PM135 Powermeter Series PM135P/PM135E/PM135EH: Installation and Operation Manual
PM135 Powermeter Series PM135P/PM135E/PM135EH: Installation and Operation Manual
PM135 Powermeter Series PM135P/PM135E/PM135EH: Installation and Operation Manual
PM135P/PM135E/PM135EH
BG0518 Rev. A3
WARNING
Read the instructions in this manual before performing installation and take
note of the following precautions:
Ensure that all incoming AC power and other power sources are
turned OFF before performing any work on the instrument. Protect
the measurement AC Inputs voltage (V1, V2, V3) with 2A external
overcurrent protection device and the power supply source inputs
with 5A external overcurrent protection device, located close to the
equipment.
CT wiring
RS-485 Terminals
Assembling a module
1.1 Features
Multifunctional 3-phase Power Meter
3 voltage inputs and 3 current transformer-isolated AC inputs for
direct connection to power line or via potential and current
transformers
1
Contact your local distributor for the desired Display languages support.
Digital I/O
Optional four, eight or 12 digital inputs with 1-ms scan time;
automatic recording of last five digital input change events with
timestamps (see the PM135 Modbus Reference Guide)
Optional two relay outputs with 1-cycle update time; unlatched,
latched, pulse and KYZ operation; energy pulses
Display
3.5 inch Monochrome Graphic LCD display with 240 x 128 dots
resolution, adjustable update time backlit and user defined
brightness setting
Auto-scroll option with adjustable page exposition time; auto-
return to a default page
Real-time Clock
Internal clock with 20-second retention time
Optional battery-operated clock unit (see Available Options)
Communications
Standard 2-wire RS-485 communication port; MODBUS RTU,
DNP3, and SATEC ASCII communication protocols
Optional second communication port (see Available Options);
MODBUS RTU, MODBUS/TCP, DNP3, DNP3/TCP, SATEC ASCII and
PROFIBUS DP communication protocols
eXpertPower client for communicating with the SATEC
proprietary eXpertPower Internet services (with the Ethernet
module or with the RS-232 module using an external GPRS
modem, see Setting Up eXpertPower Client)
TCP notification client for communicating with a remote
MODBUS/TCP server on events or periodically on a time basis
(with the Ethernet module or with the RS-232 module using an
external GPRS modem, see Setting Up TCP Notification Client)
Meter Security
Password security for protecting meter setups and accumulated
data from unauthorized changes
Upgradeable Firmware
Easy upgrading device firmware through a serial or Ethernet port.
Software Support
PAS – free meter configuration and data acquisition tool
eXpertPowerTM – SATEC proprietary Internet services
Digital I/O
The PM135 digital I/O expansion module provides:
4DI/2DO module
4 dry contact digital inputs (DI) for monitoring external contacts
and receiving pulses from energy, water, and gas meters
Programmable de-bounce time; 1-ms scan time.
8DI module
8 dry contact digital inputs (DI) for monitoring external contacts and
receiving pulses from energy, water, and gas meters
12DI/4DO module
12 dry contact digital inputs (DI) for monitoring external contacts
and receiving pulses from energy, water, and gas meters
Programmable de-bounce time; 1-ms scan time.
4 electro-mechanical relay outputs (RO) for alarms and controls,
and for output energy pulses; unlatched, latched and pulse
operations, failsafe operation for alarm notifications;
programmable pulse width; direct remote relay control through
communications; 1-cycle update time.
Analog Output
The PM135 analog output (AO) expansion module provides:
4 optically isolated analog outputs with an internal power supply;
Options for 0-20mA, 4-20mA, 0-1mA, and 1mA output; 1-cycle
update time.
Device Resolution
A low or high-resolution option can be selected for the presentation of
voltage, current, and power for use in high and low power applications.
See Measurement Units for more information.
Energy Rollover
The energy rollover limit can be changed in the meter to provide 4-digit to
9-digit energy resolution. See Device Options in Chapter 5 for details. The
meter display is capable of showing full 9-digit energy counters using two
LED windows.
Display Options
Different display options are available for customization to be used in dark
or non-safe locations, or in places that are hardly accessible for
observation. See Configuring the Display in Chapter 5 for more
information.
Chapter 2 Installation
This chapter discusses the following types of physical installations for the
PM135 Powermeter:
Mechanical Installation
Electrical Installation
I/O Connections
COM Port Connections.
Panel Mounting
To mount the meter in cutout (ANSI 4" round or DIN 92x92mm
square cutout):
1. Position the meter in the cutout.
2. Affix the meter using washers and
nuts. (Add short text on Panel
Mounting, a heading should always
have text)
Typical Installation
Terminals
690
400
Voltages
V1 V2 V3 VN
690V inputs are usually used with direct connection. Use any of the seven
wiring configurations shown in Figures 2-8 through 2-15.
120
120
Voltages
V1 V2 V3 VN
Wiring Diagrams
For AC input ratings, see Technical Specifications in Appendix A for more
details.
Table 2 presents the available wiring configurations in the meter. For
more details, see Basic Meter Setup in Chapter 5.
Figure 2-9 3-Wire 2-Element Delta Direct Connection Using 2 CTs (Wiring Mode = 3dir2)
Figure 2-10 4-Wire Wye 3-Element Direct Connection Using 3 CTs (Wiring Mode = 4LL3 or 4Ln3)
Figure 2-11 4-Wire Wye 3-Element Connection Using 3 PTs, 3 CTs (Wiring Mode = 4LL3 or 4Ln3)
Figure 2-12 3-Wire 2-Element Open Delta Connection Using 2 PTs, 2 CTs (Wiring Mode = 3OP2)
This configuration provides accurate power measurements only if the voltages are balanced.
Figure 2-13 4-Wire Wye 2½-Element Connection Using 2 PTs, 3 CTs (Wiring Mode = 3LL3 or 3Ln3)
Figure 2-14 3-Wire 2½-Element Open Delta Connection Using 2 PTs, 3 CTs (Wiring Mode = 3OP3)
Figure 2-15 4-Wire 3-Element Delta Direct Connection Using 3 CTs (Wiring Mode = 4LL3 or 4Ln3)
Figure 2-16 3-Wire 2½-Element Broken Delta Connection Using 2 PTs, 3 CTs (Wiring Mode = 3bLn3 or
3bLL3)
RS-485 Terminals
4DI/2DO Module
Relay Outputs
There are two relay outputs provided for energy pulsing, alarms, or
remote control.
Digital Inputs
Four optically isolated status inputs are provided for status monitoring,
pulse counting, external power demand period, and time synchronization.
8 DI module
Eight optically isolated status inputs are provided for status monitoring,
pulse counting, external power demand period, and time synchronization
12DI/4RO Module
The 12DI/4RO module can be equipped with optional communication port
COM2 – ETHERNET or RS-422/485.
Relay Outputs
There are four electro-mechanic relay outputs provided for energy
pulsing, alarms, or remote control.
Digital Inputs
12 optically isolated status inputs are provided for status monitoring,
pulse counting, external power demand period, and time synchronization.
Digital Inputs
WARNING!
Only qualified personnel familiar with the instrument and its
associated electrical equipment must perform the RTC battery
backup replacement.
To replace the CR1632 RTC battery:
1. Remove the TOU module from the
PM135 compartment
2. Open the TOU MODULE case by
applying a flat screwdriver at three
snap-in slit (1, 2 and 3), as shown
in Figure 2-27.
3. Remove the old battery by lifting up
the battery holder retractable tab.
4. Place the new CR1632 battery into
the battery holder while holding up
the battery holder retractable tab in
such a way that the (+) battery pole
is toward the battery holder, as
shown in Figure 2-27.
The GSM/GPRS SIM must not have any incoming voice call.
The customer must require from the Service Provider for DATA
services only
The GPRS modem module can be equipped with two different
antennas: internal Antenna for installation into plastic closet or
no-metallic environment. For metallic installation use external
antenna
Navigation Buttons
The PM135 is provided with five navigation buttons as described
below:
Button Operation
SELECT/ENTER
PAGE UP – scrolling UP
ESCAPE
Status Indicators
Graphical icons on the bottom status bar give immediate meter status
indication and show the present tariff rate.
The present date and time are indicated at left on the status bar. The date
order can be changed according to local rules via the "Real Time Clock"
device setup menu.
Voltage phase
presence indicators
Indicator Description
Icon
No load.
Indicator Description
Icon
123 All voltages are present and above the voltage dip threshold.
Blinking phase indicator – the phase voltage is below the
1 3 defined voltage dip threshold. Possibly indicates an incorrect
meter nominal voltage setting (see Basic Meter Setup in
123 Chapter 5).
Dashed phase indicator - the phase voltage is either missing or
1–3 below the voltage interruption threshold.
If the phase voltage is below the defined voltage dip threshold, its
corresponding phase indicator is blinking.
If the phase voltage is either missing or below the voltage interruption
threshold, the phase indicator is replaced with a dash
Display Features
While energizing the device the display will show an init screen followed
by phase-voltages measurements as described below:
Measurement Units
The PM135 has a selectable resolution for volts, amps and powers
presented on the front display and via communications. See Device
Options in Chapter 5 for information on selecting the data resolution in
the PM135 .
Low Resolution Option
Currents are displayed in whole amperes below 10,000 A, and in kilo
amperes above 10,000 A.
Measurement units for voltage and power depend on the voltage
connection scheme:
For direct wiring (PT=1) or wiring via PT with the PT ratio up to
and including 4.0, voltages are displayed in volts, and power in
kilowatts.
For the PT ratio above 4.0, voltages are displayed in kilovolts with
three decimal places, and power in megawatts with three decimal
places.
High Resolution Option
Currents are displayed in amperes with up to two decimal places below
10,000 A, and in kilo amperes above 10,000 A.
Measurement units for voltage and power depend on the voltage
connection scheme:
When direct wiring is used (PT=1), voltages are displayed in volts
with one decimal place, and power in kilowatts with three decimal
places.
When wiring via PT is used with the PT ratio up to and including
4.0, voltages are displayed in volts, and power in whole kilowatts.
For the PT ratio above 4.0, voltages are displayed in kilovolts with
three decimal places, and power in megawatts with three decimal
places.
The small round “Kilo” and “Mega” LEDs light up showing the appropriate
measurement units for a displayed page.
Fundamental Component
The PM135EH can display total displacement power factor and active
power for the fundamental component if it is enabled through the display
setup (see Configuring the Display).
When phase power readings are allowed, the PM135EH also displays per-
phase displacement power factor and active power for the fundamental
component.
The following example demonstrates the present billing period displays for
two configured billing registers (kWh imported and kvarh imported) and
for three active tariff rates. The actual register contents in your
installation may be different depending on your selection of register
sources.
Each billing period display lists all total and tariff energy, maximum
demand and cumulative maximum demand registers for all configured
billing registers and all active tariffs. Use the UP/DOWN button to scroll to
the desired Billing/TOU period register display
Phase-to-phase voltages
Line frequency
Voltage unbalance, %
Current unbalance, %
Harmonics Display
Harmonics display shows individual harmonics distortion for phase
voltages and current, and phase voltage/current harmonic spectrum
graphs. Use the UP/DOWN button to scroll to the specific harmonic
number or voltage and current channels harmonic spectrum.
Waveform Display
The waveform display shows per-phase voltage and current waveforms
and V/I values + THD. Use the UP/DOWN button to scroll through the
phases.
Phasor Display
The Phasor display shows a three-phase network Phasor diagram. All
phase angles are given relatively to the V1 channel.
Digital I/O
The Digital I/O display shows three sub-menus: "Digital Inputs" display to
show status of each digital input, "Pulse/Event Counters" display to count
external pulses or setpoint events, or as time counters to count setpoint
operation time, "Relay Outputs" display to show status of each relay
output. Use the UP/DOWN button to move from one display to another.
2. Specify the baud rate and data format for the port. Choose
the same baud rate and data format as you have set in the
meter, and then click OK.
The factory settings for the local PM135 RS-232 and RS-422/485 ports
are 9600 baud, 8 bits with no parity.
Selecting the Communications Protocol
1. On the Connection tab, click
Protocol.
Always set up and store the Basic Setup data to the site
database first. PAS uses this data as a reference when
arranging other meter setups.
Batch Download
To download all setups to your device at once:
1. Check the On-line button on the
PAS toolbar
2. Select the device site from the list
box on the toolbar.
3. Select Download Setups from the
Meter Setup menu.
4.5 Authorization
If communications with your meter is secured, you are prompted for the
password when you send new setup data to the meter.
Using PAS
Select Communications Setup from the Meter Setup menu, and then
click on the Serial Ports Setup tab. In the Port box, select the desired
device port.
Figure 5-1: Communication Setup Dialog Box – Serial Ports Setup Tab
NOTES:
1. The meter provides the permanent
MODBUS TCP server on port 502.
Setting Up Ethernet
Using the Front Display
Select Network Setup from the Device Setup menu. This menu entry
appears only if the optional Ethernet module is plugged into the
meter. It allows you to set up the meter network address and the default
gateway.
See Viewing and Changing Setup Options in Chapter 3 for information on
configuring parameters via the front display.
Device Setup
Real Time Clock
Display Setup
Basic Setup
Device Options
COM1 Setup
COM2 Setup
Network Setup
Using PAS
Select Communications Setup from the Meter Setup menu, and then
click on the Network Setup tab.
NOTES
1. The meter provides the permanent
MODBUS TCP server on port 502.
2. Selecting the DNP3 TCP service port
launches the second DNP3 TCP
server allowing simultaneous
connections on both TCP ports.
Selecting the MODBUS TCP port
disables the DNP3 TCP server.
The TCP service port can also be changed trough the COM2
serial port setup. Changing the communication protocol for the
port automatically changes the TCP port for the Ethernet.
COM2 Setup
Protocol Modbus RTU
Interface GPRS
Device Address 1
Using PAS
To set up GPRS communications:
1. Select Communications Setup
from the Meter Setup menu, and
then click on the GPRS Setup tab.
NOTES
6. Do not enable the eXpertPower client in your meter if you do not use
the eXpertPowerTM service.
7. Do not change the connection time
setting. It is for information only.
The eXpertPower server updates it
automatically.
Using PAS
Select General Setup from the Meter Setup menu. See the table below
for the Basic Setup options.
Transformer Correction
While using external CT meter option, transformer correction allows you
to compensate ratio and phase angle inaccuracies of the user voltage and
current instrument transformers.
The following table lists available options.
Label Parameter Options Default Description
Ratio V1-V3 V1-V3 voltage 0.700 to 1.300 1.000 The ratio of the true
transformer transformer ratio to the
ratio correction marked ratio.
factor
Angle V1-V3 V1-V3 -600 to 600 0 The phase
transformer displacement, in
phase angle minutes, between the
error, minutes primary and secondary
values. The phase angle
of a voltage transformer
is positive when the
secondary value leads
the primary value.
Ratio I1-I3 I1-I3 current 0.700 to 1.300 1.000 The ratio of the true
transformer transformer ratio to the
ratio correction marked ratio.
factor
Angle I1-I3 I1-I3 -600 to 600 0 The phase
transformer displacement, in
phase angle minutes, between the
error, minutes primary and secondary
values. The phase angle
of a current transformer
is positive when the
secondary value leads
the primary value.
Using PAS
Select General Setup from the Meter Setup menu, and then click on the
Transformer Correction tab.
Device Options
The Device Options setup allows changing user-configurable device
options or putting the meter into energy test mode.
Using PAS
Select General Setup from the Meter Setup menu, and then click on the
Device Options tab.
Table 10 lists available device options.
S P2 Q2
N S2 P2
Using PAS
Select General Setup from the Meter Setup menu, and then click on the
Digital Inputs tab.
Figure 5-8: General Setup Dialog Box – Digital Inputs Dialog Box
The debounce time is applied the same for all digital inputs. If you change
the debounce time for a digital input, the same debounce time is
automatically assigned to the others.
Using PAS
Select General Setup from the Meter Setup menu, and then click on the
Relay Outputs tab.
Using PAS
Select General Setup from the Meter Setup menu, and then click on the
Analog Outputs tab.
When you select an output parameter for the analog output channel, the
default engineering scales are set automatically. They correspond to the
maximum available scales. If the parameter actually covers a lower range,
you can change the scales to provide a better resolution on an analog
output.
Scaling Non-Directional Analog Outputs
For non-directional analog outputs with a 0-1mA, 0-20mA or 4-20mA
current option, you can change both zero and full engineering scales for
any parameter. The engineering scale need not be symmetrical.
Configuring Counters
The PM135 has four six-digit general counters that can count pulses
delivered through the device digital inputs with a programmable scale
factor. Each counter can also be incremented in response to any internal
or external event, checked and cleared through the Control Setpoints.
Using PAS
Select General Setup from the Meter Setup menu, and then click on the
Pulse/Event Counters tab.
Table 14 lists available counter options.
setup menu. See Viewing and Changing Setup Options in Chapter 3 for
Display Setup
Basic Setup
Device Options
COM1 Setup
COM2 Setup
information on configuring parameters via the front display.
Setpoint Setup
Using PAS
Select General Setup from the Meter Setup menu, and then click on the
Control/Alarm Setpoints tab.
The following table lists the available setpoint options.
Table 15: Setpoint Options
Option Range Description
Trigger parameter See Appendix C The trigger parameter that is used as an
argument in the logical expression
Operate limit The threshold (in primary units) at which the
conditional expression would be evaluated to
true. Not applicable for digital triggers.
Using PAS
Ensure that the On-line button on the PAS toolbar is checked, and then
select RTC from the Monitor menu or click on the PAS toolbar Real-
Time Clock Button.
The RTC dialog box displays the current PC date and time and the time in
your meter.
Figure 5-13: Real Time Clock Dialog Box – Time and Date setup
Device Setup
Reset
Real Time Clock
Display Setup
Basic Setup
Device Options
COM1 Setup
Local Settings
Local Settings
Date Order DD/MM/YY
Country Israel
Daylight Saving Time (DST) Enabled
DST Start Month March
DST Start Week of Month Last
DST Start Weekday Friday
DST Start Hour 2
Local Settings
DST Start Weekday Friday
DST Start Hour 2
DST End Month September
DST End Week of Month Last
DST End Weekday Sunday
DST End Hour 2
Time Synchronization Input None
Using PAS
Select General Setup from the Meter Setup menu, and then click on the
Local Settings tab.
Using PAS
Ensure that the On-line button on the PAS toolbar is checked, select
Administration from the Monitor menu, and then select Change
Password -> Password 1.
Figure 5-17: Energy/TOU Setup Dialog Box – TOU Daily Profiles Tab
The daily profile setup allows you to specify the daily tariff change points
with a 15-minute resolution for 4 seasons using 4 different daily schedules
for each season.
To configure your daily profiles:
1. Select the desired season and day
type.
2. Select the start time for each tariff
change point and the corresponding
active tariff number.
3. Repeat the setup for all active
profiles.
The first tariff change point is fixed at 00:00 hours, and the last tariff
change you specified will be in use until 00:00 hours on the next day.
NOTE
The billing daily profile log file is automatically configured for the number
of active tariffs you defined in the meter TOU daily profiles.
Figure 5-18: TOU Calendar Setup Dialog Box – TOU Calendar Tab
The meter TOU calendar allows you to configure any tariff schedule based
on any possible utility regulation. The calendar provides 32 entries that
allow you to specify profiles for working days and holidays through all
seasons in any order that is convenient for you, based on simple intuitive
rules.
To configure your season tariff schedule:
1. In the Season/Period box, select
the season, and in the Day Type
box, select a day type for this
calendar entry.
2. Define the time interval when this
daily tariff schedule is effective,
based on the start and end
weekdays and, for a multi-season
schedule, on the start and end
month for the selected season. It
does not matter which order of
weekdays or months you select: the
meter recognizes the correct order.
3. For exception days like weekends
and designated holidays, define a
specific day either by a month and a
month day, or by selecting a month,
a week and a weekday within the
month.
The above picture shows a typical single-season tariff schedule with two
daily tariff profiles configured for working days, and weekends and the
designated U.S.A. holidays.
NOTES
1. Memory is allocated for a file
statically when you set up your files
and will not change unless you re-
organize files.
2. The meter automatically performs
de-fragmentation of the memory
each time you re-organize your files.
This prevents possible leakage of
memory caused by fragmentation. It
may take a couple of seconds.
For more information on configuring specific files, see the following
sections.
The following table can help you calculate an estimated file size when
planning your memory allocation.
No. Parameter
1 kWh import
2 kWh export
3 kW import sliding demand
4 V1 demand
5 V2 demand
6 V3 demand
change the time interval for the MINUTE INTERVAL trigger in Setpoint #1
(see Configuring Alarm/Control Setpoints).
Billing/TOU Profile Data Log #16
Data log #16 is pre-configured for daily billing energy and maximum
demand recording for the last 90 days. It is automatically updated once a
day.
See Billing Profile Log File in Appendix E for the file record structure.
Configuring Modbus
Modbus Point Mapping
The PM135 provides 120 user assignable registers at addresses 0 to 119.
You can re-map any register available in the meter to any assignable
register so that registers found at different locations may be accessed
with a single request by re-mapping them to adjacent addresses.
Initially these registers are reserved and none of them points to an actual
data register. To build your Modbus register map:
1. Select Protocol Setup from the
Meter Setup menu, and click on
the Modbus Registers tab.
2. Click on the Default button to cause
the assignable registers to reference
the actual default meter register
6656 (0 through 119 are not
allowable register addresses for re-
mapping).
Configuring DNP3
Refer to the PM135 DNP3 Reference guide for information on the DNP3
protocol implementation and a list of the available data points.
DNP Options
Select Protocol Setup from the Meter Setup menu and click on the
DNP Options tab.
The following table describes available options. Refer to the DNP3 Data
Object Library document available from the DNP User’s Group on the
DNP3 object types.
2
The Select Before Operate command causes the meter to start a timer. The
following Operate command must be sent before the specified timeout value
expires.
3
The meter requests time synchronization by bit 4 in the first octet of the
internal indication word being set to 1 when the time interval specified by the
Time Sync Period elapses. The master should synchronize the time in the meter
by sending the Time and Date object to clear this bit. The meter does not send
time synchronization requests if the Time Sync Period is set to 0.
Figure 5-23: Protocol Setup Dialog Box – DNP Class 0 Points Tab
Using PAS
Ensure that the On-line button on the PAS toolbar is checked, and then
select Reset from the Monitor menu.
Using PAS
Ensure that the On-line button on the PAS toolbar is checked, select
Device Control from the Monitor menu, and then click on the Device
Diagnostics tab.
See Device Diagnostic Codes in Appendix G for the list of diagnostic codes
and their meaning.
Figure 6-5: Device Control Dialog Box – Remote Relay Control Tab
Polling Devices
Click on the “Poll” or “Continuous poll” button to poll the meter once
or continuously.
You can open as many monitor windows as you wish, either for different
sites, or for the same site using different data sets. An open data monitor
window is linked to the current site and does not change if you select
another site in the site list.
You can view acquired data in a tabular form or in a graphical form as a
data trend.
Some data sets are preset for your convenience and others are empty.
You can freely modify data sets.
See Appendix D for a list of data available in your meter.
Polling Options
To change the polling options, click on the Data Monitor window with the
right mouse button and select Options.
If you check Do not stop on errors, polling is resumed automatically
when a communication error occurs, otherwise polling stops until you
restart it manually.
To change the time range for your graph, click on the button on the
local toolbar, and then select the desired date and time range.
See Working with Graphic Windows in Chapter 9 for more information on
working with graphs.
To avoid confusion, do not store data files into the Sites directory where
site databases are located.
Printing Data
To check the report, as it will look when printed, select Print Preview
from the File menu.
To print retrieved data, click on the button on the PAS toolbar, select
a printer, and then click OK.
PAS supports 9 programmable data sets that you can organize as you
wish. To build your data sets, select MinMax Data Sets from the
Monitor menu or click on the button on the local toolbar.
Use the Poll button for a single-step poll or the Continuous poll
button for continuous polling.
Click on the “Poll” or “Continuous poll” button to poll the meter once
or continuously. Click on the Stop button to stop continuous polling.
To keep the Upload Scheduler running, the On-line button on the PAS
toolbar must be checked all the time. If you uncheck it, the scheduler
stops operations. This does not cause loss of data, since the scheduler will
resume operations when you check this button again.
To view the log data on-line, check the On-line button on the PAS
toolbar, select the log you want to retrieve in the Logs menu, and then
click on the Poll button . Only new log records are retrieved from the
device. If you want to review the entire log from the beginning, click on
the Restore log button , and then click on the Poll button .
NOTE
When reading multi-section profile data, only the first section is available
for reading online.
See Chapter 9 Viewing Files for information on using different log views.
Manual Converting
To manually convert your waveforms or a data log into COMTRADE or
PQDIF format:
Automatic Converting
PAS allows you to automatically convert data logs into PQDIF format at
the time you upload data from your devices via the Upload Scheduler.
To automatically convert your data log tables into PQDIF format:
1. Open the Upload Scheduler.
2. Highlight a desired device site with
the left mouse button, and then
click on the Export button.
3. Check the Enabled box for a data
log or a waveform log table you
want to automatically convert at the
upload time.
4. Highlight the Record to… row for
the selected table and click on the
Browse button.
5. Select a folder where you want to
store converted files, type in the
converted file’s name, select a
Customizing Views
Changing Date Order
To change the way PAS displays the date:
1. Select Options from the Tools
menu and click on the Preferences
tab.
2. Select the preferred date order.
3. Click OK.
Copying a Table
To copy the entire table, or its part, into the Clipboard or into another
application such as Microsoft Excel or Word:
1. Click on the data window with the
right mouse button and choose
Select All, or click on the upper-left
corner of the table (where the “No.”
label is commonly displayed).
2. Click with the right mouse button on
the window again and choose Copy,
or click on the Copy button on
the PAS toolbar.
3. Run the application to which you
want to copy data, position the
cursor at the correct place.
Printing a Table
To check how your document appears on a printed page, select Print
Preview from the File menu.
You can also drag both markers with the mouse, or use the right and left
arrow keys on your keyboard to change the marker position. Click on the
graph pane to allow the keyboard to get your input before using the
keyboard.
Delta Measurements
To measure the distance between two waveform or trend points, click on
the Delta button , then click on the first point, and then click on the
second point.
The first reference point is still frozen until you uncheck and check the
Delta button again, while the second point can be placed anywhere within
the graph line by clicking on the graph to the left or right from the
reference point.
To disable delta measurements, click on the Delta button once again.
Using a Zoom
You can use a horizontal and, for waveforms, also a vertical, zoom to
change size of your graph.
Use the buttons on your local toolbar to zoom in and zoom
out. One click gives you a 100-percent horizontal or 50-percent vertical
zoom. Two buttons representing magnifying glasses give you a
proportional zoom in both directions.
Copying a Graph
To copy a graph, or its part, into the Clipboard or into another application
such as Microsoft Excel or Word:
1. Click on the graph window with the
right mouse button and choose
Copy All, or Copy Waveform.
Some windows may have additional
options.
2. Position the cursor at the place
where you whish to copy the graph.
Printing a Graph
To check how the graph appears on a printed page, select Print Preview
from the File menu.
Click on the Filter button , or click on the report window with the right
mouse button and select Filter.... Check the causes of events you want to
display, and then click OK. PAS temporary hides rows you do not want
displayed.
To change the default sorting order based on the date and time, click on
the Sort button , or click on the report window with the right mouse
button and select Sort..., check the desired sort order, and then click
OK.
A.2 Construction
Dimensions see Figure 2-1
Weight: 0.70 kg (1.54 lb.)
Materials
Case enclosure: plastic PC/ABS blend
Front panel: plastic PC
PCB: FR4 (UL94-V0)
Terminals: PBT (UL94-V0)
Connectors-Plug-in type: Polyamide PA6.6 (UL94-V0)
Packaging case: Carton and Stratocell® (Polyethylene Foam) brackets
Labels: Polyester film (UL94-V0)
12 VDC Option:
Ethernet Port
Transformer-isolated 10/100BaseT Ethernet port
Supported protocols: MODBUS/TCP (Port 502), DNP3/TCP (Port 20000), IEC
60870-5-104
Number of simultaneous connections: 4 (2 MODBUS/TCP + 2 DNP3/TCP).
Connector type: RJ45 modular.
PROFIBUS DP (IEC 61158)
RS-485 optically isolated PROFIBUS interface.
Connector type: removable, 5 pins.
Baud rate: 9600 bit/s – 12 Mbit/s (auto detection).
32 bytes input, 32 bytes output.
Supported protocols: PROFIBUS
RS-232/422-485 Port
RS-232 or RS-422/485 optically isolated port
Isolation: 3000 VAC 1 min
Baud rate: up to 115.2 kbps.
Supported protocols: MODBUS RTU, DNP3, and SATEC ASCII, IEC 60870-5-
101
Connector type: removable, 5 pins for RS-422/485 and DB9 for RS-232.
Wire size: up to 14 AWG (up to 1.5 mm2).
A.10 Display
3.5" LCD Monochrome Display, 240 x 128 dots resolution
Tri-color LED load bar graph (40-110%)
COM1 RX/TX activity LED
Diagnostics indication LED
kWh/kvarh Pulse LED (for E and EH models)
Keypad: 5 push buttons
Vf - fundamental voltage
If - fundamental current
NOTES
1. Accuracy is expressed as (percentage of reading +
percentage of full scale) 1 digit. This does not
include inaccuracies introduced by the user's
potential and current transformers. Accuracy
calculated at 1second average.
1
@ 80% to 120% of voltage FS, 1% to 200% of current FS and frequency 50/60 Hz
1 In 4LN3, 3LN3 and 3BLN3 wiring modes, the voltages will be line-to-neutral; for
any other wiring mode, they will be line-to-line voltages.
Designation Description
I3 TDD I3 Current TDD
V12 V12 Voltage
V23 V23 Voltage
V31 V31 Voltage
RT TOTAL 1-Cycle Total Values
kW Total kW
kvar Total kvar
kVA Total kVA
PF Total PF
PF LAG Total PF lag
PF LEAD Total PF lead
kW IMP Total kW import
kW EXP Total kW export
kvar IMP Total kvar import
kvar EXP Total kvar export
V AVG 3-phase average L-N/L-L voltage
V LL AVG 3-phase average L-L voltage
I AVG 3-phase average current
RT AUX 1-Cycle Auxiliary Values
In In (neutral) Current
FREQ Frequency
V UNB% Voltage unbalance 2
I UNB% Current unbalance 2
AVR PHASE 1-Second Phase Values
V1 V1/V12 Voltage
V2 V2/V23 Voltage
V3 V3/V31 Voltage
I1 I1 Current
I2 I2 Current
I3 I3 Current
kW L1 kW L1
kW L2 kW L2
kW L3 kW L3
kvar L1 kvar L1
kvar L2 kvar L2
kvar L3 kvar L3
kVA L1 kVA L1
kVA L2 kVA L2
kVA L3 kVA L3
PF L1 Power factor L1
PF L2 Power factor L2
PF L3 Power factor L3
V1 THD V1/V12 Voltage THD 1
V2 THD V2/V23 Voltage THD 1
V3 THD V3/V31 Voltage THD 1
I1 THD I1 Current THD
I2 THD I2 Current THD
I3 THD I3 Current THD
I1 KF I1 K-Factor
I2 KF I2 K-Factor
Designation Description
I3 KF I3 K-Factor
I1 TDD I1 Current TDD
I2 TDD I2 Current TDD
I3 TDD I3 Current TDD
V12 V12 Voltage
V23 V23 Voltage
V31 V31 Voltage
AVR TOTAL 1-Second Total Values
kW Total kW
kvar Total kvar
kVA Total kVA
PF Total PF
PF LAG Total PF lag
PF LEAD Total PF lead
kW IMP Total kW import
kW EXP Total kW export
kvar IMP Total kvar import
kvar EXP Total kvar export
V AVG 3-phase average L-N/L-L voltage 1
V LL AVG 3-phase average L-L voltage
I AVG 3-phase average current
AVR AUX 1-Second Auxiliary Values
In In (neutral) Current
FREQ Frequency
V UNB% Voltage unbalance 2
I UNB% Current unbalance 2
PHASORS Phasors
V1 Mag V1/V12 Voltage magnitude 1
V2 Mag V2/V23 Voltage magnitude 1
V3 Mag V3/V31 Voltage magnitude 1
I1 Mag I1 Current magnitude
I2 Mag I2 Current magnitude
I3 Mag I3 Current magnitude
V1 Ang V1/V12 Voltage angle 1
V2 Ang V2/V23 Voltage angle 1
V3 Ang V3/V31 Voltage angle 1
I1 Ang I1 Current angle
I2 Ang I2 Current angle
I3 Ang I3 Current angle
DEMANDS Present Demands (Power Demands E, EH)
V1 DMD V1/V12 Volt demand 1
V2 DMD V2/V23 Volt demand 1
V3 DMD V3/V31 Volt demand 1
I1 DMD I1 Ampere demand
I2 DMD I2 Ampere demand
I3 DMD I3 Ampere demand
kW IMP BD kW import block demand
kvar IMP BD kvar import block demand
kVA BD kVA block demand
kW IMP SD kW import sliding window demand
Designation Description
kvar IMP SD kvar import sliding window demand
kVA SD kVA sliding window demand
kW IMP ACD kW import accumulated demand
kvar IMP ACD kvar import accumulated demand
kVA ACD kVA accumulated demand
kW IMP PRD kW import predicted sliding window demand
kvar IMP PRD kvar import predicted sliding window demand
kVA PRD kVA predicted sliding window demand
PF IMP@kVA DMD PF (import) at Maximum kVA sliding window demand
kW EXP BD kW export block demand
kvar EXP BD kvar export block demand
kW EXP SD kW export sliding window demand
kvar EXP SD kvar export sliding window demand
kW EXP ACD kW export accumulated demand
kvar EXP ACD kvar export accumulated demand
kW EXP PRD kW export predicted sliding window demand
kvar EXP PRD kvar export predicted sliding window demand
In DMD In (neutral) current demand
SUMM ACC DMD Billing Summary (Total) Accumulated Demands E, EH
REG1 ACD Register #1 accumulated demand
REG2 ACD Register #2 accumulated demand
REG3 ACD Register #3 accumulated demand
REG4 ACD Register #4 accumulated demand
SUMM BLK DMD Billing Summary (Total) Block Demands E, EH
REG1 BD Register #1 block demand
REG2 BD Register #2 block demand
REG3 BD Register #3 block demand
REG4 BD Register #4 block demand
SUMM SW DMD Billing Summary (Total) Sliding Demands E, EH
REG1 SD Register #1 sliding demand
REG2 SD Register #2 sliding demand
REG3 SD Register #3 sliding demand
REG4 SD Register #4 sliding demand
ENERGY Total Energy E, EH
kWh IMPORT kWh import
kWh EXPORT kWh export
kvarh IMPORT kvarh import
kvarh EXPORT kvarh export
kVAh TOTAL kVAh total
SUMMARY REGS Billing Summary (Total) Energy Registers E, EH
SUM REG1 Summary energy register #1
SUM REG2 Summary energy register #2
SUM REG3 Summary energy register #3
SUM REG4 Summary energy register #4
PHASE ENERGY Phase Energy E, EH
kWh IMP L1 kWh import L1
kWh IMP L2 kWh import L2
kWh IMP L3 kWh import L3
kvarh IMP L1 kvarh import L1
kvarh IMP L2 kvarh import L2
kvarh IMP L3 kvarh import L3
Designation Description
kVAh L1 kVAh total L1
kVAh L2 kVAh total L2
kVAh L3 kVAh total L3
%HD V1 V1/V12 Harmonic Distortions EH 1
V1 %HD01 H01 Harmonic distortion
V1 %HD02 H02 Harmonic distortion
… ...
V1 %HD40 H40 Harmonic distortion
%HD V2 V2/V23 Harmonic Distortions EH 1
V2 %HD01 H01 Harmonic distortion
V2 %HD02 H02 Harmonic distortion
… ...
V2 %HD40 H40 Harmonic distortion
%HD V3 V3/V31 Harmonic Distortions EH 1
V3 %HD01 H01 Harmonic distortion
V3 %HD02 H02 Harmonic distortion
… ...
V3 %HD40 H40 Harmonic distortion
%HD I1 I1 Harmonic Distortions EH
I1 %HD01 H01 Harmonic distortion
I1 %HD02 H02 Harmonic distortion
… ...
I1 %HD40 H40 Harmonic distortion
%HD I2 I2 Harmonic Distortions EH
I2 %HD01 H01 Harmonic distortion
I2 %HD02 H02 Harmonic distortion
… ...
I2 %HD40 H40 Harmonic distortion
%HD I3 I3 Harmonic Distortions EH
I3 %HD01 H01 Harmonic distortion
I3 %HD02 H02 Harmonic distortion
… ...
I3 %HD40 H40 Harmonic distortion
ANG V1 V1/V12 Harmonic Angles EH 1
V1 H01 ANG H01 Harmonic angle
V1 H02 ANG H02 Harmonic angle
… ...
V1 H40 ANG H40 Harmonic angle
ANG V2 V2/V23 Harmonic Angles EH 1
V2 H01 ANG H01 Harmonic angle
V2 H02 ANG H02 Harmonic angle
… ...
V2 H40 ANG H40 Harmonic angle
ANG V3 V3/V31 Harmonic Angles EH 1
V3 H01 ANG H01 Harmonic angle
V3 H02 ANG H02 Harmonic angle
… ...
V3 H40 ANG H40 Harmonic angle
ANG I1 I1 Harmonic Angles EH
I1 H01 ANG H01 Harmonic angle
Designation Description
I1 H02 ANG H02 Harmonic angle
… ...
I1 H40 ANG H40 Harmonic angle
ANG I2 I2 Harmonic Angles EH
I2 H01 ANG H01 Harmonic angle
I2 H02 ANG H02 Harmonic angle
… ...
I2 H40 ANG H40 Harmonic angle
ANG I3 I3 Harmonic Angles EH
I3 H01 ANG H01 Harmonic angle
I3 H02 ANG H02 Harmonic angle
… ...
I3 H40 ANG H40 Harmonic angle
H1 PHASE Fundamental (H01) Phase Values
V1 H01 V1/V12 Voltage 1
V2 H01 V2/V23 Voltage 1
V3 H01 V3/V31 Voltage 1
I1 H01 I1 Current
I2 H01 I2 Current
I3 H01 I3 Current
kW L1 H01 kW L1
kW L2 H01 kW L2
kW L3 H01 kW L3
kvar L1 H01 kvar L1
kvar L2 H01 kvar L2
kvar L3 H01 kvar L3
kVA L1 H01 kVA L1
kVA L2 H01 kVA L2
kVA L3 H01 kVA L3
PF L1 H01 Power factor L1
PF L2 H01 Power factor L2
PF L3 H01 Power factor L3
HRM TOT POW Fundamental and Harmonic Total Power Values
kW H01 Total fundamental kW
kvar H01 Total fundamental kvar
kVA H01 Total fundamental kVA
PF H01 Total fundamental PF
MIN PHASE Minimum 1-Cycle Phase Values
V1 MIN V1/V12 Voltage 1
V2 MIN V2/V23 Voltage 1
V3 MIN V3/V31 Voltage 1
I1 MIN I1 Current
I2 MIN I2 Current
I3 MIN I3 Current
MIN TOTAL Minimum 1-Cycle Total Values
kW MIN Total kW
kvar MIN Total kvar
kVA MIN Total kVA
PF MIN Total PF
Designation Description
MIN AUX Minimum 1-Cycle Auxiliary Values
In MIN In Current
FREQ MIN Frequency
MAX PHASE Maximum 1-Cycle Phase Values
V1 MAX V1/V12 Voltage 1
V2 MAX V2/V23 Voltage 1
V3 MAX V3/V31 Voltage 1
I1 MAX I1 Current
I2 MAX I2 Current
I3 MAX I3 Current
MAX TOTAL Maximum 1-Cycle Total Values
kW MAX Total kW
kvar MAX Total kvar
kVA MAX Total kVA
PF MAX Total PF
MAX AUX Maximum 1-Cycle Auxiliary Values
In MAX In Current
FREQ MAX Frequency
MAX DMD Maximum Demands (Power Demands E, EH)
V1 DMD MAX V1/V12 Maximum volt demand 1
V2 DMD MAX V2/V23 Maximum volt demand 1
V3 DMD MAX V3/V31 Maximum volt demand 1
I1 DMD MAX I1 Maximum ampere demand
I2 DMD MAX I2 Maximum ampere demand
I3 DMD MAX I3 Maximum ampere demand
kW IMP SD MAX Maximum kW import sliding window demand
kW EXP SD MAX Maximum kvar import sliding window demand
kvar IMP SD MAX Maximum kW export sliding window demand
kvar EXP SD MAX Maximum kvar export sliding window demand
kVA SD MAX Maximum kVA sliding window demand
In DMD MAX In (neutral) current maximum demand
MAX SUMMARY DMD Billing Summary (Total) Maximum Demands E, EH
REG1 MD Summary register #1 maximum demand
REG2 MD Summary register #2 maximum demand
REG3 MD Summary register #3 maximum demand
REG4 MD Summary register #4 maximum demand
AO RAW Raw Analog Outputs (A/D Units)
AO1 Analog output AO1
AO2 Analog output AO2
AO3 Analog output AO3
AO4 Analog output AO4
TOU PRMS TOU Parameters E, EH
ACTIVE TARIFF Active TOU tariff
ACTIVE PROFILE Active TOU profile
TOU REG1 Billing TOU Energy Register #1 E, EH
REG1 TRF1 Tariff #1 register
REG1 TRF2 Tariff #2 register
… …
REG1 TRF8 Tariff #8 register
Designation Description
TOU REG2 Billing TOU Energy Register #2 E, EH
REG2 TRF1 Tariff #1 register
REG2 TRF2 Tariff #2 register
… …
REG2 TRF8 Tariff #8 register
TOU REG3 Billing TOU Energy Register #3 E, EH
REG3 TRF1 Tariff #1 register
REG3 TRF2 Tariff #2 register
… …
REG3 TRF8 Tariff #8 register
TOU REG4 Billing TOU Energy Register #4 E, EH
REG4 TRF1 Tariff #1 register
REG4 TRF2 Tariff #2 register
… …
REG4 TRF8 Tariff #8 register
TOU MAX DMD REG1 Billing TOU Maximum Demand Register #1 E, EH
REG1 TRF1 MD Tariff #1 maximum demand
REG1 TRF2 MD Tariff #2 maximum demand
… …
REG1 TRF8 MD Tariff #8 maximum demand
TOU MAX DMD REG2 Billing TOU Maximum Demand Register #2 E, EH
REG2 TRF1 MD Tariff #1 maximum demand
REG2 TRF2 MD Tariff #2 maximum demand
… …
REG2 TRF8 MD Tariff #8 maximum demand
TOU MAX DMD REG3 Billing TOU Maximum Demand Register #3 E, EH
REG3 TRF1 MD Tariff #1 maximum demand
REG3 TRF2 MD Tariff #2 maximum demand
… …
REG3 TRF8 MD Tariff #8 maximum demand
TOU MAX DMD REG4 Billing TOU Maximum Demand Register #4 E, EH
REG4 TRF1 MD Tariff #1 maximum demand
REG4 TRF2 MD Tariff #2 maximum demand
… …
REG4 TRF8 MD Tariff #8 maximum demand
1 In 4LN3, 3LN3 and 3BLN3 wiring modes, the voltages will be line-to
neutral; for any other wiring mode, they will be line-to-line voltages.
2 The value is calculated as a relation of the maximum deviation of
phase values from a 3-phase average value to a 3-phase average.
NOTE
Designations of some enginering demands and billing energy and demand
registers are shown using a short name notation available in PAS V1.4. By
default, PAS uses long names compatible with older versions of PAS. You
can select a desired notation from the Tools/Options/Preferences tab.
PAS does not allow to store data in files using different data names. If you
have a file uploaded with a previous version of PAS using long data
names, either continue using long data names, or store data in a new file.
See table below for a list of parameters with short and long names.
Table 26: Daily Billing/TOU Profile Data Log (Data Log #16)
Index
A
L
Accuracy, 149
Active energy, 149 Low Resolution Option, 46
Active power, 149
analog outputs, 15, 34, 81, 88, M
89, 151
Apparent energy, 149 Maximum Demand Load Current,
Apparent power, 149 80
Modbus, 112
B
N
billing, 101
Broken Delta, 26, 30, 81 notification, 78
C O
H
W
High Resolution Option, 46
Wiring Mode, 6, 27, 28, 29, 30,
80, 81
I Wye, 26, 27, 28, 29, 81
inputs, 18