Old Emac
Old Emac
Old Emac
Augustenborg Landevej 19
DK-6400 Sønderborg
Denmark
Tel.: +45 74 12 36 36
Fax: +45 74 43 36 46
www.agramkow.com
INSTRUCTIONS
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
1 APPLICATION
2 SAFETY REGULATIONS
3 INSTALLATION
4 SHORT-FORM INSTRUCTION
5 OPERATION
6 TROUBLE-SHOOTING
7 MAINTENANCE
8 SHUT-DOWN
9 OPTIONS
10 SPECIFICATIONS
11 TECHNICAL DOCUMENTATION
12 ANNEX
-1.1-
Application
The Evacuation and Charging station EMAC is applied to charge systems with
refrigerant after evacuated the refrigeration systems. The specific data you will find in
the test report attached.
F
Information concerning references to other chapters, drawings etc.
This operation manual is written only for information purposes. Alterations reserved. For
direct or indirect damages, which result on using this manual, no responsibility is taken.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-2.1-
Safety regulations
• The Charging Station is built according to the newest technique and is safe for
operation. Nevertheless, danger could still arise, if incorrectly operated by non
qualified personnel, or if used for the wrong purpose.
•
• The Charging Station serves the sole purpose of charging systems with refrigerants
after the refrigerant systems have been evacuated. Any other use, apart from this, is
considered as not conforming to regulations and is entirely at the risk of the operator.
The manufacturer cannot be held liable for any damage resulting from the
aforementioned misuse.
• Any operation, which may impair the safety of the Charging Station, should be
avoided.
• The handstop valves must be continuously open during operation. Only in case of
service or a leak in the system, these valves should be closed.
• The gun has to be coupled to the system during the complete process. In case the
gun is discoupled, refrigerant can directly blow off. If necessary, it is recommended
to wear protective cloth (gloves and glasses).
• Operator changes to the mechanics or electrics, which might impair the safety,
should be avoided.
• All maintenance tasks should be performed only after switching off. The plug should
be withdrawn from the mains. In case of faults in the electrical power supply, switch
off the station directly. Works on electrical parts are allowed to carry out only by an
electrician or under supervision of an electrician by using the electrical rules.
• The process should be performed only when a system is connected. The connected
system should only be detached, when the process has been finished.
• When replacing components, use only original components Use only original fuses
with the required amperage.
• When dismantling, bear in mind that the systems are under pressure.
• When handling the refrigerant, the manufacturer's safety rules should be observed.
• For operation, the local safety rules are in any case binding.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-2.2-
Safety regulations
• During the processes ‘Self evacuation’ and ‘Manual Evacuation’ the gun can heat up.
• Depending on the use of the machine it is to define, whether protective glasses and
gloves have to be worn.
• Before start working the personnel has to read the operation manual, and here
especially the chapter Safety Instructions. During the working process it is too late.
This also applies to personnel, who only works from time to time at the machine, eg
for service or maintenance.
• From time to time you have to check, if the personnel works according to the safety
rules of the operational manual
• Pay attention to all safety and danger related text plates on the station.
• In case of functional faults the station has to be stopped. Remove then the fault.
Check the processes by means of the operational manual.
• The Charging Station is not suitable for and should not be used with flammable
refrigerants.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-3.1-
Installation
Page
Transport 3.2
Switching on 3.4
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-3.2-
Installation
Transport
F
Works on electrical parts are
allowed to carry out only by an
electrician or under supervi- Purge on inlet filter
sion of an electrician by using the
electrical rules. Follow pressure on
gauge
Remove cab
Purge on pal
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-3.3-
Installation
Release
emergency stop
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-3.4-
Installation
F
Works on electrical parts are
allowed to carry out only by an
electrician or under super-
vision of an electrician by using the
electrical rules.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-3.5-
Installation
INTERRUPT
• Be aware, that the gun is connected PLEASE CONNECT GUN TO HOLDING DEVICE
to the holding device. FORWARD INTERRUPT
• Evacuate up to appr 0.5 mbar. After PRESS : 9.10 MBAR TIME: 00:00:07
00
01
having reached this vacuum, press INTERRUPT
INTERRUPT.
INTERRUPT
01 STORAGE PLACE: 01
INFO PROG
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-3.6-
Installation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-3.7-
Installation
F
In order to guarantee a trouble
free operation of the charging
station, the refrigerant line
must be able to maintain a constant
supply pressure.
See specifications page 10.0.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-3.8-
Installation
First Charge
F
In order to weigh the charging
amount, weigh before
charging the evacuated test
container.
F
It is recommended to oil the
O-ring in the process coupling
after each 5th charge with
compressor oil. By doing this
the connection to the system is better
and the life time of the O-ring is
extended.
F
Storage place 01 is pre-set
with the following values:
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-3.9-
Installation
INFO PROG
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-4.1-
Short-form instructions
Front
1 Operation desk
3 Front door
7
2 5
3 2
Fig 1
4
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-4.2-
Short-form instructions
Rear side
1 ON/OFF switch
4 Emergency switch
5 Vacuum pump
Fig 2
4
2
7
3
6
5
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-4.3-
Short-form instructions
Operation desk
1 READY lamp
3 EVACUATION lamp
5 CHARGING lamp
11 Function keys
12 Display
3
4 1
5
12 2
11
6 7
9 10
8
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-4.4-
Short-form instructions
To the electrical control box all electrical devices are connected. The numbering is
equal to the internal numbering of the box and the connecting cables. Fig 4 (page 4.5 fig
4) indicates the internal connection of the box, fig 5 (page 4.5 fig 5) the external
connections.
1 Host connector
2 Printer port
11 Liquifier
15 Electrical mains
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-4.5-
Short-form instructions
13 4 3 6 10
11
Fig 4
5 7 8 9 15
12 2 1 14
Fig 5
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.1 -
Operation
Operation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.3 -
Operation
Basics
When the operating philosophy was conceived, it was felt that a simple and user
friendly operation was the ultimate aim.
The operation is menu driven. 4 Function keys, which are defined on the screen, are
used to choose the different menus.
01 STORAGE PLACE: 01
INFO PROG
Information line
- operator level
- program level
Data can only be saved, deleted or changed at program level. Data cannot be
manipulated at operator level!
Operator mode
Program mode
- manual evacuation
- manual charging
- recovery of the charging station
- self-evacuation of the charging station
The process itself can only be initiated by pressing the lit START key or the lit START
key on the charging gun.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.4 -
Operation
READY
EVACUATION
CHARGING
RELEASE GUN
ALARM
In the following all indication lamps and funktion keys printed bold and are
underlined (eg READY), menues printed bold (eg OPTIONS) .
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.5 -
Operation
INFO PROG
F
You must always put in 2
digits, eg if you wish to save
your data in memory 5, you
must put in 05.
INFO PROG
INFO PROG
INFO PROG
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.6 -
Operation
FORWARD INTERRUPT
FORWARD INTERRUPT
FORWARD INTERRUPT
01 LEAK-CHECK-TIME: 00:00:10
FORWARD INTERRUPT
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.7 -
Operation
The process
F
Do not charge pre-charged
systems. In case a system is
charged once, the refrigera-
tion system has to be pre-evacuated
before connecting it to the charging
station.
F
The process can be ter-
minated at any time by fusing
the function INTERRUPT
(see page 5.8).
F
It is recommended to oil the
O-ring in the process coupling
after each 5th charge with
compressor oil. By doing this
the connection to the system is better
and the life time of the O-ring is
extended.
F
The process can only be 01
INFO PROG
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.8 -
Operation
Process procedure
FORWARD INTERRUPT
01
According to how LOW-P. has been PRESS: 0.09 MBAR TIME: 00:00:00
set, you can call up the pre-set values HIGH-P. LEAK-TIME INTERRUPT
01
01
F
INTERRUPT is always to the
right of the display as you look
at the keys.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.9 -
Operation
Interrupting during
evacuation
and pressure rise test
00 PRESS: 18.23 MBAR TIME: 00:00:05
If you interrupt the process during eva-
cuation or pressure rise test, the pro- LOW -P. EVAC.-TIME INTERRUPT
INFO PROG
FORWARD
proceed.
1. Continue charging.
2. Final interruption
INTERRUPT
INFO PROG
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.10 -
Operation
Program level
INFO PROG
F
If the key switch is not open,
you cannot enter the program
level.
PLEASE OPEN THE KEY SWITCH
INTERRUPT
INTERRUPT
01 STORAGE PLACE: 01
INFO PROG
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.11 -
Operation
MANUAL
RECOVERY
MEDIA
LANGUAGE
PLEASE CHOOSE A MENU !
CLOCK
FORWARD MEDIA LANGUAGE BACKWARD
STATION
TEST
PLEASE CHOOSE A MENU !
OPTIONS
FORWARD CLOCK DEVICE BACKWARD
RESET
ADJUST
PLEASE CHOOSE A MENU !
- change data
- occupy memory
- lock/release memory
- delete memory
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.12 -
Operation
Change data
PLEASE CHOOSE A MENU:
In principle, the menu is organized in
exactly the same way as the INFO FORWARD DATA MANUALLY BACKWARD
FORWARD INTERRUPT
FORWARD INTERRUPT
FORWARD INTERRUPT
05 LEAK-CHECK-TIME: 00:00:10
FORWARD INTERRUPT
• If you want to change the LEAK-
CHECK-TIME to eg 2 min 30 s, then
give in the figures 2-3-0. F ‚
05 LEAK-CHECK-TIME: 00:02:30
TAKE-OVER INTERRUPT
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.13 -
Operation
If you have not changed any data, the 05 STORE THE DATA?
function FORWARD is displayed.
(FORWARD) DELETE STORING INTERRUPT
F
Only after you have pressed
the function key STORING,
05 STORAGE PLACE RELEASED?
the new data will be saved.
(FORWARD) LOCKING RELEASE
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.14 -
Operation
To occupy memory
05 STORAGE PLACE NOT ENGAGED
If memory is not occupied, the following
message is shown at operator level INFO PROG
FORWARD INTERRUPT
TAKE-OVER INTERRUPT
TAKE-OVER INTERRUPT
TAKE-OVER INTERRUPT
05 HIGH-P.: 5 MBAR
TAKE-OVER INTERRUPT
05 LEAK-CHECK-TIME: 00:00:30
TAKE-OVER INTERRUPT
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.15 -
Operation
F
The memory is only occupied
if the function key STORING 05 DATA TAKE-OVER?
is pressed. DELETE STORING INTERRUPT
05 STORAGE PLACE: 01
The following is shown in the display.
INFO PROG
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.16 -
Operation
Locking/releasing memory
INFO PROG
Locking memory occurs in the same
manner, except that function key LOCK
is pressed instead of function key
RELEASE.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.17 -
Operation
Deleting memory
STORAGE PLACE: 05
FORWARD INTERRUPT
INFO PROG
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.18 -
Operation
INTERRUPT
The evacuation process interrupts and
the main menu is displayed.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.19 -
Operation
Manual charging
INTERRUPT
00 15% OF 100G
TAKE-OVER INTERRUPT
00
• Now remove the charging gun. 00 CHARGING FINISHED
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.20 -
Operation
INTERRUPT
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.21 -
Operation
INTERRUPT
00
F
00 PRESS: 3.50 MBAR TIME: 00:00:27
If the station is fitted with
refrigerant pump, it is INTERRUPT
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.22 -
Operation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.23 -
Operation
F
Only the language you have
ordered is put into your
station. NEW CHOICE: FRENCH
FORWARD
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.24 -
Operation
YEAR (00-99): 94
FORWARD INTERRUPT
MONTH: 6
FORWARD INTERRUPT
DAY: 23
FORWARD INTERRUPT
HOURS: 10
FORWARD
HOURS: 11
STORING INTERRUPT
By storing, the seconds start from 0.
MINUTES: 2
FORWARD INTERRUPT
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.25 -
Operation
PASSWORD:
NTERRUPT
FORWARD FINISH
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.26 -
Operation
SENSORIK
SENSORIK
TEST-FUNCTIONS
INTERRUPT
INTERRUPT
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.27 -
Operation
F
Because the sensor is fitted
near electrical components,
the value is normally higher
than the actual ambient temperature.
F
The sensor is fitted on the
refrigerant tube.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.28 -
Operation
F
In case of non-functioning of a
button you cannot proceed in
this menu. Therefore, you
have to switch off the station and then
on again.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.29 -
Operation
TEST-FUNCTIONS
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.30 -
Operation
PRINTER
START BUTTON
F
The option bar code will only
be displayed if the station is BARCODE:
specified for bar code opera- FORWARD RELEASE LOCKING INTERRUPT
tion.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.31 -
Operation
deactivated.
F
You can test the printer in the PRINTER:
The Option
TIME-CONTROLLED
EVACUATION
this mode you evacuate a pre-set time. FORWARD TEST OPTIONS INTERRUPT
F
In the DATA menu you now
have the possibility to enter the
evacuation time.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.32 -
Operation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.33 -
Operation
F
In the bar code mode; a
BARCODE:
process start is only possible
after identification of the bar FORWARD RELEASE LOCKING INTERRUPT
code.
(START): 0
FORWARD INTERRUPT
(LENGTH): 0
FORWARD INTERRUPT
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.34 -
Operation
complete bar code, which contains the FORWARD TEST OPTIONS INTERRUPT
relevant information.
F
The maximum length of a bar
code string, which is iden-
tified, is 30 digits. BARCODE:
START POSITION: 0
FORWARD INTERRUPT
F 4
STRING-START POSITION: 4
LENGTH: 0
FORWARD INTERRUPT
F 3
F
In case the string length = 0,
the complete bar code from LENGTH: 3
be read.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.35 -
Operation
STORAGE PLACE: 05
FORWARD INTERRUPT
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.36 -
Operation
STORAGE PLACE: 05
FORWARD INTERRUPT
INTERRUPT
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.37 -
Operation
STORAGE PLACE: 05
FORWARD INTERRUPT
F
Only in case of pressing
STORING the bar code is 05 STORE THE DATA ?
deleted. DELETE STORING INTERRUPT
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.38 -
Operation
F
In the operation level it is
possible to select the storage
place either with the bar code BAR-CODE:
scanner or manually.
FORWARD RELEASE LOCKING INTERRUPT
INFO PROG
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.39 -
Operation
F
Use this menu only, when
your adjusted charging
amount does not correspond
to the charged amount.
PLEASE CHOOSE A MENU :
By activating this menu the 0-point of
the mass flow is reset. FORWARD RESET ADJUST BACKWARD
F
Your supply pressure has to START RESET
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.40 -
Operation
charging amount.
00
button.
START CHARGING
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-5.41 -
Operation
Further options
Two-sided evacuation
Pneumatic gun
Mobile version
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.1-
Trouble-shooting
Basics
FORWARD
Menus
FORWARD
If there is a fault indication during
charging process, the opposite menu
will occur.
01 15% of 100G
The charge can be continued after
INTERRUPT
clearing the fault.
FORWARD
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.2-
Trouble-shooting
F
The following fault devices
cannot identify all possible
faults. In case you are aware
of a wrong operation of your charging
station, please donot hesitate to contact
your agent.
F
In order to guarantee an
optimum operation of the
station it could be that a
parameter has to be readjusted after set
up of your station. The coming up of
several fault devices is an indication that
this is necessary.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.3-
Trouble-shooting
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.4-
Trouble-shooting
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.5-
Trouble-shooting
REASON SOLUTION
The medium temperature is out of the ad- • Ensure that the medium tempe-
missible temperature range of 10 - 50 C. rature is in the range of 10 - 50 C.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.6-
Trouble-shooting
REASON SOLUTION
The supply pressure is not in the range • Check the refrigerant and pressure
between psat-1 bar and 30 bar. supply.
• See also fault 06
psat is the saturation vapour pressure of the
stored refrigerant.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.7-
Trouble-shooting
REASON SOLUTION
The refrigerant supply vessel is empty. • Check the refrigerant tank and
make new refrigerant available.
The stored refrigerant is not equal to the • Check the internally stored refrig-
refrigerant you are using. erant.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.8-
Trouble-shooting
This fault occurs during selftest after switching on, in case after a pre-set internal time
(5 sec.) an internal vacuum (20 mbar) is not reached.
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.9-
Trouble-shooting
REASON SOLUTION
The refrigeration system is charged. • Release the gun. The charging sta-
tion is now ready for the next
system.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.10-
Trouble-shooting
This fault occurs in case of failing the pressure rise test . This happens in case the
vacuum drops during pressure rise test.
REASON SOLUTION
The values stored for high point, low point • Compare your system values to the
and pressure rise test are not adjusted for values stored.
your system.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.11-
Trouble-shooting
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.12-
Trouble-shooting
This fault occurs only in case the mode “time controlled evacuation“ is activated. The
low point is not reached in the adjusted evacuation time.
REASON SOLUTION
In case this fault is repeated, oil could be in • Switch off the charging station and
the vacuum line. then on again. Does fault no 07
occur ?
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.13-
Trouble-shooting
This fault occurs only in case you released the printer in the OPTION menu. In case
you do not use a printer, lock the printer in the OPTION menu (see page 5.31).
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.14-
Trouble-shooting
This fault is optional and normally not activated. During the charging process the
refrigerant pressure is measured. Stays this pressure during a pre-adjusted time below
an expected value, the charging process will be interrupted. This happens for example,
if the charging gun is not connected properly to your refrigeration system and falls off
during charging process.
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.15-
Trouble-shooting
REASON SOLUTION
The system is not completely recovered. • Refer to chapter 5.20 and empty
the charging station.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.16-
Trouble-shooting
REASON SOLUTION
Not stable pressure supply conditions • Check the refrigerant inlet valve.
during running of Reset mode. This should be opened.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.17-
Trouble-shooting
REASON SOLUTION
The bar code you are using has more than • Make sure, that your bar code has
30 digits. more than 30 digits.
Your parameter for the start position and • Change the parameter so that the
the string length are not correct (see last digit does not exceed the 30th
chapter 5.38). position.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.18-
Trouble-shooting
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.19-
Trouble-shooting
This fault occurs only in case your charging station is equipped with a pneumatic gun.
REASON SOLUTION
After starting the process the internally pre- • The gun is not coupled correctly to
set vacuum for the gun evacuation is not the system.
reached after a pre-set time.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.20-
Trouble-shooting
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.21-
Trouble-shooting
REASON SOLUTION
No refrigerant flows through the mass flow. • Are all valves open ?
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.22-
Trouble-shooting
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.23-
Trouble-shooting
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.24-
Trouble-shooting
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.25-
Trouble-shooting
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.26-
Trouble-shooting
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.27-
Trouble-shooting
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.28-
Trouble-shooting
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.29-
Trouble-shooting
REASON SOLUTION
Wrong storage place data. • Delete the data and occupy the
storage place again.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.30-
Trouble-shooting
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.31-
Trouble-shooting
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.32-
Trouble-shooting
REASON SOLUTION
The charging amount measured from the • Run the ADJUST menu (see page
measuring system does not correspond 5.40).
to the stored amount.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.33-
Trouble-shooting
REASON SOLUTION
During the charging process a pressure • Check the vacuum valve in the gun,
increase on the vacuum side is measured. if it is tight.
This is an indication that during the
charging process refrigerant gets to the If it is tight:
vacuum side. • Check if the vacuum system is
tight.
• Check the vacuum sensor
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.34-
Trouble-shooting
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-6.35-
Trouble-shooting
REASON SOLUTION
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-7.0-
Maintenance
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-7.1-
Maintenance
F
ring or clean it.
See page 7.2
depending on the
∗ Oil the O-ring for the Take compressor oil and oil the production rate
system connection connector in the gun with a little
amount
∗ Changing the O-ring Change the O-ring in the front part of depending on the
for the system the throw off device. production rate
connection.
∗ Changing oil of the See the manual of the producer see the manual of the
vacuum pump. producer
Cleaning of the Open the exhaust filter and clean it. when needed
exhaust filter of the
vacuum pump.
∗ Overhaul of the throw Change the throw off device and send
off device (optional it to the producer for overhaul. min each 6 months
feature).
∗ Check the pneumatic Check the pneumatic valves and depending on the
valves change the noise reducer, if production rate
necessary
∗ Check the couplings Check your used couplings for monthly
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-7.1-
Maintenance
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-7.2-
Maintenance
F
Maintenance must only be See page 5.20
! preformed after the complete
station is recovered.
087-7882038
069-5689023
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-7.3-
Maintenance
4. Check housing
for dirt, clean if
nessasery
6. Refit top
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-7.4-
Maintenance
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-8.0-
Shut down
Shut down
F
In case you pressed the
emergency stop button, you
have to release the stop
button with the key (see page 4.1 pos
7).
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-10.0-
Specifications
Operation temperature : 10 °C . . . 50 °C
Air supply (option) min 5 bar, max 8 bar, dry and free of oil
:
Weight : 110 kg
Dimensions : 600x680x1020 mm
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.0-
Technical documentation
Settings
Accumulator pressure, N2
Refrigerant
R134a 12±0.2 bar
R12 12±0.2 bar
R22 15±0.2 bar
R404A 15±0.2 bar
R407C 15±0.2 bar
R410a 22±0.2 bar
Gauge refrigerant
inlet
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.1-
Technical documentation
Settings
massflow
Remove cover
Factory settings of
actual massflow
Fig 2
Adjustment from
top, ciffer must be
adjusted to arrow.
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
AGRAMKOW Fluid Systems A/S
Product . . : Vacuum gun Emac Parts List No . . . . . . : 161-010264A Rev. date . . . . . . . : 17/04-02 Init . . . : GM Customer :
066-0000122 1,00 Pcs. 29 165-110006A-00 Hansen gun coupling 2HK Option HK2
066-0000125 1,00 Pcs. 29 165-110091A Nitto gun coupling 1/4" Option Nitto 1/4"
066-0000126 1,00 Pcs. 29 165-110090A-00 Nitto gun coupling 3/8" Option Nitto 3/8"
Product . . : Vacuum gun Emac Parts List No . . . . . . : 161-010264A Rev. date . . . . . . . : 17/04-02 Init . . . : GM Customer :
Product . . : Vacuum gun Emac Parts List No . . . . . . : 161-010264A Rev. date . . . . . . . : 17/04-02 Init . . . : GM Customer :
062-0014010 1,00 Pcs. 64 165-100032A-01 Handle for Hansen connector Option HK2
062-0014010 1,00 Pcs. 64 165-100032A-01 Handle for Hansen connector Option HK3
062-0014010 1,00 Pcs. 64 165-100032A-01 Handle for Hansen connector Option Nitto 3/8"
062-0014010 1,00 Pcs. 64 165-100032A-01 Handle for Hansen connector Option PCU 1/4"
062-0014010 1,00 Pcs. 64 165-100032A-01 Handle for Hansen connector Option Nitto 1/4"
Product . . : Vacuum gun Emac Parts List No . . . . . . : 161-010264A Rev. date . . . . . . . : 17/04-02 Init . . . : GM Customer :
Product . . : Vacuum gun Emac Parts List No . . . . . . : 161-010264A Rev. date . . . . . . . : 17/04-02 Init . . . : GM Customer :
Technical documentation
Gun evacuation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.4-
Technical documentation
Gun evacuation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.5-
Technical documentation
Gun evacuation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.6-
Technical documentation
Gun evacuation
29
Mount in station
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
AGRAMKOW Fluid Systems A/S
Product . . : Charging & evacution gun with automatic Parts List No . . . . . . : 161-010263A Rev. date . . . . . . . : 17/04-02 Init . . . : KHC Customer :
Product . . : Charging & evacution gun with automatic Parts List No . . . . . . : 161-010263A Rev. date . . . . . . . : 17/04-02 Init . . . : KHC Customer :
Product . . : Charging & evacution gun with automatic Parts List No . . . . . . : 161-010263A Rev. date . . . . . . . : 17/04-02 Init . . . : KHC Customer :
Product . . : Charging & evacution gun with automatic Parts List No . . . . . . : 161-010263A Rev. date . . . . . . . : 17/04-02 Init . . . : KHC Customer :
Product . . : Charging & evacution gun with automatic Parts List No . . . . . . : 161-010263A Rev. date . . . . . . . : 17/04-02 Init . . . : KHC Customer :
Product . . : Charging & evacuation gun Emac Parts List No . . . . . . : 161-010262A Rev. date . . . . . . . : 17/04-02 Init . . . : KHC Customer :
Product . . : Charging & evacuation gun Emac Parts List No . . . . . . : 161-010262A Rev. date . . . . . . . : 17/04-02 Init . . . : KHC Customer :
Product . . : Charging & evacuation gun Emac Parts List No . . . . . . : 161-010262A Rev. date . . . . . . . : 17/04-02 Init . . . : KHC Customer :
Product . . : Charging & evacuation gun Emac Parts List No . . . . . . : 161-010262A Rev. date . . . . . . . : 17/04-02 Init . . . : KHC Customer :
Product . . : Charging & evacuation gun Emac Parts List No . . . . . . : 161-010262A Rev. date . . . . . . . : 17/04-02 Init . . . : KHC Customer :
Technical documentation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.5 -
Technical documentation
Charging and evacuation gun
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.6 -
Technical documentation
Charging and evacuation gun
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.7 -
Technical documentation
Charging and evacuation gun
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.8 -
Technical documentation
Charging and evacuation gun
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.9 -
Technical documentation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.10 -
Technical documentation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.11 -
Technical documentation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.12 -
Technical documentation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.13 -
Technical documentation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.14 -
Technical documentation
Charging and evacuation gun
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.15 -
Technical documentation
Charging and evacuation gun
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.16 -
Technical documentation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.17 -
Technical documentation
Soft soldering
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.18 -
Technical documentation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.19 -
Technical documentation
Charging and evacuation gun
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.20 -
Technical documentation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.21 -
Technical documentation
Charging and evacuation gun
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.22 -
Technical documentation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.23 -
Technical documentation
Charging and evacuation gun
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.24 -
Technical documentation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.25 -
Technical documentation
Charging and evacuation gun
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.26 -
Technical documentation
Charging and evacuation gun
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.27 -
Technical documentation
Charging and evacuation gun
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.28 -
Technical documentation
Charging and evacuation gun
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.29 -
Technical documentation
Charging and evacuation gun
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.30 -
Technical documentation
Charging and evacuation gun
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.31 -
Technical documentation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.32 -
Technical documentation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.33 -
Technical documentation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.34 -
Technical documentation
Charging and evacuation gun
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-11.35 -
Technical documentation
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
AGRAMKOW Fluid Systems A/S
Product . . : Emac 25 & 25X mech. components Parts List No . . . . . . : 162-010236A Rev. date . . . . . . . : 26/08-02 Init . . . : BJL Customer :
Product . . : Emac 25 & 25X mech. components Parts List No . . . . . . : 162-010236A Rev. date . . . . . . . : 26/08-02 Init . . . : BJL Customer :
Technical documentation
Station
Numbers see PI diagram
162-120005AFig 2
13
12
9
11
7
5
10
4
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10
-12.0-
Annex
4 Calibration table
Calibration table.doc
5 Safty
Safty.pdf
F:\RAC\Instruktioner\162-40\0011A-01.doc
2001-07-10