Wall Footing Calculations
Wall Footing Calculations
Wall Footing Calculations
WIDTH OF FOOTING:
Critical section for two - way shear is located at a distance "d/2" from the face of the column.
Critical section for one - way shear is located at a distance "d" from the face of the column. 14.5" = d
dreq = Vu = 60100 in
f ( 2 f'c ) b 0.75(2x 4000 )84
STEEL AREA:
Mu = 12x150000 = 113.2
fbd 2 0.9x84x14.5 2
DEVELOPMENT LENGTH:
WIDTH OF FOOTING:
Critical section for two - way shear is located at a distance "d/2" from the face of the column.
Critical section for one - way shear is located at a distance "d" from the face of the column. 8.5" = d
dreq = Vu = 76800 in
f ( 2 f'c ) b 0.75(2x 4000 )96
STEEL AREA:
Mu = 12x177500 = 341.2
fbd 2 0.9x96x8.5 2
DEVELOPMENT LENGTH:
LOAD INFORMATION
Floor Load
DL LL Eff Length DL LL
Floor psf psf ft plf plf
Roof Load = 25 30 12.5 312.5 375.0
5th Floor = 25 40 12.5 312.5 500.0
4th Floor = 25 40 12.5 312.5 500.0
3rd Floor = 25 40 12.5 312.5 500.0
2nd Floor = 25 40 12.5 312.5 500.0
1st Floor = 0.0 0.0
1562.5 2375.0
Wall Load
Load Height WL
psf ft plf
Above roof 65 5 325.0
5th Floor to Roof 65 11 715.0
4th Floor to 5th Floor 65 11 715.0
3rd Floor to 4th Floor 65 11 715.0
2nd Floor to 3rd Floor 65 11 715.0
1st Floor to 2nd Floor 65 14 910.0
Fnd to 1st Floor 65 3.5 227.5
4322.5
MATERIAL INFORMATION:
Concrete f'c = 4000 psi GRADE
Reinf. Steel fy = 60 ksi
Allowable soil pressure, qa = 4 ksf
Concrte Weight (gcon) = 150 lb/ft3 3.5'
Soil Weight (g) = 110 lb/ft3 12"
LOADS:
Critical section for two - way shear is located at a distance "d/2" from the face of the column.
1.00'
Perimeter around the area bo = 4 x (a+ d/2 + d/2)
bo = 4 x (12 + 8.6875)
bo = 4 x (20.6875) = 83 "
20.7 " = 1.73'
Shear force Vu = (2.5 - 1.73 ) ( 4.52 ) = 3.48 kips
Critical section for one - way shear is located at a distance "d" from the face of the column. 8.7" = d
STEEL AREA:
Mu = 12x1300 = 19.1
fbd 2
0.9x12x8.69 2
DEVELOPMENT LENGTH:
90Degree Bend
KIELY ENGINEERING
Project #:
Prep By KR Date 10/3/22 Project
Chkd By JE Date 10/3/22 Subject Design of Eccentric Wall Footing
LOAD INFORMATION
Floor Load
DL LL Eff Length DL LL
Floor psf psf ft plf plf
Roof Load = 25 30 12.5 312.5 375.0
5th Floor = 25 40 12.5 312.5 500.0
4th Floor = 25 40 12.5 312.5 500.0
3rd Floor = 25 40 12.5 312.5 500.0
2nd Floor = 25 40 12.5 312.5 500.0
1st Floor = 0.0 0.0
1562.5 2375.0
Wall Load
Load Height WL
psf ft plf
Above roof 65 5 325.0
5th Floor to Roof 65 11 715.0
4th Floor to 5th Floor 65 11 715.0
3rd Floor to 4th Floor 65 11 715.0
2nd Floor to 3rd Floor 65 11 715.0
1st Floor to 2nd Floor 65 14 910.0
Fnd to 1st Floor 65 3.5 227.5
4322.5
MATERIAL INFORMATION:
Concrete f'c = 4000 psi GRADE
Reinf. Steel fy = 60 ksi
Allowable soil pressure, qa = 2 ksf
Concrte Weight (gcon) = 150 lb/ft3 3.5'
Soil Weight (g) = 110 lb/ft 3
24"
LOADS:
WIDTH OF FOOTING:
10.0'
2.00
1.00
0.00
1.02 ksf
-1.00
-2.00
-3.00
-4.00 3.60 ksf
0.00 2.00 4.00 6.00 8.00 10.00 12.00
2.00
1.00
0.00
KIELY ENGINEERING -1.00
Project #:
-2.00
Prep By KR Date 10/3/22 Project -3.00
Chkd By JE Date 10/3/22 Subject Design of Eccentric Wall Footing -4.00
0.00 2.00 4.00 6.00 8.00 10.00 12.00
Critical section for one - way shear is located at a distance "d" from the face of the column. 20.5" = d
STEEL AREA:
Mu = 12x175100 = 463.0
fbd 2
0.9x12x20.5 2
DEVELOPMENT LENGTH:
Column Size
Column force vertical = 179.00 kips
= 164 psi