Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Solid State Switches

P/N 8-078-393-00
effective 5/2/03

Installation Instructions and Wiring Diagrams for All Models and Ranges

Contents
Model and Ranges . . . . . . . . . . . . . . . . . . . . . . . .1-2 Installation Instructions for SINPAC Switches . . .2-3 Wiring Diagrams for SINPAC Switches . . . . . . . .4-5 Procedure for Checking SINPAC Switches . . . . . . .5 Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . .6-7 Distributors of SINPAC Switches . . . . . . . . . . . . . . .7

Models and Ranges


Typical Max. Series Motor hp 1/3 1/3 1/3 PV Series Split Phase Motors Only 1/3 1/2 1/2 1/2 1/2 1/2 3/4 3/4 1/2 1/2 1/2 1/2 1/2 1/2 1 1 CV Series Capacitor Start Motors Only 1 1 1 1 2 2 2 2 2 2 3 3 12 12 12 12 20 20 8 8 8 8 8 8 6 6 6 6 6 6 20 20 20 20 20 20 25 25 12/6 12/6 12/6 12/6 20/10 20/10 8/4 8/4 8/4 8/4 8/4 8/4 12/6 12/6 12/6 12/6 12/6 12/6 20/10 20/10 20/10 20/10 20/10 20/10 25/12.5 25/12.5 Switch Rating & Permissible Catalog Maximum Number Start Circuit Current 115 115/230 230 Volts Volts Volts (amps) 16 115 PV-16-10 8 8/4 Start Circuit Voltage Typical Full Load Motor Nameplate Current Rating (amps) 8 8 8 8/4 8/4 8/4 8 16 16 16 16 16 16 16 16 40 40 16 16 16 16 16 16 25 25 25 25 25 25 40 40 40 40 40 40 50 50 115 115 115 PV-25-10 115 Part Number Pkg. Style Series Typical Max. Motor hp 3 3 3 3 1/2 1/2 1/2 1/2 1/2 1/2 VR Series Capacitor Start/ Capacitor Run Motors Only 2 2 2 2 2 2 3 3 3 3 3 3 CVR Series Cap Start & Capacitor Start/Cap. Run Motors Only 2CV Series Capacitor Start Motors Only 1 3-5 3-5 3-5 3 3 5 5 Switch Rating & Permissible Catalog Part Number Maximum Number Start Circuit Current 115 115/230 230 Volts Volts Volts (amps) 25 25/12.5 115 CV-50-147 4-7-21050-12-UB1 147 50 Start Circuit Voltage Typical Full Load Motor Nameplate Current Rating (amps) 25 25 25 8 8 8 8 8 8 20 20 20 20 20 20 25 25 25 25 25 25 50 50 50 25/12.5 25/12.5 25/12.5 8/4 8/4 8/4 8/4 8/4 8/4 20/10 20/10 20/10 20/10 20/10 20/10 25/12.5 25/12.5 25/12.5 25/12.5 25/12.5 25/12.5 50/25 50/25 50/25 17.5 17.5 25 25 50 50 50 16 16 16 16 16 16 40 40 40 40 40 40 50 50 50 50 50 50 80 80 80 35 35 50 50 115 115 115 115 115 115 115 115 115 115 115 115 CV-50-165 4-7-21050-12-UO1 165 4-7-21050-20-UO1 165 30 30 37 37 37 37 30 30 37 37 37 37 30 30 37 37 37 37 30 37 37 70 70 70 70 4-7-71016-19-UA1 130 4-7-71016-19-UB1 147 4-7-71016-19-UO1 165 4-7-71040-19-UA1 130 4-7-71040-19-UB1 147 4-7-71040-19-UO1 165 4-7-71050-19-UA1 130 4-7-71050-19-UB1 147 4-7-71050-19-UO1 165 115 VR-16-130 4-7-71016-12-UA1 130 115 VR-16-147 4-7-71016-12-UB1 147 115 VR-16-165 4-7-71016-12-UO1 165 115 VR-40-130 4-7-71040-12-UA1 130 115 VR-40-147 4-7-71040-12-UB1 147 115 VR-40-165 4-7-71040-12-UO1 165 115 VR-50-130 4-7-71050-12-UA1 130 115 VR-50-147 4-7-71050-12-UB1 147 115 VR-50-165 4-7-71050-12-UO1 165 Cut Out Voltage Typical Cut Out Voltage Typical Cut Out Voltage Typical Cut Out Voltage Typical Pkg. Style

4-7-11016-11-UF1 4-7-11016-20-UF1 4-7-11016-20-UO1 4-7-11025-11-UF1 4-7-11025-20-UF1

10 10 30 30 60 10 10 30 30 30 30

11 20 11 20 11 11 20 11 20 11 20 30 30 37 37 37 37 30 30 37 37 37 37 30 30 37 37 37 37 30 30

115 PV-16-30 4-7-11016-11-UO1 230 2PV-16-60 4-7-12016-11-NH1

CV Series Capacitor Start Motors Only

37 37 37 37 12 19 12 19 12 19 12 19 12 19 12 19 12 19 12 19 12 19 15 15 15 15 15 15 15

4-7-21050-20-UB1 147

115 PV-25-30 4-7-11025-11-UO1 4-7-11025-20-UO1 115 115 PV-40-30 4-7-11040-11-UO1 115 4-7-11040-20-UO1 115 115 115 115

115 CV-16-130 4-7-21016-11-UA1 130 4-7-21016-20-UA1 130 4-7-21016-20-UB1 147 4-7-21016-20-UO1 165 4-7-21025-20-UA1 130 115 CV-16-147 4-7-21016-11-UB1 147 115 CV-16-165 4-7-21016-11-UO2 165 115 CV-25-130 4-7-21025-11-UA1 130 115 CV-25-147 4-7-21025-11-UB1 147 4-7-21025-20-UB1 147 115 115 CV-25-165 4-7-21025-11-UO2 165 115 4-7-21025-20-UO1 165 115 CV-40-130 4-7-21040-11-UA1 130 115 115 115 115 4-7-21040-20-UA1 130 4-7-21040-20-UB1 147 4-7-21040-20-UO1 165 4-7-21050-20-UA1 130 115 CV-40-147 4-7-21040-11-UB1 147 115 CV-40-165 4-7-21040-11-UO2 165 115 CV-50-130 4-7-21050-12-UA1 130

115 CVR-80-130 4-7-41080-15-NA1 130 115 CVR-80-147 4-7-41080-15-NB1 147 115 CVR-80-165 4-7-41080-15-NO1 165 230 2CV-35-260 4-7-22035-15-UC1 260 230 2CV-35-310 4-7-22035-15-UO1 310 230 2CV-50-260 4-7-22050-15-UC1 260 230 2CV-50-310 4-7-22050-15-UO1 310

Models and Ranges (continued)


Typical Full Load Switch Rating Typical Motor Nameplate & Permissible Current Rating Maximum Max. Series (amps) Motor Start Circuit Current hp 115 115/230 230 (amps) Volts Volts Volts 2VR Series Capacitor Start/Cap. Run Motors Only 2CVR Series Capacitor Start and Capacitor Start/Cap. Run Motors Only 3 3 5 5 7.5 17.5 17.5 25 25 35 35 35 50 50 70 Catalog Number Part Number Pkg. Style

230 2VR-35-260 4-7-72035-15-UC1 260 230 2VR-35-310 4-7-72035-15-UO1 310 230 2VR-50-260 4-7-72050-15-UC1 260 230 2VR-50-310 4-7-72050-15-UO1 310 230 2CVR-70-260 4-7-42070-17-UC1 260

70 70 70 70 70

15 15 15 15 17

7.5 1/2 12 12 12 20 20 20 12/6 12/6 12/6 20/10 20/10 20/10

35

70 25 25 25 40 40 40

230 2CVR-70-310 4-7-42070-17UO1 310 115 115 115 115 115 115 IR-25-130 4-7-51025-15-UA1 130 IR-25-147 4-7-51025-15-UB1 147 IR-25-165 4-7-51025-15-UO1 165 IR-40-130 4-7-51040-15-UA1 130 IR-40-147 4-7-51040-15-UB1 147 IR-40-165 4-7-51040-15-UO1 165

70 30 33 37 30 33 37

17 15 15 15 15 15 15

IR Series Instant Reverse Capacitor Start Motors Only

1/2 1/2 2 2 2

comparator. The SINPAC Switch interrupts the start capacitor current (between terminals 2 and 3) after the motor has accelerated to a speed in which the cut out voltage has been reached, generally 75% to 80% of synchronous motor speed. A triac or inverse parallel SCRs provides the function referred to as cut out. Once the start circuit is cut out the main winding accelerates the motor rotor up to its running speed. When an overload drops the motor speed to approximately 50% of synchronous speed the switch automatically reconnects the motor start circuit. The SINPAC Switch constantly monitors the start or auxiliary winding for cut in voltage and will reconnect the start circuit once cut in voltage is reached.

c) High ambients: Ambients greater than 55C. Note: Higher rated current switches can be used in place of lower rated switches within the same series. 5. The motor must generate a voltage across the start or auxiliary winding that is 20% greater than the SINPAC Switch cut out/cut in voltage rating.

Cut Out Voltage Typical Cut In Voltage Typical

Start Circuit Voltage

Capacitor Start and Capacitor Start/ Capacitor Run Motors


To determine the most appropriate SINPAC Switch cut out voltage rating for the particular motor application, the voltage across the motor start or auxiliary winding must be measured. This may be accomplished in the following manner: 1. Prepare the motor wiring for connection of the SINPAC Switch as shown in the Wiring Diagrams for SINPAC Switches section of this publication. Secure the motor to a firm mounting surface. 2. Connect the lead wire that is to be connected to SINPAC Switch terminal #2 securely to the lead wire that is to be connected to SINPAC Switch terminal #3. 3. Connect an AC voltmeter across the lead wires that are to be connected to SINPAC Switch terminals #1 and #4. 4. Apply power to the motor. Observe and record the voltage across the motor start or auxiliary winding, as indicated by the AC voltmeter, with the motor operating near synchronous speed. CAUTION: Measurement of the start or auxiliary winding voltage must be done quickly to prevent damage to the start capacitor, motor winding or SINPAC Switch! 5. Multiply the measured voltage by 0.8 (80%). Select a SINPAC Switch having a cut out voltage rating equal to or less than this number. Capacitor Start and Capacitor Start/ Capacitor Run Motors Voltage Across SINPAC Measured Cut Out
Voltage >226V >200-225V 176-200V 150-175V <150V >492V 370-492V 300-369V <300V Switch Terminals 1 & 2 115V 115V 115V 115V 115V 230V 230V 230V 230V Voltage Rating 180V 165V 147V 130V * 410V 310V 260V *

Selection Procedure

Installation Instructions for SINPAC Switches


UL Recognition
Most SINPAC Switches are recognized under the component program of Underwriters Laboratories E-71115. In addition, all switches have an internal surge protection which meets UL244A Specification and CSR Certification LR-6254, and are tested to the requirement of IEEE C62.41-1991, Category A3.

Construction
SINPAC Switches are potted and completely sealed making them impervious to dust, dirt and moisture. It can be immersed in electric grade oil as used in submersible pumps. The unique speed sensing circuit provides a universal design which allows a few switches to work in most standard single-phase motor applications regardless of nature.

Operation
The Stearns SINPAC Switch samples the voltage across the motor start winding (terminals 1 and 4) then it is fed into a

CAUTION: SINPAC Switches are line voltage compensated. Changes in the line voltage within 10% of nominal 115 or 230 Vac will not affect system operation. Operation of the motor at line voltages less than -10% of nominal can result in reduced motor running speeds and failure of the SINPAC Switch to disconnect the start circuit. 1. Be sure switch series matches motor type. 2. Be sure switch voltage rating matches the motor start circuit voltage. 3. Selection should be based on actual measurement of start circuit current. 4. SINPAC Switch current rating must meet or exceed the motor start circuit current requirement. Always select a SINPAC Switch with the next higher current rating for: a) High cycling applications: Stop and start rates greater than 4 times/minute. b) Long acceleration times: Greater than 5 seconds.
2

*Consult factory

Installation Instructions for SINPAC Switches (continued)


Split Phase Motors
To determine the most appropriate SINPAC Switch cut in voltage rating for the particular motor application, the voltage across the motor start winding must be measured. This may be accomplished in the following manner: 1. Prepare the motor wiring for connection of the SINPAC Switch as shown in the Wiring Diagrams for SINPAC Switches section of this publication. Secure the motor to a firm mounting surface. 2. Insulate the lead wire that is to be connected to SINPAC Switch terminal #2. 3. Connect an AC voltmeter across the lead wires that are to be connected to SINPAC Switch terminals #1 and #3. 4. Apply power to the motor. Carefully rotate the motor shaft to initiate rotation. Observe and record the voltage across the motor start winding, as indicated by the AC voltmeter, with the motor operating near synchronous speed. 5. Multiply the measured voltage by 0.8 (80%). Select a SINPAC Switch having cut in voltage rating closest to this number. Split Phase Motors
Measured Voltage >40V 15-40V <15V >70V <70V Voltage Across SINPAC Switch Cut In Voltage Rating Terminals 1 & 2 115V 30V 115V 10V 115V * 230V 60V 230V *

*Consult factory

Important
Please read these instructions carefully before installing, operating, or servicing your SINPAC Switch. Failure to comply with these instructions could cause injury to personnel and/or damage to property if the switch is installed or operated incorrectly. For definition of limited warranty/ liability, contact Rexnord Corporation, Stearns Division, 5150 S. International Dr.,Cudahy, Wisconsin 53110, (414) 272-1100. Caution: Application of 230 Vac to the line input terminals (1 and 2) of a 115 Vac rated SINPAC Switch will result in immediate switch failure. The switch may rupture and emit smoke.

Initial Inspection and Handling


Upon receipt, check for package damage. Note any signs of damage on appropriate shipper forms. Upon opening package, if concealed damage is found, immediately file a claim with carrier.

Check the label to verify that data conforms to specifications of ordered switch and the connection diagram agrees with labeling. Caution 1. Installation and servicing must be made in compliance with all local safety codes including Occupational safety and Health Act (OSHA). All wiring and electrical connections must comply with the National Electric Code (NEC) and local electric codes in effect. 2. To prevent an electrical hazard, disconnect power source before working on the motor. If power disconnect point is out of sight, lock disconnect in the off position and tag to prevent accidental application of power. 3. Make certain power source conforms to the requirements specified on the SINPAC Switch nameplate. 4. Installation and servicing should be performed only by qualified personnel familiar with the operation of the SINPAC Switch. 5. Determine what type of start switch the motor presently has: a) Externally mounted electronic switch go to Step 6. b) Internally mounted electronic switch go to Step 6. c) Externally or internally mounted mechanical switch it is not necessary to remove the existing centrifugal switch actuating mechanism, but if feasible, it should be removed as it is no longer needed, and can cause future mechanical problems in the motor should the mechanism fail. Follow the manufacturers recommendation when removing the shaft end bearing, if necessary, to take off the centrifugal actuator. 6. Remove the existing electronic switch. Determine the existing wiring diagram. Mark the existing wires and determine which wires can be reused for installation of the SINPAC Switch. Select a location in the motor conduit box or endbell for mounting the SINPAC Switch. If a metal enclosure version of SINPAC Switch is being used, the switch with SINPAC Switch gasket may be mounted on an external mounting surface such as the exterior of the conduit box. Plastic enclosure versions of the SINPAC Switch should be mounted internally, within the conduit box, or externally, under a capacitor housing. IMPORTANT: SINPAC Switch in a metal enclosure must have the metal enclosure grounded.

The temperature at the mounting location should not exceed 65C (149F). (2CVR temperature should not exceed 55C.) TEFC/TENV motors require external mounting of SINPAC Switch. 7. Refer to motor manufacturers wiring diagram to aid in identifying terminal locations for the start winding switch, start winding, start and run capacitors (if needed) and AC line. 8 Connect the SINPAC circuit per the connection diagram (on Pages 9-11) using insulated terminals. If the connections are made incorrectly, the result will be no starting torque and possible damage to the circuit and/or motor. CAUTION: Be sure that appropriate insulation is used between the terminals of the switch and the body of the motor or conduit box. If mounted external to motor, always use gasket supplied with kit. 9. DO NOT USE a Variac to gradually increase the voltage to the motor starting circuit when SINPAC Switch is installed. 10. Reassemble the motor with SINPAC Switch installed, so as to not damage lead wires. 11. If the motor fails to start or the start winding does not cut out properly, see Troubleshooting Guide (Page 13-14). 12. Hipot test procedures: Motors 250 Volts or Less and 1/2 Horsepower or Less The motor, equipped with SINPAC Switch, shall be tested for dielectric withstand (hipot), by the application of a 1200 volt sinusoidal potential, in the range of 40-70 Hz, for 1 second. During the test, each lead of the primary motor wiring, accessible at the connection board or conduit box, are to be connected together and to one terminal of the test equipment, and the second test equipment terminal is to be connected to the accessible dead metal. Motors 250 Volts or Less and More Than 1/2 Horsepower The motor, equipped with SINPAC Switch, shall be tested for dielectric withstand (hipot), by the application of an 1800 volt sinusoidal potential, in the range of 40-70 Hz, for 1 second. During the test, each lead of the primary motor wiring, accessible at the connection board or conduit box, are to be connected together and to one terminal of the test equipment, and the second test equipment terminal is to be connected to the accessible dead metal. 13. CAUTION: The terminals of the SINPAC Switch should not be used as the junction for this field wiring.

Wiring Diagrams for SINPAC Switches


Catalog Number PV-16 PV-25 PV-40 Connect to Split Phase Motors Only SINPAC Switch Rating 115 Volts 115 Volt 50/60 Hz Motor Operation 230 Volt 50/60 Hz Motor Operation Catalog Number 2CV-35 2CV-50 Connect to Capacitor Start Motors Only 2VR-35 2VR-50 Connect to Capacitor Start/ Capacitor Run Motors SINPAC Switch Rating 230 Volts Not Applicable 115 Volt 50/60 Hz Motor Operation 230Volt 50/60 Hz Motor Operation

321

230 Volts

230 Volts 2PV-16 Connect to Split Phase Motors Only

Not Applicable

Not Applicable

230 V operation

321

230 Volts 2CVR-70 Connect to Capacitor Start Motors Not Applicable

CV-16 CV-25 CV-40 CV-50 CVR-40 CVR-50 Connect to Capacitor Start Motors Only VR-16 VR-40 VR-50 CVR-40 CVR-50 CVR-80 Connect to Cap. Start/ Capacitor Run Motors

115 Volts

115 Volts

2CVR-70 Connect to Capacitor Start/ Capacitor Run Motors

230 Volts

Not Applicable

CS Start Capacitor, M Motor Main Winding,

CR run Capacitor, ST Motor Start Winding

Wiring Diagrams for SINPAC Switches (continued)


Catalog Number SINPAC Switch Rating 115 Volt 50/60 Hz Motor Operation 115 Volt Operation Dual Voltage Motor Using Two Full Voltage 2 or 3 Pole Single-Phase Reversing Contactors with Mechanical Interlock (Electrical Interlock Optional) 230 Volt 50/60 Hz Motor Operation 230 Volt Operation Dual Voltage Motor Using Two Full Voltage 2 or 3 Pole Single-Phase Reversing Contactors with Mechanical Interlock (Electrical Interlock Optional)

Procedure for Checking SINPAC Switches


1. Disconnect the SINPAC Switch from the motor and measure the resistance between terminals 2 and 3. If the resistance is less than 500K, the SINPAC Switch has been shorted or damaged, and must be replaced. If the resistance is infinite, the switch may not be damaged. CAUTION: Do not use megger to test motor circuit with SINPAC Switch. Proceed to Step 3 if you have a PV switch. 2. If resistance across SINPAC terminal 2 and 3 is greater than 500K and you have a capacitor start, instant reverse, or capacitor start/capacitor run SINPAC Switch, use Diagram 1. Note 3: If the incandescent light (L) fails to illuminate, the SINPAC Switch has been damaged and must be replaced. Note 4: Turn off voltage and disconnect the SINPAC Switch. 3. If resistance across SINPAC terminal 2 and 3 is greater than 500K and you have a split phase SINPAC Switch, use Diagram 2. Diagram 2

IR-25 115 Volts IR-40 Connect to Instant Reverse Capacitor Reversing contacts are not part Start of SINPAC Switch. Motors Only

115 V SINPAC Switch 115 V incandescent light (L) (at least 25 watts) and 115 Vac power source. 230 V SINPAC Switch 230 V incandescent light (L) or two 115 V incandescent light (L) (at least 25 watts) in series and 230 Vac power source. Diagram 1

a) Connect one line of AC power to terminal 1 through a line switch. b) Connect a (25 watt) incandescent light (L) between terminals 1 and 3 of SINPAC Switch. c) Connect other line of AC power to terminal 2 of SINPAC Switch. Note 1: Apply rated AC voltage to the SINPAC Switch. Note 2: If the incandescent light (L) begins to blink after 1/2 second, the SINPAC Switch is operable.

Reversing contacts are not part of SINPAC Switch.

a) Connect one line of AC power to terminal 1 through a line switch. b) Connect incandescent light (L) between terminals 1 and 3 of SINPAC Switch. c) Jumper terminals 1 and 4 of SINPAC Switch. d) Connect other line of AC power to terminal 2 of SINPAC Switch. Note 1: Apply rated AC voltage to the SINPAC Switch. Note 2: The incandescent light (L) will illuminate if the SINPAC Switch is operable.
5

Drum switch is not part of SINPAC Switch.

Reversing contacts are not part of SINPAC Switch.

Note 3: If the incandescent light (L) fails to illuminate or stays illuminated, the SINPAC Switch has been damaged and must be replaced. Both tests must be performed and passed to indicate a minimally good switch. Note 4: Turn off power and disconnect the SINPAC Switch.

CS Start Capacitor, M Motor Main Winding,

CR run Capacitor, ST Motor Start Winding

Troubleshooting Guide
Symptom Possible Cause Motor fails Incorrect connection of to start. SINPAC Switch. Start capacitor open or shorted. Thermal overload opened. Procedure for Checking De-energize. Check the wiring and connection diagram. De-energize motor, discharge, and check capacitor. Corrective Action Reconnect properly. Procedure for Checking Motor fails Wrong series SINPAC Consult selection chart to start. Switch installed 115 V Measure voltage across wires SINPAC Switch connected connected to terminals 1 to 230 V start winding. and 2. Symptom Possible Cause Start capacitor shorted. Corrective Action Change switch Check SINPAC Switch for damage and replace with correct switch.

Replace capacitor.

De-energize motor, discharge Replace capacitor. and check the capacitor. Select proper SINPAC Switch.

Check thermal overload. Wait until cool down. Check motor and SINPAC Check/replace thermal overload. Correct motor and Switch wiring. SINPAC Switch wiring. Remove obstruction. Increase voltage. Replace fuses as required and apply AC line voltage. Check the start winding. Motor may have to be rewound. Infinite resistance would show an open winding or loose connection.

Motor not free to rotate. Check for jam or obstruction. AC line voltage too low. Measure line voltage at the motor terminals. No line voltage. De-energize, check AC line fuses. Check wiring and connection diagram. De-energize and disconnect. Measure the resistance of the start winding.

Start winding induced Perform SINPAC Switch voltage is too low when Selection Procedure as motor reaches desired cut described on Page 12. out speed. The voltage is due to the low windingratio of certain old style motors, foreign motors, converted motors, and special motor designs. AC line voltage too low. Start winding damaged. Measure the AC line voltage across the motor terminals. De-energize and check the start winding. Check the load and motor characteristics. De-energize and check the connection diagram. Be sure that terminal 4 of switch is connected to the junction of the start capacitor and start winding (Pages 9-11).

Increase the AC line voltage. Rewind motor.

Start winding open.

Motor hipot tested with switch installed without motor and SINPAC Switch leads tied together. SINPAC Switch damaged (open circuit).

Replace switch and hipot See Procedure to check SINPAC Switch (Page 12) motor, with installed SINPAC Switch, by tying all motor and SINPAC Switch leads together. See Procedure to check Replace SINPAC Switch SINPAC Switch (Page 12) after checking all of the above possible causes

Mismatch of motor and load. Motor cannot reach cut out speed. Incorrect connection of SINPAC Switch for capacitor start motors.

Reduce load. Replace the motor with an appropriately larger sized motor. Correct wiring.

SINPAC Switch, if it has Check continuity between Ground metal case. a metal enclosure, is SINPAC Switch metal not grounded. case and ground. Current in the start winding is above rating of SINPAC Switch. Remove switch and check Replace SINPAC Switch, the current of the start if damaged. winding. See Procedure to check SINPAC Switch (Page 12).

Damaged SINPAC Switch. See Procedure to check SINPAC Switch (Page 12). SINPAC Switch exposed Check the operating ambient to excessive temperature. temperature of SINPAC Switch. It should be less than 80C (185F).

Replace SINPAC Switch after checking all of above possible causes. Change mounting location of switch. SINPAC Switches can be remotely mounted.

Troubleshooting Guide (continued)


Symptom Upon overload, the start winding is not reenergized (no cut in) Motor worked properly for many cycles of operations (days, weeks, months, years), then failed. Possible Cause Wrong switch installed. (PV Series switch on capacitor start motor.) Procedure for Checking Consult selection chart. Corrective Action Install correct switch.

Distributors of SINPAC Switches


Brownell Electro, Inc. 1-800-774-4643 E.I.S. Holden, Inc. Canada Acme Electric, Ltd. Port Hope, Ontario Canada L1A 3W3 (905) 885-2469 C.B.S. Electrical Insulation Materials, Ltd. Calgary-AB Canada T2G 4C8 (403) 243-9409 Coquitlam-BC Canada V3K 6A9 (604) 945-3634 Edmonton-AB Canada T5H 3E8 (780) 423-4301 Puerto Rico Prowire Inc. San Juan, Puerto Rico (787) 648-1725

Start capacitor failure on capacitor start or cap. start/cap. run motors. Switch failure.

De-energize motor and check capacitor and SINPAC Switch. See Procedure to check SINPAC Switch. Also check start capacitor (Page 12). De-energize motor and check start capacitor and SINPAC Switch.

Replace start capacitor and SINPAC Switch as appropriate. Replace switch.

Atlanta, GA 1-800-447-0135 Charlotte, NC 1-800-235-9491 Denver, CO 1-800-367-8333 Minneapolis, MN 1-800-328-4662 Philadelphia, PA 1-800-367-1212 San Francisco, CA 1-800-347-9611 Torq Corporation Bedford, OH (440) 232-4100 1-800-899-5533

Premature start capacitor failures.

High cycle rate. Excessive motor temperature.

Connect a 15,000 ohm, 2 watt bleeder resistor across the start capacitor(s). If a single start capacitor was originally installed, replace with two start capacitors of twice the capacitance valve and same voltage rating as the original and connected in series.

Copyright 2000 by Rexnord Industries, Inc. Instant reverse motor, upon rapid reverse, will not reverse direction. Wrong switch installed. CV or VR Series installed instead of instant reverse SINPAC Switch. Ensure that instant reverse SINPAC Switch was installed to replace any mechanical instant reversing switch. Install SINPAC instant reverse switch.

Rexnord Industries, Inc. Stearns Division 5150 S. International Dr. Cudahy, Wisconsin 53110 (414) 272-1100 Fax: (414) 277-4364

You might also like