Checklist For Desuperheater Station
Checklist For Desuperheater Station
Checklist For Desuperheater Station
1.4 Whether HOLD Control log report has been prepared if applicable. G-ENGG-009.001-F X
1.9 Whether latest revision of approved template / format has been used G-INST-004.288-F X
1.17 Whether all revision marks on revised document and index are in place. X
a General Standards X
b Norms X
c Contractual Requirements X
d Licensor documents X
Procedure Number G-INST-004.288-A-01 Control Object Check List for Desuperheater Station
Aker Powergas Pvt Ltd Operating System Sheet 2 of 7
Group Head Instruments
Control Object Check List Checklist approved for use by:
Aker Powergas Pvt Ltd
for Desuperheater Station Issued date: 15.03.2011
Whether the turndown ratio of control devices selected has been checked,
2.2 because if they have lower turndown ratio than the desuperheater itself, X X
the overall turndown of the desuperheater station will be reduced
Whether the piping specs and spec breaks properly checked from the
2.5 P&ID? (Piping specs for the desuperheater and for the water control X X
valve may be different)
Procedure Number G-INST-004.288-A-01 Control Object Check List for Desuperheater Station
Aker Powergas Pvt Ltd Operating System Sheet 3 of 7
Group Head Instruments
Control Object Check List Checklist approved for use by:
Aker Powergas Pvt Ltd
for Desuperheater Station Issued date: 15.03.2011
Whether wake frequency calculation has to be carried out for the spray
2.8 X X
nozzles?
For combined PRDS, whether noise levels (due to high pressure drop
2.9 across valve) -are within acceptable limits -85 dBA (If not then noise X
reduction methodology shall be used - Perforated plugs & silencer cages)
Procedure Number G-INST-004.288-A-01 Control Object Check List for Desuperheater Station
Aker Powergas Pvt Ltd Operating System Sheet 4 of 7
Group Head Instruments
Control Object Check List Checklist approved for use by:
Aker Powergas Pvt Ltd
for Desuperheater Station Issued date: 15.03.2011
3.1.2 Whether latest revision of P&IDs and DCNs/CMS have been referred X X
Procedure Number G-INST-004.288-A-01 Control Object Check List for Desuperheater Station
Aker Powergas Pvt Ltd Operating System Sheet 5 of 7
Group Head Instruments
Control Object Check List Checklist approved for use by:
Aker Powergas Pvt Ltd
for Desuperheater Station Issued date: 15.03.2011
In case of "SKID" we may have to attach the scope drawing and shall
involve the Piping/mechanical/Civil department as required.
Whether scope of supply for all accessories like strainer, isolation valve /
3.2.3 X X
stop valve, break-up flanges, bypass valve in both steam & cooling water
lines ( Scope by De-superheater vendor / Piping ) has been specified for
clarity
Check the valve flange rating, facing, face finish
3.2.4 Whether checked with latest revision of Piping material specification. X X & material.
Whether checked with latest revision of Piping Valve material
3.2.5 X X
specification.
Check the Design Pressure, Temperature, Full
3.2.6 Whether checked with latest revision of Line list. X X vacuum compatibility & any other relevant data.
3.3 Instruments
N.A.
3.4 Electrical
N.A.
3.5 Civil
Procedure Number G-INST-004.288-A-01 Control Object Check List for Desuperheater Station
Aker Powergas Pvt Ltd Operating System Sheet 6 of 7
Group Head Instruments
Control Object Check List Checklist approved for use by:
Aker Powergas Pvt Ltd
for Desuperheater Station Issued date: 15.03.2011
In case of "SKID" we may have to attach the scope drawing and shall
involve the Piping/mechanical/Civil department as required.
Whether scope of supply for all accessories like strainer, isolation valve /
3.5.1 X X
stop valve, break-up flanges, bypass valve in both steam & cooling water
lines ( Scope by De-superheater vendor / Piping ) has been specified for
clarity
3.6 Vessels
N.A.
3.7 Mechanical
In case of "SKID" we may have to attach the scope drawing and shall
involve the Piping/mechanical/Civil department as required.
Whether scope of supply for all accessories like strainer, isolation valve /
3.7.1 X X
stop valve, break-up flanges, bypass valve in both steam & cooling water
lines ( Scope by De-superheater vendor / Piping ) has been specified for
clarity
3.8 Construction
N.A.
Procedure Number G-INST-004.288-A-01 Control Object Check List for Desuperheater Station
Aker Powergas Pvt Ltd Operating System Sheet 7 of 7