CLIENT:

PROJECT :
IO MAP CHENLONG BINH DUONG PAPER
CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD

Date Description Filter Panel MCC2-1


07-10-21 For As built

No Tag Name Data Type Addres Tag table Comment

1 A-W1201E.Auto Bool %I252.0 MCC2-1 Agitator motor #1 Auto


2 A-W1201E.Run Bool %I252.1 MCC2-1 Agitator motor #1 Running
3 A-W1201E.FAL Bool %I252.2 MCC2-1 Agitator motor #1Tripping
4 A-W1201F.Auto Bool %I252.3 MCC2-1 Agitator motor #2 Auto
5 A-W1201F.Run Bool %I252.4 MCC2-1 Agitator motor #2 Running
6 A-W1201F.FAL Bool %I252.5 MCC2-1 Agitator motor #2Tripping
7 A-W1201G.Auto Bool %I252.6 MCC2-1 Agitator motor #3 Auto
8 A-W1201G.Run Bool %I252.7 MCC2-1 Agitator motor #3 Running
9 A-W1201G.FAL Bool %I253.0 MCC2-1 Agitator motor #3Tripping
10 A-W1201H.Auto Bool %I253.1 MCC2-1 Agitator motor #4 Auto
11 A-W1201H.Run Bool %I253.2 MCC2-1 Agitator motor #4 Running
12 A-W1201H.FAL Bool %I253.3 MCC2-1 Agitator motor #4Tripping
13 MCC2-1.ControlCircuit Bool %I253.4 MCC2-1 MCC2-1.Control Circuit
14 MCC2-1.EMS Bool %I253.5 MCC2-1 MCC2-1.EMS
Collecting discharge of the bottom of the lamella sedimentation tank and
15
LS-W1204B.LL Bool %I253.6 MCC2-1 slugde holding tank Level Switch
16 PI.Auto Bool %I253.7 MCC2-1 Pumps Instrument Tubidity
17 BUT-W1202C.1.OPL Bool %I254.0 MCC2-1 Collection Sludge Valve #1 Open Limit Switch
18 BUT-W1202C.2.OPL Bool %I254.1 MCC2-1 Collection Sludge Valve #2 Open Limit Switch
19 BUT-W1202C.3.OPL Bool %I254.2 MCC2-1 Collection Sludge Valve #3 Open Limit Switch
20 BUT-W1202C.4.OPL Bool %I254.3 MCC2-1 Collection Sludge Valve #4 Open Limit Switch
21 BUT-W1202C.5.OPL Bool %I254.4 MCC2-1 Collection Sludge Valve #5 Open Limit Switch
22 BUT-W1202C.6.OPL Bool %I254.5 MCC2-1 Collection Sludge Valve #6 Open Limit Switch
23 BUT-W1202C.7.OPL Bool %I254.6 MCC2-1 Collection Sludge Valve #7 Open Limit Switch
24 BUT-W1202C.1.CLL Bool %I254.7 MCC2-1 Collection Sludge Valve #1 Close Limit Switch
25 BUT-W1202C.2CLL Bool %I255.0 MCC2-1 Collection Sludge Valve #2 Close Limit Switch
26 BUT-W1202C.3CLL Bool %I255.1 MCC2-1 Collection Sludge Valve #3 Close Limit Switch
CLIENT:
PROJECT :
IO MAP CHENLONG BINH DUONG PAPER
CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD

Date Description Filter Panel MCC2-1


07-10-21 For As built

No Tag Name Data Type Addres Tag table Comment

27 BUT-W1202C.4CLL Bool %I255.2 MCC2-1 Collection Sludge Valve #4 Close Limit Switch
28 BUT-W1202C.5CLL Bool %I255.3 MCC2-1 Collection Sludge Valve #5 Close Limit Switch
29 BUT-W1202C.6CLL Bool %I255.4 MCC2-1 Collection Sludge Valve #6 Close Limit Switch
30 BUT-W1202C.7CLL Bool %I255.5 MCC2-1 Collection Sludge Valve #7 Close Limit Switch
31 P-W1203C.Auto Bool %I255.6 MCC2-1 Clarifier Sludge pump #1 Auto
32 P-W1203C.Run Bool %I255.7 MCC2-1 Clarifier Sludge pump #1 Running
33 BUT-W1202D.1.OPL Bool %I256.0 MCC2-1 Collection Sludge Valve #7 Open Limit Switch
34 BUT-W1202D.2.OPL Bool %I256.1 MCC2-1 Collection Sludge Valve #9 Open Limit Switch
35 BUT-W1202D.3.OPL Bool %I256.2 MCC2-1 Collection Sludge Valve #10 Open Limit Switch
36 BUT-W1202D.4.OPL Bool %I256.3 MCC2-1 Collection Sludge Valve #11 Open Limit Switch
37 BUT-W1202D.5.OPL Bool %I256.4 MCC2-1 Collection Sludge Valve #12 Open Limit Switch
38 BUT-W1202D.6.OPL Bool %I256.5 MCC2-1 Collection Sludge Valve #13 Open Limit Switch
39 BUT-W1202D.7.OPL Bool %I256.6 MCC2-1 Collection Sludge Valve #14 Open Limit Switch
40 BUT-W1202D.1.CLL Bool %I256.7 MCC2-1 Collection Sludge Valve #8 Close Limit Switch
41 BUT-W1202D.2.CLL Bool %I257.0 MCC2-1 Collection Sludge Valve #9 Close Limit Switch
42 BUT-W1202D.3.CLL Bool %I257.1 MCC2-1 Collection Sludge Valve #10 Close Limit Switch
43 BUT-W1202D.4.CLL Bool %I257.2 MCC2-1 Collection Sludge Valve #11 Close Limit Switch
44 BUT-W1202D.5.CLL Bool %I257.3 MCC2-1 Collection Sludge Valve #12 Close Limit Switch
45 BUT-W1202D.6.CLL Bool %I257.4 MCC2-1 Collection Sludge Valve #13 Close Limit Switch
46 BUT-W1202D.7.CLL Bool %I257.5 MCC2-1 Collection Sludge Valve #14 Close Limit Switch
47 P-W1203C.FAL Bool %I257.6 MCC2-1 Clarifier Sludge pump #1 Tripping
48 P-W1203D.Auto Bool %I257.7 MCC2-1 Clarifier Sludge pump #2 Auto
49 BUT-W1301D.3.OPL Bool %I258.0 MCC2-1 Butterfly Valve #3 Filter Tank #1 Open Limit Switch - Air backwash
50 BUT-W1301D.4.OPL Bool %I258.1 MCC2-1 Butterfly Valve #4 Filter Tank #1 Open Limit Switch - water backwash
51 BUT-W1301E.3.OPL Bool %I258.2 MCC2-1 Butterfly Valve #3 Filter Tank #2 Open Limit Switch - Air backwash
52 BUT-W1301E.4.OPL Bool %I258.3 MCC2-1 Butterfly Valve #4 Filter Tank #2 Open Limit Switch - water backwash
53 BUT-W1301F.3.OPL Bool %I258.4 MCC2-1 Butterfly Valve #3 Filter Tank #3 Open Limit Switch - Air backwash
CLIENT:
PROJECT :
IO MAP CHENLONG BINH DUONG PAPER
CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD

Date Description Filter Panel MCC2-1


07-10-21 For As built

No Tag Name Data Type Addres Tag table Comment

54 BUT-W1301F.4.OPL Bool %I258.5 MCC2-1 Butterfly Valve #4 Filter Tank #3 Open Limit Switch - water backwash
55 BUT-W1301D.3.CLL Bool %I258.6 MCC2-1 Butterfly Valve #3 Filter Tank #1 Close Limit Switch - Air backwash
56 BUT-W1301D.4.CLL Bool %I258.7 MCC2-1 Butterfly Valve #4 Filter Tank #1 Close Limit Switch - water backwash
57 BUT-W1301E.3.CLL Bool %I259.0 MCC2-1 Butterfly Valve #3 Filter Tank #2 Close Limit Switch - Air backwash
58 BUT-W1301E.4.CLL Bool %I259.1 MCC2-1 Butterfly Valve #4 Filter Tank #2 Close Limit Switch - water backwash
59 BUT-W1301F.3.CLL Bool %I259.2 MCC2-1 Butterfly Valve #3 Filter Tank #3 Close Limit Switch - Air backwash
60 BUT-W1301F.4.CLL Bool %I259.3 MCC2-1 Butterfly Valve #4 Filter Tank #3 Close Limit Switch - water backwash
61 SLI-W1301D.1.OPL Bool %I259.4 MCC2-1 Pen stock Valve #1 Filter Tank #1 Open Limit Switch - water inlet
62 BUT-W1301D.2.OPL Bool %I259.5 MCC2-1 Butterfly Valve #2 Filter Tank #1 Open Limit Switch - Drain sunface
63 BUT-W1301D.5.OPL Bool %I259.6 MCC2-1 Butterfly Valve #5 Filter Tank #1 Open Limit Switch - Drain based
64 SLI-W1301E.1.OPL Bool %I259.7 MCC2-1 Pen stock Valve #1 Filter Tank #2 Open Limit Switch - water inlet
65 BUT-W1301E.2.OPL Bool %I261.0 MCC2-1 Butterfly Valve #2 Filter Tank #2 Open Limit Switch - Drain sunface
66 BUT-W1301E.5.OPL Bool %I261.1 MCC2-1 Butterfly Valve #5 Filter Tank #2 Open Limit Switch - Drain based
67 SLI-W1301F.1.OPL Bool %I261.2 MCC2-1 Pen stock Valve #1 Filter Tank #3 Open Limit Switch - water inlet
68 BUT-W1301F.2.OPL Bool %I261.3 MCC2-1 Butterfly Valve #2 Filter Tank #3 Open Limit Switch - Drain sunface
69 BUT-W1301F.5.OPL Bool %I261.4 MCC2-1 Butterfly Valve #5 Filter Tank #3 Open Limit Switch - Drain based
70 SLI-W1301D.1.CLL Bool %I261.5 MCC2-1 Pen stock Valve #1 Filter Tank #1 Close Limit Switch - water inlet
71 BUT-W1301D.2.CLL Bool %I261.6 MCC2-1 Butterfly Valve #2 Filter Tank #1 Close Limit Switch - Drain sunface
72 BUT-W1301D.5.CLL Bool %I261.7 MCC2-1 Butterfly Valve #5 Filter Tank #1 Close Limit Switch - Drain based
73 SLI-W1301E.1.CLL Bool %I262.0 MCC2-1 Pen stock Valve #1 Filter Tank #2 Close Limit Switch - water inlet
74 BUT-W1301E.2.CLL Bool %I262.1 MCC2-1 Butterfly Valve #2 Filter Tank #2 Close Limit Switch - Drain sunface
75 BUT-W1301E.5.CLL Bool %I262.2 MCC2-1 Butterfly Valve #5 Filter Tank #2 Close Limit Switch - Drain based
76 SLI-W1301F.1.CLL Bool %I262.3 MCC2-1 Pen stock Valve #1 Filter Tank #3 Close Limit Switch - water inlet
77 BUT-W1301F.2.CLL Bool %I262.4 MCC2-1 Butterfly Valve #2 Filter Tank #3 Close Limit Switch - Drain sunface
78 BUT-W1301F.5.CLL Bool %I262.5 MCC2-1 Butterfly Valve #5 Filter Tank #3 Close Limit Switch - Drain based
79 P-W1203D.Run Bool %I262.6 MCC2-1 Clarifier Sludge pump #2 Running
80 P-W1203D.FAL Bool %I262.7 MCC2-1 Clarifier Sludge pump #2 Tripping
CLIENT:
PROJECT :
IO MAP CHENLONG BINH DUONG PAPER
CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD

Date Description Filter Panel MCC2-1


07-10-21 For As built

No Tag Name Data Type Addres Tag table Comment

81 A-W1201E.AC Bool %Q152.0 MCC2-1 Agitator motor #1 Active


82 A-W1201F.AC Bool %Q152.1 MCC2-1 Agitator motor #2 Active
83 A-W1201G.AC Bool %Q152.2 MCC2-1 Agitator motor #3 Active
84 A-W1201H.AC Bool %Q152.3 MCC2-1 Agitator motor #4 Active
85 P-W1203C.AC Bool %Q152.4 MCC2-1 Clarifier Sludge pump #1 Active
86 P-W1203D.AC Bool %Q152.5 MCC2-1 Clarifier Sludge pump #2 Active
87 SP Bool %Q152.6
88 SP Bool %Q152.7
89 SP Bool %Q153.0
90 BUT-W1202C.1.SV Bool %Q153.1 MCC2-1 Collection Sludge Valve #1 Solenoid Valve
91 BUT-W1202C.2SV Bool %Q153.2 MCC2-1 Collection Sludge Valve #2 Solenoid Valve
92 BUT-W1202C.3.SV Bool %Q153.3 MCC2-1 Collection Sludge Valve #3 Solenoid Valve
93 BUT-W1202C.4.SV Bool %Q153.4 MCC2-1 Collection Sludge Valve #4 Solenoid Valve
94 BUT-W1202C.5.SV Bool %Q153.5 MCC2-1 Collection Sludge Valve #5 Solenoid Valve
95 BUT-W1202C.6.SV Bool %Q153.6 MCC2-1 Collection Sludge Valve #6 Solenoid Valve
96 BUT-W1202C.7.SV Bool %Q153.7 MCC2-1 Collection Sludge Valve #7 Solenoid Valve
97 BUT-W1202D.1.SV Bool %Q154.0 MCC2-1 Collection Sludge Valve #8 Solenoid Valve
98 BUT-W1202D.2SV Bool %Q154.1 MCC2-1 Collection Sludge Valve #9 Solenoid Valve
99 BUT-W1202D.3SV Bool %Q154.2 MCC2-1 Collection Sludge Valve #10 Solenoid Valve
100 BUT-W1202D.4SV Bool %Q154.3 MCC2-1 Collection Sludge Valve #11 Solenoid Valve
101 BUT-W1202D.5SV Bool %Q154.4 MCC2-1 Collection Sludge Valve #12 Solenoid Valve
102 BUT-W1202D.6SV Bool %Q154.5 MCC2-1 Collection Sludge Valve #13 Solenoid Valve
103 BUT-W1202D.7.SV Bool %Q154.6 MCC2-1 Collection Sludge Valve #14 Solenoid Valve
104 BUT-W1301D.3.SV Bool %Q154.7 MCC2-1 Butterfly Valve #3 Filter Tank #1 Solenoid Valve - Air backwash
105 BUT-W1301D.4.SV Bool %Q155.0 MCC2-1 Butterfly Valve #4 Filter Tank #1 Solenoid Valve - water backwash
106 BUT-W1301E.3.SV Bool %Q155.1 MCC2-1 Butterfly Valve #3 Filter Tank #2 Solenoid Valve - Air backwash
107 BUT-W1301E.4.SV Bool %Q155.2 MCC2-1 Butterfly Valve #4 Filter Tank #2 Solenoid Valve - water backwash
CLIENT:
PROJECT :
IO MAP CHENLONG BINH DUONG PAPER
CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD

Date Description Filter Panel MCC2-1


07-10-21 For As built

No Tag Name Data Type Addres Tag table Comment

108 BUT-W1301F.3.SV Bool %Q155.3 MCC2-1 Butterfly Valve #3 Filter Tank #3 Solenoid Valve - Air backwash
109 BUT-W1301F.4.SV Bool %Q155.4 MCC2-1 Butterfly Valve #4 Filter Tank #3 Solenoid Valve - water backwash
110 SLI-W1301D.1.SV Bool %Q155.5 MCC2-1 Pen stock Valve #1 Filter Tank #1 Solenoid Valve - water inlet
111 BUT-W1301D.2.SV Bool %Q155.6 MCC2-1 Butterfly Valve #2 Filter Tank #1 Solenoid Valve - Drain sunface
112 BUT-W1301D.5.SV Bool %Q155.7 MCC2-1 Butterfly Valve #5 Filter Tank #1 Solenoid Valve - Drain based
113 SLI-W1301E.1.SV Bool %Q156.0 MCC2-1 Pen stock Valve #1 Filter Tank #2 Solenoid Valve - water inlet
114 BUT-W1301E.2.SV Bool %Q156.1 MCC2-1 Butterfly Valve #2 Filter Tank #2 Solenoid Valve - Drain sunface
115 BUT-W1301E.5.SV Bool %Q156.2 MCC2-1 Butterfly Valve #5 Filter Tank #2 Solenoid Valve - Drain based
116 SLI-W1301F.1.SV Bool %Q156.3 MCC2-1 Pen stock Valve #1 Filter Tank #3 Solenoid Valve - water inlet
117 BUT-W1301F.2.SV Bool %Q156.4 MCC2-1 Butterfly Valve #2 Filter Tank #3 Solenoid Valve - Drain sunface
118 BUT-W1301F.5.SV Bool %Q156.5 MCC2-1 Butterfly Valve #5 Filter Tank #3 Solenoid Valve - Drain based
119 PI.AC Bool %Q156.6 MCC2-1 Pumps Instrument Tubidity Active
120 SP Bool %Q156.7
121 SP Bool %Q157.0
122 SP Bool %Q157.1
123 SP Bool %Q157.2
124 SP Bool %Q157.3
125 SP Bool %Q157.4
126 SP Bool %Q157.5
127 SP Bool %Q157.6
128 SP Bool %Q157.7
129 LT1301D Int %IW300 MCC2-1 Level Transmitter Filter Tank #1
130 LT1301E Int %IW302 MCC2-1 Level Transmitter Filter Tank #2
131 LT1301F Int %IW304 MCC2-1 Level Transmitter Filter Tank #3
132 SP Int %IW306
133 BUT-W1301D.6.IR Int %IW309 MCC2-1 Water collection Valve #1 after Filtering - position
134 BUT-W1301E.6.IR Int %IW311 MCC2-1 Water collection Valve #2 after Filtering - position
CLIENT:
PROJECT :
IO MAP CHENLONG BINH DUONG PAPER
CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD

Date Description Filter Panel MCC2-1


07-10-21 For As built

No Tag Name Data Type Addres Tag table Comment

135 BUT-W1301F.6.IR Int %IW313 MCC2-1 Water collection Valve #3 after Filtering - position
136 SP Int %IW315
137 ATNTU-W1401 Int %IW318 MCC2-1 Treated Water after Filtering NTU Value
138 SP Int %IW320
139 SP Int %IW322
140 SP Int %IW324
141 BUT-W1301D.6.CIR Int %QW180 MCC2-1 Water collection Valve #1 after Filtering - control position
142 BUT-W1301E.6.CIR Int %QW182 MCC2-1 Water collection Valve #2 after Filtering - control position
143 BUT-W1301F.6.CIR Int %QW184 MCC2-1 Water collection Valve #3 after Filtering - control position
144 SP Int %QW186
145 FS1 Bool %I272.0 MCC2-1 Flow Switch on pipe of Instrument Tubidity pump
146 SP Bool %I272.1
147 SP Bool %I272.2
148 SP Bool %I272.3
149 SP Bool %I272.4
150 SP Bool %I272.5
151 SP Bool %I272.6
152 SP Bool %I272.7
153 SP Bool %I273.0
154 SP Bool %I273.1
155 SP Bool %I273.2
156 SP Bool %I273.3
157 SP Bool %I273.4
158 SP Bool %I273.5
159 SP Bool %I273.6
160 SP Bool %I273.7
CLIENT:
PROJECT :
IO MAP CHENLONG BINH DUONG PAPER
CLVP WATER TREATMENT PLANT - CAPACITY OF
CO.LTD

Date Description Filter Panel MCC2-1


07-10-21 For As built

No Tag Name Data Type Addres Tag table Comment

ERATECH