KYN28-24kV Switchgear
KYN28-24kV Switchgear
KYN28-24kV Switchgear
50/60Hz, 24kV single bus bar and single bus bar section electric power system, with
the function of “five preventions”. It has perfect and reliable prevention function
assembled with vacuum circuit breaker, vacuum contactor, load breaker switch and
VT handcart etc. The switchgear complies with the standards of IEC62271, GB3906.
Maximum +40°C
Ambient humidity:
and user.
The dielectric strength of the air will be reduced in when altitude is over 1000m at site.
If the ambient temperature is over the maximum degree, the capacity of the using current must be
lower than the designed current’s for both main bus bar and branching bus bar. The installation of
The switchgear is composed by the enclosure and drawable CB. The panel and main components are
shown in figures. The incoming panel and outgoing panel are the basic schemes of switchgear panel. There
are other derivative schemes, such as: contact panel or metering panel. In addition, there are so many
schemes of the switchgear panel with load switch, VCB (Vacuum Circuit Breaker) truck, VC (Vacuum
Contactor) truck, disconnect truck. The bus-bar compartment, CB truck compartment, cable compartment and
relay compartment are separated by metal sheet. The switchgear has flexible operation for CB truck’s
movement and clear position instruction. The earth switch allows making short circuit current and gains
creditable mechanical interlock. The protection degree of enclosure is IP4X; the protection degree is IP2X
when the door of VCB room is open and the truck is drawn out.
The panel has two modes of configuration: single-face configuration and face-to-face configuration.
The details of structure and main components are referenced in order documents.
Height 2430(mm)
Rated branching bus bar current up to 1250A 800*/1000(mm)
Width Rated short-circuit breaking current(rms.) up to 31.5KA
Rated branching bus bar current over 1600A 1000(mm)
Depth Cable incoming or outgoing 1860(mm)
Overhead incoming or outgoing 2360 (mm)
Weight: 840~1400kg.
Applicable occasions should be free from inflammables, explosives, corrosives and severe vibration.
If the product is used under special conditions, please state it to manufacture when you order.
Sino-Amigo Corp
-4-
Rated voltage kV 24
Rated frequency Hz 50 / 60
Rated lightning impact withstand voltage (peak) kV 125
Rated short-time power frequency withstand kV 65
voltage (1min)
Rated short-circuit breaking current kA 20 25 31.5
Rated current A 630 630 1250
1250 1250 1600
1600 2000
2500
Rated short-time withstand current (Virtual value) kA 20 25 31.5
Rated peak withstand current (peak) kA 50 63 80
Rated short-circuit making current (peak) kA 50 63 80
Rated operating sequence O-0.3s-CO-180s-CO
Making and breaking times of short-circuit current times 20
Duration of rated short-circuit current s 4
Mechanical life times 10000
Power frequency withstand voltage of secondary V 2000
circuit
Rated breaking current of single capacitor bank A 630
Rated breaking current of back to back A 400
Rated making surge current of capacitor bank kA 12 (frequency: ≤ 1000Hz)
Contact clearance mm 15±1(11±1)*
Contact travel mm 3.5 ± 0.5
Bounce time of contact closing ms ≤2
Different period of three-phase at closing and ms ≤2
Tripping
Average closing speed m/s 0.8~1.2(0.5~0.8) *
Average opening speed m/s 1.4~1.8(0.9~1.2) *
Opening time (Rated operating voltage) ms 20~50
Closing time (Rated operating voltage) ms 35~70
Rated opening / closing operating voltage V AC110 / AC220 / DC110 / DC220
Rated voltage of energy storage motor V AC110 / AC220 / DC110 / DC220
Rated power of motor W 70
Energy storage time s ≤ 15
Rebound amplitude of contact opening mm ≤3
Main conductive circuit resistance µΩ ≤ 80(630A), ≤ 60(1250A),
≤ 40(1600A~2000A), ≤ 25 (2000A
More)
Rated operation pressure of Contact N 2400 ± 200(20kA),
2400 ± 200(25kA),
3100 ± 200(31.5kA)
Sino-Amigo Corp
-5-
Static contact’s dimension of VS1 -24
body. The transformers are single phase, casting resin insulated and full
enclosed. The assembly dimensions of the body are the same as ZN63A (VSI)
according to the different requirements of users, each auxiliary switch can be installed five pairs of contacts at
most. The secondary output part of PT cart adopts 58-pin aviation plugs. Three arresters can be installed in the
PT cart. The harmonic elimination resistor can be installed in the neutral point of PT cart.
Sino-Amigo Corp
-6-
Type designation of VTC-24
Applicable occasions should be free from inflammables, explosives, corrosives and severe vibration.
Note: according to the order, the VT can be installed in the fixed switchgear
Sino-Amigo Corp
-7-
. Indoor Voltage Transformer
Description of VT
The product is single phase, casting resin and fully enclosed. It is used for electricity metering, voltage
control and relay protect in the electric system with rated frequency 50/60HZ and rated voltage 3, 6, 12kV. It
Type designation of VT
JDZ11-15,20 JDZX11-15,20
Structural feature of VT
The series voltage transformers are fully enclosed and they are insulated by casting resin. The iron core
and winding are casting together. It is small and light. The secondary outlet line is wrapped by outlet box and
Technical specification of VT
1. Power factor of load: 0.8 (lagging);
Type designation of CT
LZZB9-24/180 LZZBJ9-24/220
Structural feature of CT
The current transformer is a leg type, totally-enclosed structure. Its ring core, primary winding and
secondary winding are casted resin for insulation. The reinforced insulation makes it workable under the
The outlet marks of the product are: primary P1, P2, secondary group on 1S1, 1S2, group two 2S1, 2S2.
As the primary current flow from P1 to P2, the secondary current flow from S1 to S2 through outside return
circuit. High voltage appears if secondary return circuit opens while primary current is flowing by.
Technical specification of CT
1. Rated insulation level: 24 / 63 / 125
2. Frequency: 50 / 60 Hz;
presently in the world. The resistor slice mainly adopts zinc oxide and
multi-metal oxide, different with the traditional silicon carbide arrester. The
over-voltage, the excellent nonlinear characteristics of the arrester will make the current increase to several
thousand ampere instantaneously, while the arrester is under the low resistance state and release over-voltage
energy so as to effectively restrict the damage against the transmission equipments which caused by the
over-voltage.
The Zinc Oxide arrester is applied to protect the electrical equipment in AC power system against the
damage resulted from the atmosphere over-voltage and the switching over-voltage.
Maximum +40°C
Altitude: ≤ 1000m;
The industrial frequency voltage endured on the arrester in long-term should not overrun the sustained
Applicable occasions should be free from inflammables, explosives, corrosives and severe vibration. If the
product is used under the special conditions, please state it to manufacture when you order.
different specifications based on the size of electric current for the user’s choice.
specifications of national standard of GB1985 Alternate Current High-voltage Disconnect and Earth-switch and
non-useful-ground neutral system with rated frequency 50Hz or 60Hz and rated
voltage 35kV.
only examined. The secondary winding can withstand the power frequency test voltage of 3kV to ground.
If the customer gathers zero fault current by computer to monitor and protect, please designate the
Sino-Amigo Corp
- 14 -