Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Controlado Quemador

Download as pdf or txt
Download as pdf or txt
You are on page 1of 19

7 142

Burner Controls RMO503SE


RMO503SE/K2
RMG508SE
RMG508SE/GB
RMG509SE
RMG509SE/K
Microcontroller-based burner controls for the supervision of single- or multi-
stage forced draft gas / oil burners in intermittent operation. Oil throughput
above 30 kg / h and maximum capacity above 120 kW when firing on gas.

RMO... / RMG... and this Data Sheet are intended for use by OEMs which integrate
the burner controls in their products.

Use, features
Use The burner controls are designed for the startup and supervision of single- or multi-
stage forced draft burners in intermittent operation. The RMO... is for use with forced
draft oil burners, the RMG... for forced draft gas burners. When firing on oil, yellow-
burning flames are supervised with photoresistive detectors QRB1B..., and blue-
burning flames with blue-flame detectors QRC... When firing on gas, the flame is su-
pervised with an ionization probe or flame detector QRA... (with ancillary unit
AGQ2...A27).

Firing on oil - Forced draft oil burners conforming to EN 267


- Burner controls for use with atomization oil burners of monoblock design to EN 230

Firing on gas - Forced draft gas burners conforming to EN 676


- Burner controls conforming to EN 298

CC1N7142en
Riello Siemens Building Technologies
28.10.2003 HVAC Products
Application-specific When firing on oil
features - Contact for preheating the oil
- Monitoring of time for preheating the oil
- Limitation of the number of repetitions

When firing on gas


- Monitoring of air pressure with functional check of the air pressure switch during
startup and operation

General
- Undervoltage detection
- Accurate and reproducible program sequence owing to digital signal handling
- Controlled intermittent operation after 24 hours of continuous operation
- Multicolor display of fault and status messages

Warning notes

To avoid injury to persons, damage to property or the environment, the following


warning notes should be observed!

Do not open, interfere with or modify the unit!

• All activities (mounting, installation and service work, etc.) must be carried out by
qualified staff
• Before performing any wiring changes in the connection area, completely isolate
the burner control from the mains supply (all-polar disconnection)
• Ensure protection against electric shock hazard by providing adequate protection
for the burner control’s terminals
• Check to ensure that wiring is in an orderly state
• Press the lockout reset button of the burner control or the reset button extension
AGK20.43 only manually (applying a force of no more than 10 N), without using
any tools or pointed objects
• Fall or shock can adversely affect the safety functions. Such units may not be put
into operation, even if they do not exhibit any damage

Mounting notes

• Ensure that the relevant national safety regulation are complied with

Installation notes

• Observe the permissible lengths of the detector cables (refer to «Technical data»)
• Always run the high-voltage ignition cables separately while observing the greatest
possible distances to the unit and to other cables
• Install switches, fuses, earthing, etc., in compliance with local regulations
• Ensure that the maximum permissible current ratings will not be exceeded (refer to
«Technical data»)
• Do not feed external mains voltage to the control outputs of the unit. When testing
the devices controlled by the burner control (fuel valves, etc.), the burner control
may never be connected
• Live and neutral conductors may not be interchanged

2/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003
Electrical connection of ionization probe and flame detector

It is important to achieve practically disturbance and loss-free signal transmission:


• The cable length must not exceed 1 m
• Never run the detector cable together with other cables
– Line capacitance reduces the magnitude of the flame signal
– Use a separate cable
• Insulation resistance
– Must be a minimum of 50 MΩ between ionization probe and ground
– Soiled detector holders reduce the insulation resistance, thus supporting cree-
page currents
• Earth the burner in compliance with the relevant regulations; earthing the boiler
alone does not suffice

Only when firing on gas • Observe the polarity


With supervision of the ionization current, the burner controls can detect wrong po-
larity of live and neutral conductors, in which case they initiate lockout at the end of
«TSA»
• The ionization probe must be protected against electric shock hazard
• Locate the ionization probe such that
– the ignition spark cannot arc over to the ionization probe (risk of electrical
overloads)
– the ignition spark cannot adversely affect supervision of the ionization current
• In networks with nonearthed neutral conductor and ionization current supervision,
terminal 6 must be connected to burner ground

Commissioning notes

• When commissioning the plant or when doing maintenance work, make the follow-
ing safety checks:

Safety check Anticipated response


a) Burner startup with flame detector darkened or Lockout at the end of «TSA»
with open-circuit to the ionization probe
b) Burner startup with flame detector exposed to Lockout after no more than
extraneous light (only when firing on oil) 25 seconds or immediate lockout
during the prepurge time
c) Burner operation with simulated flame failure; for Firing on oil: Repetition followed
that purpose, darken the flame detector during by lockout at the end of «TSA»
operation and maintain that status or interrupt Firing on gas: immediate lockout
the gas supply after the flame has extinguished
d) Burner startup with response from air pressure Lockout at the end of the waiting
switch (only when firing on gas) time «tw»
e) Burner operation with simulated loss of air pres- Immediate lockout
sure (only when firing on gas)

3/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003
Standards

Conformity to EEC directives


- Electromagnetic compatibility EMC (immunity) 89 / 336 EEC
- Directive for gas appliances 90 / 396 EEC
- Low-voltage directive 73 / 23 EEC

ISO 9001: 2000 ISO 14001: 1996


Cert. 00739 Cert. 38233

Type reference
RMO503SE --- ---
RMO503SE/K2 --- ---
RMG508SE x x
RMG508SE/GB --- ---
RMG509SE x x
RMG509SE/K --- ---

Service notes

• Each time a unit has been replaced, check to ensure that wiring is in an orderly
state. Make the safety checks as listed in «Commissioning notes»

Disposal notes

The unit contains electrical and electronic components and may not be disposed of
together with household garbage.
Local and currently valid legislation must be observed.

Mechanical design

The housing of the burner controls is made of impact-proof, heat-resistant and flame-
retarding plastic.

The housing accommodates the


- microcontroller which controls the program sequence, and the relays for load con-
trol
- electronic flame signal amplifier (for the ionization probe when firing on gas, for the
flame detector when firing on oil)
- lockout reset button with its integrated 3-color signal lamp for status and error mes-
sages and the socket for connecting the interface adapter OCI400
- terminals (maximum 15) for connecting the Riello base (part nos. 2061506 and
2221314)
- Central fixing screw for securing the housing to the Riello base (part nos. 2061506
and no. 2221314)

Display and diagnosis - Multicolor display of status and error messages


- Transmission of status and error messages and detailed service information via
additional interface adapter OCI400 and PC Windows software ACS400

4/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003
Type summary

Type references Riello Siemens Building Technologies


Riello and Siemens RMO503SE LMO88.580A2RL
Building Technologies RMO503SE/K2 LMO88.582A2RL
RMG508SE LMO88.680A2RL
RMG508SE/GB LMO88.683A2RL
RMG509SE LMO88.681A2RL
RMG509SE/K LMO88.682A2RL

Firing on oil

Type reference Mains voltage tw TSA t1 t3 t3n t4 t42 Response in the event of loss of
max. max. min. min. min. min. min. flame during operation
RMO503SE AC 220...240 V ¹) 2s 5s 37 s 20 s 7s 7s 6s Max. 3 repetitions, then lockout
RMO503SE/K2 AC 220...240 V ¹) 2s 5s 37 s 20 s 7s 7s --- Max. 3 x repetitions, then lockout

Firing on gas

Type reference Mains voltage tw ²) TSA t1 t3n t4 t10 Response in the event of loss of flame during
max. max. min. min. min. max. operation
RMG508SE AC 220...240 V ¹) 2s 3s 38 s 2s 10 s 10 s Lockout
RMG508SE/GB AC 220...240 V ¹) 2s 3s 38 s 2s 10 s 10 s Lockout
RMG509SE AC 220...240 V ¹) 2s 2s 64 s 1,3 s 10 s 15 s Lockout
RMG509SE/K AC 220...240 V ¹) 2s 3s 53 s 2,2 s 8s 12 s Lockout

Legend TSA Ignition safety time t3n Postignition time


tw Waiting time t4 Interval «BV1-BV2»
t1 Prepurge time t42 Interval «BV2-BV3»
t3 Preignition time t10 Specified time for air pressure signal («LP» time)

¹) For applications outside the European Community, operation at mains voltage AC 200...240 V ±10 % is ensured
²) Max. 20 s, when «CPI» or «LP» are not in the idle position

Ordering

Burner control including plug-in base refer to «Type summary»

Photoresistive detector QRB1B...


(refer to Data Sheet 7714)

Blue-flame detector QRC1...


(refer to Data Sheet 7716)

Ancillary unit for UV supervision


- Cable length 500 mm AGQ2.1A27
- Cable length 300 mm AGQ2.2A27

Diagnostic tool
(refer to Data Sheet 7614)
- Hardware OCI400
- Software ACS400

Lockout reset button extension AGK20.43

5/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003
Technical data
General unit data Mains voltage
- RMO..., RMG... AC 220...240 V +10 % / -15 % ¹)
¹) For applications outside the European
Community, operation at mains voltage
AC 200...240 V ±10 % is ensured
Mains frequency 50...60 Hz ±6 %
Built-in fuse (F) T6,3H250V (IEC 60 127-215)
Power consumption 20 VA
Mounting position optional
Weight approx. 260 g
Safety class I
Degree of protection IP 20
(user must ensure min. IP 40 when built in)
Tightening torque fixing screw M4 max. 0.8 Nm
Perm. cable length thermostat max. 20 m at 100 pF / m
Perm. cable length oil preheater max. 20 m at 100 pF / m
Perm cable length air pressure switch max. 1 m at 100 pF / m
Perm. cable length CPI max. 1 m at 100 pF / m
Perm. cable length gas pressure switch max. 20 m at 100 pF / m
Perm. cable length detector cable max. 1 m
Undervoltage protection, switch-off voltage
- RMO..., RMG... approx. AC 165 V (AC 160...170 V)

Max. perm. RMO503SE RMO503SE/K2 RMG508SE RMG508SE/GB


amperage at cosϕ ≥ 0.6 RMG509SE
RMG509SE/K
Terminal 1 5A 5A 5A 5A
Terminal 2 --- --- --- ---
Terminal 3 --- --- --- ---
Terminal 4 --- --- --- ---
Terminal 5 1A 1A 1A 1A
Terminal 7 5 A ³) --- 5A 5A
Terminal 10 1A 1A --- ---
Terminal 11 1 A ³) 5A 1 A 4) 1 A ³)
Terminal 12 2 A ²) 2 A ²) 1A 1A
Terminal 13 1A 1A 2 A ²) 2 A ²)
Terminal 14 1A --- 1 A 4) 1 A ³)

²) 3 A at a maximum of 150,000 switching cycles


³) Max. 5 A, total of terminals 7 and 11
4
) Max. 1 A total of terminals 11 and 14

Environmental Transport DIN EN 60 721-3-2


conditions Climatic conditions class 2K2
Mechanical conditions class 2M2
Temperature range -20...+70 °C
Humidity < 95 % r.h.
Operation DIN EN 60 721-3-3
Climatic conditions class 3K5
Mechanical conditions class 3M2
Temperature range -5...+60 °C
Humidity < 95 % r.h.

Condensation, formation of ice and ingress of water are not permitted!

6/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003
Flame supervision with At mains voltage
ionization probe (only UN = AC 220...240 V ¹)
when firing on gas) Detector voltage across ionization probe and ground
(AC voltmeter, R; ≥ 10 MΩ) AC 115...240 V
Switching threshold (limit values):
Switching on ≥ DC 1.5 µA
(flame on, DC ammeter Ri ≤ 5 kΩ)
Switching off ≤ DC 0.5 µA
(flame off, DC ammeter Ri ≤ 5 kΩ)
Detector current recommended for reliable operation ≥ DC 6 µA
Maximum short-circuit current between ionization probe and ground
(AC ammeter Ri ≤ 5 kΩ) AC 100...300 µA

¹) For applications outside the European Community, operation at mains voltage


AC 200...240 V ±10 % is ensured

Flame supervision is accomplished by making use of the conductivity and rectifying


effect of the flame.

The flame signal amplifier responds only to the DC component of the flame signal.
→ A short-circuit between ionization probe and ground causes the burner control to ini-
tiate lockout!

Measuring circuit For detector currents, refer to «Technical data»


7142a08/1003

RMG...
M
- + Legend
+
C Electrolytic capacitor 100...470 µF; DC 10...25 V
ION C
ION Ionization probe
M Microammeter, Ri max. 5000 Ω

Flame supervision with Mains voltage AC 230 V +10 % / -15 %


AGQ2...A27 and flame Mains frequency 50...60 Hz ±6 %
detector QRA... Perm. cable length from QRA... to max. 20 m
AGQ2...A27
(lay separate cable)
Perm. cable length from AGQ2...A27 to max. 2 m
RMG...
Weight of AGQ2...A27 approx. 140 g
Mounting position optional
Degree of protection IP 40
Power consumption 4.5 VA

At mains voltage UN
AC 220 V AC 240 V
Detector voltage at QRA... (with no load)
Until the end of «tw» and after controlled shutdown DC 400 V DC 400 V
After the end of «tw» DC 300 V DC 300 V
Detector voltage
Load by DC measuring instrument Ri > 10 MΩ
Until the end of «tw» and after controlled shutdown DC 380 V DC 380 V
After the end of «tw» DC 280 V DC 280 V
DC current detector signals with flame detector Min. required Max. possible
QRA...
Measurement at the flame detector DC 200 µA DC 500 µA

7/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003
Ancillary unit In connection with burner controls RMG..., use of the UV ancillary unit AGQ2...A27 is
AGQ2...A27 mandatory.

Operation with permanent line:


UV test with higher supply voltage across the UV cell on startup and after controlled
shutdown.

Connection diagram Measuring circuit

7142a09/1003

7142a10/1003
RMG... RMG...

1 15 7 10 1 15 7 10

br bl rt sw br bl rt sw
sw bl AGQ2...A27 sw bl AGQ2...A27

QRA
+
QRA
-

Measurement made at flame detector

Legend C Electrolytic capacitor 100...470 µF; DC 10...25 V bl blue


M Microammeter Ri max. 5000 Ω br brown
QRA... Flame detector rt red
sw black

Flame supervision with At mains voltage UN = AC 220...240 V ¹)


QRB1B... (only when Detector current
firing on oil) Minimum Recommended for Maximum permit- Maximum possible
required reliable operation ted (without flame) with flame
(with flame) (typically)
QRB1B... DC 25 µA DC 35 µA DC 5.5 µA DC 100 µA

¹) For applications outside the European Community, operation at mains voltage


AC 200...240 V ±10 % is ensured
7142a11/1002

Measuring circuit for RMO... For detector currents, refer to «Technical data»
detector resistance M- +
measurement Legend
QRB1B... Photoresistive detector
QRB...
M Microammeter, Ri max. 5,000 Ω

As an alternative to the detector resistance measurement, the diagnostic tool OCI400 /


ACS400 can be used. In that case, use of a DC microammeter is not required.

8/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003
Flame supervision with Photoresistive detector Switching off (flame off) Switching on (without flame)
Riello photoresistive No. 2380226 100...200 kΩ 300...450 kΩ
detector no. 2380226

kOhm

Lux
7142d03/1102

9/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003
Function
Preconditions for • Burner control is reset
startup • All contacts in the line are closed
• Only when firing on gas:
– Air pressure switch «LP» is in its idle position
– CPI contact is closed
• No undervoltage
• Heat demand contact is closed
• Flame detector is darkened, no extraneous light

Undervoltage Safety shutdown from operating position in the event mains voltage drops below ap-
prox. AC 165 V.
Repetition in the event mains voltage exceeds approx. AC 175 V.

Controlled intermittent After no more than 24 hours of continuous operation, the burner control will automati-
operation cally initiate a safety shutdown followed by an unshortened repetition of startup.

CPI Only when firing on gas:


During the startup phase at the beginning of the waiting time «tw», the CPI (Closed
Position Indicator) contact in the gas valve «BV1» is checked by the RMG... to ensure it
is closed.
When the CPI contact subsequently opens, there is no response from the burner con-
trol during the times «t10 / t1 / t12».
From program phase «B», that is, at the start of the safety time «TSA», the CPI contact
is continuously checked to ensure it is open. If not, lockout will occur.

Oil preheater Only when firing on oil:


When the oil is sufficiently preheated, contact «OW» in the external oil preheater
closes.

Monitoring of time of oil If the oil preheater’s release contact does not close after 600 seconds, lockout will be
preheater initiated.

Detection of Only when firing on oil:


extraneous light If extraneous light is detected, lockout will take place within the period of time «t3».
Before a demand for heat is received (standby phase), only extraneous light is indi-
cated by the red-green flash light in the lockout reset button. Extraneous light is indi-
cated for a maximum of 25 seconds. If extraneous light is detected for a longer period
of time, lockout will be initiated.

Only when firing on gas:


If extraneous light is detected, lockout will take place within the periods of time «t1» and
«t12». During the times «t0» and «tw», only extraneous light is indicated by the red-
green flash light from the LED in the lockout reset button. Extraneous light is indicated
for a maximum of 25 seconds. If extraneous light is detected for a longer period of time,
lockout will be initiated.

Flame supervision When changing from the operating state to standby or repetition (only when firing on
oil), a flame signal is permitted for a period of 10 seconds after the heat demand con-
tact has opened. Otherwise, lockout will occur.

Loss of air pressure Only when firing on gas:


If air pressure switch «LP» switches to its idle position during the prepurge time «t1»,
the program will return to the beginning of «t10».
Loss of air pressure during «t1» may occur no more than 4 times.
If loss of air pressure occurs on completition of «t1», the burner control will immediately
initiate lockout.

Fuse If fuse is blown due to overload, the unit’s life expectancy will be shortened.

10/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003
Control sequence in the If lockout occurs, the outputs for the fuel valves and ignition will immediately be deacti-
event of fault vated (< 1 second).

Cause Response
General
Mains failure Repetition with unshortened program
sequence
Voltage has dropped below the undervoltage Repetition with unshortened program
threshold sequence
Burner does not ignite after «TSA» Lockout
Afterburn time > 10 seconds Lockout

Only when firing on oil


Loss of flame during operation Maximum 3 repetitions, followed by lockout
Oil preheater’s release contact does not Lockout 600 seconds after demand for heat
close
Extraneous light during «t0» and «tw» Red-green signal lamp steady on, lockout
after 25 seconds
Extraneous light during «t1» Lockout

Only when firing on gas


Loss of flame during operation Immediate lockout
Contacts of air pressure switch «LP» have Lockout 10 seconds after the end of «t10»
welded in their idle position
«CPI» contact is open during «tw» Lockout approx. 20 s
Contacts of air pressure switch «LP» have Prevention of startup and lockout after about
welded in their working position 20 seconds
Loss of air pressure during «t1» Maximum 4 repetitions at the start of «t10»,
followed by lockout
Loss of air pressure after the fuel valve has Immediate lockout
opened
Extraneous light during «t0» and «tw» Red-green signal lamp flashes, lockout after
25 seconds
Extraneous light 5 seconds after completion Lockout
of «tw» until start of «TSA»

Lockout In the event of lockout, the burner control remains locked (lockout cannot be changed)
and the red signal lamp will light up.
This status is also maintained in the event of a mains failure.

Resetting the burner If lockout occurs, the burner control can immediately be reset. To do this, keep the
control lockout reset button depressed for about 1 second.

11/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003
Operation, display, diagnosis

Operation Lockout reset button EK... is the key operating element for resetting the

7142z01/1002
EK burner control and for activating / deactivating the diagnostic functions.

Red The multicolor LED is the key indicating element for both the visual

7142z02e/1102
Yellow diagnosis and the interface diagnosis.
Green
LED

Both EK... and LED are located under the transparent cover of the lockout reset button.

There are 2 diagnostic choices available:


1. Visual diagnosis: Indication of the operating state.
2. Interface diagnosis: With the help of the interface adapter OCI400 and PC software
ACS400 or flue gas analyzers of different makes.

Visual diagnosis:
In normal operation, the different operating states are displayed in the form of color
codes according to the color code table below. The interface diagnosis is activated by
pressing the lockout reset button for at least 3 seconds (refer to Data Sheet 7614). If,
by accident, the interface diagnosis has been activated, in which case the slightly red
light of the signal lamp flickers, it can be deactivated by again pressing the lockout
reset button for at least 3 seconds. The moment of switching over is indicated by a
yellow light pulse.

Operating position Operating position


Visual diagnosis Interface diagnosis
PC / analyzer
>3s

Color code table


7142z03e/1102

xxxxxxxx
EK
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx

Indication of During startup, indication is according to the following table:


operating state Color code table
Sequences used Color code Color
«tw», standby with permanent phase,           Off
waiting statuses 
Oil: Oil preheater on z.......................................... Yellow
Gas: Prepurging
Ignition phase, ignition controlled zzzzzz Yellow-off
Operation, flame o.k. †.......................................... Green
Operation, poor flame (when detector †  †  †  †  †  Green-off
current drops below the recom-
mended level for reliable operation)
Undervoltage, built-in fuse z=z=z=z=z=z Yellow-red
Fault, alarm =......................................... Red
Extraneous light =†=†=†=†=†= Red-green
Error code output (e.g. 2 blinks) ====== Red-off

Legend ...... Steady on


z Yellow  Off
= Red † Green

12/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003
Diagnosis of cause After lockout, the red fault signal lamp remains steady on. In that condition, the visual
of fault diagnosis of the cause of fault according to the error code table can be activated by
pressing the lockout reset button for more than 3 seconds. Pressing the reset button
again for at least 3 seconds, the interface diagnosis will be activated. The interface
diagnosis works only if the lockout reset button AGK20.43 extension is not fitted. For
more detailed information, refer to Data Sheet 7614.

The following sequence activates the diagnosis of the cause of fault:

OCI400
Lockout position Lockout position Lockout position
Visual diagnosis Interface diagnosis
On Flashing PC / analyzer
Reset
EK EK EK

7142z04e/1102
Error code table
>3s xxxx xxxx
xxxx xxxx
>3s <3s
xxxx xxxx
xxxx xxxx
xxxx xxxx
xxxx xxxx

Error code table


Oil Gas Blink code Possible cause
RMO... RMG...
x x 2 x blinks No establishment of flame at the end of «TSA»
hh - Faulty or soiled fuel valves
- Faulty or soiled flame detector
- Poor adjustment of burner, no fuel
- Faulty ignition
--- x 3 x blinks Faulty air pressure switch
hhh
x x 4 x blinks Extraneous light
hhhh
x x 5 x blinks «CPI» contact is open during «tw»
hhhhh
x x 6 x blinks Free
hhhhhh
x x 7 x blinks Loss of flame during operation
hhhhhhh - Faulty or soiled fuel valves
- Faulty or soiled flame detector
- Poor adjustment of burner
x --- 8 x blinks Monitoring of oil preheater time
hhhhhhhh
x x 9 x blinks Free
hhhhhhhhh
x x 10 x blinks Wiring error or internal error, output contacts; faults that
hhhhhhhhhh cannot be detected, such as simultaneous faults

During the time the cause of the fault is diagnosed, the control outputs are deactivated.
- Burner remains shut down
- External fault indication remains deactivated
- Fault signal «AL» is activated

The fault diagnosis is quit and the burner switched on again by resetting the burner
control. To do this, press lockout reset button for about 1 second.

13/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003
Connection diagrams and internal diagrams

7142a06e/1203
AL EK
RMO503SE
RMO503SE/K2
Power
supply µC-control

FSV

K1 K4-2

K2-2

F
K2-1 K3 K4-1

1 15 9 5 10 4 8 3 11 14 12 13

1 15 6 9 7 5 10 4 8 3 11 14 12 13

AL OW
R

STB Z
1 W

1) M
br sw M
HS
QRC
Si BV1 BV0 BV3 BV2
L bl QRB

1) Alternativer Gebläsemotoranschluss für RMO503SE

7142a12e/1003
RMG508SE/GB AL EK

Power
µC-control
supply

FSV

K1
K3 K4-2
K2-2
F K4-1
K2-1

1 15 10 6 5 3 4 7 9 8 14 12 13 11 2

1 15 10 6 5 3 4 7 9 8 14 12 13 11 2
ION (Option)
CPI

STB AL LP
R BV1

HS W BV2
Si
L M Z

N
Without CPI wiring between terminal 2 and terminal 8

14/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003
Connection diagrams and internal diagrams (cont´d)

7142a07e/1003
RMG508SE AL EK

RMG509SE
RMG509SE/K Power
µC-control
supply

FSV

K1
K3 K4-2
K2-2
F K4-1
K2-1

1 15 10 6 5 3 4 7 9 8 14 12 13 11 2

1 15 10 6 5 3 4 7 9 8 14 12 13 11 2
ION (Option)
CPI

STB AL LP R
BV1 BV3
W
HS BV2
Si
L M Z

N
Without CPI wiring between terminal 2 and terminal 8

15/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003
Control sequence
RMO503SE A A´ B B´ C D
STB 1

7142d01e/1003
R
W 8
t0 tw
OW 4
max. 600 s
M 7
t1 t3n
Z 12
t3 TSA
BV0 3

BV1 10

BV2 13
t4 t42
BV3 14

FS 9
Yellow Flashing yellow Green
LED

Response in the event of loss of flame during operation (max. 3 failures permitted)

FS 9

RMO503SE/K2 A A´ B B´ C D
STB 1

7142d04e/1003
R
W 8
t0 tw
OW 4
max. 600 s
M 11
t1 t3n
Z 12
t3 TSA
BV0 3

BV1 10

BV2 13

FS 9
Yellow Flashing yellow Green
LED

Response in the event of loss of flame during operation (max. 3 failures permitted)

FS 9

16/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003
Control sequence (cont´d)

RMG508SE A B B´ C D
RMG509SE STB 1
RMG509SE/K t0

7142d02e/1102
R 8
W
tw TSA
CPI 2
t1

LP 4
t10
M 7
t3n
Z 13

BV1 12
t4
BV2/LR 14

BV3 11

FS 10
Flashing
Yellow yellow Green

LED
Yellow
Response in the event of loss of air pressure

LP 4
1) 1) 1) 1)

AL 5

RMG508SE/GB A B B´ C D
STB 1
t0

7142d05e/1003
R 8
W
tw TSA
CPI 2
t1

LP 4
t10
M 7
t3n
Z 13

BV1 12
t4
BV2/LR 14

FS 10
Flashing
Yellow Yellow Green

LED
Yellow
Response in the event of loss of air pressure

LP 4
1) 1) 1) 1)

AL 5

17/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003
Legend AL Alarm device M Burner motor
BV... Fuel valve QRB... Photoresistive detector
CPI Closed Position Indicator QRC... Blue-flame detector
EK Lockout reset button bl Blue
F Built-in fuse br Brown
ION Ionization probe sw Black
FS Flame signal R Control thermostat or pressurestat
FSV Flame signal amplifier Si External primary fuse
HS Main switch STB Safety limit thermostat
K... Contacts of control relay OW Release contact of oil preheater
LP Air pressure switch W Limit thermostat or pressure switch
LR Load controller Z Ignition transformer

A´ Beginning of startup with B-B´ «TSA»


burners using «OW» C Change to operation
A Heat demand C-D Operation
B End of prepurging, start of D Change to standby
«TSA»

Control signals of burner control 1) Lockout


Required input signals
Permitted input signals

tw Waiting time t3n Postignition time


TSA Ignition safety time (ignition time during «TSA»)
t0 Waiting for heat demand from t4 Interval «BV1-BV2»
«R» t10 Specified time for air pressure
t1 Prepurge time signal
t42 Interval «BV2-BV3»

18/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003
Dimensions

Dimensions in mm

Burner control with


plug-in base

64,5
110,7 7142m01/1002

RMO503SE
LMO88.580A2RL
220-240 V
TSA 5 s

85,35
103,7

Burner control complete 26


22
with lockout reset but-
ton extension
5,5

AGK20.43 and plug-in


43

base

7142m02/1002

RMO503SE
LMO88.580A2RL
220-240V
TSA 5 s

© 2003 Siemens Building Technologies


Subject to change!
19/19

Siemens Building Technologies CC1N7142en


HVAC Products Riello 28.10.2003

You might also like