Ecofit Pure: en Installation and Maintenance Instructions
Ecofit Pure: en Installation and Maintenance Instructions
Ecofit Pure: en Installation and Maintenance Instructions
825 - 835
0020230531_07 - 20.10.2020
1.3.9 Frost
To prevent material damage:
▶ Do not install the product in rooms prone
to frost.
Guarantee Registration
Thank you for installing a new Vaillant appliance in your home.
Vaillant appliances are manufactured to the very highest standard so we are pleased to offer our
customers a comprehensive guarantee.
To maintain your guarantee, the boiler must be serviced annually by a competent person who
holds the required qualifications in accordance with the rules in force of the country where the
product is installed and in accordance with the manufactures recommendations.
We recommend you complete your guarantee registration as soon as possible.
Sales Support:
Telephone: 0345 602 0262
Technical Enquiries:
Telephone: 0344 693 3133
Email: technical@vaillant.co.uk
General Enquiries:
Telephone: 0345 602 2922
Training Enquiries:
Telephone: 0345 601 8885
Email: training.enquiriesuk@vaillant-group.com
Spares Enquiries:
Telephone: 01773 596 615
To register your Vaillant appliance visit:
https://self-service.vaillant.co.uk/warranty-registration
Vaillant is a licensed member of the Benchmark Scheme. Benchmark places responsibilities on both manufacturers and installers.
The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned
and serviced in accordance with the manufacturer’s instructions by a competent person approved at the time by the Health and
Safety Executive and that it meets the requirements of the appropriate Building Regulations.
The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer
for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of
Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme.
Benchmark is managed and promoted by the Heating and Hotwater Industry Council.
295
1 Unit mounting bracket
1 Flexible condensate discharge pipe
121
96
6 3/4" seals
4 1/2" seals
58 58
1 Service valve
123 123
1 Gas stopcock 185
1 Filling loop
390
2 Connection pipe (heating flow and return) 150
1 Cold water connection pipe
76
1 Domestic hot water connection pipe
6
1 Gas pipe
1 Drain pipe for the Pressure relief valve
1 Mounting template
1 Enclosed documentation
700
34
220
150
Aa
Ba Z
W
N G
C
J
V M H
J
Z B
U G E S
S Q
J F K
J A
P D R
S L T
P
S S
ry
Bounda
A
F
Y
ry
nda
Bou
Balcony/eaves
Gutter
You can use a plume management kit to enable the termination point to be positioned and directed away from the building
fabric.
1 Gasket (fitted)
Note Consult the separate installation manual for air/flue gas sys-
tems supplied with your appliance for all possibilities and as-
If the terminal is at less than 1.80 m from the
sociated accessories and how to install the flue system.
ground, you must install a terminal protection kit.
6.7 Using the mounting template
Consult the separate installation manual for air/flue gas sys-
tems supplied with your appliance for all possibilities and as-
▶ Use the mounting template to ascertain the locations at
which you need to drill holes.
sociated accessories and how to install the flue system.
B
2x
D
A
B
6.10.2 Installing the side section
▶ Refit the components in the reverse order.
Caution.
Risk of material damage caused by mech-
anical deformation.
Removing both side sections may cause
mechanical distortion in the product, which
may cause damage to the piping, for ex-
ample, and potentially result in leaks.
▶ Always only remove one side section –
never both side sections at the same time.
Note
If there is sufficient lateral clearance (at least
70 mm), you can remove the side section to fa-
cilitate maintenance or repair work.
7.3 Check compliance with the local gas group ▶ Ensure that the pipeline is visible.
The product's combustion has been factory tested and is ▶ The pipe must have a continuous fall and be routed to a
preset for operation with the gas group indicated on the data position so that any discharge of water, possibly boiling,
plate. or steam cannot create any danger to persons, damage
The product is only authorised to be operated with natural to property or external electrical components and wiring.
gas. ◁ The piping must be installed in such a way that you
can see when water drips out.
▶ Check the information about the gas type indicated on
the data plate and compare this with the gas type avail-
able at the installation site.
Condition: The product design is not compatible with the local gas group
Condition: The product design is compatible with the local gas group
1 Ø22mm
Note
The condensate drain pipework must have a
continuous fall (45 mm per metre) and should
whenever possible terminate at a suitable ≤3m Ø22mm
drain point within the heated envelope of the
building that will remain frost free under long
periods of low external temperatures. Ø 32mm
Ø32mm
≤3m
1 ≤3m
< 500 mm
Ø22mm
100 mm
Ø 32mm
< 300 mm
< 25
2
Ø12
25
3 NB only combined foul/rainwater drain
4
50 25
7.6.1.8 Additional methods of introducing air breaks
5
6 25
Ø22mm 2 3
Ø32mm
Open end of pipe direct into gulley below ground level but
above water level
Susceptible to siphonage, must terminate in a gulley
≥3m
Ø22mm
≤ 30 mm
L
N
PE
B ≤ 40 mm
+
-
≤ 30 mm
≤ 30 mm
ally securely in the terminals of the plug. Remedy this if
necessary.
11. Plug the plug into the associated PCB slot. LN
RT
– In doing so, observe the wiring diagram in the ap-
pendix. 1
X1
L N
7.8.4 Establishing the power supply RT
230V~
B.off
Burner
2. Ensure that the nominal mains voltage is 230 V. 24 V BUS
off
3. Do not interrupt the mains supply with a time switch or
RT
24V =
RT
X106
programmer. BUS
BUS
– +
- +
Burner 24V=
4. Set up a fixed connection and install a partition with off RT BUS
≤ 30 mm
L N RT X1
230V~
Burner
off
RT
24V =
RT
BUS
BUS
- +
– Water temperature: ≤ 50 ℃
D.--- 8.6 Using check programmes
PF Call up the installer level + 1 x
Display Meaning
P.-- P.00 Purging check programme:
The internal pump is cyclically actuated.
D F The heating circuit and the hot water circuit are
purged via the automatic air vent (the cap of the
automatic air vent must be released).
--/-- 1x
2x
: Start heating circuit purging
( → ): Start domestic hot water circuit
purging
DP
3x ( → ): Restart heating circuit purging
1x (Cancel): End purge programme
8.3 Calling up the installer level Note
The purge programme runs for 7.5 min per circuit
1. Only call up the installer level if you are a competent and then terminates.
person. Purging the heating circuit:
2. Press and ("i") at the same time. Prioritising diverter valve in heating position, ac-
◁ S.xx appears in the display (current unit status). tuation of internal pump for 9 cycles: 30 sec. on,
20 sec. off. Display: Active heating circuit.
3. Press to access the installer level.
Purging the hot water circuit:
◁ Code and -- appear in the display.
After the above-mentioned cycles have run or the
4. Set the value 17 (code) and confirm by pressing . right-hand selection button has been pressed again:
5. Press to access the check programmes (P) and the Prioritising diverter valve in the domestic hot water
fault codes (F) and to return to the diagnostics codes position, actuation of the internal pump as above.
(D). Display: Active hot water circuit.
6. Use or to set the required value and confirm by P.01 Maximum load check programme:
pressing . After successful ignition, the product is operated at
maximum heat input.
7. Confirm by pressing ( ).
P.02 Minimum load check programme:
8. Press to cancel a setting or exit the installer level.
After successful ignition, the product is operated at
minimum heat input.
P.06 Filling mode check programme:
The prioritising diverter valve is moved to the mid-
position. The burner and pump are switched off (to
fill or drain the product).
heating
output > 20 l/kW
9.1 Carrying out the initial start-up ≤ 20 l/kW > 50 l/kW
≤ 50 l/kW
Initial start-up must be carried out by a customer service ppm mol/ ppm mol/ ppm mol/
kW
technician or an authorised competent person using the CaCO₃ m³ CaCO₃ m³ CaCO₃ m³
benchmark checklist. The benchmark checklist in the ap- < 50 < 300 <3 200 2 2 0.02
pendix (→ Page 48) of the installation instructions must be
> 50 200 2 150 1.5 2 0.02
filled out and stored carefully along with the unit's document-
to ≤ 200
ation.
> 200 150 1.5 2 0.02 2 0.02
▶ Carry out the initial start-up using the benchmark check- to ≤ 600
list in the appendix. > 600 2 0.02 2 0.02 2 0.02
▶ Fill out and sign the benchmark checklist.
1) Nominal capacity in litres/heating output; in the case of multi-
boiler systems, the smallest single heating output is to be used.
9.2 Checking and treating the heating
water/filling and supplementary water
Caution.
Caution. The use of unsuitable heating water may
Risk of material damage due to poor-qual- cause aluminium corrosion and a result-
ity heating water ing lack of leak-tightness.
▶ Ensure that the heating water is of suffi- In contrast to steel, grey cast iron or copper,
cient quality. for example, aluminium reacts with alkaline
heating water (pH value > 8.5) to produce
▶ Before filling or topping up the installation, check the
substantial corrosion.
quality of the heating water. ▶ When using aluminium, make sure that
Checking the quality of the heating water the pH value of the heating water is
▶ Remove a little water from the heating circuit. between 6.5 and a maximum of 8.5.
▶ Check the appearance of the heating water.
▶ If you ascertain that it contains sedimentary materials, Caution.
you must desludge the installation.
Risk of material damage if the heating
▶ Use a magnetic rod to check whether it contains mag-
water is treated with unsuitable additives.
netite (iron oxide).
▶ If you ascertain that it contains magnetite, clean the in- Unsuitable additives may cause changes in
stallation and apply suitable corrosion-inhibition meas- the components, noises in heating mode and
ures, or fit a magnetic filter. possibly subsequent damage.
▶ Check the pH value of the removed water at 25 °C.
▶ If the value is below 6.5 or above 8.5, clean the installa-
▶ Do not use any unsuitable antifreeze and
corrosion inhibitors, biocides or sealants.
tion and treat the heating water.
▶ Ensure that oxygen cannot get into the heating water.
No incompatibility with our products has been detected to
Checking the filling and supplementary water date with proper use of the following additives.
▶ Before filling the installation, measure the hardness of the
filling and supplementary water. ▶ When using additives, follow the manufacturer's instruc-
tions without exception.
Treating the filling and supplementary water
We accept no liability for the compatibility of any additive or
▶ Observe all applicable national regulations and technical
its effectiveness in the rest of the heating system.
rules when treating the filling and supplementary water.
Additives for cleaning measures (subsequent
Provided the national regulations and technical rules do not
stipulate more stringent requirements, the following applies:
flushing required)
– Adey MC3+
You must treat the heating water in the following cases
– Adey MC5
– If the entire filling and supplementary water quantity dur- – Fernox F3
ing the operating life of the system exceeds three times – Sentinel X 300
the nominal volume of the heating installation, or
– Sentinel X 400
– If the guideline values listed in the following table are not
met, or Additives intended to remain permanently in the
– If the pH value of the heating water is less than 6.5 or installation
more than 8.5. – Adey MC1+
– Fernox F1
– Fernox F2
– Sentinel X 100
– Sentinel X 200
5. Clip the lower section of the condensate trap (1) into the
9.7 Filling and purging the heating installation
upper section of the condensate trap (2).
Preliminary work
9.4 Switching on the product ▶ Flush the heating installation through.
▶ Switch on the product via the main switch installed on-
site.
Condition: If the noise persists in the boiler 25.7 2.72 2.86 2.45
28.6 3.03 3.18 2.73
▶ Purge the product again by activating check programme
30.6 3.24 3.40 2.92
P.00.
35.7 3.78 3.97 3.40
9.8 Filling the domestic hot water circuit
Condition: Gas flow rate not in the permissible range
1. Open the water tap to fill the domestic hot water circuit.
2. Close the water tap once the appropriate volume of ▶ Check all of the piping and ensure that the gas flow rates
water has flowed out. are correct.
◁ The domestic hot water circuit is filled. ▶ Only put the product into operation once the gas flow
3. Check all connections and the entire system for leak- rates have been corrected.
tightness. Condition: Gas flow rate in the permissible range
9.9 Checking the gas setting ▶ End the check programme P.01.
Only a qualified competent person is authorised to imple- ▶ Allow the boiler to cool down by allowing pump overrun to
ment the settings on the gas valve assembly. operate for a minimum of 2 minutes.
▶ Record the boiler maximum gas flow rate onto the
Each destroyed seal must be replaced. Benchmark gas boiler commissioning checklist.
The CO₂ adjusting screw must be sealed.
Never modify the factory setting of the gas pressure regu- 9.9.3 Checking the gas connection pressure (gas
lator of the gas valve assembly. flow pressure)
9.11.1 Checking the heating mode TFlow Set maximum burner anti-cycling time
(target) [min]
1. Activate the heating mode on the user interface.
[°C] 35 40 45 50 55 60
2. Turn all thermostatic valves on the radiators until they
are fully open. 30 29.0 33.0 37.0 41.0 45.0 49.5
3. Allow the product to operate for at least 15 minutes. 35 25.5 29.5 33.0 36.5 40.5 44.0
4. Fill and purge the heating installation. (→ Page 25) 40 22.5 26.0 29.0 32.0 35.5 38.5
5. Call up the status codes. (→ Page 23)
45 19.5 22.5 25.0 27.5 30.5 33.0
Status codes – Overview (→ Page 43)
50 16.5 18.5 21.0 23.5 25.5 28.0
◁ If the product is working correctly, the display shows
S.04. 55 13.5 15.0 17.0 19.0 20.5 22.5
60 10.5 11.5 13.0 14.5 15.5 17.0
9.11.2 Checking the hot water generation 65 7.0 8.0 9.0 10.0 11.0 11.5
1. Activate the hot water handling mode on the user 70 4.0 4.5 5.0 5.5 6.0 6.5
interface.
75 1.0 1.0 1.0 1.0 1.0 1.0
2. Open a hot water valve completely.
3. Call up the status codes. (→ Page 23)
10.1.2 Resetting the remaining burner anti-cycling
Status codes – Overview (→ Page 43)
time
◁ If the product is working correctly, the display shows
S.14. ▶ Press .
350
Caution.
300
Risk of material damage caused by incor-
1 rect setting of the high-efficiency pump
250
200 If the pressure at the bypass valve is in-
150
creased (by turning it clockwise) and the
pump output is set to less than 100%, the
100
product may not operate correctly.
50 2
0 ▶ In this case, set the pump output to
0 200 400 600 800 1000 1200 A 5 = 100% using diagnostics parameter
d.14.
A Remaining feed head 1 Max. PWM
[mbar]
2 Min. PWM 1. Remove the front casing. (→ Page 16)
B Flow rate [l/h]
30c:
B
450
400
350
300 1 1
250
200
150
100 2
50
2. Regulate the pressure using the adjusting screw (1).
0 Position of the adjusting
0 200 400 600 800 1000 1200 A Notes/application
screw
If the radiators do not heat
A Remaining feed head 1 Max. PWM up sufficiently at the factory
Right-hand stop (screwed
[mbar] setting. In this case, you must
2 Min. PWM all the way in)
B Flow rate [l/h] set the pump to the maximum
speed.
35c: Mid-position (six anti-
Factory setting
clockwise rotations)
A 8
B
2 10. Remove the burner seals (7) and the burner (8).
11. Check the burner and the heat exchanger for damage
and dirt.
12. If necessary, clean or replace the components accord-
D ing to the following sections.
13. Install the two new burner seals.
5
1. Protect the open electronics box from spraying water.
4 2. Clean the ribs of the heat exchanger (1) with water.
◁ The water runs out into the condensate tray.
1
6
D B
1
C
B
A
1. Drain the product. (→ Page 34)
2. Remove the temperature sensor (1).
3
3. Remove the upper clip (2).
1
Note
Check whether the float is present in the 4. Remove the lower clip (3).
condensate trap. 5. Remove the flow pipe (4).
6. Remove the heating filter (5) and clean it.
6. Clip the lower section of the condensate trap (1) into the 7. Reinstall the components in the reverse order.
upper section of the condensate trap (2).
12.13 Installing the gas-air mixture unit
12.11 Cleaning the strainer in the cold water inlet 1. Install the burner.
1. Close the main cold water supply line. 2. Install two new burner seals in the burner hood.
2. Drain the product on the domestic hot water side. 3. Install the gas-air mixture unit.
3. Remove the connector from the connection for the pro- 4. Tighten the screws in a cross-wise pattern until the
duct's cold water pipe. burner flange fits closely and uniformly onto the mat-
4. Clean the strainer in the cold water inlet without remov- ing surfaces.
ing it. – Tightening torque: 7 Nm, if a torque spanner is
available
5. Install the flue pipe.
6. Install the air intake pipe.
13.5.3 Replacing the heat exchanger 8. Remove the upper clip (1).
1. Remove the front casing. (→ Page 16) 9. Remove the lower clip (3).
2. Remove the gas-air mixture unit. (→ Page 31) 10. Remove the return pipe (2).
1 A A
2
3. Remove the gas pipe (1). 11. Remove the clip underneath the condensate tray (1).
12. Undo the four screws (2).
1
2
A
1 C
2 4
A
2
B
3
B
B
1
D
A
3 C
C
B
2. Undo the nut (3).
3. Remove both screws on the support plate (1). A
4. Remove the support plate .
5. Pull out the expansion vessel (2) towards the front.
6. Insert the new expansion vessel into the product.
7. Screw the new expansion vessel to the water connec-
tion. To do this, use a new seal. A
8. Attach the support plate using both screws.
9. Fill and purge the product (→ Page 25)and, if required,
the heating installation.
1
14 Decommissioning the product
▶ Switch off the product.
2 ▶ Disconnect the product from the electrical installation.
▶ Close the gas stopcock.
▶ Close the cold-water isolation valve.
▶ Drain the product. (→ Page 34)
Note
For those appliances which are not part of an annual service agreement/policy, maintenance must be carried out
at least every 5 years.
1 Record all of the analysis results in the Benchmark service record in Annually
these instructions
2 Ask the end user whether any significant problems occur when operating Annually
the product
3 Use the diagnostics system to check the product's fault history Annually
4 Visually inspect whether the air/flue pipe and its opening have been in- Annually
stalled correctly in accordance with the set-up instructions
5 Check that the unit has been installed correctly and the connections have Annually
been secured
6 Check all of the connections for tightness Annually
7 Check that the condensate pipe is in good condition, that it is leak-tight Annually
and that the drain is correct
8 Check whether all of the externally routed condensate pipes are dimen- Annually
sioned correctly and have been insulated sufficiently (frost protection)
9 Check whether the gas flow rate corresponds with the specifications on Annually
the data plate and lies within the tolerances specified in these instructions
10 If the gas flow rate lies outside of the tolerances specified in these in- Annually
structions, eliminate the fault in accordance with the regulations and the
current technology
11 Check the general condition of the product and, if required, eliminate any Annually
faults that are found
12 Carry out the combustion analysis: Measure the CO content, CO₂ content Annually
and the CO/CO₂ ratio. For products with a rear air/flue connection: The
combustion analysis can only be carried out when the unit casing has
been removed; it is not necessary to test these products for flue gas recir-
culation
13 Check the product's recirculation at the supply air test point on the air/flue Annually
pipe. If required, inspect the entire air/flue system and, if necessary, cor-
rect the fault
14 Disconnect the product from the electrical installation Annually
15 Check and, if required, correct the electrical installation Annually
16 Remove the unit casing, check the condition of all of the functional com- Annually
ponents, in particular for leaks, corrosion, rust, etc. and, if required, repair
any damage
17 Visual inspection of the heat exchanger and burner seals Annually
18 Carefully clean the inside of the product: The air passages to the burner Annually
must be clear and clean
19 Close the installation's gas stopcock and, if required, service valves Annually
20 Check the quality of the heating water: Clarity (clouding), correct inhibitor Annually
and pH value
21 Removing the gas-air mixture unit at regular intervals 31
22 Checking the burner at regular intervals 32
23 Cleaning the heat exchanger at regular intervals 32
24 Check and, if required, replace the insulating mat in the burner area at regular intervals
25 Installing the gas-air mixture unit at regular intervals 33
26 Cleaning the condensate trap Annually 33
27 Filling the condensate trap Annually 25
Note
Since the code table is used for various products, some codes may not be visible for the product in question.
Note
Since the code table is used for various products, some codes may not be visible for the product in question.
Note
Since the code table is used for various products, some codes may not be visible for the product in question.
X35
3
Burner off
RT 24V
X106
eBUS 4
X51
13
1 5
2 X51 2
6
1
5
2
10
X20 11
4
1 6
15
3
2 M
4
16
5
1
3
9
1 X51 X35
1
7
X106
8
X40 X51 X32 X35 – + 8
Burner 24V= 6
off RT BUS 17
7
4 M
3
18 1 9
X41
X2 14
24V
X90 11
1
4
13
X2 3
10
3
X20 6
1
X22
3
2
2
20
3
10
2
19
1
11
X30
1
X21 X21
4
3
2
13
FUS
L 24V
X14
N
L 230V~
X1
X14 N
X12
230V~
RT
RT 230Vac L
230Vac
12
X1 N N
L L
14
X35
3
Burner off
RT 24V
X106
eBUS 4
X51
13
1 5
2 X51 2
6
1
5
2
10
X20 11
4
1 8 1 6
15
3
2 7 2 M
4 6 3
16
5 5 4
1
3
9
1 X51 X35
1
7
X106
8
X40 X51 X32 X35 – + 8
Burner 24V= 6
off RT BUS 17
7
4 M
3
18 1 9
X41
X2 14
24V
X90 11
1
4
13
X2 3
10
3
X20 6
1
X22
3
2
2
20
3
10
2
19
1
X30 11
1
X21 X21
4
3
2
L
13
FUS
X12 N
L
24V
X14
N
X14
L
N 230V~
X1
X12
230V~
RT 230Vac L
RT
230Vac
X1 N N
L L
14 12
To instigate the boiler warranty the boiler needs to be registered with the
manufacturer within one month of the installation. The warranty rests with the
end-user (consumer), and they should be made aware it is ultimately their
responsibility to register with the manufacturer, within the allotted time period.
www.hhic.co.uk
This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating
compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
Failure to install and commission according to the manufacturers’ instructions and complete this Benchmark Commissioning Checklist will invalidate the
warranty. This does not affect the customer’s statutory rights.
* All installations in England and Wales must be notified to Local Authority Building Control (LABC) either directly or through a
Competent Persons Scheme. A Building Regulations Compliance Certificate will then be issued to the customer.
www.centralheating.co.uk
Time, temperature control and boiler interlock provided for central heating and hot water Yes
Boiler Plus requirements (tick the appropriate box(s))
Time and temperature control to hot water Cylinder thermostat and programmer/timer Combination boiler
Gas rate (for combination boilers complete DHW mode gas rate) m3/hr or ft3/hr
www.centralheating.co.uk
Service provider
When completing a service record (as below), please ensure you have carried out the service as described in the manufacturers’ instructions. Always use the
SERVICE/INTERIM WORK ON BOILER delete as appropriate Date: SERVICE/INTERIM WORK ON BOILER delete as appropriate Date:
undertaken in accordance with manufacturers’ yes undertaken in accordance with manufacturers’ yes
instructions, and readings are correct?” instructions, and readings are correct?”
System inhibitor concentration has been checked and System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593 yes n/a appropriate action taken, in accordance with BS 7593 yes n/a
and boiler manufacturers’ instructions. * and boiler manufacturers’ instructions. *
Comments: Comments:
Signature: Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component. attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER delete as appropriate Date: SERVICE/INTERIM WORK ON BOILER delete as appropriate Date:
undertaken in accordance with manufacturers’ yes undertaken in accordance with manufacturers’ yes
instructions, and readings are correct?” instructions, and readings are correct?”
System inhibitor concentration has been checked and System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593 yes n/a appropriate action taken, in accordance with BS 7593 yes n/a
and boiler manufacturers’ instructions. * and boiler manufacturers’ instructions. *
Comments: Comments:
Signature: Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component. attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER delete as appropriate Date: SERVICE/INTERIM WORK ON BOILER delete as appropriate Date:
undertaken in accordance with manufacturers’ yes undertaken in accordance with manufacturers’ yes
instructions, and readings are correct?” instructions, and readings are correct?”
System inhibitor concentration has been checked and System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593 yes n/a appropriate action taken, in accordance with BS 7593 yes n/a
and boiler manufacturers’ instructions. * and boiler manufacturers’ instructions. *
Comments: Comments:
Signature: Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component. attendance visit was in between annual services to attend a non-water facing component.
www.centralheating.co.uk
Service provider
When completing a service record (as below), please ensure you have carried out the service as described in the manufacturers’ instructions. Always use the
SERVICE/INTERIM WORK ON BOILER delete as appropriate Date: SERVICE/INTERIM WORK ON BOILER delete as appropriate Date:
undertaken in accordance with manufacturers’ yes undertaken in accordance with manufacturers’ yes
instructions, and readings are correct?” instructions, and readings are correct?”
System inhibitor concentration has been checked and System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593 yes n/a appropriate action taken, in accordance with BS 7593 yes n/a
and boiler manufacturers’ instructions. * and boiler manufacturers’ instructions. *
Comments: Comments:
Signature: Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component. attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER delete as appropriate Date: SERVICE/INTERIM WORK ON BOILER delete as appropriate Date:
undertaken in accordance with manufacturers’ yes undertaken in accordance with manufacturers’ yes
instructions, and readings are correct?” instructions, and readings are correct?”
System inhibitor concentration has been checked and System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593 yes n/a appropriate action taken, in accordance with BS 7593 yes n/a
and boiler manufacturers’ instructions. * and boiler manufacturers’ instructions. *
Comments: Comments:
Signature: Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component. attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER delete as appropriate Date: SERVICE/INTERIM WORK ON BOILER delete as appropriate Date:
undertaken in accordance with manufacturers’ yes undertaken in accordance with manufacturers’ yes
instructions, and readings are correct?” instructions, and readings are correct?”
System inhibitor concentration has been checked and System inhibitor concentration has been checked and
appropriate action taken, in accordance with BS 7593 yes n/a appropriate action taken, in accordance with BS 7593 yes n/a
and boiler manufacturers’ instructions. * and boiler manufacturers’ instructions. *
Comments: Comments:
Signature: Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers
attendance visit was in between annual services to attend a non-water facing component. attendance visit was in between annual services to attend a non-water facing component.
www.centralheating.co.uk
Is
O2 20.6% YES
and
CO2 < 0.2%
NO
TURN OFF APPLIANCE AND CALL CHECK CO AND COMBUSTION RATIO AT MAX. RATE
MANUFACTURER’S TECHNICAL HELPLINE With boiler still set at maximum rate, insert analyser probe into flue gas
FOR ADVICE. sampling point. Allow readings to stabilise before recording.
THE APPLIANCE MUST NOT BE NOTE - If no flue gas sampling point is present and the correct procedure is
COMMISSIONED UNTIL PROBLEMS ARE not specified in the manual, consult boiler manufacturer for guidance.
IDENTIFIED AND RESOLVED.
Is
CO less than
Check all seals around the appliance burner, NO 350ppm and
internal flue seals, door and case seals. CO/CO2 ratio
Rectify where necessary. less than 0.004
Is YES
CO less than
335ppm YES
and
CO/CO2 ratio less
than 0.004
SET BOILER TO MINIMUM RATE
In accordance with boiler instructions, set boiler to operate at minimum rate (to
minimum load condition). Allow sufficient time for combustion to stabilise.
NO NOTE - If manufacturer’s instructions do not specify how to set boiler to minimum
rate contact Technical Helpline for advice.
Publisher/manufacturer
Vaillant GmbH
Berghauser Str. 40 D-42859 Remscheid
Tel. +492191 18 0 Fax +492191 18 2810
info@vaillant.de www.vaillant.de
© These instructions, or parts thereof, are protected by copyright and may be reproduced or distributed only with
the manufacturer's written consent.
Subject to technical modifications.