BR 6000
BR 6000
BR 6000
www.epcos.com
Preview
U I
I U
Power factor
Power factor improvement Types of PFC
results in Power factor improvement can be (detuned or conventional)
4 EIPL 2013
Preview
EIPL 2013 5
PQS Key Components Overview
PF controllers
BR6000
BR6000-R06 BR6000-R12 BR6000-T06 BR6000-T12
Supply voltage 245 V AC ( 20%; L-N) 245 V AC ( 20%; L-N) 245 V AC ( 20%; L-N) 245V AC ( 20%; L-N)
BR5000
BR5000-R08 BR5000-R16 BR5000-T16
Supply voltage 415V AC 415V AC 415V AC
(-40% to +20%; L-L) (-40% to +20%; L-L) (-40% to +20%; L-L)
Measurement 3Ph 3wire 415V AC 3Ph 3wire 415V AC 3Ph 3wire 415V AC
voltage range (-40% to +20%) (-40% to +20%) (-40% to +20%)
Measurement current X/5 or X1/A selectable X/5 or X1/A selectable Only 5Amp CT secondary
Frequency 45Hz to 62.5Hz 45Hz to 62.5Hz 45 Hz to 55 Hz
BR4000
BR4904 BR4008
Supply voltage 230V AC (-25% to +20%; L-N) 230V AC (-25% to +20%; L-N)
Measurement voltage range 230V AC (-25% to +20%; L-N) 230V AC (-25% to +20%; L-N)
Measurement current X/5 or X1/A externally selectable X/5 or X1/A externally selectable
Frequency 47Hz to 53 Hz 47Hz to 53 Hz
BR7000 15 relay outputs PF controller for 3 phase measuring and controlling B44066R7415E230
MC7000-3 Grid analysis tool for 3 phase measuring, display and storage B44066M1301E230
of electric parameters
8 EIPL 2013
Important Notes
The following applies to all products named in this 4. In order to satisfy certain technical requirements,some of
publication: the products described in this publication may contain
1. Some parts of this publication contain statements about substances subject to restrictions in certain jurisdictions
the suitability of our products for certain areas of appli- (e.g. because they are classed as hazardous).
cation. These statements are based on our knowledge Useful information on this will be found in our Material
of typical requirements that are often placed on our prod- Data Sheets on the Internet (www.epcos.com/material).
ucts in the areas of application concerned. We neverthe- Should you have any more detailed questions, please
less expressly point out that such statements cannot be contact our sales offices.
regarded as binding statements about the suitability 5. We constantly strive to improve our products. Conse-
of our products for a particular customer application. quently, the products described in this publication
As a rule, EPCOS is either unfamiliar with individual may change from time to time. The same is true of the
customer applications or less familiar with them than corresponding product specifications. Please check
the customers themselves. For these reasons, it is always therefore to what extent product descriptions and speci-
ultimately incumbent on the customer to check and decide fications contained in this publication are still applicable
whether an EPCOS product with the properties described before or when you place an order.
in the product specification is suitable for use in a partic- We also reserve the right to discontinue production
ular customer application. and delivery of products. Consequently, we cannot
2. We also point out that in individual cases, a malfunc- guarantee that all products named in this publication will
tion of electronic components or failure before the always be available.
end of their usual service life cannot be completely The aforementioned does not apply in the case of
ruled out in the current state of the art, even if they are individual agreements deviating from the foregoing for
operated as specified. In customer applications requiring customer-specific products.
a very high level of operational safety and especially in
customer applications in which the malfunction or failure 6. Unless otherwise agreed in individual contracts, all
of an electronic component could endanger human life or orders are subject to the current version of the “General
health (e.g. in accident prevention or life-saving systems), Terms of Delivery for Products and Services in
it must therefore be ensured by means of suitable design the Electrical Industry” published by the German
of the customer application or other action taken by the Electrical and Electronics Industry Association (ZVEI).
customer (e.g. installation of protective circuitry or 7. The trade names EPCOS, BAOKE, Alu-X, CeraDiode,
redundancy) that no injury or damage is sustained by third CSMP, CSSP, CTVS, DeltaCap, DigiSiMic, DSSP,
parties in the event of malfunction or failure of an electronic FormFit, MiniBlue, MiniCell, MKD,MKK, SquareCap,
component. AgriCap, PoleCap, MLSC, MotorCap, PCC, PhaseCap,
3. The warnings, cautions and product-specific notes PhaseCube, PhaseMod, PhiCap, SIFERRIT, SIFI,
must be observed. SIKOREL, SilverCap, SIMDAD, SiMic,SIMID, SineFormer,
SIOV, SIP5D, SIP5K, ThermoFuse, WindCap are
trademarks registered or pending
in Europe and in other countries. Further information
will be found on the Internet at
www.epcos.com/trademarks.
10 EIPL 2013
PF Controllers BR6000 Series
Intelligent l
User-friendly l
Cost-effective l
Version 5.0
General
Controllers for PFC are of major Different versions of the BR6000
importance in the PFC system. series provide solutions to various
They measure the actual power applications:
factor and connect or disconnect
capacitor stages to achieve a BR6000-R6 and BR6000-R12
specific desired value (cos j ). for conventional applications with
slowly changing loads (optionally
The PF controller series with RS485 interface)
and BR6000 (six and twelve
stages) offer highly intelligent BR6000-T6 and BR6000-T12
control behavior and are very for dynamic PFC in applications
user-friendly thanks to menu-driven with fast-changing loads
handling (plain language). Their
multifunctional display greatly
simplifies installation, handling and
maintenance.
38 EIPL 2013
PF Controllers BR6000 Series
Intelligent l
User-friendly l
Cost-effective l
Version 5.0
EIPL 2013 39
PF Controllers BR6000 Series
Intelligent l
User-friendly l
Cost-effective
*RS 232-B44066R6312R230N1
*RS 485-B44066R6412R230N1
40 EIPL 2013
Copying of this document and giving it to others and the use or communication of the contents thereof, are forbidden without
express authority. Offenders are liable of the payment of damages. All rights are reserved in the event of the grant of a patent Page
of registration of a utitily model or design. Proprietary data, company confidential. All rights reserved. BR6000 Controller Setting Procedure 1 /2
Pre checks:
Measurement voltage & measurement current (load CT) should be from same phase.
Ensure that the controller relay output P1 & P2 common 230V supply should be drawn
from the measurement phase
Programming Procedure
Go to programming mode.
A. Press “Auto/Program/Manual/Service “ mode button – Programming will display. Press ENTER /OK button.
C. I– CT Primary Ratio – Set the load CT primary current by pressing UP/DOWN key button. Press ENTER /OK
button.
D. I –CT secondary –Set load CT secondary current by pressing UP/DOWN key button. Press ENTER /OK
button.
E. END STEP (12) – Set the end step number as per total number of steps connected by pressing UP/DOWN
button. Press ENTER /OK button.
F. Control series 1 – Press UP button & go to control series E, Press ENTER /OK button.
G. Control Mode- set to’ Intelligent’ mode, Press ENTER /OK button.
st
H. Power of 1.Stage – Set 1 step minimum KVAR rating , Press ENTER /OK button.(*Ensure that the outputs
of controller (relay / transistor) are connected from min to max kVAr rating)
L. Switching ON Time – Press UP/DOWN button set to 30SEC (For BR6000/T – 1000ms), Press ENTER/OK
M. Switching OFF Time – Press UP/DOWN button set to 40SEC (For BR6000/T – 1000ms),Press ENTER/OK
N. Discharge Time – Press UP/DOWN button set to 60SEC (For BR6000/T – 1000ms),Press ENTER/OK
P. (27)Harmonics setting – Set at 6% (If it exceed the limit, controller will give step OFF signal) – (Not
Applicable for Harmonics setting in BR6000-T type )
Q. Basics Setting – set to ‘NO’ If made YES – Then all previous setting will change to default setting, Press
ENTER/OK.
1. Press Auto/Program/Manual/Service button
A. Control Series Editor
B. Press ENTER/OK
C. Set step according step rating
Example No : 01 : - if there are 6 steps of 25,25,50,50,100,100 then minimum step rating 25 Kvar will be
1 & 50 Kvar will be multiple of 25 kvar is 2 & ,100 kvar will be multiple of 25 Kvar is 4 hence setting would
be 1,1,2,2,4,4
st
Example No : 02 :- If step rating are-5,10,25,25,50,100 then controller can take multiple of 9 of 1
minimum step i.e 5Kvarx9=45Kvar which is lesser than 50 & 100 kvar step hence for 50 kvar step has to
assign A, 100 Kvar step B & so on. The final setting for above step will be = 1,2,5,5,A,B,
D. Press ENTER/OK.
N. Rajkumar
Responsible: CSS
Date
/2011
20/03/2015
Pictorial View
Report number:
BR6000 Controller Setting Procedure
------
Communication
--------------------------------------- END -------------------------------------------------------
Page
2
Issue
2 /2