 001 or
VSE 002 interface modules.
VIO 12A I/O modules can be connected to PowerLogic P3U20 and P3U30 using
RS-485 connection in interface modules. Alternatively VIO 12A I/O modules can
be connected to PowerLogic P3U20 and P3U30 using RS-232 connection. If
RS-232 connection is used a separate VX082 or VX083 connection cable and
VSE001 or VSE002 option module are needed.
The status of the output contacts is shown when the relay is energized but none
of the protection, controlling or self-supervision elements are activated.
402 P3T/EN/M/30-208A
10 Installation Transformer protection relay
Figure 247 - Typical block diagram for P3M32, P3T32 and P3G32 relays
P3T32-CGITA-AAENA-BAAAA
1/C/1:16 T10
M
G
DI1 2/G/1:1 1/C/1:15 T10
DI
DI1 2/G/1:2 1/C/1:14 T9
DI2 2/G/1:3 1/C/1:13 T9
DI2 2/G/1:4 1/C/1:12 T1
DI3 2/G/1:5
1/C/1:11 T1
DI3 2/G/1:6
1/C/1:10 A1 NO
1
DI4 2/G/1:7 1/C/1:9 A1 NC
DI4 2/G/1:8 1/C/1:8 A1 COM
DI5 2/G/1:9 1/C/1:7 SF NC
DI5 2/G/1:10 1/C/1:6 SF NO
DI6 2/G/1:11 1/C/1:5 SF COM
1
DI6 2/G/1:12
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
P3T/EN/M/30-208A 403
Transformer protection relay 10 Installation
3LN_Uo_P3T32_connection_v1
1
IL1
2
3 IL2 5A
4 1A
8/E/1 : 1...12
5 IL3
Slot 8
6
7 Io1
8
9
10
Io2
1) 11 1A
12 0.2A
P3T32
1
2 I’L1
5A
3 1A
4
4/T/1 : 1 ... 12
5 I’L2
5A
6 1A
Slot 4
7
8 I’L3
5A
9 1A
10
11 5A
Io3
12 1A
1
UL1
2
3 8/E/2 : 1...8
UL2
Slot 8
4
5 UL3
6
7 Uo
8
L1
L2
L3
1) Power direction
404 P3T/EN/M/30-208A
10 Installation Transformer protection relay
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
P3T/EN/M/30-208A 405
Transformer protection relay 10 Installation
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Ensure that the wiring connections for Master Trip (MT) input and MT
output are secure and meet industry standards for reliability.
This section contains the commissioning testing instructions. The figure below
shows the testing sequence.
406 P3T/EN/M/30-208A
10 Installation Transformer protection relay
Checking zones
End
1. Check the protected zones where sensors have been installed and compare
them against the drawings.
2. Consult the customer if the configuration does not match with the drawings.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Disconnect the trip signals to the circuit breakers that may disturb other parts
of the system during the test.
P3T/EN/M/30-208A 407
Transformer protection relay 10 Installation
• Also disconnect trip signals routed to other parts of the system, such as the
breaker failure (ANSI 50BF) backup trip to upstream breakers and the transfer
trip signals.
• Test the disconnected trip signals with a multimeter.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Testing the arc flash sensors with the light-only criteria operates the trip outputs of
the device or the I/O units for the protected zone.
Testing the arc flash sensors with the light and current criteria, without an injected
current, only generates an indication on the unit that protects the zone. The
indication of the arc fault is registered by the possible main unit and I/O unit.
NOTE: Testing the arc flash sensors using a light source can trip the
neighboring zones.
408 P3T/EN/M/30-208A
10 Installation Transformer protection relay
NOTE: For more information on viewing and resetting indications, see the
corresponding sensor user manual or se.com.
Test the sensors with the main device. See VAMP 125 Arc Flash Protection
Device User Manual.
1. Point light to each arc flash sensor, one at a time, with a powerful light source
such as camera flash unit or flashlight.
P3T/EN/M/30-208A 409
Transformer protection relay 10 Installation
O 1 2 3 4 5 6 7 8
N
ACT
t/int
L>ex tch
La TRIP
L+I/L
Zone TS
PU
OR IN
Addr. SENS
4
3
2
1
T3 11
R3 9 10
T2 7 8
R2 5 6
T1 3 4
1 2
R1
X1
1. Disconnect one wire from one point sensor, one for each unit, to see that the
self-supervision system recognizes the fault in the sensor.
2. Wait until the arc fault indication appears.
Depending on the device, this can take several minutes. See HMI functions
and indications in the device user manual.
BI/O signals such as light and overcurrent information are transmitted between
devices through dedicated inputs/output.
1. Activate the signal outputs in the binary I/O by generating arc fault light signal,
overcurrent pickup or both.
1. Download the test report template from the Schneider Electric website.
2. Fill in all the required information about the system, the tested arc flash units
and the test results.
410 P3T/EN/M/30-208A
10 Installation Transformer protection relay
Supervisor
Date
P3T/EN/M/30-208A 411
Transformer protection relay 10 Installation
10.7.4 Troubleshooting
This table describes some common problems in the arc flash system and how
they can be solved.
The trip signal does not Faulty trip circuit wiring Check that the wiring of the
reach the circuit breaker. trip circuit is not faulty.
The protection does not trip The protection needs both Check the dip switch
even when a sufficient light light and current information configuration. The protection
signal is provided. to trip. may be configured to
require both the light and
current condition to trip.
Faulty sensor wiring Loose sensor wire Check the sensor wiring.
detected by the self- The sensor wire may have
supervision loosened in the terminal
blocks.
Error message indicating Light pulse to the arc flash Check that the light pulse to
blocked sensor channel sensor is too long. the arc flash sensor is not
too long.
412 P3T/EN/M/30-208A
10 Installation Transformer protection relay
Table 170 - Correlation between voltage measuring mode and physical voltage
input in Terminals 8/E/1 and 8/F/2
Terminal 1 2 3 4 5 6 7 8
3LN+U0 U0
UL1 UL2 UL3
3LN+LLy LLy
3LN+LNy LNy
P3T/EN/M/30-208A 413
Transformer protection relay 10 Installation
This section introduces various voltage connections and the required voltage
measuring modes for the connections. The settings are defined in the Scalings
view.
3LN
UL1
P3x3x 3LN
UL2
UL3
8/E/2 : 1...8
8/F/2 : 1...8
1
U1
2
3
U2
4
5
U3
6
7
U4
8
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
3LN+U0
This connection is typically used for feeder and motor protection schemes.
414 P3T/EN/M/30-208A
10 Installation Transformer protection relay
UL1
P3x3x 3LN + Uo
UL2
UL3
8/E/2 : 1...8
8/F/2 : 1...8
1
U1
2
3
U2
4
5
U3
6
7
U4
8
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
3LN+LLy
P3T/EN/M/30-208A 415
Transformer protection relay 10 Installation
8/E/2 : 1...8
8/F/2 : 1...8
1
U1
2
3
U2
4
5
U3
6
7
U4
8
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
3LN+LNy
This connection is typically used for feeder protection scheme where line-to-
neutral voltage is required for synchrocheck application.
416 P3T/EN/M/30-208A
10 Installation Transformer protection relay
8/E/2 : 1...8
8/F/2 : 1...8
1
U1
2
3
U2
4
5
U3
6
7
U4
8
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
2LL+U0
P3T/EN/M/30-208A 417
Transformer protection relay 10 Installation
UL1
P3x3x 2LL + Uo
UL2
UL3
8/E/2 : 1...8
8/F/2 : 1...8
1
U1
2
3
U2
4
5
U3
6
7
U4
8
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
2LL+U0+LLy
418 P3T/EN/M/30-208A
10 Installation Transformer protection relay
UL1
8/E/2 : 1...8
8/F/2 : 1...8
1
U1
2
3
U2
4
5
U3
6
7
U4
8
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
2LL+U0+LNy
P3T/EN/M/30-208A 419
Transformer protection relay 10 Installation
UL1
8/E/2 : 1...8
8/F/2 : 1...8
1
U1
2
3
U2
4
5
U3
6
7
U4
8
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
LL+U0+LLy+LLz
This scheme has two CBs to be synchronized. The left side of the bus bar has
line-to-line and the right side line-to-line connection for synchrocheck's reference
voltages. In the middle, the system voltages are measured by phase-to-neutral
and open delta connection.
420 P3T/EN/M/30-208A
10 Installation Transformer protection relay
UL1
8/E/2 : 1...8
8/F/2 : 1...8
1 U1
2
3 U2
4
5 U3
6
7 U4
8
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
LN+U0+LNy+LNz
This scheme has two CBs to be synchronized. The left and right sides of the bus
bar have line-to-neutral connections for synchrocheck's reference voltages. In the
middle, system voltages are measured by phase-to-neutral and broken delta
connection.
P3T/EN/M/30-208A 421
Transformer protection relay 10 Installation
UL1
8/E/2 : 1...8
8/F/2 : 1...8
1 U1
2
3 U2
4
5 U3
6
7 U4
8
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Always connect the polarity of the current transformer (CT) and the
voltage transformer (VT) and their secondary ground wiring according to
the connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to
the connection diagrams presented in this document.
The specifically designed CSH120 and CSH200 core balance CTs are for direct
earth fault overcurrent measurement. The difference between CSH120 and
CSH200 is the inner diameter.
422 P3T/EN/M/30-208A
10 Installation Transformer protection relay
Characteristics
CSH120 CSH200
(-13°F to +158°F)
Maximum permissible 20 kA - 1 s
current
Dimensions
A B
C
G H J D
I K
F E
P3T/EN/M/30-208A 423
Transformer protection relay 10 Installation
Dime C. D. E. F. G. H. I. J. K.
nsion
s
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Only qualified personnel should install this equipment. Such work should
be performed only after reading this entire set of instructions and checking
the technical characteristics of the device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing device to confirm that all
power is off.
• Only CSH120 and CSH200 core balance CTs can be used for direct earth
fault overcurrent measurement.
• Install the core balance CTs on insulated cables.
• Cables with a rated voltage of more than 1000 V must also have an
earthed shielding.
Assembly
Group the MV cable (or cables) in the middle of the core balance CT.
424 P3T/EN/M/30-208A
10 Installation Transformer protection relay
CAUTION
UNINTENDED EQUIPMENT OPERATION
Connect the secondary circuit and the cable shielding of the CSH core
balance CTs to earth in the shortest possible manner according to the
connection diagram presented in this document.
Connection
Recommended cable
The maximum resistance of the PowerLogic P3T32 connection wiring must not
exceed 4 Ω (i.e. 20 m maximum for 100 mΩ/m or 66 ft maximum for 30.5 mΩ/ft).
Two CSH200 CTs can be connected in parallel if the cables do not fit through a
single CT.
P3T/EN/M/30-208A 425
Transformer protection relay 10 Installation
DE80231
426 P3T/EN/M/30-208A
11 Test and environmental conditions Transformer protection relay
±15 kV air
Fast transients (EFT)100) IEC/EN 61000-4-4 Level 4 ±4 kV, 5/50 ns, 5 kHz
IEEE C37.90.1
P3T/EN/M/30-208A 427
Transformer protection relay 11 Test and environmental conditions
Impulse voltage withstand IEC/EN 60255-27, Class III 5 kV, 1.2/50 μs, 0.5 J
0.5 kV, 50 Hz
Communication
428 P3T/EN/M/30-208A
11 Test and environmental conditions Transformer protection relay
Device in operation
Device de-energized
Device in operation
P3T/EN/M/30-208A 429
Transformer protection relay 11 Test and environmental conditions
93% RH
5 cycles
Device in storage
Condition Value
430 P3T/EN/M/30-208A
11 Test and environmental conditions Transformer protection relay
11.6 Casing
Table 176 - Casing
Parameter Value
Degree of protection (IEC 60529) IP54 Front panel, IP20 rear side, IP10 rear
side (if analog measurement card with ring
lug connectors is used)
P3T/EN/M/30-208A 431
Transformer protection relay 12 Maintenance
12 Maintenance
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Wear your personal protective equipment (PPE) and comply with the safe
electrical work practices. For clothing, see applicable local standards.
• Only qualified personnel should install this equipment. Such work should
be performed only after reading this entire set of instructions and checking
the technical characteristics of the device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing device to ensure that all
power is off.
• Do not open the secondary circuit of a live current transformer.
• Always connect the polarity of the current transformer (CT) and the voltage
transformer (VT) and their secondary ground wiring according to the
connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
The PowerLogic P3 protection relays and arc flash detection products together
with their extension units, communication accessories, arc flash detection sensors
and cabling, later called “device”, require maintenance in work according to their
specification. Keep a record of the maintenance actions. The maintenance can
include, but is not limited to:
• preventive maintenance
• periodic testing
• hardware cleaning
• system status messages
• spare parts
• self-supervision
• dirty components
• loose wire connections
• damaged wiring
• indicator lights
• other mechanical connections
Related topics
2.5.7 Testing the LEDs and LCD screen
432 P3T/EN/M/30-208A
12 Maintenance Transformer protection relay
Conduct the testing with a secondary injection principle for the protection stages
used in the device and its extension units.
In corrosive or offshore environments, carry out functional testing every three (3)
years. For the testing procedures, see separate testing manuals.
12.6 Self-supervision
NOTICE
LOSS OF PROTECTION OR RISK OF NUISANCE TRIPPING
Check that the operating mode and SF relay wiring are compatible with the
installation.
Description
The electronic parts and the associated circuitry as well as the program execution
are supervised by means of a separate watchdog circuit. Besides supervising the
device, the watchdog circuit attempts to restart the microcontroller in an
P3T/EN/M/30-208A 433
Transformer protection relay 12 Maintenance
inoperable situation. If the microcontroller does not restart, the watchdog issues a
self-supervision signal indicating a permanent internal condition.
When the watchdog circuit detects a permanent fault, it always blocks any control
of other digital outputs (except for the self-supervision SF output). In addition, the
internal supply voltages are supervised. Should the auxiliary supply of the device
disappear, an indication is automatically given because the device status
inoperative (SF) output functions on a working current principle. This means that
the SF relay is energized, the 1/C/1:5–7 (or 1/D/1:5-7) contact closed, when the
auxiliary supply is on and the PowerLogic P3T32 device is fully operational.
434 P3T/EN/M/30-208A
12 Maintenance Transformer protection relay
Having the Seldiag alarm grouping made, the appropriate alarms can be assigned
to SF relay. By default, selfdiag alarm 2 is linked to SF relay (Figure 267). The
function of this default setup is the same as in the older systems where this
configuration was not possible.
It is possible to choose what selfdiag alarms 1-3 do when activated. This option
can be done through the output matrix (Figure 268). This allows you to categorize
and prioritize actions for each selfdiag alarms individually. For example, in this
configuration, selfdiag alarm 2 activates T9.
Figure 268 - Selecting selfdiag 1-3 actions. The number of outputs varies
depending on the device and order code
12.6.1 Diagnostics
The device runs self-diagnostic tests for hardware and software in boot sequence
and also performs runtime checking.
Diagnostic registers
P3T/EN/M/30-208A 435
Transformer protection relay 12 Maintenance
The following table shows the meaning of each diagnostic register and their bits.
1 (Reserved) (Reserved)
2 T1 Detected digital
output fault
3 T2
4 T3
5 T4
6 T5
7 T6
8 T7
9 T8
10 A1
11 A2
12 A3
13 A4
14 A5
15 T9
2 T12
3 T13
4 T14
5 T15
6 T16
7 T17
8 T18
436 P3T/EN/M/30-208A
12 Maintenance Transformer protection relay
9 T19
10 T20
11 T21
12 T22
13 T23
14 T24
8 BI Detected ARC BI
error
The code is displayed in self-diagnostic events and on the diagnostic menu on the
local panel and eSetup Easergy Pro.
NOTE: All signals are not necessarily available in every P3 product.
P3T/EN/M/30-208A 437
Transformer protection relay 12 Maintenance
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Carry out periodic system testing as per the testing recommendation in this
manual or of the protection system scheme has been changed.
• Connect the watchdog (SF) output contact to a monitoring device, such as
SCADA or Distributed Control System (DCS) to detect a power-off or a
permanent fault state.
NOTE: If the arc flash detection unit is no longer supplied with power or is in
permanent non-operational state, the protection functions are no longer active
and all the output contacts are dropped out.
Pay special attention to ensure that the device, its extension units and sensors do
not become dirty.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Do not use any type of solvents or gasoline to clean the device, sensors
or cables.
• When cleaning the sensor, make sure that the cleaning solution does not
contact anything other than the sensor.
438 P3T/EN/M/30-208A
12 Maintenance Transformer protection relay
Always check that the sensor positioning remains as it was originally designed
after:
• commissioning
• sensor replacement
• modification procedure
• cleaning
• arc flash fault
• periodic testing
P3T/EN/M/30-208A 439
Transformer protection relay 13 Order codes and accessories
Application
T32 = Transformer protection relay with differential protection
I/O Card I
G = 6DI+4DO (6 x DI, 4 x DO) Slot 3 = A, G, H or I
B = 3BIO+2Arc (3 x BI/BO, 2 x Arc point sensor, T2, T3, T4) Slot 3 = A, G, H or I
C = F2BIO+1Arc (Fibre 2 x BI/BO, 1 x Arc loop sensor, T2, T3, T4) Slot 3 = A, G, H or I
I/O Card II
A = None
G = 6DI+4DO (6 x DI, 4 x DO)
H = 6DI+4DO (6 x DI, 4 x DO(NC))
I = 10DI (10 x DI)
I/O Card III
T = 3xI (5/1A) + Io (5/1A) clamp for transformer differential protection Slot 8 = E or F
1 = 3xI (5/1A) + Io (5/1A) ringlug for transformer differential protection Slot 8 = 1 or 2
I/O Card IV
A = None
Option card I
A = None
D = 4Arc (4 x Arc sensor)
K = RS232 (RS232, IRIG-B)
Future option
A = None
Communication interface I
A = None
B = RS232 (RS232, IRIG-B)
C = RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mb/s)
D = RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mb/s)
E = 2xRS485 (2-wire)
F = RS485+RJ (RS485 2-wire + Ethernet RJ-45 100 Mb/s)
G = RS485+LC (RS485 2-wire + Ethernet LC 100 Mb/s)
N = 2xRJ (Ethernet RJ 100 Mb/s, RSTP)
O = 2xLC (Ethernet LC 100 Mb/s, RSTP)
P = PP (Plastic / Plastic serial fibre)
R = GG (Glass / Glass serial fibre)
Reserved
A = Reserved
Display type
B = 128x128 (128 x 128 LCD matrix)
C = 128x128Ext (128 x 128 LCD matrix, detachable)
Product version
A = Version 2.1
Future option
A = None
Region
A = English, IEC
B = English, ANSI Slot 4 = 1 and Slot 8 = 1
C = Chinese
R = Russian
W = OEM W
440 P3T/EN/M/30-208A
13 Order codes and accessories Transformer protection relay
13.2 Accessories
Table 178 - Accessories for PowerLogic P3 Advanced
P3T/EN/M/30-208A 441
Transformer protection relay 13 Order codes and accessories
442 P3T/EN/M/30-208A
13 Order codes and accessories Transformer protection relay
P3T/EN/M/30-208A 443
Transformer protection relay 14 Firmware revision
14 Firmware revision
Table 179 - Firmware revisions
FW revision Changes
Version: 30.208 • Added two stages for directional earth fault overcurrent (total five stages)
• New scaling settings for conventional VT connection to PowerLogicTM P3 LPVT
Release date: October 2024
input (via adapter)
• Improved method to monitor Circuit Breaker open and close time
• Added busbar voltage measurement on P3G32 local HMI and eSetup Easergy
Pro in DiffGenTra mode
• Added bias current view to PowerLogicTM P3 Advanced differential relays’ local
HMI & eSetup Easergy Pro Setting tool
• Adjustable time delay setting for object’s closing operation
• Configurable Virtual Inputs with adjustable pulse timer
• Various communication parameter updates
• Disabling remote configuration, communication port locking by password
444 P3T/EN/M/30-208A
14 Firmware revision Transformer protection relay
FW revision Changes
Version: 30.205 • Polarity of the output contacts in the power supply card is now SW selectable
between NO and NC
Release date: October 2021
• Frequency stage improvement
• Global trip line to output matrix
• Phasor symbol improvement in the HMI
• Local panel control no longer requires activation of the Operator access level
when it is disabled in the Objects setting view
• HMI password enhancement with letters and characters
• Communication:
◦ IEC61850 new LN (LTIM) added for time management
◦ IEC61850 new LN (ZMOT) added for running hours
◦ Modbus update to access arc sensor status
◦ New timeout mechanism added for Telnet/Serial/Http connections (not
applicable to ANSI model)
Version: 30.204 •
• Updated secondary current representation for P3T32
Release date: January 2021
• Communications:
◦ IEC61850 and Modbus: Alarm setting and operations left parameters for circuit
breaker monitoring
◦ Ethernet/IP communication protocol restored back to use
• Cybersecurity:
◦ Removed Administrator account due to cybersecurity requirement.
Version: 30.203 • I>>> stage latch function upgrade during the power on-off-on state
• RSTP network reconstruction optimization
Release date: July 2020
• Adjusted time stamps for disturbance recorder and events logs
• Backlight off default timeout changed to 10 min
• Added Modbus registers for alarm setting of CB wear (read) and Operation left
data (read)
• DNP3 updates:
◦ Added function 24 record current time
◦ Added VO and LED status to BI data list
◦ Added the possibility to configure time reference to UTC
P3T/EN/M/30-208A 445
Transformer protection relay 14 Firmware revision
FW revision Changes
Version: 30.111 • Improved menu titles for COM ports and Ethernet ports in the Protocol
Configuration menu
Release date: October 2019
• IEC-61850 speed optimizations
• Added IRIG-B support for option 'K' in slot 6
• Support for eight (8) controllable objects and protocol parameters for Modbus, IEC
61850, IEC 103, IEC 101, Device Net, Profibus, DNP 3, and SPAbus
• Modbus:
◦ registers to include protection function status
◦ added LED status information
Version: 30.109 • Arc protection I>int. start setting changed to be relative to CT primary instead of
application nominal current.
Release date: March 2019
• Unit for start setting of I0>int. arc protection changed to "pu".
• Negative sequence voltage U2>, U2>> and U2>>>(ANSI 47) stages added.
• Maximum number of disturbance records increased from 12 to 24.
• IEC 61850 logical nodes added for digital inputs 32....36.
• Digital inputs 33...36 added to IEC 103 protocol.
• BIO and IGBT support added to P3x3x models.
446 P3T/EN/M/30-208A
14 Firmware revision Transformer protection relay
FW revision Changes
Version: 30.106 • The setting "Inv. time coefficient k" in stages I>, Iφ>, Iφ>>, Io>, Ioφ>, Ioφ>>,
Ioφ>>> has three decimals instead of two and the minimum value for the earth
Release date: 16.5.2018
fault overcurrent was changed from 0.05 to 0.025.
• Communication protocol updates
P3T/EN/M/30-208A 447
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison - France
Phone: +33 (0) 1 41 29 70 00
www.schneider-electric.com
P3T/EN/M/30-208A — 10/2024