33/11 KV Sub-Station: A Main Project On
33/11 KV Sub-Station: A Main Project On
33/11 KV Sub-Station: A Main Project On
A MAIN PROJECT ON
33/11 KV SUB- STATION
A Main project report submitted in partial
of the
DIPLOMA IN
ELECTRICAL AND ELECTRONICS ENGINEERING
Submitted by
2019-2020
1
33/11KV SUB STATION chalapathi institute of technology
CERTIFICATE
This is to certify that the foregoing thesis entitled “SUB-STATION” is a
bonafide work
T.SOMNADHPAVANKALYAN [17457-EE-037]
N.LOKESHREDDYREDDY [17457-EE-020]
K.CHANDRASHEAKER [17457-EE-012]
SK.AARIZAHAMEDH [17457-EE-031]
P.GOPIKRISHNA [17457-EE-025]
V.NAGASAI [17457-EE-038]
EXTERNAL EXAMNER
2
33/11KV SUB STATION chalapathi institute of technology
ACknowledgment
We would also like to thank all our teaching staff members of EEE for giving us
their valuable suggestions.
Finally, we are thankful to one and all who contributed for the successful
completion for our project work. We are specially thankful for our Executive Engineer sir
MR.J.HARI BABU. By accepting our permission to join industrial training during the
period of six months
3
33/11KV SUB STATION chalapathi institute of technology
DECLARATION
K.CHANDRASHEKAR [17457-EE-012]
4
33/11KV SUB STATION chalapathi institute of technology
INDEX
CONTENTS PAGENO
List of figures IV
CHAPTER-1 33/11kv substation
1.1 INTRODUCTION 08
1.2 Substation 09
1.3 Types of substation 10
1.4 Sub Station characteristics 11
1.5 Sub Station the constructional features 12
1.6 Earthing and Bonding 12
1.7 Sub Station Earthing calculation methodology 13
1.8 Earthing materials 13
1.9 Switch yard fence earthing 14
1.10 conductor used in Sub Station 15
1.11 conclusion 15
CHAPTER-2 TRANSFORMERS
2.1 Introduction 16
2.2 Power transformer 17
2.3 Instrument transformer 17
2.4 Auto transformer 18
2.5 On the basis of working 18
2.6 On the basis of structure 19
2.7 specification of ct 20
2.8 Types of current transformer 20
2.9 protection of substation 21
2.10 Transformer parts 22
2.11 Conclusion 27
5
33/11KV SUB STATION chalapathi institute of technology
4.1 Introduction 37
4.2 Circuit breaker 38
4.3 Oil circuit breaker 39
4.4 Air blast circuit breaker 39
4.5 Sulphur hexafluoride circuit breaker 40
4.6 Vacuum circuit breaker 41
4.7 Relay 42
4.8 Differential relay 43
4.9 Over current relay 43
4.10 Directional relay 44
4.11 Tripping relay 44
4.12 Auxiliary relay 45
4.13 Conclusion 45
6
33/11KV SUB STATION chalapathi institute of technology
LIST OF FIGURES
Figure No. Name of figure Page no
CHAPTER-1
CHAPTER-2
2.1 Transformer 16
2.2 Power transformer 17
2.3 Instrument transformer 17
2.4 Auto transformer 18
2.6 Core type& shell type 19
2.7 Current transformer 20
2.10 transformer parts 23-24
CHAPTER-3
3.1 Power line carrier communication (PLCC) 28
3.9 capacitor bank 31
3.10 fuse 32
3.11 bus coupler 33
3.12 bus bars 33
3.13 Types of bus bars 35
CHAPTER-4
4.1 Introduction 37
4.2 Circuit breaker 38
4.3 Oil circuit breaker 39
4.4 Air blast circuit breaker 39
4.5 Sulphur hexafluoride circuit breaker 40
4.6 Vacuum circuit breaker 41
4.7 Relay 42
4.8 Differential relay 43
4.9 Over current relay 43
4.10 Directional relay 44
4.11 Tripping relay 44
4.12 Auxiliary relay 45
CHAPER-5 DC PANEL BOARD
5.1 24Volts DC panel board 46
7
33/11KV SUB STATION chalapathi institute of technology
CHAPTER-1
33/11KV SUBSTATION
1.1INTRODUCTION
8
33/11KV SUB STATION chalapathi institute of technology
The main bus 33KV is connected to grid located at I.P.D colony, SANGADIGUNTA, GUNTUR.
Now the transmission line first parallel connected with lightning arrester to diverge surge, followed by
CVT connected parallel. CVT measures voltage and steeps down at 110V. A.C. for control panel, at the
location a wave trap is connected to carrier communication at higher frequencies. A current transformer is
connected in series with line which measure current and step down current at ratio 800:1 for control
panel.
Switchgear equipment is provided, which is the combination of a circuit breaker having an
isolator at each end. A transformer is connected to main bus though a bus coupler. The main bus has total
capability of 160 MVA for 33 KV, which is subdivided into two transformer capacity of 80 MVA
(40MVA+40MVA) parallel connected for 33KV and other two transformer capacity of 80KV
(40KV+40KV) are parallel connected for substation.
At both ends of transformer lightning arrester current transformer and switchgear equipment
provided. Transformer step downs voltage from 33KV to 11KV. The main bus is provided with
switchgear equipment & a current transformer. This gives way to six feeders transmitting power to
SANGADIGUNTA and some other AREAS. The main bus is connected to jack bus or transfer bus
through a bus coupler & 11KV is provided with switchgear equipment. This gives way to feeders
transmitting power to CHOWTRA, I.P.D COLONY, KAMMA SESHAYYA GROUND,
PALABAZAR etc.
A step down transformer of 11KV/440V is connected to control panel to provide supply to the
equipment of the substation. Capacitor bank is connected to main bus of 11KV. It is provided to improve
power factor & voltage profile.
1.2SUBSTATION
The present day electrical power system is A.C. i.e. electrical power is generated, transmitted &
distributed in the form of the alternating current. The electric power is produced at power plant stations
which are located at favorable places generally quite away from the consumers. It is delivered to the
consumers through a large network of transmission 7 distribution.
At many places in the power system, it may be desirable and necessary to change some
characteristics e.g. voltage, ac to dc, frequency, power factor etc. of electric supply. This accomplished by
suitable apparatus called substation. For example; generation voltage (11 KV or 33 KV) at the power
station is set up to high voltage (say 220 KV or 132 KV) for transmission of electric power. The assembly
of apparatus (e.g. transformer etc.) used for this purpose in the substation. Similarly near the consumer’s
localities, the voltage may have to be step down to utilization level. This job is again accomplished by
suitable apparatus called substation.
The assembly of apparatus to change some characteristic of electric power supply is called
substation.
The two most ways to classify substation are:-
1.3Transformer substation
10
33/11KV SUB STATION chalapathi institute of technology
They are known as transformer substations as because transformer is the main component
employed to change the voltage level, depending upon the purposed served
PRIMARY GRIDSUBSTATION
Here, electric power is received by primary substation which reduces the voltage level to 11KV
for secondary transmission. The primary grid substation is generally of outdoor type.
SECONDARY SUBSTATIONS
At a secondary substation, the voltage is further steeped down to 11KV. The 11KV lines runs
along the important road of the city. The secondary substations are also of outdoor type.
1.1.1.1.3DISTRIBUTION SUBSTATION
These substations are located near the consumer’s localities and step down to 400V, 3-phase, 4-
wire for supplying to the consumers. The voltage between any two phases is 400V & between any phase
and neutral it is 230V.
1.4 SUBSTATIONCHARACTERISTICS:
Each circuit is protected by its own circuit breaker and hence plant outage does not necessarily result in
loss of supply.
A fault on the feeder or transformer circuit breaker causes loss of the transformer and feeder circuit, one
of which may be restored after isolating the faulty circuit breaker
A fault on the bus section circuit breaker causes complete shutdown of the substation. All circuits may be
restored after isolating the faulty circuit breaker.
Maintenance of a feeder or transformer circuit breaker involves loss of the circuit.
Introduction of bypass isolators between bus bar and circuit isolator allows circuit breaker maintenance
facilities without loss of that circuit.
11
33/11KV SUB STATION chalapathi institute of technology
SECONDARY SUBSTATIONS
At a secondary substation, the voltage is further steeped down to 11KV. The 11KV lines runs
along the important road of the city. The secondary substations are also of outdoor type.
1.5STEPS IN DESIGNINGSUBSTATI
The First Step in designing a Substation is to design an Earthing and Bonding System.
Touch Voltage:
This is the difference in potential between the surface potential and the potential at earthed
equipment whilst a man is standing and touching the earthed structure.
12
33/11KV SUB STATION chalapathi institute of technology
Step Voltage:
This is the potential difference developed when a man bridges a distance of 1m with his feet while not
touching any other earthed equipment.
Mesh Voltage:
This is the maximum touch voltage that is developed in the mesh of the earthing grid.
Connections to the grid and other earthing joints should not be soldered because the heat
generated during fault conditions could cause a soldered joint to fail. Joints are usually bolted.
Earthing Rods:
The earthing grid must be supplemented by earthing rods to assist in the dissipation of earth fault currents
and further reduce the overall substation earthing resistance. These rods are usually made of solid copper,
or copper clad steel.
The earthing grid must be supplemented by earthing rods to assist in the dissipation of earth fault currents
13
33/11KV SUB STATION chalapathi institute of technology
and further reduce the overall substation earthing resistance. These rods are usually made of solid copper,
or copper clad steel.
Extend the substation earth grid 0.5m-1.5m beyond the fence perimeter. The fence is then bonded to
the grid at regular intervals.
Place the fence beyond the perimeter of the switchyard earthing grid and bond the fence
to its own earthing rod system. This earthing rod system is not coupled to the main substation earthing
grid.
Should be capable of carrying the specified load currents and short time currents.
Should be able to withstand forces on it due to its situation. These forces comprise self weight, and
weight of other conductors and equipment, short circuit forces and atmospheric forces such as wind and
ice loading.
Should be corona free at rated voltage.
Should have the minimum number of joints.
Should need the minimum number of supporting insulators.
Should be economical.
The most suitable material for the conductor system is copper or aluminums. Steel may be used
but has limitations of poor conductivity and high susceptibility to corrosion.
In an effort to make the conductor ideal, three different types have been utilized, and these
include: Flat surfaced Conductors, Stranded Conductors, and Tubular Conductor
14
33/11KV SUB STATION chalapathi institute of technology
The choice is influenced by the height of towers and the proximity to the substation. The
following clearances should be observed:
15
33/11KV SUB STATION chalapathi institute of technology
CHAPTER-2
TRANSFORMER
TYPES OFTRANSFORMER
Power transformer
Instrument transformer
Autotransformer
On the basis of working
On the basis of structure
16
33/11KV SUB STATION chalapathi institute of technology
2.2POWERTRANSFORMER:
a) Current transformer
b) Potential transformer
Current transformer:
Potential transformer:
The current transformer the high value of current into the low value so that it can conventialy
measure by the transformer converts the high value of voltage into low values
18
33/11KV SUB STATION chalapathi institute of technology
Plinth mounted DT Substations As per IS 1180, DTs above 500 KVA have necessarily to be
mounted on a plinth, however, lower capacity DTs may also mounted on plinth as per the practices
being followed in Discos. The Pad, which is a low height platform/plinth, normally made of
concrete structure. It can also be prefabricated by fiber blocks on which the transformers can be
mounted, however, the strength of the fiber block have to be ensured by the Discos before
installation. The Pad should be capable to carry the weight of the DT and should also have the
facility for cable entry and exit at two sides as per the terminals available at the Transformers. The
plinth shall be higher than the surroundings and plinth foundation is normally made of concrete.
Plinth mounted distribution sub-stations should be adequately protected by fencing so as to prevent
access to the equipment by unauthorized persons, animals and should be provided with standard
danger boards. The enclosure should also permit free circulation of air on all sides This type of DT
substations is best suitable for higher load centers areas where adequate land is available such as in
urban areas , housing complex, office complex and other developed areas. This substation can be
indoor type or outdoor type and the rating of Transformer may normally be more than 250KVA to
1000KVA depending on load requirement in the localities and also for economic reasons as this
needs control gears/ switchgears and proper enclosed wall boundary. The height of Pad/plinth
should be designed by considering the factors such flood level & topography of the locality etc and
should be adequately protected by fencing so as to prevent access by any unauthorized persons.
Depending upon the distribution system available in the area, the provisions for entry of cables or
for connection with overhead systems at DT primary and the exit from secondary side with
underground arrangement for laying the LT lines up to consumer premises is made accordingly.
19
33/11KV SUB STATION chalapathi institute of technology
20
33/11KV SUB STATION chalapathi institute of technology
Marshalling box:
It has two meter which indicate the temperature of the oil and winding of main tank. If
temperature of oil or winding exceeds than specified value, relay operates to sound an alarm. If
there is further increase in temperature then relay completes the trip circuit to open the circuit
breaker controlling the transformer.
Transformer cooling:
When the transformer is in operation heat is generated due to iron losses the removal of heat
is called cooling.
There are several types of cooling methods, they are as follows:
Air natural cooling:
In a dry type of self cooled transformers, the natural circulation of surrounding air is used
for its cooling. This type of cooling is satisfactory for low voltage small transformers.
21
33/11KV SUB STATION chalapathi institute of technology
TRANSFORMER PARTS
2.10 TRANSFORMER PARTS:
1. Transformer tank
2. High voltage bushings
3. Low voltage bushings
4. Cooling fins/Radiator
5. Cooling fans
6. Conservator tank
7. System ground terminal
TRANSFORMER TANK:
When transformer is loaded and when ambient temperature rises, the volume of oil
inside transformer increases . A conservator tank of transformer provides adequate space to this
expanded transformer oil. It also acts as a reservoir for transformer insulating oil.
22
33/11KV SUB STATION chalapathi institute of technology
23
33/11KV SUB STATION chalapathi institute of technology
24
33/11KV SUB STATION chalapathi institute of technology
25
33/11KV SUB STATION chalapathi institute of technology
Provide a relatively low-impedance path to ground, thereby maintaining the system neutral at or
near ground potential.
Limit the magnitude of transient over voltages when restriking ground faults occur.
Provide a source of ground fault current during line-to-ground faults.
Permit the connection of phase-to-neutral loads when desired.
Three-phase electric power is a common method of alternating current electric power generation,
transmission, and distribution.[1] It is a type of poly phase system and is the most common method
used by electrical grids worldwide to transfer power. It is also used to power large motors and other
heavy loads.
A three-wire three-phase circuit is usually more economical than an equivalent two-wire single-
phase circuit at the same line to ground voltage because it uses less conductor material to transmit a
given amount of electrical power. [2] Poly phase power systems were independently invented by
Galileo Ferraris, Mikhail Dolivo-Dobrovolsky, Jonas Wenström, John Hopkinson and Nikola Tesla
in the late 1880s.
In a symmetric three-phase power supply system, three conductors each carry an alternating current
of the same frequency and voltage amplitude relative to a common reference but with a phase
difference of one third of a cycle between each. The common reference is usually connected to
ground and often to a current-carrying conductor called the neutral. Due to the phase difference, the
voltage on any conductor reaches its peak at one third of a cycle after one of the other conductors
and one third of a cycle before the remaining conductor. This phase delay gives constant power
transfer to a balanced linear load. It also makes it possible to produce a rotating magnetic field in an
electric motor and generate other phase arrangements using transformers (for instance, a two phase
system using a Scott-T transformer). The amplitude of the voltage difference between two phases is
times the amplitude of the voltage of the individual phases.
The symmetric three-phase systems described here are simply referred to as three-phase systems
because, although it is possible to design and implement asymmetric three-phase power systems
(i.e., with unequal voltages or phase shifts), they are not used in practice because they lack the most
important advantages of symmetric systems.
26
33/11KV SUB STATION chalapathi institute of technology
In a three-phase system feeding a balanced and linear load, the sum of the instantaneous
currents of the three conductors is zero. In other words, the current in each conductor is equal in
magnitude to the sum of the currents in the other two, but with the opposite sign. The return path for
the current in any phase conductor is the other two phase conductors Transmission lines are current
carrying lines that carry power from generating stations to the substations. Feeder is an electrical
distribution network. They carry power from substation to consumers. Electrical distribution is the
final stage in the delivery of electricity to end users. ... The transmission power lines will enter a
distribution substation where the voltage will be stepped down to distribution levels where it will be
distributed for use by industrial, commercial and residential customers.
2.11 Conclusion:
In transformer everything is important The fins project outwards making the area for
emitting heat back into, say, an electronic circuit's container, smaller than the area emitting heat
to the outside environment. Grounding transformers most commonly incorporate a single
winding transformer with a zigzag winding configuration, but may also be created with a wye-
delta winding transformer. Neutral grounding transformers are very common on generators in
power plants and wind farms. Neutral grounding transformers are sometimes applied on high-
voltage (sub-transmission) systems, such as at 33 kV, where the circuit would otherwise not have
a ground; for example, if a system is fed by a delta-connected transformer. The grounding point
of the transformer may be connected through a resistor to limit the fault current on the system in
the event of a line-to-ground fault. current transformer provides a secondary current that is
accurately proportional to the current flowing in its primary. The current transformer presents a
negligible load to the primary circuit. Transformer s are basic need for electricity because of if
transformer is not present the conductor may damage and make disturbance to public and there
will be breakdown by trees on lying on conductor and there will be voltage consumption
problems without transformer so transformer plays a major role in electrical department. There
will rating of transformer to areas by the consumption so there are different rating of transformer
It works on the principle of static induction principle. When the energy is transformed into a high
voltage
27
33/11KV SUB STATION chalapathi institute of technology
CHAPTER-3
CHRONOLOGICAL TRAININGDIARY&BUS BARS
( based on study & observation at different Departments andsections)
Introduction:
28
33/11KV SUB STATION chalapathi institute of technology
3.2 APPLICATIONS:
The PLCC can be used for the following facilities:
Telephony
Tele protection
Remote control or indication
Telemetry
Tele printing
3.3PRINCIPLE OFPLCC:
The principle of PLCC is the simple one:
All type of information is modulated on carried wave at frequency 50Hz to 500 KHz. The
modulated HF carrier fed into the power line conductor at the sending end and filtered out again
at the respective stations. Long earlier system double side band amplitude modulation was more
common but the present amplitude modulated system.
Since high voltage power lines are designed to carry large quantities of energy on the
high voltage and the communication system at low voltage, they cannot be directly connected to
high voltage lines. Suitably designed coupling equipments have therefore to be employed which
will permit the injection of high frequency carrier signal without undue loss and with absolute
protection of communication equipments or operating personal from high voltage hazard.
Therefore, the coupling equipment essentially comprises the following:
29
33/11KV SUB STATION chalapathi institute of technology
3.5 Couplingcapacitor:
The modulated carrier is let into power line through coupling capacitor specially designed
to with stand line voltage under all weather condition. The upper end of the coupling capacitor is
connected directly to the line and the lower end is connected to the ground through a carrier
frequency chock coil or drain coil. Thus coupling capacitor forms the link between the PLCC
equipment and power line. The coupling capacitor used in UPSEB is 2200pf capacitance.
The coupling capacitor are designed for outdoor use and hence to withstand normal
atmospheric phenomenon such as temperature & humidity changes, rain, snow, anticipated wind
load, nominal wire tension etc. at full rated voltage. In some case capacitive voltage transformers
(CVT) used as a source of line voltage for metering and protection as also used coupling
capacitor for PLCC.
3.8H.F.Cable:
H.F. cable normally used to connect the coupling filter to another coupling terminal. The
cable is insulated to withstand the test voltage of 4KV. The impedance of this H.F. cable is so as
to match with the output of the PLCC terminal and secondary impedance of coupling filter.
30
33/11KV SUB STATION chalapathi institute of technology
TYPES OF COUPLING:
The following three types of coupling are being used in UPSEB depending on the
requirement:
Phase to ground coupling
Phase to phase coupling
Internal Coupling
COUPLING LOSSES:
Coupling loss, also known as connection loss, is the loss that occurs when energy is
transferred from one circuit, circuit element, or medium to another. Coupling loss is usually
expressed in the same units—such as watts or decibels—as in the originating circuit element or
medium .Coupling loss in fiber optics refers to the power loss that occurs when coupling light from
one optical device or medium to another. (See also Optical return loss.)
Coupling losses can result from a number of factors. In electronics, impedance
mismatch between coupled components results in a reflection of a portion of the energy at the
interface. Likewise, in optical systems, where there is a change in index of refraction (most
commonly at a fiber/air interface), a portion of the energy is reflected back into the source
component.
Another major source of optical coupling loss is geometrical. As an example, two fibers
coupled end-to-end may not be precisely aligned, with the result that the two cores overlap
somewhat. Light exiting the source fiber at a portion of its core that is not aligned with the core of
the receiving fiber will not (in general) be coupled into the second fiber. While some such light will
be coupled into the second fiber, it is not likely to be efficiently coupled, nor will it generally travel
in an appropriate mode in the second fiber
The load on the power system is varying being high during morning and evening which
increases the magnetization current. This result in the decreased power factor. The low power
factor is mainly due to the fact most of the power loads are inductive and therefore take lagging
currents. The low power factor is highly undesirable as it causes increases in current, resulting in
additional losses. So in order to ensure most favorable conditions for a supply system from
engineering and economical stand point it is important to have power factor as close to unity as
possible. In order to improve the power factor come device taking leading power should be
connected in parallel with the load. One of the such device can be capacitor bank. The capacitor
draws a leading current and partly or completely neutralize the lagging reactive component of
load current.
3.10 Fuse
A fuse is a short piece of wire or thin strip which melts when excessive current through it
for sufficient time. It is inserted in series with the circuit under normal operating conditions; the
fuse element is at a nature below its melting point. Therefore it carries the normal load current
overheating. It is worthwhile to note that a fuse performs both detection and interruption
functions.
32
33/11KV SUB STATION chalapathi institute of technology
3.11BUS COUPLER:
BUSBARS
3.12 BUSBARS:
33
33/11KV SUB STATION chalapathi institute of technology
Power neutral busbars may also be insulated because it is not guaranteed that the potential between
power neutral and safety grounding is always zero. Earthing (safety grounding) busbars are
typically bare and bolted directly onto any metal chassis of their enclosure. Busbars may be
enclosed in a metal housing, in the form of bus duct or busway, segregated-phase bus, or isolated-
phase bus.
Busbars may be connected to each other and to electrical apparatus by bolted, clamped, or
welded connections. Often, joints between high-current bus sections have precisely-machined
matching surfaces that are silver-plated to reduce the contact resistance. At extra high
voltages (more than 300 kV) in outdoor buses, corona discharge around the connections becomes a
source of radio-frequency interference and power loss, so special connection fittings designed for
these voltages are used.
35
33/11KV SUB STATION chalapathi institute of technology
CONCLUSION:
In large stations it is important that break downs and maintenance should interfere as little
as possible with the continuity of supply to achieve this, duplicate bus bar system is used such a
system consists of two bus bars, main bus bar and a spare bus bars with the help of bus coupler
which consists breaker and isolate potential between power neutral and safety grounding is always
Zero. Earthing bus bars are typically bare and bolted directly on to any, metal chassis of their
enclose. Bus bars may be enclosed in a metal housing, in the form of bus duct or bus way
segregated-phase bus or isolated phase bus.
The coupling capacitor are designed for outdoor use and hence to withstand normal
atmospheric phenomenon such as temperature & humidity changes, rain, snow, anticipated wind
load, nominal wire tension etc. at full rated voltage. In some case capacitive voltage transformers
Long earlier system double side band amplitude modulation was more common but the present
amplitude modulated system. Since high voltage power lines are designed to carry large
quantities of energy on the high voltage and the communication system at low voltage, they
cannot be directly connected to high voltage lines.
36
33/11KV SUB STATION chalapathi institute of technology
CHAPTER-4
ISOLATORS AND CIRCUIT BREAKERS
4.1INTRODUCTION
The insulator serves two purposes. They support the conductors (bus bar) and confine the
current to the conductors. The most common used material for the manufacture of insulator is
porcelain. There are several types of insulators (e.g. pin type, suspension type, post insulator etc.)
and their use in substation will depend upon the service requirement. For example, post insulator
is used for bus bars. A post insulator consists of a porcelain body, cast iron cap and flanged cast
iron base. The hole in the cap is threaded so that bus bars can be directly bolted to the cap.
With the advantage of power system, the lines and other equipment operate at very high
voltage and carry high current.
The arrangements of switching along with switches cannot serve the desired function of
switchgear in such high capacity circuits. This necessitates employing a more dependable means
of control such as is obtain by the use of the circuit breakers. A circuit breaker can make or break
a circuit either manually or automatically under all condition as no load, full load and short
circuit condition.
A circuit breaker essentially consists of fixed and moving contacts. These contacts can be
opened manually or by remote control whenever desired. When a fault occurs on any part of the
system, the trip coils of breaker get energized and the moving contacts are pulled apart by some
37
33/11KV SUB STATION chalapathi institute of technology
38
33/11KV SUB STATION chalapathi institute of technology
Fast operations, suitability for repeated operation, auto reclosure, unit type multi break
constructions, simple assembly, modest maintenance are some of the main features of air blast
circuit breakers. A compressors plant is necessary to maintain high air pressure in the air
receiver. The air blast circuit breakers are especially suitable for railways and arc furnaces,
where the breaker operates repeatedly. Air blast circuit breakers is used for interconnected lines
and
39
33/11KV SUB STATION chalapathi institute of technology
40
33/11KV SUB STATION chalapathi institute of technology
In such circuit breaker, sulphar hexafluoride (SF6) gas is used as the arc quenching
medium. The SF6 is an electronegative gas and has a strong tendency to absorb free electrons.
The SF6 circuit breaker have been found to a very effective for high power and high voltage
service. SF6 circuit breakers have been developed for voltage 115 KV to 230 KV, power rating
10 MVA.
It consists of fixed and moving contacts. It has chamber, contains SF6 gas. When the
contacts are opened, the mechanism permits a high pressure SF6 gas from reservoir to flow
towards the arc interruption chamber. The moving contact permits the SF6 gas to let through
these holes.
41
33/11KV SUB STATION chalapathi institute of technology
4.7 RELAY:
42
33/11KV SUB STATION chalapathi institute of technology
This type of relay works when current in the circuit exceeds the predetermined value. The
actuating source is the current in the circuit supplied to the relay from a current transformer.
These relay are used on A.C. circuit only and can operate for fault flow in the either direction.
This relay operates when phase to phase fault occurs.
43
33/11KV SUB STATION chalapathi institute of technology
44
33/11KV SUB STATION chalapathi institute of technology
An auxiliary relay is used to indicate the fault by glowing bulb alert the employee.
4.13 CONCLUSION:
The electrical quantities which may change under fault condition are voltage, frequency,
current, phase angle. When a short circuit occurs at any point on the transmission line the current
flowing in the line increases to the enormous value .This result in a heavy current flow through
the relay coil, causing the relay to operate by closing its contacts. This in turn closes the trip
circuit of the breaker making the circuit breaker open and isolating the faulty section from the
rest of the system. In this way, the relay ensures the safety of the circuit equipment from the
damage and normal working of the healthy portion of the system. When contacts of a circuit
breaker are separated, an arc is struck; the current is thus able to continue. The production of arcs
are not only delays the current interruption, but is also generates the heat . A compressors plant
necessary to maintain high air pressure in the air receiver. The air blast circuit breakers are
especially suitable for railways and arc furnaces, where the breaker operates repeatedly .The
arrangements of switching along with switches cannot serve the desired function of switchgear in
such high capacity circuits. This necessitates employing a more dependable means of control
such as is obtain by the use of the circuit breakers. A circuit breaker can make or break a circuit
either manually or automatically under all condition as no load, full load and short circuit
condition.
45
33/11KV SUB STATION chalapathi institute of technology
CHAPTER-5
PANNEL BOARD
5.1 3/11KV SANGADIGUNTA SS PANNEL BOARD
IMAGE : OS DC PANNEL BOARD:
KV METER:
The kv meter is used to measure the voltage which is providing to the consumers. If
the voltage is Below 11kv it is called low load or rise 11.5kv above means overload.
Kv meter is used for this purpose.
DC LEAKAGE:
This indication system is used to check the dc supply which is given to the feeders.
How to check the dc leakage is working is properly. If we on those switches if the
light blinks it is working properly
1
33/11KV SUB STATION chalapathi institute of technology
PTR-1&2:
The PTR1&2 indicates if there is any problem in power transformer
GAS (alarm):
A gas alarm has a point detector, which measures the concentration of gas in the air through
the use of various sensors, such as infrared sensors, ultrasonic sensors, electrochemical gas sensors,
etc. ... They are especially useful in industrial plants for monitoring concentrations of gas and
vapors.
FEEDER:
The function of the feeder pillar is to take in a supply of electrical energy from a transformer
and distribute it, via fuse ways, to a number of outgoing circuits, providing each with a mean of
protection and control.
FEEDER TRIPING:
The DC Panel board is generally indicate the colors red when the feeder get in the position
tripping then the color indicates the red and green there will be a siren to alert the people to come
and repair the whole feeder to take the control of LI (LINE INSPECTOR) by overcoming the repair
then the feeder will get the normal asusually then there will be no alert sound at same feeder if
again the same feeder trips there be a breakdown and check the whole section then we may solve
the problem
5.2 CONCLUSION:
The panel board is made up of the sunglass and attached with wood why because of when
the breakage occurs there will be no shock they can immediately can change the circuit mean
while they are connected with feeders so we have to change immediately respond to everything
The heat produce in the cores and winding is passed to the oil becomes lighter and rises to the
top and place is taken by cool oil from the bottom of the cooling tank