Operation Manual
1. GENERAL DESCRIPTION
Epoxy sealed model SS15A-2, 15 Amp voltage regulators is a General Purpose Heavy
Duty AVR that will work singly or in parallel with almost any large brushless generator
without a PMG.
Electrical Specification
Basically there is no limit to how low in Ohms a Voltage Regulator can go. The important is not to
exceed continuous Amps rating of the model AVR you are using. Most alternators exciter runs
under 45 V-DC at full load. We can say “statistically” that the minimum resistor value should be
around 3 Ohms for McPherson Model SS15A2 working with a maximum 45 volt output.
Remember Ohms= Voltage/ Current.
Also remember that most Voltage Regulators become unstable when working at 15 to 20 volts
output. If this happens add a resistor in series with the field to work the AVR at higher voltages.
2.
3.
4.
5. NOTICE OF USE
3-1
The SSEA15A-2 can be mounted in any place like, inside generator control panel,
switchgear cabinets, etc. Try to prevent high temperature, high moisture, and /or severe
vibration location. See figure 1 for mounting dimensions.
3-2
The SSEA15A-2 surface temperature can not be over 60C when in operation. DANGER
HIGH VOLTAGE do not touch the heat sink
1. Ensure all the wires of the regulator are correctly connected and the proper fuse
(15A250V) is installed.
2. Turn voltage adjustment potentiometer counter clockwise to lowest voltage level.
3. If used, turn external voltage potentiometer to a centered position.
4. Turn stability potentiometer clockwise to highest stability level.
5. Connect an 110VDC meter across the exciter fields observing proper polarity.
6. Connect a 300VAC meter from line to neutral of generator output.
7. Start and run the generator at no load and at rated speed. The generator output
voltage should build up to a minimum level. If the voltage does not build up, it
may be caused by low residual generator voltage. Refer to field flashing section
in generator manual.
8. Slowly adjust voltage potentiometer until the generator voltage reaches the
proper value.
9. Turn the stability potentiometer clockwise until instability is shown, and then
turn it counterclockwise slightly until both meters mentioned in (5) and (6) are
shown to be stable.
10. Interrupt regulator power for a short time (approximately 1 to 2 second). If the
voltage is still stable, the adjustment is now completed. Otherwise increase the
stability slightly, and repeat procedure (10) until stability is reached.
6. ADJUSTMENTS
4-1 FREQUENCY ROLL-OFF ADJUSTMENT (Normally Factory Preset)
For 50 Hz operation connect a jumper from “COM” to the “50Hz” terminal. For 60Hz
operation do not use the jumper. To adjust the frequency roll-off, proceed as follow:
1. Set the engine speed to normal RPM for the desired frequency compensation
(corner frequency roll-off) point.
2. Adjust the front panel FREQ control until the output voltage is about 5V less
then nominal voltage. (For 50Hz operation, the roll-off frequency is factory set
to 45Hz, and for 60Hz operation, the frequency is 55Hz).
3. Adjust the front panel “VOLT” potentiometer to set the generator voltage.
4. If needed 1K~1.5KW 1/2 watt potentiometer may be connected to terminals VR
and VR, for remote voltage adjustment. Refer to figure 4.5.
5. Adjust the front panel “STAB” potentiometer control for generator stability.
6. Turn potentiometer counter-clockwise (CCW) for rapid generator load response.
7. Turn the “STAB” potentiometer slowly (CCW) until the system STARTS
oscillating.
8. Turn the “STAB” potentiometer slowly (CW) until the system STOPS
oscillating.
The droop control allows for adjustment of the amount of droop, which will occur in the
generator output voltage for a given amount of reactive load current. A CT should be
selected which will supply the A.V.R with 3 to 5 AMPS of current at rated generator
load. The 5 Amps of current supplied is connected to terminal L and K and the amount of
droop can be adjusted from 0 to 6% of nominal generator voltage.
7. FLASH WITH BATTERY
When lack of residual generator voltage occurs flash field with 3~24VDC when
generator is running. Stop flashing when output is 30% of the nominal voltage.
S
GENERATOR
FIELD
F+ F- VF VF VS VS l k
DROOP
U/F
CC
VOLTS
STABILITY
T0 T8
5
T1
6
STABILITY
DROOP
VOLTS
8 24
U/F
L6 0
VR 50HZ COM
7 9 20
4 6
k
1
l
3 SS15A2
F- VF VF VS VS
22
CC
26
F+
L5
CR6
CR7
CR1 CR4
CR2 CR5
CR3 CR6
R6
+ - F2 F2
F1 F1 Wirering a SS15A2
McPherson AVR into
any SR4 Caterpillar
Generator
SS15A2 Set Up
U/F U/F
VOLTS VOLTS
STAB. STAB.
DOOP
208 to 240 v operation U/F
208, 240, 380, 415, 480, volts operation DOOP
VOLTS sellect voltage with CC
U/F
STAB.
VOLTS
STAB.