Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

KYN28-24kV Switchgear

Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

KYN28-24 Indoor Metal-clad Enclosed Switchgear

Summary of KYN28-24 switchgear

KYN28-24 indoor metal-clad enclosed switchgear is applied to 3-phase AC

50/60Hz, 24kV single bus bar and single bus bar section electric power system, with

the function of “five preventions”. It has perfect and reliable prevention function

against misoperation. The removing compartment of the switchgear may be

assembled with vacuum circuit breaker, vacuum contactor, load breaker switch and

VT handcart etc. The switchgear complies with the standards of IEC62271, GB3906.

DL404.Service conditions of KYN28-24 switchgear

Normal service conditions of switchgear as follows:


Ambient temperature:

Maximum +40°C

Maximum 24 hour average +35°C

Minimum (according to minus 15 indoor classes) -15°C

Ambient humidity:

Daily average relative humidity less than 95%

Monthly average relative humidity less than 90%

Height above sea level at site less than 1000m

Earthquake intensity less than 8 degree

Height above sea level less than 1000m


This product should not be used under conditions of fire, explosion, earthquake and chemical
corrosion environments.
Special service conditions
Each special service condition should be proposed in advance and confirmed by the manufacturer

and user.

The dielectric strength of the air will be reduced in when altitude is over 1000m at site.

If the ambient temperature is over the maximum degree, the capacity of the using current must be

lower than the designed current’s for both main bus bar and branching bus bar. The installation of

aerator is propitious to reduce heat.


Type designation of KYN28-24 switchgear

Structural feature of KYN28-24 switchgear


The enclosure is made of aluminum-zinc plated steel by CNC machine with high precise dimension, short

production cycle, excellent mechanical strength and nice appearance.

The switchgear is composed by the enclosure and drawable CB. The panel and main components are

shown in figures. The incoming panel and outgoing panel are the basic schemes of switchgear panel. There

are other derivative schemes, such as: contact panel or metering panel. In addition, there are so many

schemes of the switchgear panel with load switch, VCB (Vacuum Circuit Breaker) truck, VC (Vacuum

Contactor) truck, disconnect truck. The bus-bar compartment, CB truck compartment, cable compartment and

relay compartment are separated by metal sheet. The switchgear has flexible operation for CB truck’s

movement and clear position instruction. The earth switch allows making short circuit current and gains

creditable mechanical interlock. The protection degree of enclosure is IP4X; the protection degree is IP2X

when the door of VCB room is open and the truck is drawn out.

The panel has two modes of configuration: single-face configuration and face-to-face configuration.

The details of structure and main components are referenced in order documents.

Technical specification of KYN28-24 switchgear

Item Unit Data


Rated voltage kV 24
Insulation Rated power-frequency withstand voltage(1min) kV 65 / 79 (phase to earth / across open contacts)
level Rated lightening impulse withstand voltage kV 125 / 145 (phase to earth / across open contacts)
Rated frequency Hz 50 / 60
Rated main bus bar current A 630,1200,1600,2000,2500
Rated branching bus bar current A 630,1250,1600,2000,2500
4s Short-time withstand current(rms.) kA 16, 20, 25
Peak withstand current(peak.) kA 40, 50, 63
Structural drawing of KYN28-24 switchgear

A Bus-bar compartment B CB truck compartment


C Cable compartment D Relay compartment

1. Enclosure 8. Earth-switch 15. CB truck


2. Sub--bus-bar 9. Cable 16. Heater
3. Main bus-bar bushing 10. Surge arresters (not installed) 17. Draw-out type horizontal isolating plate
4. Main bus-bar 11. Bus-bar of earthing 18. Operating mechanism of earth-switch
5. Fixed contact assembly 12. Isolating plate 19. Control cable groove
6. Fixed contact box 13. Partition (shutter) 20. Pressure releasing device
7. Current transformer (CT) 14. Secondary circuit plug

Outline dimension and weight of KYN28-24 switchgear

Height 2430(mm)
Rated branching bus bar current up to 1250A 800*/1000(mm)
Width Rated short-circuit breaking current(rms.) up to 31.5KA
Rated branching bus bar current over 1600A 1000(mm)
Depth Cable incoming or outgoing 1860(mm)
Overhead incoming or outgoing 2360 (mm)
Weight: 840~1400kg.

* Suitable for miniaturization product being equipped.


Main components of KYN28-24 switchgear

. VS1-24 Indoor AC Medium Voltage Vacuum Circuit Breaker


Summary of VS1 -24
VS1 (VCBI) series high-voltage vacuum circuit breaker is a kind

of indoor high-voltage switch equipment with 50/60Hz three-phase

alternating current and 24kV rated voltage, which combined the

technique of the ABB Corporation in Switzerland and domestic

development state and manufacturing capability. The general

framework is composed by the body and operation system.

The composite insulated material insures no pollution and

explosion danger with high insulation level.

The product conforms to IEC62271, GB 1984, JB3855 and DL1403.

Service condition of VS1 -24


Altitude: ≤ 1000 m;

Ambient temperature:-25℃ ~ +40℃;

Relative humidity: daily average ≤95%, monthly average ≤90%;

Earthquake intensity: ≤8 degree;

Applicable occasions should be free from inflammables, explosives, corrosives and severe vibration.

If the product is used under special conditions, please state it to manufacture when you order.

Type designation of VS1 -24

Technical specification of VS1 -24

Item Unit Data

Sino-Amigo Corp
-4-
Rated voltage kV 24
Rated frequency Hz 50 / 60
Rated lightning impact withstand voltage (peak) kV 125
Rated short-time power frequency withstand kV 65
voltage (1min)
Rated short-circuit breaking current kA 20 25 31.5
Rated current A 630 630 1250
1250 1250 1600
1600 2000
2500
Rated short-time withstand current (Virtual value) kA 20 25 31.5
Rated peak withstand current (peak) kA 50 63 80
Rated short-circuit making current (peak) kA 50 63 80
Rated operating sequence O-0.3s-CO-180s-CO
Making and breaking times of short-circuit current times 20
Duration of rated short-circuit current s 4
Mechanical life times 10000
Power frequency withstand voltage of secondary V 2000
circuit
Rated breaking current of single capacitor bank A 630
Rated breaking current of back to back A 400
Rated making surge current of capacitor bank kA 12 (frequency: ≤ 1000Hz)
Contact clearance mm 15±1(11±1)*
Contact travel mm 3.5 ± 0.5
Bounce time of contact closing ms ≤2
Different period of three-phase at closing and ms ≤2
Tripping
Average closing speed m/s 0.8~1.2(0.5~0.8) *
Average opening speed m/s 1.4~1.8(0.9~1.2) *
Opening time (Rated operating voltage) ms 20~50
Closing time (Rated operating voltage) ms 35~70
Rated opening / closing operating voltage V AC110 / AC220 / DC110 / DC220
Rated voltage of energy storage motor V AC110 / AC220 / DC110 / DC220
Rated power of motor W 70
Energy storage time s ≤ 15
Rebound amplitude of contact opening mm ≤3
Main conductive circuit resistance µΩ ≤ 80(630A), ≤ 60(1250A),
≤ 40(1600A~2000A), ≤ 25 (2000A
More)
Rated operation pressure of Contact N 2400 ± 200(20kA),
2400 ± 200(25kA),
3100 ± 200(31.5kA)

Sino-Amigo Corp
-5-
Static contact’s dimension of VS1 -24

Rated current 630A 1250A 1600A 2000A 2500A


Diameter of static contact(mm) 35 49 55 / 49 79 79 / 109

Structural drawing of VS1 -24

1. Circuit breaker 4. Handcart


2. Contact arm 5. Operating Mechanism
3. Contact plum blossom 6. Secondary plug

. VTC-24 Indoor Voltage Transformer Truck


Description of VTC-24
The product adopts the voltage transformers- type JDZX8-15, 20 as its main

body. The transformers are single phase, casting resin insulated and full

enclosed. The assembly dimensions of the body are the same as ZN63A (VSI)

circuit breaker’s for convenient design, manufacturing, installation and

maintenance. The insulation support of the contact arm uses composite

materials to enhance the overall dielectric strength and ability to withstand

voltage. Auxiliary switches (Position switch) can be equipped in the PT cart;

according to the different requirements of users, each auxiliary switch can be installed five pairs of contacts at

most. The secondary output part of PT cart adopts 58-pin aviation plugs. Three arresters can be installed in the

PT cart. The harmonic elimination resistor can be installed in the neutral point of PT cart.

Sino-Amigo Corp
-6-
Type designation of VTC-24

Service condition of VTC-24


Altitude: ≤ 1000 m;

Ambient temperature:-25℃ ~ +40℃;

Relative humidity: daily average≤95%, monthly average≤90%;

Earthquake intensity: ≤8 degree;

Applicable occasions should be free from inflammables, explosives, corrosives and severe vibration.

Structural drawing of VTC-24

1. Contact plum blossom 4. Fuse


2. Contact arm 5. Voltage transformer(VT)
3. Insulation cover 6. Handcart

Note: according to the order, the VT can be installed in the fixed switchgear

Sino-Amigo Corp
-7-
. Indoor Voltage Transformer
Description of VT
The product is single phase, casting resin and fully enclosed. It is used for electricity metering, voltage

control and relay protect in the electric system with rated frequency 50/60HZ and rated voltage 3, 6, 12kV. It

conforms to IEC186 and GB1207.

Type designation of VT

JDZ11-15,20 JDZX11-15,20
Structural feature of VT
The series voltage transformers are fully enclosed and they are insulated by casting resin. The iron core

and winding are casting together. It is small and light. The secondary outlet line is wrapped by outlet box and

has three exits with different direction feed lines.

Technical specification of VT
1. Power factor of load: 0.8 (lagging);

2. Surface creepage distance: the product accords with request of II class;


3. The other technical data are shown as follows:
Type Rated voltage Frequency Rated output burden(VA) Limit output Rated
ratio(kV/kV) 0.2 0.5 1 3P(6P) burden(VA) insulated level
JDZ□-15 15/ 0.1 30 80 200 500 18 / 55/ 105
JDZ□-20 20 / 0.1 30 80 200 24 / 63 / 125
JDZX□-15 (15/√3)/(0.1/√3)/(0.1/3) 50 / 60 Hz 30 80 150 100 18 / 55/ 105
JDZX□-20 (20/√3)/(0.1/√3)/(0.1/3) 30 80 150 100 600 24 / 63 / 125
JDZX□-15G (3/√3)/(0.1/√3)/(0.1/3) 20 60 120 100 600 18 / 55/ 105
JDZX□-20G (10/√3)/(0.1/√3)/(0.1/3) 20 60 120 100 24 / 63 / 125
Note: 1. Any special requirements can be negotiated with us;
2.Rated output burden and its relative accuracy class only one alternative.

. Indoor Current Transformer


Description of CT
The current transformer is fully enclosed and insulated by casting resin. It is designed for current, power
measurement and relay protection in AC power supply system with rated frequency 50/60HZ, rated voltage
24kV and below.

Type designation of CT

LZZB9-24/180 LZZBJ9-24/220
Structural feature of CT
The current transformer is a leg type, totally-enclosed structure. Its ring core, primary winding and

secondary winding are casted resin for insulation. The reinforced insulation makes it workable under the

conditions of humidity condensation and pollution II.

The outlet marks of the product are: primary P1, P2, secondary group on 1S1, 1S2, group two 2S1, 2S2.

As the primary current flow from P1 to P2, the secondary current flow from S1 to S2 through outside return

circuit. High voltage appears if secondary return circuit opens while primary current is flowing by.

Technical specification of CT
1. Rated insulation level: 24 / 63 / 125

2. Frequency: 50 / 60 Hz;

3. Rated primary current: 50~2500A;

4. Rated secondary current: 5A / 1A ;

5. Accuracy classes: 0.2 / 0.5 / 5P10 / 10P10 / 10P15;

6. Meter rage class safe-guard system: Fs<10;

7. Power factor: 0.8(hysteresis);

8. The secondary winding is 3 pieces at most.

. Indoor zinc oxide arrester


Description of arrester
The zinc oxide arrester is the most advanced over-voltage protector

presently in the world. The resistor slice mainly adopts zinc oxide and

multi-metal oxide, different with the traditional silicon carbide arrester. The

product greatly improves the Volt-Ampere characteristics and increases

the current capability of the resistor slice so as to bring ultimate changes to

the characteristics of the arresters.

Under the circumstance of normal working voltage, the current

through the arrester is just on microampere degree. When suffered from

over-voltage, the excellent nonlinear characteristics of the arrester will make the current increase to several

thousand ampere instantaneously, while the arrester is under the low resistance state and release over-voltage
energy so as to effectively restrict the damage against the transmission equipments which caused by the

over-voltage.

The Zinc Oxide arrester is applied to protect the electrical equipment in AC power system against the

damage resulted from the atmosphere over-voltage and the switching over-voltage.

Service condition of arrester


Ambient temperature in room:

Maximum +40°C

Minimum (according to minus 15 indoor classes”) -40°C

Altitude: ≤ 1000m;

AC system frequency range: 48Hz~62Hz;

Max. wind velocity: ≤ 35m/s;

Earthquake intensity: ≤7 degree;

The industrial frequency voltage endured on the arrester in long-term should not overrun the sustained

operating voltage of the arrester.

Applicable occasions should be free from inflammables, explosives, corrosives and severe vibration. If the

product is used under the special conditions, please state it to manufacture when you order.

Type designation of arrester


Technical specification of arrester
Type Rated Max. DC(U1mA) Normal Max. residual voltage(peak) (kV) Discharging capacity
voltage continuous Reference discharging Steep Lightning Switching 2000µs 4/10µs
servicing Voltage Current current Current Current Square- impulse
voltage (kV) (kA) impulse impulse Impulse Wave current
(kV) 1/5µs 8/20µs 8/20µs (A) (kA)
HY5W-21/62 21 17.1 33.4 5 70 62 54.2 150 65
HY5W-24/70 24 19.5 38.0 5 80 70 62.0 150 65
HY10W-21/62 21 17.1 33.0 10 70 62 54.2 250 100
HY10W-24/70 24 19.5 37.0 10 80 70 62.0 250 100

. 24kV Contact Box


Description of contact box
The product adopts epoxy resin material. It gains high level of insulation, intensity and stability. It provides

different specifications based on the size of electric current for the user’s choice.

Picture of contact box

Type: CH3 -24Q/185 Type: CH3-24Q/225 Type: CH3 -24Q/250


Rated current: 630A Rated current: 630~1600A Rated current: 2000~2500A

. 24kV Wall Bushing


Description of wall bushing
The product adopts epoxy resin material. It gains high level of insulation,

intensity and stability.

Picture of wall bushing


. 24kV JN15-24 Earth-Switch
Description of JN15-24

JN15-15 series indoor A.C. medium-voltage earth-switch can

be used for earthing protection during inspection and

maintenance of medium-voltage apparatus and can also be

matched with various type of high-voltage switch gears in power

system with rated voltage of 10kV or below and rated frequency of

50Hz. The performance of the earth-switch meets the

specifications of national standard of GB1985 Alternate Current High-voltage Disconnect and Earth-switch and

international standard of IEC60129.

Type designation of JN15-24

Technical specification of JN15-24

Item Unit Data


Rated voltage kV 24
Rated short time withstand current kA 31.5
Rated frequency Hz 50 / 60
Duration of short-time withstand current s 4
Rated lightning impact withstand voltage (peak) kV 125
Rated short-time power frequency withstand voltage (1min) kV 65
Rated short-circuit breaking current kA 80
Mechanical life times 2000
. 24kV LXK Zero Sequence Transformer
Description of LXK
The product is indoor and used for over driven current protection in the electric

non-useful-ground neutral system with rated frequency 50Hz or 60Hz and rated

voltage 35kV.

Type designation of LXK

Technical specification of LXK


The cable protects the primary main insulation, so the insulation characteristics of secondary winding are

only examined. The secondary winding can withstand the power frequency test voltage of 3kV to ground.

If the customer gathers zero fault current by computer to monitor and protect, please designate the

gathering of current and load when ordering.

Using of the transport truck

Sino-Amigo Corp
- 14 -