2021-12 MPII-ESII-QUAII Current Sense Socket Issue - Rev3
2021-12 MPII-ESII-QUAII Current Sense Socket Issue - Rev3
2021-12 MPII-ESII-QUAII Current Sense Socket Issue - Rev3
This affects the common use case: systems where such external current sensor is not installed.
The problem appears when AC (grid or generator) is connected to the AC-input. There is no problem showing
when inverting.
Possible symptoms:
• Power Assist will not work correctly.
• During charge the AC current input limit is ignored.
• In an ESS system the unit will behave unpredictable, resulting in (high) power being randomly generated to or taken from
the grid.
And lastly, in all above mentioned cases the real power from/to the grid will have no relation with the power displayed on the GX,
VRM Portal, VictronConnect App or VEConfigure. The displayed power will likely (but not necessarily) stay at 0 W and 0 Amps.
Picture left showing incorrect data on (CC)GX and the VRM Dashboard.
Picture right showing 0.0W AC Loads and 63W consumed power from the grid. In reality a 600W load is connected.
The background: in the socket, there is a mechanism that electrically connects the internal current sensor to the measurement
circuitry. Inserting an external current sensor breaks that connection and makes it use the external current sensor instead. The
problem is a bad contact when there is no external current sensor inserted.
Step 1: turn the I-0-II switch, see lower right in below picture, to the ‘0’ (Off) position.
Step 2: open the black connection cover by unscrewing the two screws at the bottom.
Step 3: insert a 3,5mm jack plug (any 3.5mm jack plug will do, also when connected to a headphone), and remove it. Do this a few
times. Then remove the plug.
Step 4: Turn the unit ‘On’ and check on your GX device and/or on the VRM dashboard to see if the AC-input current is showing the
correct values.
Picture of the connections of the MultiPlus-II. Encircled the Current Sense socket.