varlogicNRC12 UserManual
varlogicNRC12 UserManual
varlogicNRC12 UserManual
User manual
DB121583
User's manual
Menu Structure
DB121603
Sequences
2 3653493EN_01.indd
User's manual
D121604
Menus
3653493EN_01.indd 3
User's manual
2. Installation ........................................................................................ 9
3. Display ............................................................................................ 12
6. Miscellaneous ................................................................................ 38
7. Options ........................................................................................... 47
8. Glossary .......................................................................................... 48
4 3653493EN_01.indd
User's manual
1. General
1.1 Safety
The following precautions must be taken into account when installing and operating
the controller:
@ The installation of the controller must be performed by a qualified electrician
@ Do not touch the connectors when the controller is energized, make sure that the
operating voltage is disconnected before touching any parts located on the rear
side of the controller
@ Do not open a live current circuit, this may cause dangerous overvoltages. Always
short circuit the current transformer (CT) before replacing or removing the controller
installed in a bank.
@ Do not open the controller casing, there are no user serviceable parts inside
@ External computing devices connected to the communication connector of Power
Factor Controller have to comply with the standard
IEC 60950-1
For better understanding of the terminology used, please refer to the Glossary
(chapter 8) at the end of this manual.
1.2 Environmental conditions
The controller is designed for the following environmental conditions:
@ Indoor use
@ Altitude up to 2000 m
@ Ambient temperatures within 0°…+60°C
@ Maximum relative humidity 80 percent for temperatures up to 31°C decreasing
linearly to 50 percent relative humidity at 40°C
@ Mains supply voltage fluctuations not to exceed –20/+15 percent of the nominal
voltage
@ Transient overvoltage for the Mains supply according to installation categories III
(IEC 61010-1)
@ Pollution degree 2 (IEC 61010-1)
3653493EN_01.indd 5
User's manual
1.3 Description
Front view:
DB121586
Legend
A Display
B Keys
C Opening of door
D Door
E Mounting bracket for panel mounting installation
6 3653493EN_01.indd
User's manual
Rear view:
DB121587
Legend
3653493EN_01.indd 7
User's manual
Side view:
DB121588
Legend
8 3653493EN_01.indd
User's manual
2. Installation
The controller is designed for either panel (cut-out 138 x 138 mm) or DIN-rail
installation. It is locked to a panel by a side fitting springs or to the rail by a
screwdriver-operated fixing spring.
should be L1.
Separated inputs exist for measurement voltage ("U1" and " U2") and supply voltage
measurement connection when Auto Setup is selected from the main menu.
and connected to inputs "T1" and "T2". The cable used needs to be certified to
Alternative target cos ϕ can be controlled by using external relay contact connected
between inputs "ϕ1" and "ϕ2". The cable used needs to be certified to national
at least 80°C.
Notes on installation:
A switch or circuit-breaker shall be included in the building installation. It shall be in
close proximity to the equipment and within easy reach of the operator. It shall be
marked as the disconnecting device for the equipment. An equipment switch or
circuit-breaker employed as a disconnecting device shall comply with relevant
requirements of IEC 60947-1 and IEC 60947-3.
10
Anschluß von stufen 2...11 wie mit 1 und 12
C
C
R1
R2
R3
R4
R5
R6
R7
R8
R9
R11
R10
R12
User's manual
Blindleistungsregler
NRC12
Hintere Ansicht
1
2
U1
U2
400V
230V
110 V
0V
S1
S2
T1
T2
AL 1
AL 2
F1
F2
Kein Anschluß
Alarm
kreis Externe
Temperaturprüfspitze
Regelanlag
AN/AUS Lüfter
koppler
Zünder max. 10 A
L1
L2
L3
LAST
400V 50/60 Hz
PE
3653493EN_01.indd
DB121723
C
C
3653493EN_01.indd
R1
R2
R3
R4
R5
R6
R7
R8
R9
R11
R10
R12
User's manual
Blindleistungsregler
NRC12
Hintere Ansicht
U1
U2
400V
230V
110V
0V
S1
S2
T1
T2
�1
AL1
AL2
F1
F2
�2
Kein Anschluß
Alarm Externe
kreis Temperaturprüfspitze
Regelanlag
AN/AUS Lüfter
koppler
Zünder max. 10 A
L1
L2
L3
LAST
400V 50/60 Hz
PE
11
User's manual
3. Display
The controller is equipped with a backlighted dot matrix display with a resolution of
128 x 64 pixels.
Essential indicators:
DB121607
12 3653493EN_01.indd
User's manual
4. Start-up Procedure
Before connecting power, check the wiring of all controller terminals. Check
carefully for correct operating voltage. Selection of wrong voltage input can
permanently damage the controller.
After the first power switch-on, the controller will automatically ask for the language
setting of the menu.
DB121608
3653493EN_01.indd 13
User's manual
5. Menu Operations
5.1 General
Navigation between different menu levels
Keylock type 1
DB121609
Keylock type 2
DB121609
Adjusting a value
DB121610
Multiparameter editor
3653493EN_01.indd 15
User's manual
16 3653493EN_01.indd
User's manual
3653493EN_01.indd 17
User's manual
5.4 Commissioning
5.4.1 Commissioning sequence
A pre-configured controller is put into service by this menu. The sequence contains
an automatic C/K value detection and automatic parameter verification to check
that the manually entered parameters comply with the network.
Disconnected bank disables Verify and Search functions and "Alarm with shutdown"-text
20 3653493EN_01.indd
User's manual
Auto setup forces application setting to 4-quadrant, step program to optimal, and
disables step size monitoring. C/K-value, step setup and wiring are detected
automatically. The automatic detection is unavailable if fixed steps are set.
Notes: The use of Auto Setup of Parameters menu is forbidden on HV network
applications.
In the event of error, see the error table on previous page.
DB121620
The manual setup sequence is intended for experienced users. There are nine
important parameters to input before the controller can be taken into service. This
sequence is completed by an automatic verification of the parameters entered in
this sequence.
This menu item is a forced sequence, meaning that all items must be accessed
before the validation of the setup takes place.
22 3653493EN_01.indd
User's manual
DB121621
24 3653493EN_01.indd
User's manual
Measurement Explanations:
harmonic components.
harmonic components.
Reactive power.
Apparent power.
limit.
3653493EN_01.indd 25
User's manual
Nominal value
Alarm limit Alarm limit
DB121635
LL connection of voltage
Measured value
Figure 13-2: Measured value and alarm limits.
Fan
Internal temperature
External temperature (Only present if external
Temperature values temperature sensor is connected)
26 3653493EN_01.indd
User's manual
5.8 Parameters
CAUTION: In case of installation in a HV bank (with VT), you must adjust the default
factory settings. The reconnection delay must be changed to a larger
value (e.g. 600 secs) to prevent destruction of capacitors.
The most common operating parameters can be accessed from this menu.
Unlike the configuration and setup sequences presented earlier in this text, this is a
menu allowing a free and unrestricted entry into all of its items and should be used
when occasional parameter access is needed. Restart the controller after major
changes in parameters.
To start the step size monitoring, set number of steps, step sequence and the size
of the 1st step (reactive power and voltage), initialize the measurement (asked when
exiting the editor). If wanted, set the alarm on from the alarm menu. If the step size
is set to 0 the step size monitoring is disabled.
Fixed steps cannot be monitored or verified. Setting 1st step fixed disables also
3653493EN_01.indd 27
User's manual
DB121624
28 3653493EN_01.indd
User's manual
Parameter Explanations:
possible.
Setup.
secondary current.
L3.
measurement.
measurement.
applications.
3653493EN_01.indd 29
User's manual
30 3653493EN_01.indd
User's manual
3653493EN_01.indd 31
User's manual
counter +
writes information.
Also, some alarm triggering levels can be adjusted. Disconnection of steps due to
alarms 2, 9, 10 can be enabled or disabled from alarm settings.
Alarm indications can be reset in base display alarm dialog ( F1 ), this clears all
passive alarms. If alarm condition is still active, the alarm cannot be reset.
32 3653493EN_01.indd
User's manual
3653493EN_01.indd 33
User's manual
34 3653493EN_01.indd
User's manual
In case of Alarm 12 user can set the defective capacitor Fixed OFF to clear the
alarm situation.
3653493EN_01.indd 35
User's manual
DB121625
Parameter Description
ACT = Alarm active and triggered.
OFF = No shutdown.
36 3653493EN_01.indd
User's manual
3653493EN_01.indd 37
User's manual
Maintenance explanations:
6. Miscellaneous
6.1 Stepping programs
The controller's algorithm will try to reach the target cos φ inside a tolerance area
dependant upon the C/K value, figure 18. It reaches the value by switching on or off
All capacitor steps are of equal size (i.e:1.1.1.1). The operation sequence obeys to
a last-in-firstout (LIFO) principle. The first step connected will be the last one to be
38 3653493EN_01.indd
User's manual
Normal program can be used on bank whose step ratio is 1.2.4.4.. The linear
sequence starts with the 3rd step. The two first steps are used as fine-tuning. The
controller always start by switching the first step then the second. Other steps are
All capacitor steps are of equal size (i.e:1.1.1.1). The operation sequence obeys the
first-in-firstout (FIFO) principle. With this stepping program the amount of on- and
off-connections at each step will eventually be the same. The first step connected
will be the first one to be disconnected and vice versa. Then a circular sequence is
followed. In order to operate correctly, the number of steps programmed into the
controller must strictly comply with the number of physical steps See Table 3.
Circular B program can be used on a bank whose step ratio is 1.2.2.2. The first step
is used as tuning after the activating limit is exceeded. The circular sequence starts
e) Optimal Program:
The target cos φ power is reached using the fewest number of steps in minimal
time. Like the circular program, this algorithm equalizes the usage of largest steps.
This program uses optimally selected step sizes when approaching the target
power and at the same time the response delays are shortened, particularly if there
is a large requirement for compensation power or if the network suddenly becomes
capacitive. As circular program, this stepping program keeps the usage of steps
even.
3653493EN_01.indd 39
User's manual
+ X + X
+ X X + X X
+ X X X + X X X
+ X X X X + X X X X
+ X X X X X - X X X
+ X X X X X X - X X
- X X X X X + X X X
- X X X X + X X X X
- X X X + X X X X X
- X X - X X X X
+ X X X - X X X
+ X X X X - X X
+ X X X X X - X
- X X X X Table 2:
- X X 1:2:4:4
- X
Table 1:
+ X + X
+ X X + X X
+ X X X + X X X
+ X X X X - X X
- X X X + X X X
- X X + X X X X
+ X X X - X X X
+ X X X X - X X
- X X X - X
- X X + X X
+ X X X + X X X
+ X X X X + X X X X
- X X X + X X X X X
Table 3:
- X X X X
Circular A program - Operation sequence 1:1:1
- X X X
- X X
Table 4:
Circular B program - Operation sequence
1:2:2
40 3653493EN_01.indd
User's manual
Normal program will reach the cos ϕ target value by successive connection/
disconnection of capacitors corresponding to the smallest step value.
Optimal program will reach the target cos ϕ value by successive connection/
disconnection of capacitors corresponding to the highest relevant and available
step value.
3653493EN_01.indd 41
User's manual
42 3653493EN_01.indd
User's manual
Q1st
C/K= ————————
I1 / 5A x ULL x 3
Alternatively, the C/K value can be taken from the table below (valid for 400 V
networks)
3653493EN_01.indd 43
User's manual
DB121628
44 3653493EN_01.indd
User's manual
The application menu has two voltage ranges for HV applications: 0.5 - 50 kV and
10 - 400 kV. The lower voltage range has finer VT ratio resolution and range than
the higher voltage range.
Safety (or reconnection) delay must be adapted to the value of the discharge
resistors of the capacitors, the most usual value is 600 seconds (10 minutes). The
controller’s default reconnection delay is adapted for LV use. Using too short a
reconnection delay may damage the capacitors.
Important:
@ the whole commissioning process must be performed using the Parameter menu.
@ the commissioner should not use Bank Pre-Configuration, Manual Setup and
Commissioning menus.
@ the use of Auto Setup menu is strictly forbidden to prevent capacitor destruction.
@ do not use "Verify" or "Auto Seek" on HV network applications!
3653493EN_01.indd 45
User's manual
DB121629
46 3653493EN_01.indd
User's manual
7. Options
7.1 External Temperature Sensor
The controller has terminals T1/T2 for external temperature sensor. With the
external temperature probe the temperature in a critical point in a capacitor bank
can be monitored with the controller. The external temperature measurement
overrides the internal temperature in fan and alarm monitoring. The External
Temperature Sensor can be purchased as an option and installed into the capacitor
bank.
Do not touch the connectors when the controller is energized, make sure that the
operating voltage is disconnected before touching any parts located on the rear
side of the controller.
Always switch off the power from the controller before installation.
Make sure that the communication connector is always covered, either
with CCA-01 adapter or the original cover before switching on the
power. Touching an uncovered connector with the power applied may
lead to an electrical shock.
3653493EN_01.indd 47
User's manual
8. Glossary
Display
information Description Min value Default
value Max value
Current too high. >1.10 ×
Inom
Current too low. All steps are <0.025 ×
disconnected in 2 quadrant Inom
application.
No Input Voltage.
Size and voltage of 1st step 0 kvar 0 kvar 400 kvar
(Step Setup) (the line-line voltage of 200V 400V 800V
capacitor) for step size
monitoring. 0 = step size
monitoring disabled.
See Alarms Menu (chapter
5.9) / Alarm 12
The Modbus slave address 1 1 247
(Modbus Setup) of the controller.
List of detected active (A)
and passive alarms. Reset
clears passive alarms.
Log of 5 latest alarms.
Alarm Menu.
48 3653493EN_01.indd
User's manual
3653493EN_01.indd 49
User's manual
50 3653493EN_01.indd
User's manual
Internal temperature.
menus.
experts)
Measurements Menu.
3653493EN_01.indd 51
User's manual
52 3653493EN_01.indd
User's manual
3653493EN_01.indd 53
User's manual
Normal
Circular 1.1.1
Circular 1.2.2
Optimal
54 3653493EN_01.indd
User's manual
10 – 400 kV
Connections of voltage L2-L3
(Wiring) inputs.
Example: Voltage phase L2
L3
(Voltage connected between
phase 2 and 3)
Detected in Auto Setup and
Auto seek, checked with
verify function. See also
Installation (chapter 2).
3653493EN_01.indd 55
User's manual
9. Technical specifications
Number of steps 12
Dimensions 155 x 158 x 80 mm
Frequency 50 Hz nominal (range 48...52 Hz)
60 Hz nominal (range 58...62 Hz)
Measuring current 0…1 A or 0...5 A
Measuring voltage 80…690 V (nominal, max. 115%)
Displayed measuring power 100000 kVA
Nominal power consumption 13 VA
Supply voltages 110 V nominal, (range 88...130 V)
230 V nominal, (range 185...265 V)
400 V nominal, (range 320...460 V)
Relay inputs/outputs 250 V, 2 A
Display Dot matrix display, resolution 64x128 pixels, backlighted.
Protection class IP41 front panel, IP20 rear part.
Target cos ϕ -range 0.85 ind …1.00 … 0.90 cap
Response limits 0.01 … 1.99, symmetrical or asymmetrical
Reconnection delay 10…900 s
Response delay 20 % of reconnection delay, min. 10 s
Displayed measurements cos ϕ, Iact, Ireact, Iapp, IRMS/I1, P, Q, S, THD (U) and voltage
harmonics, THD(I) and current harmonics, internal and
external temperature.
Installation method Panel installation, DIN-rail installation.
Casing Impact resistant PC/ABS, UL94V-0
Operating temperature range 0…60°C
Alarm log List of 5 last alarms.
Step counters Yes
Fan control with dedicated relay Yes. 250 V AC, 8A
Alarm relay Yes. 250 V AC, 8A
Accuracy (of FS) I: 2%
IQ: 2%
U/I-samples: 2%
Phase: 1°
Schneider Electric Industries SAS As standards, specifications and designs change from time to
Rectiphase time, please ask for confirmation of the information given in this
399 rue de la Gare publication.
74370 Pringy
France Printed on ecological paper.
Tel.: 33 (0)4 50 66 95 00 Layout: Schneider Electric - Sedoc
Fax: 33 (0)4 50 27 24 19 Photos: Schneider Electric
http://www.schneider-electric.com Printing:
http://www.merlin-gerin.com
04-2009
N° 3653493EN_01