Professional Documents
Culture Documents
Lab 8
Lab 8
Experiment # 8
Analysis
of data in Modern Ethics and Individual
Viva / Quiz / Lab Tool Safety and
Name Reg. No Lab Report Usage Teamwork
Performance
5 Marks 5 Marks 5 Marks 5 Marks 5 Marks
Lab no. 8
OBJECTIVE
In this lab, you will be introduced to Fiber-Optic photoelectric switches; and you will learn
• Uses of Fiber-optic photoelectric switches
• Advantages and Disadvantages of Fiber-optic switches
• Their operations using reflective block
Introduction
Fiber-optic sensors are designed for applications where the sensor cannot be placed at
the actual sensing position. Fiber-optics is not a sensing technique but a method of
transmitting light energy. Fiber-optic cables use transparent fibers of glass, or plastic, to
conduct and guide light energy. They are used in photoelectric controls as light "pipes"
as shown in Figure 8-1
Light from the emitter is transmitted through a fiber-optic cable and emerges at the end
of the cable. The reflected beam is then carried back to the receiver through a separate
fiber optic cable combined either in the cable assembly (bifurcated) or within a separate
cable assembly. Fiber-optic cables can be mounted in locations that would otherwise be
inaccessible to photoelectric sensors.
A typical optical fiber consists of an inner core and outer cladding. The inner core is
composed of either glass or plastic. Figure 8-2 shows how an optical fiber transmits light.
The inner core has a higher index of refraction than the cladding. Light entering the fiber
is reflected by the boundary between the core and cladding. Light rays travel the entire
length of the cable because of internal reflections.
Table 8-1b. Characteristics of the Fiber-Optic Photoelectric Switch with Digital Display
Figure 8-4a. Fiber-Optic Photoelectric Switch with LED Indicators.
Figure 8-4b. Fiber-Optic Photoelectric Switch with Digital Display
Sensitivity Adjustments
There are different procedures, called teaching methods, to adjust the sensitivity of a
fiber-optic photoelectric switch:
• Maximum sensitivity setting is used to detect the presence of objects that completely
block the sensor light beam, and to detect the presence of objects with no background.
• With/without object teaching is used for detection of a slight difference in reflection,
color discrimination, background objects with unstable reflection, detection of object
surface irregularities, and for elimination of background object influence. This method is
used with both photoelectric switch models.
• No-object/Automatic teaching is used when teaching is impossible by stopping the
movement of sensing objects, for detection of bright/dark objects by teaching only with
background objects, and for elimination of background object influence. Changes in the
incident light level are detected within a certain time interval and the operating point is
set at the midpoint between the maximum and minimum detected levels. This method,
described in Appendix D, is used with both photoelectric switch models.
Procedure Summary
In the first part of the exercise, Sensitivity Adjustment, you will adjust the
sensitivity of the Fiber-Optic Photoelectric Switch using the With/without object
teaching method.
In the second part of the exercise, Characteristics, you will observe the ability of
the Fiber-Optic Photoelectric Switch to detect each surface of the Reflective
Block. You will also experiment with the light operate/dark operate modes of the
photoelectric switch.
In the third part of the exercise, Sensitivity Adjustment Using the Retroreflective
Surface of the Reflective Block, you will adjust the sensitivity of the Fiber-Optic
Photoelectric Switch using the With/without object teaching method using the
retroreflective surface of the Reflective Block.
EQUIPMENT REQUIRED
Refer to the Equipment Utilization Chart, in Appendix A of this manual, to obtain the list
of equipment required to perform this lab.
PROCEDURE
Sensitivity Adjustment
With/without object teaching
1. Connect the circuit as shown in figure below to DC supply and turn on DC power
supply
*
Figure 8-5. Circuit using the Fiber-Optic Photoelectric Switch.
• Put the Reflective Block on a white sheet of paper and position the block so the
white plastic surface is on top.
• Aim the sensor sensing face toward the white plastic surface of the Reflective
Block at a distance of 75 mm (3 in) as shown in Figure 8-5.
If you are using the photoelectric switch model with LED indicators, proceed with
the steps in 3.a. If you are using the photoelectric switch model with digital display, proceed
with the steps in 3.b.
• Set the photoelectric switch detection mode to Light operate by setting its L.ON/D.ON
selector to the L.ON position.
• The output indicator and the stability indicator should turn off.
• Depress the TEACH button once. The TEACH indicator (red) is lit and the built-in buzzer
beeps once.
• Remove the Reflective Block and depress the TEACH button once. If the teaching is
correct, the TEACH indicator (red) turns green and the built-in buzzer beeps once.
• If the teaching is not correct, the TEACH indicator (red) starts flashing and the built-in
buzzer beeps 3 times. Change the position of the target and the detection distance that
have been set and repeat from the beginning.
• Set the TEACH/RUN selector to RUN to complete the setting. The TEACH indicator
(green) turns off. Replace the protective cover and go to step 3.
• Set the photoelectric switch detection mode to Light operate by pressing the L/D button so
that the L (Light) indicator is lit.
• Depress the TEACH button once. This sets the first detection point (point with a
workpiece).
• Remove the Reflective Block and depress the TEACH button once. This sets the second
detection point (point without a workpiece).
• Verify that the teaching is correct: the output (orange) indicator turns on when the
Reflective Block is moved past the sensor, while the output (orange) indicator turns off
when the Reflective Block is removed.
Characteristics
Test the ability of the Fiber-Optic Photoelectric Switch to detect the various surfaces of the
Reflective Block. Leave the photoelectric switch detection mode set to Light operate.
Position the photoelectric switch and the Reflective Block as shown in Figure 8-5 and
determine which surfaces are detected by the sensor. Note your observations in Table 8-2.
LO (light Operate) DO (Dark Operate)
Surfaces Detected Not Detected Not
Detected Detected
Black Plastic
Surface
White Plastic
Surface
Matte Black
Metallic
Surface
Shiny Metallic
Surface
Retroreflective
Surface
Table 8-2
5. Set the Photoelectric switch to the Dark operate mode: if you are using the photoelectric
switch model with LED indicators, set its L.ON/D.ON selector to the D.ON position; if you
are using the photoelectric switch model with digital display, press the L/D button so that
the D (Dark) indicator is lit.
6. Repeat your observations for each surface of the Reflective Block and determine which
surfaces are detected by the sensor. Note your observations in Table 8-2.
7. Compare result obtained in light operate, dark operate mode. What can you conclude
from these results?
Black Plastic
Surface
White Plastic
Surface
Matte Black
Metallic Surface
Shiny Metallic
Surface
Retroreflective
Surface
Table 8-3
9. Compare the results obtained for each sensitivity setting indicated in Table 8-2 and
Table 8-3. Are the results similar? Explain why.
10. Turn off DC power supply and remove all the leads.
CONCLUSION
In this lab, you were introduced to fiber-optic photoelectric switches. You learned how and
when they are used, their advantages and disadvantages. You adjusted the sensitivity of
the Fiber-Optic Photoelectric Switch using the With/without object teaching method. You
observed its ability to detect the presence of various reflective surfaces in the light operate
and dark operate modes of operation. By adjusting the sensitivity using the retroreflective
surface of the Reflective Block instead of the white plastic surface, you observed that this
photoelectric switch is capable of discrimination.
REVIEW QUESTIONS
1. For which applications are the fiber-optic photoelectric switches designed for?
2. Explain why fiber-optic photoelectric switches can be easily obstructed by dirt or other opaque
substances
3. Which teaching method should be used to adjust the sensitivity of the Fiber-Optic
Photoelectric Switch to detect the presence of objects with no background?.