An Examination of Power
Converter Architectures for
Utility-Scale Hybrid Solar
Photovoltaic and Battery Energy
Storage Systems
THE FEATURES OF SEVERAL POWER CONVERSION ARCHITECTURES
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE SANTA CATARINA. Downloaded on February 09,2023 at 16:22:52 UTC from IEEE Xplore. Restrictions apply.
by featuring fast dispatch flexibility [13]. Moreover, power architectures
and voltage-ampere reactive support. are expected to evolve over time
Although many proposed PV plants A utility-scale PV based on future trends.
are being developed with colocated Currently, hybrid PV+BS power
batteries, the dominant architecture power plant can plants can be broadly classified as
of utility-scale PV+BS power plants is comprise several PV either ac grid- or converter-coupled
uncertain. Moreover, power architec- systems based on their point of com-
tures are expected to evolve over time modules that connect mon coupling. These systems do not
based on future trends. The primary share any components and the stor-
goal of this article is to critically exam- in series and/or in age systems can act independent of
ine and compare several dc–dc and parallel to form PV the PV system. From the perspective
dc–ac power converter architectures of power converter architectures, ac
that are suitable candidates for hybrid strings or PV arrays. grid-coupled systems are expected to
PV+BS power plants. In particular, the have similar characteristics to inde-
article presents characteristics of sev- pendently operated PV and BS plants
eral power conversion architectures [13]. On the other hand, in converter-
from the point of view of power semiconductor require- coupled systems, PVs and BSs share the dc–ac grid-con-
ments, efficiency, reactive component requirements, modu- nected inverter. This article focuses on converter-coupled
larity, control complexity, and so forth. Detailed analytical configurations for utility-scale hybrid PV+BS power plants
models are utilized, along with a benchmark design exam- because of their distinct characteristics and expected
ple to present a comparative evaluation of the alternatives advantages. Further, the design of converter-coupled
for performing engineering tradeoff studies. configurations are more complex and integrated due to
the sharing of electronic and control systems and hence
Introduction requires detailed studies.
The increasing share of intermittent sources of energy Although the growth of hybrid plants is driven by
such as solar and wind intensifies the need for energy significant declines in project costs due to cost savings by
storage technologies such as batteries and pumped- sharing equipment, cutting interconnection, and permit-
storage hydropower. Although pumped-storage facili- ting costs and leveraging federal tax credits [14], there are
ties account for nearly 92% of the U.S. energy storage several other technical advantages as well. First, convert-
capacity [1], battery energy storage systems are growing er-coupled systems permit the energy storage of other-
quickly [2], [3]. This is due to their high energy densi- wise clipped energy that occurs when the inverter loading
ties and smaller size and weight, which leads to added ratio (ILR) exceeds one. Typically, the ILR varies between
flexibility and ease of installation [4], [5]. More recently, one and two and is assumed to be 1.3 in this study, which
the falling costs of PV and BS technologies have raised is equal to the average value for utility-scale PV systems
interest in the creation of hybrid PV+BS power plants. [13]. Further, as the batteries are directly charged from the
These technologies are enabled by the development of PV system, converter-coupled systems have higher charg-
advanced power electronics with unprecedented func- ing efficiency due to a lower number of power electronic
tionality, efficiency, reliability, and power density critical stages. Finally, independent of the point of coupling,
for an electrified world economy. According to some hybridization of the PV power plants with BSs broaden
estimates, 80% of all U.S. electricity could pass through the plant’s grid services, including fast dispatch flexibility,
power electronics devices by 2030 [6]. Further, continu- frequency regulation, and voltage-ampere reactive sup-
ous advancements in control architectures are critical to port. In summary, PV+BS power plants have the potential
support electrified systems that present different and to offer 1) energy savings by capturing clipped energy
challenging characteristics as compared to conventional from PV panels, 2) higher round-trip efficiency during
electrical generators [7], [8], [9]. battery charging times, and 3) improved dispatch flex-
Most of the utility-scale battery energy storage systems ibility, making them more attractive for grid operations. It
that are expected to come online in the United States must be noted that converter-coupled systems also suffer
from 2021 to 2023 are to be colocated with PV power from challenges compared to ac grid-coupled systems.
plants, a change in trends from recent years [10], [11]. Due to the highly integrated structure in converter-cou-
Further, considering the interconnection queues in the pled systems, they are expected to have a higher struc-
United States, 34% of the proposed PV plants are being tural balance of systems due to distributed and smaller
developed with colocated batteries [11]. It may, however, battery packs, in comparison to a larger centralized bat-
be noted that the dominant architecture for the proposed tery pack in colocated ac systems [13].
and future utility-scale PV+BS power plants is highly The primary goal of this article is to critically exam-
uncertain. Most of the interconnection queue data do not ine and compare several dc–dc and dc–ac power con-
include information about the inverter characteristics [12], verter architectures and their control strategies that can
follows: The “Block Diagram of PV+BS Power Plants” average value for utility-scale PV systems. Hence,
section presents simplified block diagrams of the con- the PV power plant’s rated power is Ppv = 1.3 # Pinv .
figurations of hybrid PV+BS systems; the “DC-Stacked The BS-rated power is assumed to be Pbatt. Typically,
Architectures” and “Cascaded Bridge Architectures” Pbatt . 0.5 # Pinv in today’s hybrid power plants [13]. In
sections examine dc-stacked and modular power con- summary, the PV and the battery converter are rated
verter architectures in terms of power semiconductor for Ppv and Pbatt, respectively.
switch and energy storage element ratings, respectively; As hybrid PV+BS power plants become common, the
the “Control Strategies for Hybrid PV+BS Plants” sec- average ILR is expected to increase [13] as more clipped
tion discusses the control architectures suitable for the energy can be stored in the BS. Analytical results from
topologies under consideration; the “Double-Star Config- the article will still hold true for many purposes, and the
uration” section briefly discusses double-star design con- tools provided in the article can be used for extended
figurations for hybrid power configurations; the “Results designs. In the remainder of the article, the following
and Discussion” section presents detailed comparative notations are commonly used across all the considered
results for a design example; and finally, the “Conclu- power converter architectures: fS represents the switching
sion” section summarizes the article. frequency; TS = 1/fS represents the switching cycle; Vac,
I ac represent the root-mean-square (RMS) values of the ac
Block Diagram of PV+BS Power Plants grid-phase voltages and currents; Vt ac, Itac represent peak
Figure 1 illustrates the simplified block diagram of a values of the ac grid voltages and currents, respectively;
converter-coupled hybrid PV+BS power plant. The PV and fac, Tac represent the ac grid frequency and time period,
BS power plants share a common dc–ac grid-connected respectively; VA represents the voltage × current ratings
inverter that connects the two dc systems (i.e., the PV and of the semiconductor switches; and subscript p and b indi-
the BS) to the ac grid. The two dc systems interface to cate variables for PV and BS, respectively.
each other, either at the dc or ac node. Figure 1(a) and (b)
illustrates block diagrams for dc- and ac-coupled systems, DC-Stacked Architectures
respectively. Based on the coupling-node configuration,
galvanic isolation between the dc sources and the ac grid Topology and Operation
may be at the ac grid or at the converter level, which is Three-phase two-level voltage source converters (VSCs)
discussed later. have traditionally been ubiquitous and are the workhorse
The following assumptions about hybrid power plant topology in many applications such as traction inverters,
systems have been made while examining several power industrial motor drive systems, uninterruptible power
converter architectures. supplies, and so on [15], [16]. In fact, two-level VSCs have
PV System PV System
(ILR × Pinv) (ILR × Pinv)
dc–dc dc–ac
(ILR × Pinv) (ILR × Pinv)
dc–dc dc–ac
BS (Pbatt) BS (Pbatt)
(Pbatt) (Pbatt)
dc–ac ac–ac
ac Grid (Pinv) ac Grid
(Pinv)
(a) (b)
FIGURE 1. A block diagram of converter-coupled PV and BS power plants with (a) a dc-coupled configuration and (b) an ac-coupled
configuration. ILR: inverter loading ratio.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE SANTA CATARINA. Downloaded on February 09,2023 at 16:22:52 UTC from IEEE Xplore. Restrictions apply.
dominated industrial-scale grid-con- of the following: 1) a multistring, 2)
nected energy storage projects [17], string, or 3) module distribution. In
[18]. Further, VSCs offer an architec- To provide galvanic the case of large utility-scale installa-
tural solution for hybrid utility-scale tions (beyond 100 kW), the prospect
power plants. The connection of isolation, the of a per-module power converter is
low-voltage battery and PV systems cascaded bridge limited [21], [23]. Large-scale installa-
to the medium-voltage utility grid is tions feature improved module-level
enabled by 1) series connection of architecture can uniformity, in contrast to residential
several low-voltage systems and 2) or commercial rooftop installations.
utilization of a low-frequency step-up feature a low- Further, the additional part count,
transformer, which may be a solid- frequency transformer monitoring and installation time,
state-based transformer for increased and cost-effectiveness are disadvan-
efficiency and power density. at the ac grid or tages to per-module power electron-
Figure 2 illustrates the circuit ics in large installations. Hence, this
schematic for the solution. Although module level. article assumes the distribution of
dc batteries may be directly con- dc–dc converters at the string level
nected to the dc link, PV systems for PV systems.
are typically cascaded via dc–dc Several strings interface to the dc
converters featuring distributed maximum power point link using dc–dc converters while implementing MPPT
tracking (MPPT) algorithms. In the case of hybrid algorithms to maximize energy yield. String-level dc–dc
PV+BS systems, dc–dc converters that interface each of converter systems, which integrate into the utility-scale
the dc systems with each other and the ac grid play a grid, can feature a boost or buck-boost converter configu-
distinct role in the control of power flow. As the com- ration [22], [24]. Similarly, based on the voltage class of
mon point of coupling between the PV, BS, and the ac the battery energy storage, dc–dc converters can feature
grid converters is dc, this topology is a dc-coupled con- either a boost or buck-boost configuration, as detailed
figuration in Figure 1(a). next. Due to the presence of a low-frequency transformer
between the ac converter and ac grid, an isolated dc–dc
Decentralized Converter Architecture Approach converter configuration may not be necessary. On the
DC energy sources such as PV panels and batteries other hand, ac-coupled PV+BS systems will typically
are all series and/or parallel connections of a basic feature transformer-coupled converters, as discussed in
cell. These cells operate at a low voltage, ranging from the “Cascaded Bridge Architectures” section. This article
less than 1 to 4 V [19], [20]. These low-voltage systems considers nonisolated dc–dc converters for dc-stacked
do not interface well with higher-voltage systems and architectures.
hence, several PV or battery cells are connected in The remaining sections discuss voltage × current (VA)
series to form a PV module or a BS. ratings of the semiconductor components and the energy
Considering PV module technologies, PV modules storage ratings of the inductors and capacitors that togeth-
can be categorized into three categories: 1) high-voltage er play a key role in determining the efficiency, power
(. 240 V) amorphous silicon modules, 2) medium- density, cost, and reliability of the architectures.
voltage (. 60 V) amorphous silicon modules, and 3) low-
voltage multicrystalline silicon modules (. 30 V) [21]. VA Ratings of Semiconductor Components
A utility-scale PV power plant can comprise several PV The VA ratings that are imposed by the converter design
modules that connect in series and/or in parallel to form and operation assist in the selection of power semicon-
PV strings or PV arrays. Traditional PV power plants ductor devices for the converter design. Here, the VA rat-
feature a central dc–dc converter that cascades to a grid- ing calculation incorporates the peak voltage stresses and
connected dc–ac inverter for power transport. The dc–dc RMS current values on the devices.
converter implements the MPPT algorithm to maximize
energy yield. In contrast to central dc–dc converters,
distributed dc–dc converters are growing quickly due to +
several advantages, including energy-yield improvements SA+ SB+ SC+
during shading, module mismatch, elimination of single- LVAc MVAc
Vdc
point failure, and added monitoring and diagnostics.
PV BS 1:t
Literature studies indicate that an energy-yield gain of SA– SB– SC–
4–12% can be obtained for distributed systems over cen- –
tral inverter systems [21], [22], [23]. The distribution of
dc–dc converters, along with the MPPT controllers asso- FIGURE 2. The converter topology of a three-phase two-level VSC with
ciated with them for dc-stacked architectures can be one cascaded BSs, and cascaded PV systems connected to the dc link.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE SANTA CATARINA. Downloaded on February 09,2023 at 16:22:52 UTC from IEEE Xplore. Restrictions apply.
Battery/PV Energy Storage Ratings Efficiency Calculations
The article presents analytical models to quantify and
DC–AC Grid Inverter compare efficiency of the power electronic architectures
To filter the switching action of the six semiconductor under discussion by characterizing the RMS and aver-
switches, the topology typically features a dc-link capaci- age current calculations in the semiconductor switching
tor and an input inductor to smoothen the dc-link voltage devices, transformers, and the filtering and energy stor-
and input current, respectively. Equation (5) character- age elements. Table 2 summarizes the current expres-
izes the capacitor size, which is a function of the current sions for loss calculations for the dc–dc conversion stage
magnitude, modulation strategy, and the allowed ripple in terms of the duty ratios. For switching-loss calcula-
voltage at the dc link ^rVdch. tions, the switching energies provided by the data sheets
for the reference operating conditions are employed
Itac # dt 0 - dc TS
C link . (5) (characterized by k SW in the equations and defined in
rVdc
“Loss Calculations”). The switching-loss equation per
where dt 0 - dc represents the maximum value of the dc- switch for dc–dc converters is given by (7).
side zero-state duty ratio when only the peak ac current
^ Itac h flows into the capacitor. Due to the buck mode of Psw = '
k sw Vdc I p/b, Boost
.(7)
k sw V p/b + dc I p/b + dc, Buck boost, SEPIC, Cl uk
operation from the dc to the ac side, ac-side currents
will be of higher magnitude. Hence, the capacitor ripple
calculation features the peak value of the ac current
during the freewheeling duration of the dc current 15
when the net capacitor current is not offset by the dc
current. Note that the dc- and ac-side switches may be
12
operating at a different switching frequency and may
not be synchronized.
Similarly, (6) characterizes the net size of the filter 9
VA (p.u.)
Table 2. RMS and average current expressions for dc–dc converters useful for loss calculations
I RMS Iavg
Filtering Energy Storage
Topology Switch 1 Switch 2 L C L C Switch 1 Switch 2
Boost D I p/b Dl I p/b I p/b D Dl I p/b — — DI p/b DlI p/b
Buck boost D I p/b + dc Dl I p/b + dc — Dl I p/b + dc — DI p/b + dc DlI p/b + dc
I p/b
D
SEPIC D I p/b + dc Dl I p/b + dc I p/b Dl IDC Dl DI p/b + dc DlI p/b + dc
I p/b I p/b
D D
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE SANTA CATARINA. Downloaded on February 09,2023 at 16:22:52 UTC from IEEE Xplore. Restrictions apply.
Loss Calculations
The transistor and diode conduction losses can be calculated where E onT , E offT , and E rr represent the energy loss during
using an approximation with a series connection of the dc transistor turn on, transistor turn off, and diode reverse-
voltage drop representing the on-state voltage drop (v on) recovery event, respectively. The switching energy loss values
and the on-state resistance (ron), as illustrated in (S1). are provided in the manufacturer’s data sheet at reference
current (I R) and voltage (VR) operating conditions. Hence,
Pc = v on I avg + ron I 2rms(S1) the switching energies are normalized at VR, I R to derive the
switching losses under the operating conditions imposed by
where v on is the on-state collector-emitter voltage (v ce),
the circuit operation Vop, I op.
drain-source voltage (v ds), or forward voltage (v f ), in the
case of IGBTs, MOSFETs, or diodes, respectively. The switching Converter Parameter Details for
loss is characterized by the switching-loss energy associated Efficiency Calculations
Table S1 lists the converter parameters along with
with each switching event and is typically assumed to be
selected device parameters for the design example under
proportional to the blocking voltage and the conducting
consideration, with a power level of Ppv = 1.3 per unit (p.u.),
current at the instant of switching event. Equation (S2)
P batt = 0.3 p.u., and Pac = 1p.u., as discussed in the “Results
characterizes the switching loss associated with one half
and Discussion” section. The results obtained from the
bridge during a switching cycle.
simulations and the analytical equations are listed. Due to
(E + E offT + E rrD) the similarity between three-winding triple-active bridge
Psw = fSW onT Vop I op(S2) (3-W TAB) and five-winding (5-W) TAB designs, the 5-W TAB
14444442V44444
R IR
43
k sw is excluded from the table.
FB configuration. It is noted that the voltage scaling at rent value, power cycle frequency, and allowed ripple at
the PV or BSs considers the assumptions discussed in the the dc link ^rVdch.
“Block Diagram of PV+BS Power Plants” section. The PV
and the BSs can interface to the modular dc–ac convert- C link = 2 I dc Tac 1 (12)
r 4 rVdc
ers by employing any of the nonisolated dc–dc topologies
discussed in the “DC–dc Converter” section. The “Results where the factor of four in the denominator accounts for a
and Discussion” section presents a design example that second-harmonic ripple from the FB dc–ac converter, and
compares the dc-stacked architectures with the cascaded (2/r) I dc represents the average value of the mean current
bridge architecture. flowing into the dc–ac converter. In the case of a cas-
caded boost converter at the dc link, I dc = (2/r) I dc (1 - D).
Battery/PV Energy Storage Ratings The switching frequency is considered high in compari-
It may be observed that the modular dc–ac converters in son to the ac power frequency, and hence, the ripple due
Figure 5 have to be sized to filter single-phase ac power to the switching action is ignored. Similarly, (13) charac-
requirements. This is in contrast to dc-stacked topologies, terizes the net size of a series filter inductance to limit the
which only need to filter high switching-frequency com- ripple current from the dc source ^rI dch.
ponents. Equation (12) characterizes the capacitor size at
L s = 2 rVdc Tac 1 (13)
the module level, which is now a function of the ac cur- r 4 rI dc
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE SANTA CATARINA. Downloaded on February 09,2023 at 16:22:52 UTC from IEEE Xplore. Restrictions apply.
where the factor of 2/r accounts for the average value VA ratings for the cascaded 3-W TAB topology in a step-
of the ripple voltage across the inductor. In summary, by-step manner, as detailed further. Figure 7 illustrates a
energy storage elements will be bulkier in the case of the single 3-W TAB module fed from a PV system and a BS.
cascaded bridge architecture as compared to dc-stacked Here, the two dc systems are integrated into a single-phase
topologies due to the design archi-
tecture. Together with the dc-link MVAc MVAc
capacitor, the filtering elements at
the dc source will be sized to limit
the single-phase ac ripple from the
dc–ac inverter, as illustrated in (13). PV1A PV1B PVC
1
VA Ratings of Semiconductor
Components
This section presents a systematic FIGURE 7. Circuit schematic of a single module of TAB converter with both BSs and PV systems
approach for the derivation of the connected to modular dc–ac–ac converters via a 3-W transformer.
where p = b represents the number of TAB modules, and where the definition of the variables remain the same.
I L represents the RMS value of the net inductor current on
the secondary side, which is shared between the two dc Efficiency Calculations
systems during the power-transfer process, and the ratio Table 3 derives the current expressions critical for loss
of I L - x/I DC - x = rx . 1.1 - 1.3 results in an optimized calculations in a 3-W TAB. The notations I x0, I x1 represent
design with minimized VA requirements ^ x = pv, batt h. the current values when the transformer leakage induc-
The analysis assumes a phase shift of up to 0.2 per unit tance is referred to the PV, battery, and ac side bridge
(p.u.) to minimize reactive power flow [30], [31]. Similarly, where x = P, B, ac (I P0, I P1 are annotated in Figure 7).
equation sets (15) and (16) characterize the per-switch VA Duty ratios d 0, d z represent the duty ratios of the diode
rating for bridges 2 and 3, as annotated in the figure. conduction interval referred to the primary side and the
phase shift, respectively. Here, the distribution of currents
V 1 - SW = Vdc between the transistors and the diodes for the RMS and
I 1 - SW = I L average calculations assumes that the power is transferred
Bridge 2: 2 (15)
n SW = 4 # 3 # p = 12p from the PV panel to the battery and the ac grid, where
VA SW = 2 2 Pinv # rinv fb, fac represent the fraction of PV power transfer to the
battery and the ac grid, respectively. Similar expressions
where again the ratio of I L /I dc = rinv . 1.1 - 1.3 results in can be derived for other power-transfer cases. For the
an optimized design with minimized VA requirements. power loss calculations in the output ac bridge (referred
to as bridge 3), the loss expressions (8)–(10) discussed
V 1 - SW = Vdc = 1 Vac in the “Efficiency Calculations” section hold true. The
p 2d m “Results and Discussion” section presents comparative
1 - SW I ac
I = results for a design example under discussion.
Bridge 3: 2 (16)
n SW = 4 # 3 # p = 12p
2 Pinv TAB With a Five-Winding High-Frequency
VA SW = Transformer Topology
dm
To overcome the disadvantage of processing single-phase
It may be observed that the ratio between the mod- ac power processing requirements in modular topologies
ule’s dc-link voltage and the ac grid voltage features the such as CBC and TAB converter, the three ac legs can
number of modules p = b and the ac-modulation strategy be integrated using a high-frequency transformer [31].
factor d m. The total VA rating of the overall converter is The circuit schematic of the converter is illustrated in
characterized in (17). Figure 8. The high-frequency transformer interfaces the
PV and the BSs with the three-ac phases to eliminate the
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE SANTA CATARINA. Downloaded on February 09,2023 at 16:22:52 UTC from IEEE Xplore. Restrictions apply.
c onverter, with control complexity as a tradeoff. The next
MVAc
few sections detail quantitative and qualitative results.
ILA
VA Ratings of Semiconductor Components
VA ratings of the 5-W TAB converter are expected CA
to be comparable to the 3-W TAB converter of the PV1 ILB
“Triple-Active Bridge With a Three-Winding High-
CB
Frequency Transformer Topology” section. Equation
ILC
sets (20)–(22) characterize net VA ratings for the three B1
bridges wherein the current magnitudes will include CC
three-phase power calculations.
V 1 - SW = '
V p = n p # Vdc, PV
Vb = n b # Vdc, BS
Z I L - pv
] , PV
] 2 PVp
I 1 - SW = [
Bridge 1: ]] I L - batt , BS (20)
\ 2
n SW = 4 # p Bb
VA SW = )
2 2 Ppv # rpv, PV
2 2 Pbatt # rbatt, BS
V 1 - SW = Vdc
I 1 - SW = I L FIGURE 8. The converter topology of a three-phase cascaded TAB
Bridge 2: 2 (21) converter with both BSs and PV systems connected to modular
n SW = 4 # 3 # p = 12p dc–ac–ac converters via a 5-W transformer. Note that the three ac
VA SW = 2 2 Pinv # rinv phases are integrated together with the same dc systems.
Table 3. RMS and average current expressions for TAB converters useful for loss calculations
Component IRMS Iavg
2 2
PV Transistors (I + I + I P 0 I P1)
P0 P1 I2 I P0 (0.25 - 0.5d z) + I P1 (0.25 - 0.5d 0)
(0.5 - d z) + P1 (d z - d 0)
3 3
Diodes d0 0.5I P0 d 0
I P0
3
Inductor LP (I 2P0 + I P21 + I P0 I P1) (I 2 + I 2 - I I ) -
(1- 2d z) + P0 P1 P0 P1 2d z
3 3
- rc - Vb m 2zVb + r c - Vb m
2zV p n b Vp n b Vp n b
L p n 2b np np np
where L b = , I B0 = fb and I B1 = fb
n 2p 4rfS L b 4rfS L b
rent values. This can be identified in the net VA rating power control is permitted. The central controller con-
calculations of (23). sists of a phase-locked loop (PLL) unit, maintains the
power dispatched from the hybrid plant, and provides
VA SW = 2 2 P 8r # (ILR + z) + r inv p + 1 B(23)
2~
energy balancing between several converters/modules.
dm
Further, the central controller determines the reference
where the ratio of I L - x/I DC - x = rx . 1.2 for the PV and power commands for the modular PV and BS, P kref, pv
2~
battery converters. Note that the factor r inv p will be much and P kref, batt, respectively, where k refers to the kth mod-
higher than a 3-W TAB because the current waveforms ule. The remaining section discusses the several control
will feature a second-harmonic ripple. The “Results and approaches within the central controller and for the local
Discussion” section demonstrates the performance of this controllers suitable for hybrid PV+BS plants. Note that
architecture using a design example. superscript m refers to the measured quantities in the
following discussion.
Battery/PV Energy Storage Ratings
In contrast to a 3-W TAB converter, the energy storage Central Controller
elements of the 5-W TAB converter process only high- The ac grid-side voltages ^v m g h are typically processed by
frequency current and voltage ripples. The sizing equations a PLL to determine the peak value of the grid voltage ^Vt g h
for the capacitive and inductive energy storage that reduce and the frequency (f). Consequently, Vt g and f are utilized
the impact of the switching action at the dc and ac side are to determine the reference active ^ P acref
h and reactive ^ Q ref
ac h
characterized in (24) and (25), and (26), respectively. power values, respectively, typically using synchronverters
or virtual synchronous generators (VSGs) [32], [33].
C Batt - PV = I dc # TS 1 (24) The VSG control concept exploits the idea of operating
4 rVdc
an inverter to mimic a synchronous generator to emulate
rVdc TS 1
L Batt - PV = (25) its inertial characteristics. Typical VSG methods include
4 4 rI dc
voltage and frequency filtering, which are obtained from
It + I dc # dt T
c ac m 0 S the PLL using a deadband and a proportional controller.
3
C dc = (26) The deadband reduces noisy voltage or frequency-support
rVdc
needs to prevent false VSG activation. The proportional
where dt 0 represents the maximum value of the zero state controller is designed based on the megawatt/hertz capa-
of ac bridge 3 when the peak value of the ac phase current bility of the plant. As these methods include deriva-
and rectified inductor current flows into the capacitor. Simi- tive terms and their measurement through PLLs, their
lar to dc-stacked topologies, the size of the energy storage implementation uses slower controllers. Recent advanced
elements is a function of the modulation strategy because VSG schemes illustrate improvements in performance
the dominant ripple is due to the switching action. It may in hybrid plants by eliminating PLL and derivative terms
be noted that while under ideal scenarios although the [34]. Alternatively, although VSGs inherit the advantages
energy storage elements will be sized to filter high-frequen- of droop-control methods and provide inertia support,
cy switching ripples, energy storage elements will need to droop-control methods can be considered where no
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE SANTA CATARINA. Downloaded on February 09,2023 at 16:22:52 UTC from IEEE Xplore. Restrictions apply.
inertia emulation and a fast response [43]. Nevertheless, all of these invert-
is required [35], [36]. er control architectures are suitable
The VSG control for the four power electronic archi-
Local Controllers tectures under consideration as they
Based on grid demand, the power concept exploits the are designed for the dc–ac inverter
availability in PV systems ^ Pk, pv h, and idea of operating an connected to the grid.
the state of charge (SOC) of the BS
^ Pk, batth, the central controller cre- inverter to mimic DC-Stacked and CBC Architectures
ates the reference power dispatch Figure 9 also illustrates the control
commands for local controllers of a synchronous structure of a local PV controller
the PV, BS, and inverter systems. generator to suitable for dc-stacked and CBC
The local controllers are responsible architectures. The MPPT algorithm
for PV/MPPT, BS/SOC, and invert- emulate its inertial identifies the maximum power that
er dc voltage control. Although the can be generated by the PV and
control variable for dc-stacked and characteristics. controls the voltage at the termi-
CBC architectures are duty-ratio nals of the PV module v k, p. Based
variables, the 3-W and 5-W TAB on the PV power reference received
architectures require phase-shift from the central controller P kref, pv, a
modulation. The following sections discuss control voltage controller based on PI control creates a current
methods for several cases. reference I ref
k, pv command. Consequently, the PI current
controller generates the duty ratio for the PV dc–dc
Inverter dq Current Controls and Their Alternatives converter [33]. In a BS, the local SOC controller deter-
Synchronous reference frame control, also called dq con- mines the SOC of the batteries and controls the power
trol, transforms grid currents and voltages into a reference of the battery module. Based on the BS power reference
frame that rotates synchronously with the grid voltage, received from the central controller P kref, batt, a power con-
e.g., abc " dq, using PLL techniques. Consequently, as troller based on PI control creates a current reference
the control variables become dc values, control and fil- I ref
k, batt command. Consequently, the PI current controller
tering is simplified. As illustrated in the figure, the grid- generates the duty ratio for the PV dc–dc converter [33].
side converter control strategy typically consists of two
hierarchical loops. The inner-current loop regulates the 3-W and 5-W TAB Architectures
grid current, while the outer-voltage loop regulates the The voltage-transfer ratio between the input and output in
dc voltage based on power demand. Hence, the loops are TAB topologies is a critical design factor that has a direct
designed for power quality and power flow, respectively. effect on the reactive power flow within the topology.
These control loops typically feature proportional–integral In other words, if V p /n p ! Vb /n b ! Vdc, high circulating
(PI) controllers as they have a satisfactory behavior when currents can have a significant effect on converter perfor-
regulating dc variables [37]. Advanced controllers feature mance [30], [44]. Consequently, the complexities in control
cross coupling or voltage feedforward terms to improve strategies for these topologies are higher than traditional
the performance of PI controllers [38], [39]. dc-stacked and CBC topologies.
Due to poor compensation of low-order harmonics With the control architecture in Figure 9, the inverter
with PI control techniques, advanced techniques such as dc voltage is regulated by the central controller refer-
proportional–resonance (PR) controllers, hysteresis and ences and is fixed. Consequently, the reference active
deadbeat controllers are gaining popularity. The imple- power command ^ P kref, pv h and the PV module voltage
mentation of PR controllers is simpler in a stationary ^ v k, p h obtained from the central controller and the MPPT
reference frame, e.g., abc " ab, or a natural frame of algorithm is utilized using a PI controller to gener-
reference and phase-angle information are not necessities ate the phase shift for the output ac bridge. A similar
[40]. A hysteresis controller introduces variable switching- control strategy can be implemented on the BSs. As
frequency operation, which is not suitable for grid-tied V p /n p . Vb /n b . Vdc may not hold true, the converter
applications. Several methods have been proposed in the would not operate at the optimized efficiency operating
literature, employing an adaptive band to obtain a fixed condition. The “Results and Discussion” section quanti-
switching frequency. Complexity of the hysteresis control- fies this using a case scenario based on specifications
ler is high for current regulation [9], [41]. Alternatively, of the design example under consideration. In [45], the
deadbeat controllers are simpler and attempt to mitigate authors suggest regulating the PV panel voltage to main-
errors in the control variables within one sample delay. To tain converter performance. Alternatively, current-fed
compensate for this delay, an observer can be introduced dual-active bridge dc–dc converters are gaining popular-
into the structure of the controller, with the aim to modify ity, where the duty ratio and the phase shift are regulated
the current reference to compensate for the delay [42], to maintain a high efficiency operation [44]. An alternate
Central Controller
Pk,pv Pk,batt Pgref Qgref f θ
m
I inv m
Vk,dc
at the ac Grid
ref
Pk,inv
"
Vg
Vdc Voltage Control ref
Vk,inv dk,inv
vgm PQ Inverter PWM
PLL f ref
Qk,inv and
Calculation Modulator
dq Current Control
θ ref
Pk,pv ref
Pk,batt k th dc–ac Inverter Module
ref m ref
Pk,pv Ik,p Pk,batt m
Ik,b
ref
Vk,p ref
I k,p dk,p P k,batt I k,b d k,b
PI Voltage PI Current PI Power PI Current
MPPT Controller Controller SOC Controller Controller
Pk,pv
k th dc–dc PV Module k th dc–dc Battery Module
FIGURE 9. A block diagram of the hierarchical control approach for a hybrid PV+BS plant. PLL: phase-locked loop; SOC: state of charge;
PI: proportional integral.
Vg ref ref
I k,inv Vk,inv dk,inv
vgm PQ VDC Voltage dq Current Inverter PWM
PLL f ref
Qk,inv
Calculation PI Control Control Modulator
ref ref
θ Pk,pv Pk,batt
k th dc–ac Inverter Module
m ref m
ref
Pk,pv vk,p Pk,batt vk,dc
Bridge 2 Batt.
Vk,p φk,b vk,b φk,b
PI Voltage Phase-Shift dc/dc PI Voltage Phase-Shift dc–dc
MPPT Controller SOC Controller Modulator
Modulator
FIGURE 10. A block diagram of the hierarchical control approach for a hybrid PV+BS plant suitable for TAB topologies. Batt.: battery.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE SANTA CATARINA. Downloaded on February 09,2023 at 16:22:52 UTC from IEEE Xplore. Restrictions apply.
a Five-Winding High-Frequency Transformer Topology” converter configurations feature a higher per-unitized rat-
section, a 5-W TAB topology necessitates a per-phase ing for the power semiconductor devices in comparison to
phase shift on the ac side to minimize the dc–ac convert- the dc-stacked and cascaded bridge topologies. Further,
er capacitor value and reaps the benefits of a three-phase as noted previously, the 5-W TAB has a slightly higher
integrated transformer-winding configuration [31]. VA rating in comparison to the 3-W TAB architecture due
to the second-harmonic current ripple in the ac/dc/ac
Double-Star Configuration bridges. However, in contrast to other modular topologies,
Cascaded bridge architectures may be viewed as single- the 5-W TAB features a low energy storage requirement
star configurations, which comprise three arms for each due to three-phase transformer integration at the module
of the three ac phases. Although this article focuses on level. It may also be noted that the higher RMS current
cascaded bridge architectures for modular power conver- ratings in TAB converters also result in higher per-unit-
sion, the modular multilevel converter (MMC) configu- ized ratings for high-frequency transformers.
ration provides an alternative for integration of hybrid Using the efficiency calculation analytical models
PV+BS systems to the grid. In contrast to cascaded bridge detailed in the “DC-Stacked Architectures” and “Cas-
architectures, the MMC architecture is a double-star caded Bridge Architectures” sections, and the time-
configuration featuring six arms. The neutral points of domain simulations, Figures 11–15 present and compare
the two-star networks formed by the three arms provide the performance of the four converter approaches in
an accessible dc port output. Hence, MMC architectures terms of efficiency and loss distribution. Figure 11 com-
enable bulk-transmission renewable power by utilizing pares the efficiency of the various topologies as a func-
high-voltage dc (HVdc) transmission infrastructure, along tion of the switching frequency with a power level of
with other grid-support functions [18], [33], [49]. Ppv = 1.3 p.u., Pbatt = 0.3 p.u., and Pac = 1 p.u. The details
The module designs examined in the “Cascaded of the part numbers and the loss parameter values
Bridge Architectures” section, including FB modules, employed for efficiency calculations are summarized in
3-W, and 5-W transformer TAB modules can be connect-
ed in series to form six arms for an MMC configuration.
These architectures will be suitable for HVdc transmis- Table 4. Parameter design values for the design
sion from hybrid PV+BS power plants. The analytical example under consideration
results discussed in the article can be extended for such
double-star configurations. Parameter Value
Power 18 MVA
Results and Discussion
This section presents quantified and qualitative results of Frequency 60 Hz
the power converter architectures in terms of VA ratings, AC source voltage 13.8-kV RMS
energy storage requirements, efficiency estimations, and PV:battery:inverter power ratio 1.3:0.5:1
control complexity for a design example. Table 4 details
DC battery voltage 400–650V
specifications of the parameter design values suitable for
a utility-scale hybrid PV and battery energy storage power PV panel voltage 200–600V
plant. As noted in the “Block Diagram of PV+BS Power
Plants” section, the ILR and the battery plant power rat-
ings are assumed to be 1.3 and 0.5 p.u., respectively, Table 5. Specifications of the selected configurations
which are typical in today’s plants. for the several power converter architectures
Table 5 lists specifications of the selected benchmark
configurations. With a safety margin of 1.2 and a FB DC Cascaded 3-W 5-W
converter approach, both the dc-stacked and modular Topology Stacked Bridge TAB TAB
converter architectures feature eight converters and 14 IGBT voltage 1.2 kV (nominal)
modules, respectively. As the net theoretical per-unitized
Safety factor 1.2
VA and energy storage ratings will not be affected by the
transformer turns ratio, for simplicity, it is assumed to be DC voltage 1,000 V (nominal)
one-for-all configurations. In practical industrial solutions, Converters 8 — — —
other turns ratios could be used for optimization purposes. Modules — 14 14 14
Table 6 details ratings of the power semiconductor
LF-TF 13.8/0.55 1:1 — —
switches and the energy storage elements for the bench- turns-ratio
mark cases under consideration. The circuit architectures
HF-TF — — 1:1:1 1:1:1:1:1
have been developed in the piecewise linear electrical turns-ratio
circuit simulation environment to verify analytical calcu-
LF-TF: low-frequency transformer; HF-TF: high-frequency transformer.
lations. As noted in the analytical models, TAB modular
1
0.99 dc Stacked
CBC
0.98
3-W TAB
0.97 5-W TAB 1
Efficiency (p.u.)
0.96
0.95
0.94
0.93 dc CBC 3-W TAB 5-W TAB
Stacked
0.92
0.91 PV Conduction PV Switching Batt. Conduction
0.9 Batt. Switching B2 Conduction B2 Switching
2 4 6 8 10 12 14 16 18 20
Switching Frequency (kHz) ac Conduction ac Switching Transformer
FIGURE 11. Efficiency of the compared topologies as a FIGURE 12. Loss distribution with a switching frequency of 2 kHz
function of the switching frequency with a power level of with a power level of Ppv = 1.3 p.u., Pbatt = 0.3 p.u., and
Ppv = 1.3 p.u., Pbatt = 0.3 p.u., and Pac = 1p.u. Pac = 1p.u. Batt.: battery.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE SANTA CATARINA. Downloaded on February 09,2023 at 16:22:52 UTC from IEEE Xplore. Restrictions apply.
is the most efficient in high switching-frequency designs. operation ^n p = 0.6 h, during low power output from the
Switching losses at the dc–ac inverter dominate, with a PV panel, the PV panel voltage is operating at 525 V. In
switching frequency of 20 kHz in all of the topologies. the case of dc bus voltage regulation at the ac inverter
Figures 14 and 15 quantify the effect of difference in control loop, the dc voltage is maintained at 1 kV. On the
control methods for TAB topologies. Here, with a power other hand, if the dc inverter’s voltage is regulated by the
level of Ppv = 0.5 p.u., Pbatt = 0 p.u., and Pac = 0.5 p.u., a PV panel voltage, the dc voltage is regulated to 875 V to
low-PV power output scenario is considered. Although minimize circulating currents. Figure 14 illustrates the
the high-frequency transformer turns ratio is optimized current waveform at the PV side of the high-frequency
for a 600-V PV operation and a 1-kV dc inverter voltage transformer. It is noted that the RMS value of the cur-
rent increases by 5% in the case of Vdc = 1 kV. Figure 15
shows the loss distribution, where the net losses are
increased by 10.2 and 9.8% in the case of 3-W and 5-W
Switching Frequency = 20 kHz TABs, respectively. Hence, the tradeoff in adding control
·10−2
10 complexity with efficiency in the case of TAB topologies
is readily observed.
Table 7 provides a summary of the qualitative char-
8
acteristics of the candidate topologies under discussion.
Loss (p.u.)
2
4
Loss (p.u.)
0
dc CBC 3-W TAB 5-W TAB
2
Stacked
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE SANTA CATARINA. Downloaded on February 09,2023 at 16:22:52 UTC from IEEE Xplore. Restrictions apply.
plants,” in Proc. 2010 36th Annu. Conf. IEEE Ind. Electron. Soc. (IECON), verters,” in Proc. 2004 9th Int. Conf. Optim. Elect. Electron. Equip., Optim.,
pp. 2753–2758, doi: 10.1109/IECON.2010.5675108. vol. 3, pp. 9–14.
[22] M. S. Agamy et al., “A high efficiency DC-DC converter topology [41] L. Malesani, P. Mattavelli, and P. Tomasin, “Improved constant-
suitable for distributed large commercial and utility scale PV systems,” in frequency hysteresis current control of VSI inverters with simple feed-
Proc. 2012 15th Int. Power Electron. Motion Control Conf. (EPE/PEMC), forward bandwidth prediction,” IEEE Trans. Ind. Appl., vol. 33, no. 5, pp.
pp. LS2d.3–1–LS2d.3–6, doi: 10.1109/EPEPEMC.2012.6397420. 1194–1202, Sep./Oct. 1997, doi: 10.1109/28.633796.
[23] C. Deline, B. Marion, J. Granata, and S. Gonzalez, “A performance [42] S. Buso, T. Caldognetto, and D. I. Brandao, “Dead-beat current
and economic analysis of distributed power electronics in photovoltaic controller for voltage-source converters with improved large-signal
systems,” National Renewable Energy Laboratory, Golden, CO, USA, Tech. response,” IEEE Trans. Ind. Appl., vol. 52, no. 2, pp. 1588–1596, Mar./Apr.
Rep. NREL/TP-5200-50003, Jan. 2011. 2016, doi: 10.1109/TIA.2015.2488644.
[24] G. Walker and P. Sernia, “Cascaded DC-DC converter connection of [43] S. Buso, T. Caldognetto, and D. I. Brandao, “Oversampled dead-beat
photovoltaic modules,” in Proc. 2002 IEEE 33rd Annu. IEEE Power Electron. current controller for voltage source converters,” in Proc. 2015 IEEE
Specialists Conf. (Cat. No. 02CH37289), vol. 1, pp. 24–29, doi: 10.1109/ Appl. Power Electron. Conf. Expo. (APEC), pp. 1493–1500, doi: 10.1109/
PSEC.2002.1023842. APEC.2015.7104545.
[25] T. L. Fantham and D. T. Gladwin, “Impact of cell balance on grid [44] Y. Shi, R. Li, Y. Xue, and H. Li, “Optimized operation of current-fed dual
scale battery energy storage systems,” Energy Rep., vol. 6, pp. 209–216, active bridge DC–DC converter for PV applications,” IEEE Trans. Ind. Electron.,
May 2020, doi: 10.1016/j.egyr.2020.03.026. vol. 62, no. 11, pp. 6986–6995, Nov. 2015, doi: 10.1109/TIE.2015.2432093.
[26] Z. Yu, X. Hu, Z. Yao, L. Chen, M. Zhang, and S. Jiang, “Analysis and [45] C. P. Kumar, P. Alam, and A. Jamatia, “Modeling and control of dual-
design of a transformerless boost inverter for stand-alone photovoltaic active-bridge converter for grid-connected PV system,” in Proc. 2020 Int.
generation systems,” CPSS Trans. Power Electron. Appl., vol. 4, no. 4, pp. Conf. Power Electron. IoT Appl. Renewable Energy Control (PARC), pp.
310–319, Dec. 2019, doi: 10.24295/CPSSTPEA.2019.00029. 461–466, doi: 10.1109/PARC49193.2020.236656.
[27] M. Bierhoff and F. Fuchs, “Semiconductor losses in voltage source [46] S. Saeed, “Design and construction of a dab converter for integra-
and current source IGBT converters based on analytical derivation,” in tion of energy storage systems in power electronic applications,” in
Proc. 2004 IEEE 35th Annu. Power Electron. Specialists Conf. (IEEE Cat. Proc. 2015 6th Int. Conf. Power Electron. Syst. Appl. (PESA), pp. 1–7, doi:
No. 04CH37551), vol. 4, pp. 2836–2842, doi: 10.1109/PESC.2004.1355283. 10.1109/PESA.2015.7398954.
[28] R. Viju Nair et al., “Large scale grid integration of photovoltaic [47] T. Liu et al., “Start-up scheme for dual-active-bridge based 10kv power
and energy storage systems using triple port dual active bridge con- electronics transformer in PV application,” in Proc. 2018 IEEE Energy Con-
verter modules,” in Proc. 2018 IEEE Power Energy Soc. General Meeting vers. Congr. Expo. (ECCE), pp. 7083–7087, doi: 10.1109/ECCE.2018.8557632.
(PESGM), pp. 1–5, doi: 10.1109/PESGM.2018.8586158. [48] Y. Zhang, O. Akeyo, J. He, and D. M. Ionel, “On the control of a solid
[29] J. Hu, Z. Quan, S. Cui, Y. Li, and R. W. De Doncker, “Modular triple- state transformer for multi-MW utility-scale PV-battery systems,” in Proc.
active bridge DC-DC converters for utility-scale photovoltaics-plus-battery 2019 IEEE Energy Convers. Congr. Expo. (ECCE), pp. 6481–6486, doi:
storage systems connected to MVDC grids,” in Proc. 2020 IEEE 9th Int. 10.1109/ECCE.2019.8912477.
Power Electron. Motion Control Conf. (IPEMC2020-ECCE Asia), pp. 880– [49] M. A. Perez, S. Bernet, J. Rodriguez, S. Kouro, and R. Lizana, “Circuit
887, doi: 10.1109/IPEMC-ECCEAsia48364.2020.9368139. topologies, modeling, control schemes, and applications of modular mul-
[30] P. Channegowda and G. Venkataramanan, “Comparative evaluation tilevel converters,” IEEE Trans. Power Electron., vol. 30, no. 1, pp. 4–17,
of capacitor-coupled and transformer-coupled dual active bridge convert- Jan. 2015, doi: 10.1109/TPEL.2014.2310127.
ers,” in Proc. 2016 IEEE Energy Convers. Congr. Expo. (ECCE), pp. 1–8, [50] A. Joshi and S. Nath, “Efficiency comparison of solid-state trans-
doi: 10.1109/ECCE.2016.7854935. former and low-frequency power transformer,” in Proc. 3rd Int. Conf.
[31] P. K. Achanta, B. B. Johnson, G.-S. Seo, and D. Maksimovic, “A multi- Energy, Power Environ. Towards Clean Energy Technol., 2021, pp. 1–6,
level DC to three-phase AC architecture for photovoltaic power plants,” IEEE doi: 10.1109/ICEPE50861.2021.9404376.
Trans. Energy Convers., vol. 34, no. 1, pp. 181–190, Mar. 2019, doi: 10.1109/ [51] E. S. Lee, J. H. Park, M. Y. Kim, and J. S. Lee, “High efficiency inte-
TEC.2018.2877151. grated transformer design in dab converters for solid-state transformers,”
[32] Q.-C. Zhong and G. Weiss, “Synchronverters: Inverters that mimic IEEE Trans. Veh. Technol., vol. 71, no. 7, pp. 7147–7160, Jul. 2022, doi:
synchronous generators,” IEEE Trans. Ind. Electron., vol. 58, no. 4, pp. 10.1109/TVT.2022.3168561.
1259–1267, Apr. 2011, doi: 10.1109/TIE.2010.2048839. [52] “IGBT-Module FZ3600R12HP4.” Infineon Technologies. Accessed:
[33] S. Debnath et al., “Renewable integration in hybrid AC/DC sys- Mar. 2, 2022. [Online]. Available: https://www.infineon.com/dgdl/Infineon
tems using a multi-port autonomous reconfigurable solar power plant -FZ3600R12HP4-DS-v02_03-en_de.pdf?fileId=db3a3043163797a6011657
(MARS),” IEEE Trans. Power Syst., vol. 36, no. 1, pp. 603–612, Jan. 2021, 42504207c7
doi: 10.1109/TPWRS.2020.3037520. [53] “Extra fast recovery diode type F1600NC120.” IXYS Corporation.
[34] P. R. V. Marthi, S. Debnath, and M. L. Crow, “Synchronverter-based Accessed: Mar. 2, 2022. [Online]. Available: https://www.littelfuse.com/
control of multi-port autonomous reconfigurable solar plants (MARS),” products/power-semiconductors/discrete-diodes/fast-recovery/extra-fast
in Proc. 2020 IEEE Energy Convers. Congr. Expo. (ECCE), pp. 5019–5026, -capsule-type/f1600nc120.aspx
doi: 10.1109/ECCE44975.2020.9236019. [54] “IGBT-Module FZ1800R12HP4_B9.” Infineon Technologies.
[35] J. Liu, Y. Miura, and T. Ise, “Comparison of dynamic characteristics Accessed: Mar. 2, 2022. [Online]. Available: https://www.infineon.com/
between virtual synchronous generator and droop control in inverter- cms/en/product/power/igbt/igbt-modules/fz1800r12hp4_b9/
based distributed generators,” IEEE Trans. Power Electron., vol. 31, no. 5, [55] “IGBT-Module FZ2400R12HP4.” Infineon Technologies. [Online].
pp. 3600–3611, May 2016, doi: 10.1109/TPEL.2015.2465852. Available: https://www.infineon.com/dgdl/Infineon-FZ2400R12HP4
[36] X. Meng, Z. Liu, J. Liu, S. Wang, B. Liu, and R. An, “Comparison -DS-v02_02-en_de.pdf?fileId=db3a30432313ff5e0123942e580d04a2
between inverters based on virtual synchronous generator and droop [56] “IGBT-Module FZ600R12KS4.” Infineon Technologies. Accessed: Mar. 2,
control,” in Proc. 2017 IEEE Energy Convers. Congr. Expo. (ECCE), pp. 2022. [Online]. Available: https://www.infineon.com/dgdl/Infineon-FZ2400
4077–4084, doi: 10.1109/ECCE.2017.8096710. R12HP4-DS-v02_02-en_de.pdf?fileId=db3a30432313ff5e0123942e580d04a2
[37] M. P. Kazmierkowski, R. Krishnan, F. Blaabjerg, and J. D. Irwin, Con- [57] “Extra fast recovery diode type F1000LC120.” IXYS Corporation.
trol in Power Electronics: Selected Problems, 1st ed. New York, NY, USA: Accessed: Mar. 2, 2022. [Online]. Available: https://www.littelfuse.com/
Academic, 2002. products/power-semiconductors/discrete-diodes/fast-recovery/extra-fast
[38] E. Twining and D. Holmes, “Grid current regulation of a three-phase -capsule-type/f1000lc120.aspx
voltage source inverter with an LCL input filter,” in Proc. 2002 IEEE 33rd [58] “IGBT-Module FF300R12KS4.” Infineon Technologies. Accessed:
Annu. IEEE Power Electron. Specialists Conf. (Cat. No. 02CH37289), vol. Mar. 2, 2022. [Online]. Available: https://www.infineon.com/dgdl/Infineon
3, pp. 1189–1194, doi: 10.1109/TPEL.2003.810838. -FF300R12KS4-DS-v03_02-en_cn.pdf?fileId=db3a30433dd42dcf013dd530
[39] G. Saccomando and J. Svensson, “Transient operation of grid-con- e70c0256
nected voltage source converter under unbalanced voltage conditions,” in [59] “IGBT-Module FZ600R12KE3.” Infineon Technologies. Accessed:
Proc. Conf. Rec. 2001 IEEE Ind. Appl. Conf. 36th IAS Annu. Meeting (Cat. Mar. 2, 2022. [Online]. Available: https://www.infineon.com/dgdl/Infine-
No. 01CH37248), vol. 4, pp. 2419–2424, doi: 10.1109/IAS.2001.955960. on-FZ600R12KE3-DS-v03_04-en_de.pdf?fileId=db3a304412b407950112b
[40] R. Teodorescu and F. Blaabjerg, “Proportional-resonant controllers. A 433c3b25d79
new breed of controllers suitable for grid-connected voltage-source con-