PV Grid-Connected Inverter
SG30CX / SG33CX / SG40CX / SG50CX / SG30CX-NI /
SG50CX-NI
SG30CX /
SG33CX / SG40CX / SG50CX /
SG30CX-NI / SG50CX-NIPV Grid-
Connected InverterUser
ManualSG30_33_40_50CX/SG30_
50CX-NI-UEN-Ver21-202211
SG30_33_40_50CX/SG30_50CX-NI-UEN-Ver21-202211
All Rights Reserved
I
About This Manual
The manual mainly contains the product information, as well as guidelines for installation,
operation, and maintenance. The manual does not include complete information about the
photovoltaic (PV) system. Readers can get additional information at www.sungrowpower.
com or on the webpage of the respective component manufacturer.
Validity
This manual is valid for the following model of low-power grid-connected PV string inverters:
• SG30CX
• SG33CX
• SG40CX
• SG50CX
• SG30CX-NI
• SG50CX-NI
• Know electronic, electrical wiring and mechanical expertise, and be familiar with electri-
cal and mechanical schematics.
• Have received professional training related to the installation and commissioning of elec-
trical equipment.
• Be able to quickly respond to hazards or emergencies that occur during installation and
commissioning.
• Be familiar with local standards and relevant safety regulations of electrical systems.
• Read this manual thoroughly and understand the safety instructions related to
operations.
How to Use This Manual
Please read this manual carefully before using the product and keep it properly at a place
for easy access.
All contents, pictures, marks, and symbols in this manual are owned by SUNGROW. No part
of this document may be reprinted by the non-internal staff of SUNGROW without written
authorization.
II
Contents of this manual may be periodically updated or revised, and the actual product pur-
chased shall prevail. Users can obtain the latest manual from support.sungrowpower.com
or sales channels.
Symbols
This manual contains important safety instructions, which are highlighted with the following
symbols, to ensure personal and property safety during usage, or to help optimize the prod-
uct performance in an efficient way.
Please carefully understand the meaning of these warning symbols to better use the manual.
Indicates high-risk potential hazards that, if not avoided, may lead to death or seri-
ous injury.
Indicates moderate-risk potential hazards that, if not avoided, may lead to death or
serious injury.
Indicates low-risk potential hazards that, if not avoided, may lead to minor or mod-
erate injury.
Indicates potential risks that, if not avoided, may lead to device malfunctions or fi-
nancial losses.
III
Contents
All Rights Reserved .....................................................................................................I
About This Manual......................................................................................................II
1 Safety Instructions ............................................................................................1
1.1 Unpacking and Inspection ...............................................................................1
1.2 Installation Safety ...........................................................................................2
1.3 Electrical Connection Safety............................................................................2
1.4 Operation Safety ............................................................................................4
1.5 Maintenance Safety ........................................................................................4
1.6 Disposal Safety ..............................................................................................5
2 Product Description ..........................................................................................6
2.1 System Introduction ........................................................................................6
2.2 Product Introduction........................................................................................7
2.3 Symbols on Product........................................................................................9
2.4 LED Indicator .................................................................................................9
2.5 DC Switch....................................................................................................10
2.6 Circuit Diagram ............................................................................................ 11
2.7 Function Description .....................................................................................12
3 Unpacking and Storage .................................................................................14
3.1 Unpacking and Inspection .............................................................................14
3.2 Inverter Storage ...........................................................................................14
4 Mechanical Mounting .....................................................................................16
4.1 Safety During Mounting.................................................................................16
4.2 Location Requirements .................................................................................16
4.2.1 Environment Requirements..................................................................17
4.2.2 Carrier Requirements ..........................................................................17
4.2.3 Angle Requirements............................................................................18
4.2.4 Clearance Requirements .....................................................................19
4.3 Installation Tools...........................................................................................20
4.4 Moving the Inverter .......................................................................................22
4.4.1 Manual Transport ................................................................................22
4.4.2 Hoisting Transport...............................................................................22
V
4.5 Installing Mounting-bracket............................................................................24
4.5.1 PV Bracket-Mounted Installation ..........................................................24
4.5.2 Wall-Mounted Installation.....................................................................25
4.6 Installing the Inverter.....................................................................................26
5 Electrical Connection .....................................................................................28
5.1 Safety Instructions ........................................................................................28
5.2 Terminal Description .....................................................................................29
5.3 Electrical Connection Overview .....................................................................30
5.4 Crimp OT/DT terminal ...................................................................................32
5.5 External Protective Grounding Connection .....................................................33
5.5.1 External Protective Grounding Requirements ........................................33
5.5.2 Connection Procedure.........................................................................33
5.6 AC Cable Connection ...................................................................................34
5.6.1 AC Side Requirements ........................................................................34
5.6.2 Requirements for OT/DT Terminal ........................................................36
5.6.3 Connection Procedure.........................................................................36
5.7 DC Cable Connection ...................................................................................39
5.7.1 PV Input Configuration ........................................................................40
5.7.2 Assembling PV Connectors .................................................................41
5.7.3 Installing PV Connector .......................................................................42
5.8 Communication Junction Box ........................................................................43
5.9 Communication Wiring Board ........................................................................44
5.10 RS485 Connection......................................................................................44
5.10.1 Interface Description .........................................................................44
5.10.2 RS485 Communication System ..........................................................45
5.10.3 Connection Procedure(Terminal Block) ...............................................47
5.10.4 Connection Procedure (RJ45 Ethernet Port)........................................48
5.11 Dry Contact Connection ..............................................................................50
5.11.1 Dry Contact Function .........................................................................50
5.11.2 Wiring Procedure...............................................................................52
5.12 DRM Connection(For Countries “AU” and “NZ”)........................................52
5.12.1 DRM Function...................................................................................52
5.12.2 Connection Procedure .......................................................................53
5.13 Communication Module Connection (optional) ..............................................55
6 Commissioning ...............................................................................................56
6.1 Inspection Before Commissioning..................................................................56
VI
6.2 Commissioning Procedure ............................................................................56
7 iSolarCloud App ..............................................................................................57
7.1 Brief Introduction ..........................................................................................57
7.2 Installing App ...............................................................................................57
7.3 Function Overview........................................................................................58
7.4 Login ...........................................................................................................58
7.4.1 Requirements .....................................................................................58
7.4.2 Login Procedure .................................................................................58
7.5 Home ..........................................................................................................62
7.6 Run Information............................................................................................64
7.7 Records .......................................................................................................66
7.8 More............................................................................................................68
7.8.1 System Parameters.............................................................................68
7.8.2 Operation Parameters .........................................................................69
7.8.3 Power Regulation Parameters..............................................................71
7.8.4 Communication Parameters.................................................................76
7.8.5 Firmware Update ................................................................................76
7.8.6 Password Changing ............................................................................77
8 System Decommissioning ............................................................................79
8.1 Disconnecting Inverter ..................................................................................79
8.2 Dismantling the Inverter ................................................................................79
8.3 Disposal of Inverter.......................................................................................80
9 Troubleshooting and Maintenance ..............................................................81
9.1 Troubleshooting ...........................................................................................81
9.2 Maintenance ................................................................................................89
9.2.1 Maintenance Notices...........................................................................89
9.2.2 Routine Maintenance ..........................................................................90
9.2.3 Cleaning Air Inlet and Outlet.................................................................91
9.2.4 Fan Maintenance ................................................................................91
10 Appendix .......................................................................................................93
10.1 Technical Data............................................................................................93
10.2 Wring Distance of DI Dry Contact.................................................................99
10.3 Quality Assurance .................................................................................... 101
10.4 Contact Information .................................................................................. 101
VII
1 Safety Instructions
When installing, commissioning, operating, and maintaining the product, strictly observe the
labels on the product and the safety requirements in the manual. Incorrect operation or work
may cause:
• The safety instructions in this manual are only supplements and cannot cover
all the precautions that should be followed. Perform operations considering ac-
tual onsite conditions.
• SUNGROW shall not be held liable for any damage caused by violation of gen-
eral safety operation requirements, general safety standards, or any safety in-
struction in this manual.
• When installing, operating, and maintaining the product, comply with local laws
and regulations. The safety precautions in this manual are only supplements
to local laws and regulations.
After receiving the product, check whether the appearance and structural parts of
the device are damaged, and check whether the packing list is consistent with the
actual ordered product. If there are problems with the above inspection items, do
not install the device and contact your distributor first. If the problem persists, con-
tact SUNGROW in time.
1
1 Safety Instructions User Manual
• When moving the product, be aware of the product weight and keep the balance
to prevent it from tilting or falling.
Before operating the product, must check and ensure that tools to be used have
been maintained regularly.
Before electrical connections, please make sure that the inverter is not damaged,
otherwise it may cause danger!
Before electrical connections, please make sure that the inverter switch and all
switches connected to the inverter are set to "OFF", otherwise electric shock may
occur!
The PV string will generate lethal high voltage when exposed to sunlight.
• Must ensure that cables are voltage-free with a measuring instrument before
touching DC cables.
• The inverter must not be connected to a PV string that requires positive or neg-
ative grounding.
2
User Manual 1 Safety Instructions
• Note and observe the warning labels on the product, and perform operations
strictly following the safety instructions.
• Respect all safety instructions listed in this manual and other pertinent
documents.
Damage to the product caused by incorrect wiring is not covered by the warranty.
• All cables used in the PV generation system must be firmly attached, properly
insulated, and adequately dimensioned.
Check the positive and negative polarity of the PV strings, and connect the PV con-
nectors to corresponding terminals only after ensuring polarity correctness.
During the installation and operation of the inverter, please ensure that the positive
or negative poles of PV strings do not short-circuit to the ground. Otherwise, an
AC or DC short-circuit may occur, resulting in equipment damage. The damage
caused by this is not covered by the warranty.
Comply with the safety instructions related to PV strings and the regulations re-
lated to the local grid.
3
1 Safety Instructions User Manual
Please comply with the following requirements when the product is running:
• Do not touch any wiring terminal of the inverter. Otherwise, electric shock may
occur.
• Do not disassemble any parts of the inverter. Otherwise, electric shock may
occur.
• It is strictly forbidden to touch any hot parts of the inverter (such as the heat
sink). Otherwise, it may cause burns.
• Do not operate the DC switch if the inverter is equipped with the DC switch. Oth-
erwise, device damage or personal injury may occur.
• Before any service work, first disconnect the grid-side AC circuit breaker and
check the inverter status. If the inverter indicator is off, please wait until night to
disconnect the DC switch. If the inverter indicator is on, directly disconnect the
DC switch.
• After the inverter is powered off for 5 minutes, measure the voltage and current
with professional instrument. Only when there is no voltage nor current can op-
erators who wear protective equipment operate and maintain the inverter.
• Even if the inverter is shut down, it may still be hot and cause burns. Wear pro-
tective gloves before operating the inverter after it cools down.
Touching the power grid or the contact points and terminals on the inverter con-
nected to the power grid may lead to electric shock!
• The power grid side may generate voltage. Always use a standard voltmeter to
ensure that there is no voltage before touching.
4
User Manual 1 Safety Instructions
To avoid the risk of electric shock, do not perform any other maintenance opera-
tions beyond those described in this manual. If necessary, contact your distributor
first. If the problem persists, contact SUNGROW. Otherwise, the losses caused is
not covered by the warranty.
Please scrap the product in accordance with relevant local regulations and stand-
ards to avoid property losses or casualties.
5
2 Product Description
The inverter must not be connected to a PV string that requires positive or negative
grounding.
Do not connect any local load between the inverter and the AC circuit breaker.
6
User Manual 2 Product Description
Appearance
The following figure shows the appearance of the inverter. The image shown here is for
reference only. The actual product received may differ.
7
2 Product Description User Manual
Dimensions
The following figure shows the dimensions of the inverter.
*The image shown here is for reference only. The actual product you receive may differ.
8
User Manual 2 Product Description
Symbol Explanation
CE mark of conformity.
EU/EEA Importer.
Disconnect the inverter from all the external power sources before
maintenance!
Burn danger due to the hot surface that may exceed 60°C.
Do not touch live parts for 5 minutes after disconnection from the power
sources.
* The table shown here is for reference only. The actual product received may differ.
The LED indicator on the front of the inverter indicates the working state of the inverter.
9
2 Product Description User Manual
Gray
Voltage may still be present in AC side circuits after the indicator is off. Pay atten-
tion to the electricity safety when operating.
2.5 DC Switch
10
User Manual 2 Product Description
* The image shown here is for reference only. The actual product received may differ.
• The DC SPD provides a discharge circuit for the DC side overvoltage to prevent it from
damaging the internal circuits of the inverter.
• EMI filters can filter out the electromagnetic interference inside the inverter to ensure that
the inverter meets the requirements of electromagnetic compatibility standards.
• The MPPT is used to ensure a maximum power from PV arrays at different PV input
conditions.
• The Inverter Circuit converts the DC power into grid-compliant AC power and feeds it into
the grid.
• The AC filter filters the output AC component of high frequency to ensure that the output
current meets the grid requirements.
• The AC relay isolates the AC output of the inverter from the grid, making the inverter safe
from the grid in case of inverter failure or grid failure.
• The AC SPD provides a discharge circuit for the AC side overvoltage to prevent it from
damaging the internal circuits of the inverter.
11
2 Product Description User Manual
The inverter can provide export control but will require the use of a external smart meter.
The export control functionality has not been tested to AS/NZS 4777.2:2020.
Protection Function
The protective functions are integrated in the inverter, including anti-island protection, LVRT/
ZVRT, DC reversed polarity protection, AC short circuit protection, leakage current protec-
tion, DC overvoltage/overcurrent protection, etc.
PID recovery
The PID effect (Potential Induced Degradation) of PV modules will cause serious damage to
generated output and yield, which can be avoided or recovered by PID recovery function.
• For positive voltage scheme, after the PID is enabled, the voltage to ground of all PV
strings is greater than 0, and therefore the PV string-to-ground voltage is a positive value.
12
User Manual 2 Product Description
• For negative voltage scheme, after the PID is enabled, the voltage to ground of all PV
strings is lower than 0, and therefore the PV string-to-ground voltage is a negative value.
• Before enabling the PID recovery function, make sure the voltage polarity of the
PV modules to ground meets requirement. If there are any questions, contact
the PV module manufacturer or read the corresponding user manual.
• PID recovery function and Q at night cannot be enabled at the same time.
• If the voltage scheme for the PID protection/recovery function does not meet
the requirement of corresponding PV modules, the PID will not work as ex-
pected or even damage the PV modules.
• After the PID recovery function is enabled, the voltage of the PV string to
ground is 500Vdc by default, and the default value can be modified through the
App.
AFCI Function(Optional)
• AFCI activation
This function can be enabled to detect whether arc occurs in the DC circuit of the inverter.
• AFCI self-test
This function is intended to detect whether the AFCI function of the inverter is normal.
13
3 Unpacking and Storage
The product is thoroughly tested and strictly inspected before delivery. Nonetheless, dam-
age may still occur during shipping. For this reason, please conduct a thorough inspection
after receiving the product.
• Check the scope of delivery for completeness according to the packing list.
After receiving the product, check whether the appearance and structural parts of
the device are damaged, and check whether the packing list is consistent with the
actual ordered product. If there are problems with the above inspection items, do
not install the device and contact your distributor first. If the problem persists, con-
tact SUNGROW in time.
If any tool is used for unpacking, be careful not to damage the product.
• Store the inverter in the original packing case with the desiccant inside.
• The storage temperature must be always between -40℃ and +70℃, and the storage rel-
ative humidity must be always between 0 and 95 %, non-condensing.
• In case of stacking storage, the number of stacking layers should never exceed the limit
marked on the outer side of the packing case.
• If the inverter needs to be transported again, pack it strictly before loading and transport-
ing it.
14
User Manual 3 Unpacking and Storage
• Do not store the inverter in places susceptible to direct sunlight, rain, and strong electric
field.
• Do not place the inverter in places with items that may affect or damage the inverter.
• Store the inverter in a clean and dry place to prevent dust and water vapor from eroding.
• Do not store the inverter in places with corrosive substances or susceptible to rodents
and insects.
• Carry out periodic inspections. Inspection shall be conducted at least once every six
months. If any insect or rodent bites are found, replace the packaging materials in time.
• If the inverter has been stored for more than a year, inspection and testing by professio-
nals are required before it can be put into operation.
Please store the inverter according to the storage requirements. Product damage
caused by failure to meet the storage requirements is not covered by the warranty.
15
4 Mechanical Mounting
• Do not install the inverter in an environment with flammable and explosive ob-
jects or smoke.
• When moving the inverter, be aware of its weight and keep the balance to pre-
vent it from tilting or falling.
• The bottom terminals and interfaces of the inverter cannot directly contact the
ground or other supports. The inverter cannot be directly placed on the ground.
To a large extent, a proper installation location ensures safe operation, service life, and per-
formance of the inverter.
• The inverter with protection rating IP66 can be installed both indoors and outdoors.
• The inverter should be installed at a height that allows easy viewing of the LED indicator
panel, as well as easy electrical connection, operation and maintenance.
16
User Manual 4 Mechanical Mounting
• The ambient temperature and relative humidity must meet the following requirements.
• Do not install the inverter outdoors in areas with high salinity, which mainly refer to the
areas within 500 m away from the coast. The deposition of salt fog varies largely with
nearby seawater characteristics, sea wind, precipitation, relative humidity, terrain, and
forest coverage.
• Inverters free from direct sunlight, direct rain and snow have longer service life. Consider
sheltered places as the installation location.
• The inverter generates noise during operation and is not recommended to be installed in
living areas.
The mounting structure where the inverter is installed must comply with local/national stand-
ards and guidelines. Ensure that the installation surface is solid enough to bear four times
the weight of the inverter and is suitable for the dimensions of the inverter (e.g. cement walls,
plasterboard walls, etc.).
17
4 Mechanical Mounting User Manual
Install the inverter vertically or at the maximum allowable rear tilt angle. Do not install the in-
verter horizontally, forward, excessively backward, sideways, or upside down.
Inverters in floating plants cannot be installed at a back tilt.
In case the installation site is a level surface, mount the inverter to the bracket to
meet the mounting angle requirements, as shown in the figure below.
Take the following items into account when designing the bracket scheme:
• Consider onsite climate conditions and take anti-snow and anti-rain measures
if necessary.
• Ensure that the waterproof connectors are at least 300mm higher than the
ground surface.
• Bind the cables at the positions 300~350mm away from the DC connector, AC
waterproof terminal, and communication waterproof terminal.
• The various waterproof terminals should be tightened with the torque specified
in this manual to ensure that they are securely sealed.
18
User Manual 4 Mechanical Mounting
Reserve enough clearance around the inverter to ensure sufficient space for heat
dissipation.
* In case this distance is less than the distance in the diagram, move the inverter from the
mounting-bracket or wall before maintaining fans.
The distance between the bottom of the inverter and the ground surface is deter-
mined according to the bending radius of the AC cable used and the installation
environment. In addition, the following conditions must be met:
• The distance between the bottom of the inverter and the ground surface is not
less 650 mm.
• The AC cable is vertically led into the cabinet, and the straight length is higher
than 200mm.
19
4 Mechanical Mounting User Manual
In case of multiple inverters, reserve specific clearance between the inverters. For other in-
stallation scenarios, please refer to the relevant technical documents on http://support.sun-
growpower.com/.
In case of back-to-back installation, reserve specific clearance between the two inverters.
Install the inverter at an appropriate height for ease of viewing LED indicator and operating
switch(es).
Installation tools include but are not limited to the following recommended ones. If necessary,
use other auxiliary tools on site.
20
User Manual 4 Mechanical Mounting
Vacuum cleaner
21
4 Mechanical Mounting User Manual
Before installation, remove the inverter from the packing case and move it to the installation
site. Follow the instructions below as you move the inverter:
• Lift the inverter using the handles positioned on both sides of the inverter.
• Move the inverter by one or two people or by using a proper transport tool.
• Attention must be paid to the center of gravity of the inverter to avoid tilting dur-
ing handling.
• Placing the inverter directly on a hard ground may cause damage to its metal
enclosure. Protective materials such as sponge pad or foam cushion should be
placed underneath the inverter.
• Move the inverter by holding the handles on it. Do not move the inverter by
holding the terminals.
Lift and move the inverter to the destination by using the side handles and bottom handles.
22
User Manual 4 Mechanical Mounting
step 2 Lead the sling through the two lifting rings and fasten the tie-down strap.
step 3 Hoist the inverter, and stop to check for safety when the inverter is 100mm above the
ground. Continue hoisting the device to the destination after ensuring the safety.
step 4 Remove the lifting rings and reassemble the sealing screws released in Step 1.
Keep the inverter balanced throughout the hoisting process and avoid collisions
with walls or other objects.
Stop hoisting in the event of severe weather, such as heavy rain, thick fog, or
strong wind.
23
4 Mechanical Mounting User Manual
The lifting rings and the sling are not within the delivery scope.
- - End
step 2 Level the assembled mounting-bracket by using the level, and mark the positions for drilling
holes on the PV bracket. Drill the holes by using a hammer drill.
24
User Manual 4 Mechanical Mounting
- - End
step 2 Level the assembled mounting-bracket by using the level, and mark the positions for drilling
holes.
step 3 Insert the expansion bolts into the holes and secure them with a rubber hammer. Fasten the
nut with a wrench to expand the bolt. Remove the nut, spring washer, and flat washer, and
store them properly.
25
4 Mechanical Mounting User Manual
step 4 Install the mounting-bracket to the wall with the expansion bolts with the expansion bolts.
- - End
step 2 If the installation position is high, hoist the inverter to the position (refer to ""4.4.2 Hoisting
Transport""). Otherwise, skip this step.
step 3 Hang the inverter to the mounting-bracket and ensure that the mounting ears perfectly en-
gage with the mounting-bracket.
26
User Manual 4 Mechanical Mounting
- - End
27
5 Electrical Connection
The PV string will generate lethal high voltage when exposed to sunlight.
• Must ensure that cables are voltage-free with a measuring instrument before
touching DC cables.
• Before electrical connections, please make sure that the inverter switch and all
switches connected to the inverter are set to "OFF", otherwise electric shock
may occur!
• Ensure that the inverter is undamaged and all cables are voltage free before
performing electrical work.
• Do not close the AC circuit breaker until the electrical connection is completed.
Damage to the product caused by incorrect wiring is not covered by the warranty.
• All cables used in the PV generation system must be firmly attached, properly
insulated, and adequately dimensioned.
All electrical connections must comply with local and national/regional electrical
standards.
• Cables used by the user shall comply with the requirements of local laws and
regulations.
• Only with the permission of the national/regional grid department, the inverter
can be connected to the grid.
28
User Manual 5 Electrical Connection
• All vacant terminals must be covered with waterproof covers to prevent affect-
ing the protection performance.
• When the wiring is completed, seal the gap at the cable inlet and outlet holes
with fireproof/waterproof materials such as fireproof mud to prevent foreign
matter or moisture from entering and affecting the long-term normal operation
of the inverter.
• Comply with the safety instructions related to PV strings and the regulations re-
lated to the utility grid.
The cable colors in figures in this manual are for reference only. Please select ca-
bles according to local cable standards.
* The image shown here is for reference only. The actual product received may differ.
29
5 Electrical Connection User Manual
Item Designation
A PV string
B Inverter
C Grid
D Monitoring device
E AC circuit breaker
30
User Manual 5 Electrical Connection
Specification
No. Cable Type Cable Diame- Cross-sectional Area
ter(mm) (mm2)
PV cable comply-
1 DC cable ing with 1,500V 6~9 4~6
standard
Additional Outdoor single-
The same as that of the PE wire in the AC
2 grounding core copper wire
cable
cable cable
L1,L2,L3,N wire (SG30CX,
SG30CX-NI, SG33CX): 16
~ 70
Outdoor multicore L1,L2,L3,N wire (SG40CX):
3 AC cable copper or alumi- 20 ~ 50 25 ~ 70
nium cable L1,L2,L3,N wire (SG50CX,
SG50CX-NI): 35 ~ 70
PE wire: refer to "table 5-2
PE Wire Requirements"
Shielded twisted
Communi- pair (terminal 0.1 ~ 1.5
4 cation block) 4.5 ~ 18
cable CAT-5 Ethernet ca-
/
ble (RJ45)
31
5 Electrical Connection User Manual
Ensure that the selected terminal can directly contact with the copper bar. If there
are any problems, contact the terminal manufacturer.
Ensure that the copper bar is not in direct contact with the aluminum wire. Other-
wise, electrochemical corrosion may occur, impairing the reliability of electrical
connection.
32
User Manual 5 Electrical Connection
Electric shock!
• Make sure that the grounding cable is connected reliably. Otherwise, it may
cause electric shock.
• Since the inverter is not equipped with a transformer, neither the negative elec-
trode nor the positive electrode of the PV string can be grounded. Otherwise,
the inverter will not operate normally.
• Connect the grounding terminal to the external protective grounding point be-
fore AC cable connection, PV string connection, and communication cable
connection.
The external protective grounding terminal must meet at least one of the following
requirements.
• The cross-sectional area of the grounding cable is not less than 10 mm2 for cop-
per wire or 16 mm2 for aluminum wire. It is recommended that both the external
protective grounding terminal and the AC side grounding terminal be reliably
grounded.
• If the cross-sectional area of the grounding cable is less than 10 mm2 for copper
wire or 16 mm2 for aluminum wire, ensure that both the external protective
grounding terminal and the AC side grounding terminal are reliably grounded.
The grounding connection can be made by other means if they are in accordance
with the local standards and regulations, and SUNGROW shall not be held liable
for the possible consequences.
All non-current carrying metal parts and device enclosures in the PV power system should
be grounded, for example, brackets of PV modules and inverter enclosure.
When there is only one inverter in the PV system, connect the external protective grounding
cable to a nearby grounding point.
When there are multiple inverters in the PV system, connect the external protective ground-
ing terminals of all inverters and the grounding points of the PV module brackets to ensure
equipotential connections to ground cables (according to the onsite conditions).
33
5 Electrical Connection User Manual
step 2 Remove the screw on the grounding terminal and fasten the cable with a screwdriver.
The grounding screws have been anchored to the side of the inverter before deliv-
ery, and do not need to be prepared.
There are two grounding terminals. Use one of them to ground the inverter.
- - End
Only with the permission of the local grid department, the inverter can be con-
nected to the grid.
Before connecting the inverter to the grid, ensure the grid voltage and frequency comply with
requirements, for which, refer to "Technical Data". Otherwise, contact the electric power
company for help.
AC Circuit Breaker
An independent circuit breaker or fuse should be installed on the output side of the inverter
to ensure safe disconnection from the grid.
34
User Manual 5 Electrical Connection
AC circuit breakers should be installed on the output side of the inverter and the
grid side to ensure safe disconnection from the grid.
• Do not connect any local load between the inverter and the AC circuit breaker.
• A distribution transformer can be used if it is designed for the typical cyclical loads of a
PV system (there is load in the day and no load at night).
• A liquid-immersed type transformer or a dry type transformer can be used, and the shield
winding is not a requisite.
• The line-to-line voltage on the LV side of the transformer should endure the output volt-
age of inverter. When the transformer is connected to the IT grid, to-ground withstanding
voltage of the LV winding of the transformer, the LV side AC cables, and the LV side sec-
ondary equipment (including the relay protection device, detection & measuring device,
and other related auxiliary devices) should not be lower than 1,100V.
• The line-to-line voltage on the HV side of the transformer should comply with the local
power grid voltage.
• A transformer with a tap changer on the HV side is recommended in order to keep the
voltage consistent with the grid voltage.
35
5 Electrical Connection User Manual
• At an ambient temperature of 45℃, the transformer can run in 1.1 times of load for long
time.
• The DC component that the transformer can withstand is 1% of the fundamental current
at rated power.
• For thermal rating, the load curve of the transformer and environment conditions should
be taken into account.
• The apparent power of the inverter should never exceed the power of the transformer.
The maximum AC current of all inverters connected in parallel must be taken into ac-
count. It is recommended that the total number of inverters that are connected to the grid
not exceed 30.
• Take ambient temperature, relative humidity, altitude, air quality, and other environmental
conditions into account when selecting and installing the transformer.
OT/DT terminals (not included in the delivery scope) are required for fixing AC cables to the
terminal block. Purchase the OT/DT terminals according to the following requirements.
• Specification: M8;
step 1 Disconnect the AC-side circuit breaker and prevent it from inadvertent reconnection.
step 2 Take out the AC junction box and loosen the swivel nut. Remove the seals and select an ap-
propriate one according to cable outer diameter. Lead the cable through the swivel nut, seal,
and junction box successively.
36
User Manual 5 Electrical Connection
step 3 Strip the protection layer and insulation layer by specific length, as described in the figure
below.
step 4 Make the cable and crimp OT/DT terminal,refer to " Crimp OT/DT terminal".
Observe the terminal layout on the block. Do not connect the phase wires to "PE"
terminal or PE wire to "N" terminal. Otherwise, unrecoverable damage to the inver-
ter may follow.
37
5 Electrical Connection User Manual
Ensure that the depth L of the socket used is not less than 18mm.
step 7 Secure the junction box, fasten the buckle, and secure it with supplied M4×10 screw.
step 8 Gently pull the cable backwards to ensure firm connection, and fasten the swivel nut
clockwise.
38
User Manual 5 Electrical Connection
- - End
The PV string will generate lethal high voltage when exposed to sunlight.
• Make sure the PV array is well insulated to ground before connecting it to the
inverter.
• Make sure the maximum DC voltage and the maximum short circuit current of
any string never exceed inverter permitted values specified in "Technical Data".
• Check the positive and negative polarity of the PV strings, and connect the PV
connectors to corresponding terminals only after ensuring polarity correctness.
• During the installation and operation of the inverter, please ensure that the posi-
tive or negative electrodes of PV strings do not short-circuit to the ground. Oth-
erwise, an AC or DC short-circuit may occur, resulting in equipment damage.
The damage caused by this is not covered by the warranty.
• If the DC input cables are reversely connected or the positive and negative ter-
minals of different MPPT are shorted to ground at the same time, while the DC
switch is in the "ON" position, do not operate immediately. Otherwise, the inver-
ter may be damaged. Please turn the DC switch to "OFF" and remove the DC
connector to adjust the polarity of the strings when the string current is lower
than 0.5 A.
39
5 Electrical Connection User Manual
• The inverter enters standby state when the input voltage ranges between 1,000
V and 1,100 V. The inverter returns to running state once the voltage returns to
the MPPT operating voltage range, namely, 200 V to 1,000 V.
• Each PV input operates independently and has its own MPPT. In this way, string struc-
tures of each PV input may differ from each other, including PV module type, number of
PV modules in each string, angle of tilt, and installation orientation.
• Each PV input area includes two DC inputs DC1 and DC2. For the best use of DC power,
DC1 and DC2 should be the same in PV string structure, including the type, number, tilt,
and orientation of the PV modules.
Prior to connecting the inverter to PV inputs, the specifications in the following table should
be met:
40
User Manual 5 Electrical Connection
• Use MC4 DC terminals if the maximum input voltage is no more than 1,000 V.
• Use MC4-Evo2 DC terminals if the maximum input voltage is greater than 1,000
V. To purchase the MC4-Evo2 DC terminals, contact SUNGROW.
step 3 Lead the cable through the cable gland, and insert the crimp contact into the insulator until it
snaps into place. Gently pull the cable backward to ensure firm connection. Tighten the ca-
ble gland and the insulator (torque 2.5 N.m to 3 N.m).
41
5 Electrical Connection User Manual
- - End
step 2 Check the cable connection of the PV string for polarity correctness and ensure that the
open circuit voltage in any case does not exceed the inverter input limit of 1,100V.
step 3 Connect the PV connectors to corresponding terminals until there is an audible click.
42
User Manual 5 Electrical Connection
If the PV string is equipped with the optimizer, please refer to the optimizer manual for elec-
trical connections and make sure that the polarity of the optimizer cables is correct.
- - End
The pin removed is a required accessory for fixing the junction box. Store it prop-
erly and protect it against missing or deformation.
43
5 Electrical Connection User Manual
During installation, firmly press the junction box to ensure that the pin can be in-
serted successfully.
Never hit the pin with a heavy object, such a hammer. Otherwise, it will be irrecov-
erably damaged.
The communication board of the inverter includes two layers. The upper layer communica-
tion board mainly includes RS485 communication interfaces while the lower layer communi-
cation board mainly includes DI/DO interface and DRM interface.
As shown in the Figure below, the inverter is equipped with three RS485 communication in-
terfaces and one dip switch.
44
User Manual 5 Electrical Connection
All three interfaces can be connected to a data acquisition device (Data Logger), to achieve
data exchange with PC or other monitoring devices.
The RS485-1 crimp and the RJ45 interface can be applied to applications where multiple in-
verters communicate in a daisy-chain form.
A 120Ω resistor can be connected in parallel between RS485-1 A/B pins by configuring the
dip switch.
RS485-1 crimp interface and RJ45 interface serve as the same function with differ-
ent wiring manner.
45
5 Electrical Connection User Manual
When more than 15 inverters are connected to the same daisy chain, in order to ensure the
communication quality, the Logger at the first end of the daisy chain needs to be equipped
with a terminal resistor of 120Ω, the inverter at the last end needs to be equipped with a
RS485-dip switch (SW1), and the shielding layer of the communication cable should be sin-
gle-point grounded.
The length of the RS485 cable and twisted pair cable should be no longer than
1,200m.
If multiple inverters are connected to the data logger, the number of permissible
daisy chains and the number of devices allowed to be connected should meet the
requirements (refer to the user manual for the data logger).
46
User Manual 5 Electrical Connection
step 1 Remove the communication junction box, see" Remove the Junction Box".
step 2 Strip the protection layer and insulation layer by appropriate length.
step 3 Loosen the swivel nut of the junction box and select an appropriate seal according to cable
outer diameter. Lead the cable through the swivel nut, seal, and junction box successively.
47
5 Electrical Connection User Manual
No Definition
1 RS485 A IN, RS485A differential signal+
2 RS485 A OUT, RS485A differential signal+
3 RS485 B IN, RS485B differential signal-
4 RS485 B OUT, RS485B differential signal-
step 6 If other wiring operations need to be performed on the communication board, finish the wir-
ing operations before performing the following steps. If otherwise, continue to perform the
following steps.
step 7 Install the junction box, see " Install the Junction Box".
step 8 Pull the cable gently to make sure it is secured, tighten the swivel nut clockwise.
- - End
step 2 Loosen the swivel nut of the junction box and select an appropriate seal according to cable
outer diameter. Lead the cable through the swivel nut, seal, and junction box successively.
48
User Manual 5 Electrical Connection
step 3 Strip the insulation layer of the Ethernet cable with a wire stripper, and insert the signal wires
to the RJ45 connector(Pin 3 and Pin 6 are for communication connection). Crimp the RJ45
connector with a crimping tool.
step 5 If other wiring operations need to be performed on the communication board, finish the wir-
ing operations before performing the following steps. If otherwise, continue to perform the
following steps.
step 6 Install the junction box, see " Install the Junction Box".
step 7 Pull the cable gently to make sure it is secured, tighten the swivel nut clockwise.
- - End
49
5 Electrical Connection User Manual
The configuration circuit board is provided with fault output dry contact and emergency stop
dry contact, as shown in the figure below.
Connection method of the dry contacts is similar to that of the RS485 terminal block.
DO terminal (fault output dry contact): The relay can be set to output fault alarms, and
user can configure it to be a normally open contact (COM&NO) or a normally closed contact
(COM&NC).
The relay is initially at the NC contact, and it will trip to another contact when a fault occurs.
When alarm occurs, signal status change will not be triggered.
Use LED indicators or other equipment to indicate whether the inverter is in the faulty state.
The following Figures show the typical applications of normal open contact and normaliy
closed contact:
50
User Manual 5 Electrical Connection
The following figure shows the typical application of local stop dry contact.
51
5 Electrical Connection User Manual
When wiring DI dry contacts, ensure that the maximum wiring distance meet the require-
ments in "10.2 Wring Distance of DI Dry Contact".
The inverter supports the demand response modes as specified in the standard AS/NZS
4777. The inverter has integrated a terminal for connecting to a DRED. After the connection,
the method of asserting DRMs as specified in the follow table.
52
User Manual 5 Electrical Connection
Enable the DRM function through the iSolarCloud APP. If there are any problems,
contact your distributor first. If the problem persists, contact SUNGROW.
The DRM function is only applicable to devices for Australia and New Zealand.
step 2 Strip the insulation layer of the Ethernet cable with a wire stripper, and insert the signal wires
to the RJ45 connector. Crimp the RJ45 connector with a crimping tool.
53
5 Electrical Connection User Manual
step 3 Loosen the swivel nut and select an appropriate seal according to cable outer diameter.
Lead the cable through the swivel nut, and seal successively.
Outer Diameter D
Seal
(mm)
4.5 ~ 6 c
6 ~ 12 a+b
12 ~ 18 b
step 5 If other wiring operations need to be performed on the communication board, finish the wir-
ing operations before performing the following steps. If otherwise, continue to perform the
following steps.
step 6 Install the junction box, see " Install the Junction Box".
step 7 Pull the cable gently to make sure it is secured, tighten the swivel nut clockwise.
54
User Manual 5 Electrical Connection
- - End
*The image shown here is for reference only. The actual product you receive may differ.
Once the communication module is in use, do not connect the inverter to a 3rd
party data logger at the same time via RS485.
For details on module installation and configuration, refer to the manual delivered
together with the module.
55
6 Commissioning
• No foreign items, such as tools, are left on the top of the machine or in the junction box (if
there is).
• The AC circuit breaker is selected in accordance with the requirements of this manual
and local standards.
If all of the items mentioned above meet the requirements, proceed as follows to start up the
inverter for the first time.
step 1 Connect the AC switch or circuit breaker between the inverter and the grid.
step 3 Connect the DC switch (if applicable) between the inverter and the PV string.
step 4 Set initial protection parameters via the iSolarCloud App. For details, please refer to "7.2 In-
stalling App",and "7.4.2 Login Procedure". If the irradiation and grid conditions meet require-
ments, the inverter will normally operate.
step 5 Observe the LED indicator to ensure that the inverter operates normally. Refer to "2.4 LED
Indicator" for details.
- - End
56
7 iSolarCloud App
The iSolarCloud App can establish communication connection to the inverter via the Blue-
tooth, thereby achieving near-end maintenance on the inverter. Users can use the App to
view basic information, alarms, and events, set parameters, or download logs, etc.
*In case the communication module Eye, WiFi or WiNet-S is available, the iSolarCloud App
can also establish communication connection to the inverter via the mobile data or WiFi,
thereby achieving remote maintenance on the inverter.
• This manual describes only how to achieve near-end maintenance via the
Bluetooth connection. For remote maintenance through the Eye, WiFi or
WiNet-S, refer to the related manuals in the delivery scope.
• Screenshots in this manual are based on the Android system V2.1.6 , and the
actual interfaces may differ.
57
7 iSolarCloud App User Manual
The App provides parameter viewing and setting functions, as shown in the following figure.
7.4 Login
7.4.1 Requirements
• The mobile phone is within 5 meters away from the inverter and there are no obstructions
in between.
The inverter can only pair with one phone at a time through Bluetooth.
step 2 Establish the Bluetooth connection by either of the two following ways. If the LED indicator
flashes blue, the connection is successfully established.
• Scan the QR code on the side of the inverter for Bluetooth connection.
58
User Manual 7 iSolarCloud App
• Tap "Manual connection" and select "Others" at the bottom of the page, the Bluetooth
search page will automatically pop up, and select the inverter to be connected according
to the SN on the nameplate on the side of the inverter body.
step 3 Enter the identity verification interface after the Bluetooth connection is established.
59
7 iSolarCloud App User Manual
step 4 If the inverter is not initialized, you will enter the quick setting interface of initializing protec-
tion parameter. Tap Country/Region to select the correct country, as shown in the following
figure.
60
User Manual 7 iSolarCloud App
step 5 When the country is set to Australia, additionally set the applicable network service provider
and then the grid type.Tap Power Company to select the correct power company.
The image shown here is for reference only. Refer to the actual interface for the supported
network service providers.
61
7 iSolarCloud App User Manual
step 6 After finishing the settings, tap TUNR ON DEVICE at the upper right corner and the device
will be initialized. The App will send start instructions and the device will start and operate.
step 7 After initialization settings, the App will return automatically to the home page.
- - End
7.5 Home
62
User Manual 7 iSolarCloud App
63
7 iSolarCloud App User Manual
State Description
After being energized, inverter tracks the PV arrays’ maximum power
Run point (MPP) and converts the DC power into AC power. This is the nor-
mal operation mode.
Stop Inverter is stopped.
Press to Shut Inverter will stop operation by tapping "Stop" via app. In this way, inverter
Down internal DSP stops. Restart the inverter via app if needed.
Inverter enters standby mode when DC side input is insufficient. In this
Standby
mode inverter will wait within the standby duration.
Initial standby The inverter is in the initial power-on standby state.
Starting up The inverter is initializing and synchronizing with the grid.
Warn run Warning information is detected.
Derating The inverter derates actively due to environmental factors such as tem-
running perature or altitude
Dispatch The inverter runs according to the scheduling instructions received from
Running the monitoring background
If a fault occurs, inverter will automatically stop operation, and the AC re-
lay acts. The fault information will be displayed on the app. Once the
Shut down
fault is removed in recovery time, inverter will automatically resume
running.
State Description
PID recovery
The inverters perform PID recovery actively.
running
It is detected that the ISO impedance is abnormal or the PID cannot
PID abnormity
work normally after the PID function is enabled.
If the inverter is running abnormally, the alarm or fault icon will be displayed in the lower
right corner of the inverter icon in power flow chart. The user can tap this icon to enter the
alarm or fault interface to view detailed information and corrective measures.
Tap Run Information on the navigation bar to enter the screen showing running information,
slide the screen upwards to view all detailed information.
64
User Manual 7 iSolarCloud App
Classifica-
Parameter Description
tion
PV String n Voltage The input voltage of the nth string
Information String n current The input current of the nth string
Total On-grid Run-
/
ning Time
Daily On-grid Run-
/
ning Time
Negative Voltage to
Inverter DC side negative to ground voltage value
Ground
Voltage between the positive and negative poles
Bus Voltage
of the DC side of the inverter
Inverter
Internal Air
Information /
Temperature
Array Insulation Insulation resistance value of the input side to the
Resistance protection ground
Country Information /
Power Limitation
/
Mode
Reactive Power
/
Mode
Total DC Power DC side total input power
Input MPPT x Voltage The input voltage of the xth MPPT
MPPT x Current The input current of the xth MPPT
Daily Yield /
Monthly Yield /
Annual Yield /
Total Active Power Current active power value of the inverter
Total Reactive Power Current reactive power value of the inverter
Total Apparent
Current apparent power value of the inverter
Power
Output
Total Power Factor Power factor of the AC side of the inverter
Gird Frenquency Frequency of the AC side of the inverter
A-B Line Voltage
B-C Line Voltage Line voltage
C-A Line Voltage
Phase A Current
Phase current
Phase B Current
65
7 iSolarCloud App User Manual
Classifica-
Parameter Description
tion
Phase C Current
7.7 Records
Tap Records on the navigation bar to enter the interface showing event records, as shown
in the following figure.
Select one of the records in the list and tap the record to view the detailed fault information
as shown in following figure.
66
User Manual 7 iSolarCloud App
The App displays power generation records in a variety of forms, including daily power gen-
eration graph, monthly power generation histogram, annual power generation histogram
and total power generation histogram.
Parameter Description
Shows the power output from 5 am to 23 pm in a single day. Each
Power curve point on the curve represents the percentage of present inverter
power to rated power.
Daily yield
Shows the power output every day in the present month.
histogram
67
7 iSolarCloud App User Manual
Parameter Description
Monthly yield
Shows the power output every month in a year.
histogram
Annual yield
Shows the power output every year.
histogram
Tap the time bar on the top of the interface to select a time segment and view the corre-
sponding power curve.
Swipe left to check the power yields histogram.
Event Record
Tap Event Record to view event record list.
7.8 More
Tap More on the navigation bar to enter the corresponding interface, as shown in the follow-
ing figure.
68
User Manual 7 iSolarCloud App
69
7 iSolarCloud App User Manual
Parameter Description
Enabling/Disable the PID night recovery function. Once enabled, it
PID Recovery
works between 22:00 pm and 5:00 am by default.
If ISO impedance abnormality or PID function exception is de-
tected during running of the PID function, the inverter reports a
Clear PID alarm PID abnormity and reminds the user to take corresponding meas-
ures. Clear the alarm report via this parameter once the problems
are handled.
Apply negative voltage when the inverter is connected to negative
voltage panel.
PID Scheme
Apply positive voltage when the inverter is connected to positive
voltage panel.
After the PID night recovery function is enabled, the fault indicator on the inverter
front panel turns green.
AFCI Parameters(Optional)
Tap Settings→Operation Parameters→AFCI Parameters to enter the corresponding
screen, on which you can set "AFCI Parameters".
70
User Manual 7 iSolarCloud App
Definition/Setting
Parameter Range
Description
Active power soft start Time that the soft start takes to 1s~1200s
time after fault raise the power from 0 to
100% rated power.
71
7 iSolarCloud App User Manual
Definition/Setting
Parameter Range
Description
72
User Manual 7 iSolarCloud App
Definition/Setting
Parameter Range
Description
73
7 iSolarCloud App User Manual
Definition/Setting
Parameter Range
Description
74
User Manual 7 iSolarCloud App
Definition/Setting
Parameter Range
Description
75
7 iSolarCloud App User Manual
To avoid download failure due to poor on-site network signal, it is recommended to download
the firmware package to the mobile device in advance.
Perform firmware update only during high irradiance conditions in order to prevent equip-
ment failure.
step 2 Open the App, enter the account and password on the login interface. Tap Login to enter
the home interface.
step 3 Tap More→Firmware Download to enter corresponding interface on which you can view
the device list.
76
User Manual 7 iSolarCloud App
step 4 Select the device model before downloading the firmware. Tap the device name in the de-
vice list to enter the firmware upgrade package detail interface, and tap behind the firm-
ware upgrade package to download it.
step 5 Return to the Firmware Download interface, tap in the upper right corner of the interface
to view the downloaded firmware upgrade package.
step 6 Login the App via local access. Refer to "7.4 Login".
step 7 Tap More on the App home screen and then tap Firmware Update.
step 8 Tap the upgrade package file, a prompt box will pop up asking whether to upgrade the firm-
ware with the file, tap CONFIRM to perform the firmware upgrade.
step 9 Wait for the file to be uploaded. When the upgrade is finished, a message is displayed indi-
cating that the upgrade is completed. Tap Complete to end the upgrade.
- - End
Tap Modify Password to enter the modify password interface, as shown in the following
figure.
77
7 iSolarCloud App User Manual
The password shall consisit of 8–20 digits, including letters and numbers.
78
8 System Decommissioning
Danger of burns!
Even if the inverter is shut down, it may still be hot and cause burns. Wear protec-
tive gloves before operating the inverter after it cools down.
For maintenance or other service work, the inverter must be switched off.
Proceed as follows to disconnect the inverter from the AC and DC power sources. Lethal
voltages or damage to the inverter will follow if otherwise.
step 1 Disconnect the external AC circuit breaker and prevent it from inadvertent reconnection
step 2 Rotate the DC switch to the "OFF" position for disconnecting all of the PV string inputs.
step 3 Wait about 5 minutes until the capacitors inside the inverter completely discharge.
- - End
Before dismantling the inverter, disconnect the inverter from both AC and DC
power sources.
If there are more than two layers of inverter DC terminals, dismantle the outer DC
connectors before dismantling the inner ones.
step 1 Refer to "5 Electrical Connection", for the inverter disconnection of all cables in reverse
steps. In particular, when removing the DC connector, use an MC4 wrench to loosen the
locking parts and install waterproof plugs.
79
8 System Decommissioning User Manual
step 2 Refer to"4 Mechanical Mounting", to dismantle the inverter in reverse steps.
step 4 If the inverter will be used again in the future, please refer to "3.2 Inverter Storage" for a
proper conservation.
- - End
Please scrap the inverter in accordance with relevant local regulations and stand-
ards to avoid property losses or casualties.
Some parts of the inverter may cause environmental pollution. Please dispose of
them in accordance with the disposal regulations for electronic waste applicable at
the installation site.
80
9 Troubleshooting and Maintenance
9.1 Troubleshooting
Once the inverter fails, the fault information is displayed on the App interface. If the inverter
is equipped with an LCD screen, the fault information can be viewed on it.
The fault codes and troubleshooting methods of all PV inverters are detailed in the table be-
low, and only some of the faults may occur to the model you purchased. When a fault occurs,
you can check the fault information according to the fault code on the mobile app.
81
9 Troubleshooting and Maintenance User Manual
82
User Manual 9 Troubleshooting and Maintenance
28, 29, 208, PV Reserve Con- 2. Contact Sungrow Customer Service if the pre-
212, 448-479 nection Fault ceding causes are ruled out and the fault persists.
*The code 28 to code 29 are corresponding to
PV1 to PV2 respectively.
*The code 448 to code 479 are corresponding to
string 1 to string 32 respectively.
1. Check whether the corresponding string is of
reverse polarity. If so, disconnect the DC switch
and adjust the polarity when the string current
drops below 0.5 A.
2. Contact Sungrow Customer Service if the pre-
532-547, 564- PV Reverse Con-
ceding causes are ruled out and the alarm
579 nection Alarm
persists.
*The code 532 to code 547 are corresponding to
string 1 to string 16 respectively.
*The code 564 to code 579 are corresponding to
string 17 to string 32 respectively.
83
9 Troubleshooting and Maintenance User Manual
84
User Manual 9 Troubleshooting and Maintenance
85
9 Troubleshooting and Maintenance User Manual
86
User Manual 9 Troubleshooting and Maintenance
87
9 Troubleshooting and Maintenance User Manual
88
User Manual 9 Troubleshooting and Maintenance
9.2 Maintenance
9.2.1 Maintenance Notices
• Before any service work, first disconnect the grid-side AC circuit breaker and
check the inverter status. If the inverter indicator is off, please wait until night to
disconnect the DC switch. If the inverter indicator is on, directly disconnect the
DC switch.
• Turn the DC switch from ON to OFF, the DC switch can be locked here. (For
countries “AU” and “NZ”)
• After the inverter is powered off for 5 minutes, measure the voltage and current
with professional instrument. Only when there is no voltage nor current can op-
erators who wear protective equipment operate and maintain the inverter
• Even if the inverter is shut down, it may still be hot and cause burns. Wear pro-
tective gloves before operating the inverter after it cools down.
89
9 Troubleshooting and Maintenance User Manual
Restart the inverter only after removing the fault that impairs safety performance.
As the inverter contains no component parts that can be maintained, never open
the enclosure, or replace any internal components.
To avoid the risk of electric shock, do not perform any other maintenance opera-
tions beyond this manual. If necessary, contact your distributor first. If the problem
persists, contact SUNGROW. Otherwise, the losses caused is not covered by the
warranty.
Touching the PCB or other static sensitive components may cause damage to the
device.
90
User Manual 9 Troubleshooting and Maintenance
• Power off the inverter and disconnect it from all power supplies before main-
taining fans.
• After the inverter is powered off for 5 minutes, measure the voltage and current
with professional instrument. Only when there is no voltage nor current can op-
erators who wear protective equipment operate and maintain the inverter.
Fans inside the inverter are used to cool the inverter during operation. If the fans do not op-
erate normally, the inverter may not be cooled down and inverter efficiency may decrease.
Therefore, it is necessary to clean dirty fans and replace the broken fans in a timeiy manner.
The operation procedure is as follows:
step 2 Loosen the screw on the sealing plate of the fan module.
91
9 Troubleshooting and Maintenance User Manual
step 3 Press the tab of the latch hook, unplug the cable connection joint outwards, and loosen the
screw on the fan holder.
step 4 Pull out the fan module, clean the fans with soft brush or vacuum cleaner, and replace them
when necessary.
step 5 Reinstall the fan back to the inverter in reverse order and restart the inverter.
- - End
92
10 Appendix
93
10 Appendix User Manual
94
User Manual 10 Appendix
95
10 Appendix User Manual
96
User Manual 10 Appendix
97
10 Appendix User Manual
98
User Manual 10 Appendix
(1) The inverter enters the standby state when the input voltage ranges between1,000V and
1,100V. If the maximum DC voltage in the system can exceed 1000V, the MC4 connectors
included in the scope of delivery must not be used. In this case MC 4 Evo2 connectors must
be used.
(2) For inverters without a DC switch, it is necessary to prepare an external DC switch ac-
cording to AS 60947.3.
The wiring distance between DI dry contact terminals must meet the requirements in the ta-
ble below. The wiring distance L is the total length of all DI signal cables.
99
10 Appendix User Manual
LK refers to the cable length in one direction between the DI dry contact terminal of the kth in-
verter and the corresponding terminal of the (k-1)th inverter.
table 10-1 Correspondence Between Inverter Quantity and Maximum Wiring Distance
1 13030 10552
2 6515 5276
3 4343 3517
4 3258 2638
5 2606 2110
6 2172 1759
7 1861 1507
8 1629 1319
9 1448 1172
10 1303 1055
11 1185 959
12 1086 879
13 1002 812
14 931 754
15 869 703
16 814 660
17 766 621
18 724 586
19 686 555
20 652 528
21 620 502
22 592 480
23 567 459
24 543 440
25 521 422
100
User Manual 10 Appendix
In case the specification of the cable used is not included in the table above, when
there is only one inverter, ensure that the line impedance of the input node is less
than 300Ω; and when there are multiple inverters connected in the daisy chain, en-
sure that the impedance is less than 300Ω/number of inverter.
When product faults occur during the warranty period, SUNGROW will provide free service
or replace the product with a new one.
Evidence
During the warranty period, the customer shall provide the product purchase invoice and
date. In addition, the trademark on the product shall be undamaged and legible. Otherwise,
SUNGROW has the right to refuse to honor the quality guarantee.
Conditions
• The customer shall give SUNGROW a reasonable period to repair the faulty device.
Exclusion of Liability
In the following circumstances, SUNGROW has the right to refuse to honor the quality
guarantee:
• The free warranty period for the whole machine/components has expired.
• The device operates in harsh conditions beyond those described in this manual.
• The installation and use range are beyond stipulations of relevant international
standards.
For faulty products in any of above cases, if the customer requests maintenance, paid main-
tenance service may be provided based on the judgment of SUNGROW.
101
10 Appendix User Manual
• Fault code/name
102