W18X46 W3-7 1/2" NW 30 10 106: The Beam Design Is Adequate
W18X46 W3-7 1/2" NW 30 10 106: The Beam Design Is Adequate
W18X46 W3-7 1/2" NW 30 10 106: The Beam Design Is Adequate
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Composite Collector Beam Design with Seismic Loads Based on AISC 360-05 / CBC 07 / IBC 06
DESIGN CRITERIA
1. When welded shear connectors are used for transfer of lateral shear loads to drags/collectors, the allowable shear strength shall be
one-third of the available strength for both gravity and lateral design (CBC 07 2204A.1.2), to consider concrete craked at lateral loads.
2. The input STUDS SPACING must be based on actual deck ribs spacing for perpendicular to beam. For the following total [15] studs, if ribs
spacing 12" o. c., the minimum composte beam capacity
is from 2 rows @ 12" o.c., not one row @ 8.57" o.c.
BEAM SPAN L= 30 ft
BEAM SPACING (TRIB. WIDTH) B= 10 ft, o.c.
SUPERIMPOSED LOAD, ASD ws = 106 lbs / ft2
COLLECTOR / DRAG AXIAL LOAD P= 106 kips, (ASD level, including W0)
WEAK AXIS EFFECTIVE LENGTH KLy = 10 ft
ANALYSIS
DETERMINE REACTIONS, MOMENTS & SHEARS
w = ws+ wwt= 106 +( 72.50 + 4.59 ) = 183.09 lbs / ft2
= 1.83 kips / ft (total gravity loads on span beam)
Mmax = 206.0 ft-kips R1 = 27.46 kips
Vmax = 27.46 kips, at R1 right. R2 = 27.46 kips
E
n 8.73 , (ACI 318-05 8.5.1)
Ec
2 Actr t 02 2
I tr I x A y b 0.5d Actr 0.5t 0 h r d y b 2928 in4
12
I tr
S tr 146 in3, referred to steel bottom.
yb
I tr
St 535 in3, referred to concrete top.
d hr t 0 yb
CHECK BENDING & SHEAR CAPACITIES
Middle Bottom : Mmax = (Ztr / Zx) MDL + MLL = 365.5 ft-kips
< Mn / Wb = Ztr Fy / Wb = 642.5 ft-kips, (AISC 360 I3.2a) [Satisfactory]
where Wb = 1.67 (AISC 360-05 I3.2a)
3.76(E / Fy )0.5 = 90.55 > h / tw = 50.28
Shear : Vmax = 27.46 kips < V n / v 0.6 F y AwC v / v 117.054 kips, (AISC 360-05 I3.1b)
[Satisfactory]
where 2.24 (E / Fy )0.5 = 53.9463
kv = 5 (AISC 360-05 G2.1b) Cv = 1 (AISC 360-05 G2.1b)
(kv E / Fy ) 0.5
= 53.8516 Wv = 1.67 (AISC 360-05 G1)
S eff S s 2
V ' MAX S tr S s , 0.25 C f 168.75 kips, (AISC 360-05 C-I3-4)
Qn = (1/3) MIN [ 0.5 Asc (fc' Ec)0.5 , RgRpAscFu] = 4.36 kips, (AISC 360-05 I3.2d.3 & CBC 07 2204A.1.2)
where wc = 150 pcf
Ec = wc1.5 33 (fc')0.5 = 3320.56 ksi
Asc = 0.44 in 2
Fu = 58 ksi
Rg = 0.85 (AISC 360-05 Table I3.2b.3)
Rp = 0.60 (AISC 360-05 Table I3.2b.3)
Where Pc = Pn / Wc = 359 / 1.67 = 214.90 kips, (WF steel only, AISC 360-05 Chapter E)
> Pr = 106.00 kips [Satisfactory]
Mcx = Mn / Wb = 642.51 ft-kips, (AISC 360 I3.2a)
> Mrx = 365.50 ft-kips [Satisfactory]
5wL4
Mid 0.51 in, downward perpendicular at middle of beam.
384EI
Mmax = 65.0 ft-kips < M n / W b = Z x F y / Wb = 226.3 ft-kips [Satisfactory]
5wL4
Mid 0.23 in, downward. < L / 360 = 1.00 in [Satisfactory]
384EI eff
Technical References:
1. AISC 360-05: "Specification for Structural Steel Buildings", American Institute of Steel Construction, March 9, 2005.
2. CBC 2007: "California Building Code, Volume 2 of 2", International Building Code, January 1, 2008.
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Steel Beam Design with Gravity Loading Based on AISC-ASD 9th
ANALYSIS
DETERMINE REACTIONS, MOMENTS & SHEARS
w DL ,1
R 2 0.5 w LL ,1 L1 w DL ,2 wLL ,2 L1 0.5 L 2 L 2 P L1 L 2
cos cos L1 L1
= 27.46 kips
w DL ,1
R1 w LL ,1 L1 w DL ,2 w LL ,2 L 2 P R 2
cos cos
= 27.46 kips
X1 = 15.00 ft
X2 = 15.00 ft
X3 = 0.00 ft
w DL ,2
M Min 0.5 w LL ,2 L 22 P L 2 0.0 ft-kips
cos
X 1 X 2
2
w DL ,1
M Max w LL ,1 206.0 ft-kips
cos 8
2
M1 M1
C b 1.75 1.05 0.3 1.75 , since M1 is 0
M2 M2
rT = 1.54 in , Af = 3.67 in2
76b f 20000
L c MIN , 5.43 ft
Fy
d / A f F y
102000C b 12000C b
L u MAX r T , 11.82 ft
Fy 0.6 d / A f F y
510000C b
L3 r T 17.15 ft
Fy
(cont'd)
2 2
F yl / r T
F b1 MIN F y , 0.6F y 30.0 ksi
3 1530000C b
170000C Fy
b
F b 2 MIN 2
, N/A
l / r T 3
12000C
b
F b3 MIN , 0.6 F y N/A
l d / A f
0.66 F y , for l Lc
0.6
F y , for L c l L u
Fb 33.0 ksi
MAX F b1 , F b3 , for L u l L3
MAX F
b 2 , F b3 , for l L 3
CHECK LOCAL BUCKLING (AISC-ASD Tab. B5.1) < = does not apply for top flange continuously braced without cantilever.
bf / (2tf ) = 5.01 < 65 / (Fy)0.5 = N/A
[Satisfactory]
d / tw = 50.28 < 640 / (Fy)0.5 = N/A
[Satisfactory]
Pa 2 L a w1 L 3a w 2 a 4 L 3a
3
End 0.00 in, downward perpendicular to beam.
3EI 24 EI 24 EI
USE C = 0/4" AT CANTILEVER.
Pa L 2 4 2 2
5w1 L w a
Mid 2L 0.68 in, downward perpendicular at middle of beam.
16 EI 384 EI 32 EI
USE C = 3/4" AT MID BEAM.
Pa2 L a w L 3a w 2 a 3 4 L 3a
End 1 cos 0.00 in, downward to vertical direction.
3EI 24 EI 24 EI
< 2L2 / 240 = 0.00 in [Satisfactory]
Pa L 2 5w1 L 4 w2 L 2 a 2
Mid cos 0.23 in, downward to vertical direction.
16 EI 384 EI 32 EI
< L1 / 240 = 1.50 in [Satisfactory]