Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Unit 3

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 13

Unit 3

Control of Three-Phase Induction Motors:

Motor current at start and during acceleration – Automatic starters – Increment Resistor type starter –
Automatic Autotransformer starter – Open circuit and closed-circuit transition

Part winding motor starters Two step and Three step starting – Automatic Star-Delta starters Open
circuit and closed-circuit transition – Starters for multi-speed motors. Starters for Wound rotor motors
– Control circuit using contactor and flux delay relays.

• Three phase squirrel cage motors are the most widely used motors in industry. About 80% of
the motors manufactured are squirrel cage motors.

• Simplicity, ruggedness and reliability of such a motor make it the standard choice for alternating
current, all purpose, constant speed applications.

• These motors are less expensive, require less maintenance than dc motors of equal kilowatt
rating and speed.

• Before discussing the various types of starters for this motor, brief description of characteristics
of this type of motor is included as follows:

• A squirrel cage induction motor consists of a frame, a stator and a rotor. The stator or the
stationary portion carries the three stator windings.

• The rotor consists of cylindrical member made of steel laminations mounted rigidly on the
motor shaft. The rotor winding consists of copper or aluminium bars fitted into slots in the rotor
member.

• The bars are shorted at each end by a closed continuous ring. This assembly of bars and end
rings looks like a squirrel cage and this similarity has given the motor its name.

• When a three phase supply is given to the three stator windings a resultant magnetic field is set
up which revolves

• where Ns = Speed in revolutions of the magnetic field

• f = Supply frequency

• p = Number of stator poles for which the stator winding is made.

• The minimum number of poles for a winding can be two. Thus, at 50 Hz supply the maximum
speed of revolution of the field is 3000 r.p.m. For a 4 pole machine it would be 1500 r.p.m. This
revolving field cuts the rotor bars and induce current in them. The induced current in the rotor
produces its own magnetic field.

• The stator magnetic field and rotor magnetic field interact and the rotor magnetic field follows
the stator magnetic field thereby establishing a torque on the motor shaft. The current in the
rotor is maximum at standstill (when the rotor is stationary, emf induced in the standstill rotor is
maximum).

• As the motor picks up speed, the rotor current decreases as the relative speed between the
rotating field produced by the stator and rotor speed decreases. The torque speed characteristic
of a typical squirrel cage motor is shown in Fig. 3.1.

• This characteristic remains fixed for a particular rotor design. The characteristic can be changed
by making changes in the rotor resistance and reactance.

Motor Current at Start and During Acceleration

• At standstill when voltage is applied to the stator winding, the rotor winding acts like a short
circuited secondary of a transformer.

• The secondary current and thus in turn the primary current drawn by stator winding from supply
is large.

• The starting current may be as high as 4.5 to 6 times the full load current of the motor
depending upon the motor characteristics.

• As the motor accelerates, the current goes on decreasing but at a slow rate. The current decays
sharply when motor reaches near its rated speed.

• Fig. 3.2 shows the current versus speed characteristic of an induction motor.

• As shown in Fig. 3.2 upto 50% of the rated speed the current drawn remains approximately 6
times the full load current.

• When motor reaches about 80% of the rated speed the decline in the current is very fast. The
motor heating rate is proportional to I2R (copper loss).

• Thus the rate of heating of the motor is high during acceleration.

Starting of Motor

• A motor may be required to start on no-load or on full load depending upon the machinery to
which it is connected.
• Many industrial applications require a machine to be started at no-load, while some machines
may require starting at its full-rated load. In the first case during no load starting motor needs
only a small torque to overcome the starting inertia. In the second case the motor starting
torque should be enough to start with the normal load against the starting inertia

• The most common method of starting of poly-phase squirrel cage motor is to connect the motor
directly to the main supply through a manual or magnetic starter.

• At starting, the inrush current is high but due to this high current a high starting torque is
developed, which accelerate the motor quickly to its final speed. As the accelerating rate is fast
the I2R heating time in the motor is small. This starting method is however used only for small
motors upto 5 hp.

• Higher capacity motors are generally started at a reduced voltage for the following two reasons:
(i) The high starting current drawn from the main supply is objectionable to the supply
authorities as it causes heavy line voltage drops which adversely effects the performance of
other loads connected to the system.

• The supply authorities, therefore, impose restriction on the industries not to start large motors
directly from supply. Consider a 415 V, 50 hp motor whose full load current is about 70 amps.
The motor if started direct-from main supply will draw a current of about 6 × 70 = 420 A.

• Thus it is apparent that such a high current will disturb the supply network system. The motors
are therefore recommended to be started at a lower voltage so that the inrush current drawn
from supply is lower. The voltage, however, can be reduced upto a certain level as, lowering of
voltage also lowers the starting torque. (as T ∝ V 2).

• To start a motor from standstill, certain minimum starting torque is required depending upon
the load on the motor.

• For motors which have to start on full-load the supply authorities allows the direct on line
starting, provided the peak current is drawn in steps so that the rate of rise of current/sec is
reduced.

• The purpose is to enable the automatic voltage regulators provided in the supply system to
have sufficient time to adjust system voltage due to peak currents drawn. (ii) The second reason
for starting motors on reduced voltage may be to obtain low starting torque. This may be
desired in certain machinery where full voltage starting torque applied suddenly may cause
machinery to get damaged due to sudden jerk. The sudden application of high torque may cause
wear or damage of gears, chains or couplings.

• The belts may slip and the material being processed on conveyors may get damaged.

• It thus follows that squirrel cage motors are usually to be started at a reduced voltage.

• The desired result may be either reduced current drawn from supply to avoid disturbance in the
supply system or reduced torque to avoid jerk.

• The reduced voltage at the motor terminals can be applied by using different types of starters.
Different types of reduced voltage starter used are:

(i) Resistance reduced voltage starter;

(ii) Increment resistance starter;

(iii) Reactance reduced voltage starter;

(iv) Auto transformer reduced voltage starter;


(v) Part winding reduced voltage starter;

(vi) Star delta starter.

• Detailed description on all these starters are included in the next section. It is very important to
understand the behavior of an induction motor during the start up and acceleration periods.
Such an understanding would enable one to select the proper starting method to confirm to
local supply authorities regulation. Though several starting methods may appear suitable for a
particular motor application, a careful examination of the specific application will lead to the
selection of the best method of starting.
Automatic Primary Resistor Type Starter

• This starter also has two contactors marked START and RUN as in the case of semi-automatic
starter. Here, the time gap between closing of start contactor and run contactor is controlled
automatically with the help of an electrical timer. The time can be adjusted as per requirement.

• The power and control diagram for the starter is shown in Fig. 3.7. When ON-push button is
pressed the control relay CR gets energized and is held energized through its contact CR1, the
over-load relay contact being in closed condition.

• Normally open contact CR2 also closes and energizes the rest of control circuit. Closing of CR2
energizes contactor S and the time delay relay TR through normally closed contact R1 of
contactor R.

• Energization of contactor S causes the main contacts to close and the motor starts running with
resistance connected in series with the supply lines [see Fig. 3.7 (a)].

• When the time delay relay TR operates after a pre-set time, its delayed contact TR1 closes and
thereby energises the run contactor R. Contactor R remains energised by getting supply through
its own contact R2. Closing of contactor R short circuits the resistances and the motor gets
supply through the closed contacts of contactor R.

• The energization of contactor R causes switching off of start contactor S and time delay relay TR.
De-energization of contactor S disconnects resistors from main supply.

• Also opening of delayed contact TR1 of time delay relay TR does not effect the working of the
run contactor as it is now held through its own contact.

• The time set on the time delay relay determines the acceleration time of the motor with
resistors in circuit. This time can be increased or decreased depending upon the load on the
machines.

Automatic primary resistor type starter (a) Power diagram (b) Control diagram

INCREMENT RESISTANCE STARTER

• In increment resistance starter the resistance connected in the motor circuit is cut off in steps.
• The motor starts only when all the resistances have been cut off and motor gets connected to
full supply voltage and draws the normal direct on line current, which is about six times the full
load current.

• At this point one may wonder, that what is then the need for inserting resistance in the circuit
and cut it off in increments till the motor again gets connected to supply !

• This starter is used for large motors which require high starting torque to start from standstill.

• A reduced inrush current cannot start these motors from standstill. The current required for
starting such motors is the direct on line current. However, if this large current is drawn by
connecting the motor directly to supply, the supply network gets unstable.

• The voltage regulators connected in the network cannot correct the voltage drop due to this
sudden heavy current drawn from supply.

• In order to allow time for the voltage regulators to correct the system network voltage, the
direct on line inrush current from the supply is drawn in two or three steps with certain fixed
time delays.

• This time delay after each current inrush allows the voltage regulators to adjust the network
voltage.

• This would become more clear when we look at the motor current versus time characteristic of
this increment resistance starter as shown in Fig. 3.8.

• When motor is first switched ON, the current drawn from supply is 2 times the full load current
and the motor does not start up as the starting torque developed is not sufficient to pull the
motor from standstill.

• After time t1, some resistance is cut out from the motor circuit and as a consequence another
inrush of current takes place. The current drawn becomes 4 times the full load current but even
then the motor is not able to pull from standstill.

• After another gap of t2 – t1 seconds the rest of the resistance is cut off and the motor gets
directly connected to supply. Now the current inrush reaches 6 times the full load and motor
develops sufficient starting torque to start from standstill. Beyond this time the current time
curve follows the direct on line starting current as shown in Fig. 3.8.

• Thus it is seen that although the current drawn from supply is high, rate of rise of current is
reduced very much to allow system voltage regulators to adjust for the increase of current from
the network. The power circuit and the control circuit for this type of a starter are shown in Fig.
3.9.

• Referring to the power circuit it is seen that when contactor 1S closes, the motor gets connected
to supply with full line resistances. When contactor 2S is energized half of the resistance is by-
passed and when the contactor R closes, the whole of the resistances is bypassed and the motor
terminals get connected to full supply voltage. Let us see how this operation is accomplished
through the control circuit. When the ON-push button is pressed, control relay CR gets
energised and is held through its own contact CR1.

• It’s another contact CR2 energizes the rest of the control circuit. Contactor 1S and timer 1T gets
energized through the normally closed contact R1 of the contactor R.

• Energization of contactor 1S connects motor terminal to supply through the resistance. When
timer 1T times out (say in 5 secs), its delayed contact 1T1 closes and energizes contactor 2S and
the coil of timer 2T. Energization of contactor 2S, closes its main contacts and half of the
resistance is cut off from the motor circuit.

• After 5 secs the timer 2T also operates and its delayed contact 2T1 closes and energizes the coil
of the run contactor R. Run contactor immediately gets held through its own contact R2. The
normally closed contact R1 of contactor R is now open which de-energizes contactor 1S, 2S and
timers 1T and 2T.

• The RUN contactor R, however, remains energized through its own contact and the motor runs
by getting supply directly from the mains, the resistances being by-passed.

Increment resistance starter (a) Power diagram (b) Control diagram

Automatic Auto-transformer Starter (Open Circuit Transition)

• In automatic starter, the transition from start to run condition takes place automatically with
the help of a timer.

• The motor is connected to the lines through contactors as shown in power diagram shown in
Fig. 3.13 (a).

• The control circuit diagram has been shown in Fig. 3.13 (b). Four main contacts of start
contactor (S) have been used to connect the auto-transformer windings in open delta.

• As the starter shown is for a large motor, motor has been connected to supply through, circuit
breaker and magnetic overload relay. When the start contactor is energized, contacts S4 and S5
connect the transformer windings to neutral points.

• At the same time closing of contacts S1, S2 and S3 causes supply of reduced voltage from the
transformer taps to the motor terminals. The motor accelerates at this reduced voltage. After
the motor reaches near its final speed, if contactor R is energized keeping contactor S ON, a
circulating current will flow in the auto-transformer windings between the transformer taps and
neutral points, causing severe over heating of the transformer windings.

• Heavy mechanical stresses produced will also be harmful to the windings. Thus the design is
such that contactor R cannot be energized unless contactor S is open.
• This however will be an open circuit transition and a transient inrush current may flow into the
motor. Opening of contactor S first and then energization of contactor R is accomplished with
the help of a control circuit shown in Fig. 3.13 (b).

• On pressing the ON-push button, the control relay CR is energized and the contactor S gets
energized through normally closed delayed contact

• TR1 of timer TR. Timer TR coil is energized through closed contact S6 of the

• contactor S and gets hold through its own instantaneous contact. The operating time of timer
TR determines the accelerating time for the motor. When after a pre-set time the timer TR
operates, its normally closed contact TR1 opens and normally open contact TR2 closes.

• Opening of contact TR1 de-energizes contactor S. Due to de-energization of the contactor its
auxiliary contact S6 opens and S7 closes. Opening of S6 has no effect on timer TR while closing
of S7 causes energization of the run contactor R through the closed contact TR2 of the timer.
The motor runs on full voltage when the run contactor gets energized after a pre-set time from
the instant of starting of the motor.

• The motor starting current versus time characteristic during the starting is shown in Fig. 3.14.
The dotted line in Fig. 3.14 shows the direct on line characteristic while the full line shows the
current with auto-transformer in the circuit.

• At time t1 the start contactor is opened and at time t2 the run contactor is closed. For a time
gap t2 – t1 the motor winding is disconnected from the supply. During this period a voltage is
generated in the motor winding due to rotor flux.

At t2 when run contactor is energized the induced voltage and supply voltage may get superimposed to
give a high transient current of short duration which may be higher than even the direct on line starting
current

Automatic auto-transformer starter: (a) Power circuit (b) Control circuit


Auto-Transformer Voltage Starter (Closed Circuit Transition)

• Closed circuit transition operation requires two starting contactors, both having three poles.

• The contacts used are as shown in Fig. 3.16.

• Contacts of contactor 1S are used for the neutral of the auto-transformer windings.

• Contactor 2S connects the transformer windings to the supply. When contactors 1S and 2S are
closed, the transformer is energized from the supply.

• Reduced voltage from the tapping A, B and C is available at the motor terminals. After the motor
picks up sufficient speed contactor 1S is first de-energized.

• Auto-transformer neutral connection gets disconnected. The motor remains connected to mains
through contacts of contactor 2S and the transformer acts as a reactance in the motor circuit.
Next, the run contactor R is energized which by-passes the reactance and connects the motor
directly to the supply.

• Thus, it is seen that the motor gets connected to full supply without getting disconnected from
the supply. This avoids the sudden inrush of current as experienced by motor windings in open
circuit transition.

• The control circuit for an auto-transformer reduced voltage starter in closed circuit transition is
shown in Fig. 3.17.

Power connection with three winding auto-transformers


• When by pressing ON-push button the control circuit is energized, the contactor 1S gets
energized through normally closed delayed contacts of timer 1TR and simultaneously the coil of
timer 1TR is also energized.

• Closing of contactor 1S also causes closing of contactor 2S through its auxiliary contact 1S1 and
normally closed delayed contact of timer 2TR.

• Contactor 2S is held through its auxiliary contact 2S1. When timer 1TR times out, the NC contact
1TR1 opens and NO contact 1TR2 closes.

• Opening of 1TR1 causes de-energization of contactor 1S. When contactor 1S is open, its auxiliary
contact 1S2 closes and thus contactor R gets energised. Alongwith contactor R, timer 2TR is also
energized.

• When timer 2TR operates, its delayed contact which is in series with coil of contactor 2S, opens
and de-energises the contactor 2S. De-energisation of 2S disconnects the windings of the
transformer which were acting as reactance.

• The motor now runs directly from the supply. The starting current versus time characteristic for
closed circuit transition is shown in Fig. 3.18.

Auto-transformer reduced voltage starter for closed circuit transition Control circuit for closed circuit
transition

• As seen from Fig. 3.18, two small inrush of currents take place at time t1 and time t2.

• First inrush at t1 takes place when motor gets disconnected from transformer tappings and runs
with reactor in the circuit.

• Second inrush at t2 takes place when reactor is by-passed due to energisation of the Run
contactor.

• After that, motor characteristic follows the original direct on line current path.

• When this characteristic is compared with open circuit transition characteristic of Fig. 3.14, it is
quite evident that high inrush current experienced in the former is eliminated in this circuit.
PART WINDING MOTOR STARTER

• Part winding starters are used with squirrel cage motors having two separate and parallel stator
windings. Large motors can be built with three parallel windings also. The windings may be star
connected or delta connected depending upon the design of the motor. Part winding motors are
used to drive centrifugal loads such as fans, blowers or centrifugal pumps. These motors can
also be used for other loads requiring low starting torque. In cases where the motor is started
with only one winding, the starting current drawn from line is reduced. When started on one
winding the motor draws approximately two thirds of the normal starting current and develops
approximately one half of the normal direct on line starting torque. It may however be clearly
understood here that if the motor is connected to a heavy inertia load, the starter would work
as incremental starting device. The motor will not begin to accelerate until the second winding is
connected.

The advantages of the part winding starters are:

• (i) It is less expensive than other reduced voltage starters using resistors, reactors and
transformers;

• (ii) It requires only two contactors having half the rating of the full-load rating of the motor;

• (iii) The starter provides closed circuit transition.

The disadvantage of part winding starting are:

• (i) The starting torque is fixed and is low;

• (ii) Neither of the two windings has thermal capacity to operate along for more than a

• few seconds. Thus, this type of starting is unsuitable for high inertia loads where

• starting time is long.

Part-winding starter may be of the following two types, namely:

• (i) Two-step starting, and

(ii) Three-step starting.

• Two Step Starting: In two step starting, two contactors control the two windings of the motor.
Refer power and control circuit diagrams shown in Fig. 3.19.

Two step starting circuits for induction motors

• (a) Power circuit diagram; (b) Control circuit diagram


• When the ON-push button is pressed, the control relay, CR is energized which inturn energizes
contactor S and timer TR simultaneously.

• Closing of contactor S connects one winding of the motor to the lines. After some time, when
timer TR operates, Run contactor R gets closed and therefore the second winding also gets
connected to the lines in parallel with the first winding. Now the motor runs with two windings
in parallel.

• Current drawn by the motor gets equally divided between the two windings. The over-load
relays are connected in both the windings. Setting of these relays is done according to the
current taken by the individual windings.

• If current increases in any one of the windings and the corresponding overload relay trips, both
the contactors get de-energized. This happens because both the contacts are connected in
series with the coil of the control relay (CR).

Three Step Starting

• In three step starting when first contactor is closed, one of the two windings gets connected to
the lines through resistors in each of the phases. After a time delay of approximately two
seconds, the resistances are cut off and this winding gets connected to the full line voltage
through the closing of the second contactor.

• After another time delay of two seconds, the Run contactor is energised to connect the second
winding to the lines. The value of resistance can be so selected that 50% of the line voltage is
available at the motor terminals during first step. Thus the motor starts with three
approximately equal increments of the starting current.

• The power and control circuit diagrams for three step starting is shown in Fig. 3.20. Pressing of
the ON-push button will energise contactor S and timer 1T.

• Contactor S closes to start the motor with resistors in circuit and the supply reaches motor
terminals T1, T2 and T3. When Timer 1T operates after 2 seconds, its delayed contact closes to
energise contactor 1S. Closing of contactor 1S shorts the resistances from the circuit. A timer 2T
is also energised along with 1S.

• When timer 2T operates after 2 second the Run contactor R is energised, which closes to
connect the second winding of the motor also to the lines.
• Now both the windings are connected in parallel to the lines through contactors R and 1S.
Contactor S opens when the Run contactor is energised (due to opening of NC contact R1).

Three step starting of an induction motor


(a) Power circuit diagram; (b) Control circuit diagram

You might also like