Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Testing Report For Pressure Relief Valves: Petrofac International (UAE) LLC

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Petrofac International (UAE) LLC. Format No.

2040-27001-Q99-I-0005-E

PROJECT : VISAKH REFINERY MODERNIZATION PROJECT(VRMP) Rev. 0

CLIENT : HPCL
JOB NO. J1 - 2040
CONSULTANT : ENGINEERS INDIA LIMITED
Report No. PIUL/FORAYS/IINST/PSV-028
TESTING REPORT FOR PRESSURE RELIEF VALVES Date. 22-Nov-2022

Instrument Details Details of Master Calibration Instruments used :


Type CONVENTIONAL Type PRESSURE GAUGE
Tag No 509-PSV-21321B Make BAUMER
Make LESER VALVES Model No -
Model No 5260.0411 Serial No STA/PG/04
Sr. no. 11645586 Cal Range 0-40 Kg/cm²
Test pressure 14.9 Kg/cm² Testing Agency SRI CALIBRATION SERVICES

Ref.Data Sheet 2040-J-DSP-CO-0008-0001 Ref.T/C NO SCS/01-22/229-04


Calibration Date 22-Nov-2022 Valid up to 30-Jan-2023

Valves Data
Service Lean Amine E-1001A Safety Relief Set pressure 15 Kg/cm²
Inlet Size/Rating 3" / 150# Back pressure 0.1 Kg/cm²
Outlet Size/Rating 4" / 150# Operating temperature 60℃
Orifice size K

Physical Check : OK
Test Media Yes Test Gag Yes
Lift lever open N/A Locking Device Yes
Lift lever packed N/A
Screwed cap Yes

Testing Details Units Specified Test Results Remarks

Cold spring set Pressure Kgf/cm² 14.9 Kg/cm² 14.9 Kg/cm²


No Visible Leakage found at 90% of Set
Reset Pressure Kgf/cm² 13.41 Kg/cm² 13.41 Kg/cm²
Pressure / CDTP

Seat leakage Rate Bubbles / Minute 20 4

COMMENTS.

FORAYS Petrofac Execution Petrofac Quality EIL/HPCL

Name
Signature
Date